This technical datasheet provides specifications for a 2 core 1.5 sqmm fire resistant cable manufactured by Polycab India Ltd. The key details are:
- It is a low voltage 0.6/1kV fire resistant cable compliant with IEC 60502-1.
- It has 2 cores of 1.5 sqmm copper conductor insulated with 1mm thick EPR and an inner sheath of 0.4mm thick black LSZH compound.
- The cable has armoring of 0.9mm galvanized steel wires, and an outer sheath of 1.24mm thick black LSZH compound.
- The cable passes IEC 60331 for 90 minutes at
This technical datasheet provides specifications for a 2 core 1.5 sqmm fire resistant cable manufactured by Polycab India Ltd. The key details are:
- It is a low voltage 0.6/1kV fire resistant cable compliant with IEC 60502-1.
- It has 2 cores of 1.5 sqmm copper conductor insulated with 1mm thick EPR and an inner sheath of 0.4mm thick black LSZH compound.
- The cable has armoring of 0.9mm galvanized steel wires, and an outer sheath of 1.24mm thick black LSZH compound.
- The cable passes IEC 60331 for 90 minutes at
This technical datasheet provides specifications for a 2 core 1.5 sqmm fire resistant cable manufactured by Polycab India Ltd. The key details are:
- It is a low voltage 0.6/1kV fire resistant cable compliant with IEC 60502-1.
- It has 2 cores of 1.5 sqmm copper conductor insulated with 1mm thick EPR and an inner sheath of 0.4mm thick black LSZH compound.
- The cable has armoring of 0.9mm galvanized steel wires, and an outer sheath of 1.24mm thick black LSZH compound.
- The cable passes IEC 60331 for 90 minutes at
Technical Datasheet of LT EPR FIRE RESISTANT Cables
CUSTOMER - Paradise Electrical Industries
S.No Particulars 2 X 1.5
1 Name of Manufacturer Polycab India Ltd 2 Type of cable Fire Resistant Cable 3 Voltage Grade kV 0.6/1 (1.2) 4 Applicable Standard Generally to IEC 60502-1 5 No of cores X size in sqmm 2 X 1.5 6 Conductor a) Material Annealed Tinned Class -2 Copper to IEC 60228
b) Max. d.c. resistance of conductor at 20° C (ohm/km) 12.20
c) Shape of the conductor Stranded Circular
d) Fire Barrier tape over conductor Glass Mica Tape(s) 7 Insulation a) Material EPR as per IEC 60502-1 b) Nominal thickness (mm) 1.0 c) Core Identification Red & Black 8 Inner Sheath a) Material Extruded LSZH Type ST8 as per IEC 60502-1 b) Approx thickness (mm) 0.4 c) Colour of Inner sheath. Black 9 Armouring a) Material Galvanised Steel b) Type of armouring Round Wire c) Nominal size of armour (mm) 0.90 10 Outer Sheath a) Material Extruded LSZH Type ST8 as per IEC 60502-1 b) Thickness (mm) 1.24 (Min) c) Colour of outer sheath. Black 11 Nominal overall diameter of the cable in mm 16.0 +/- 2.0 12 LSZH PROPERTIES a) Temperature Index Min.250% as per ASTM. D 2863 b) Oxygen Index Min.30% as per ASTM D 2863 c) HCL Gas Emission Max. 0.5% as per IEC-754-1 d) Smoke Density Max. 20% as per ASTMD 2843 e) Flammability IEC- 60332 Part 1 f) Fire Performance IEC 60331 (750°C for 90minutes) 13 Electrical Parameters Maximum conductor temperature under normal a) 15.6 operating conditions b) Calculated Cable reactance (ohm/km) 0.105 c) Impedance of cable (ohm/km) 15.6 d) Approx. Cable Capacitance (mfd/km) 0.18 Maximum conductor temperature under normal 14 90°C operating conditions Maximum conductor temperature at the termination 15 250°C of short circuit Short Circuit rating of conductor for the duration of 16 0.215 1 sec (kA) 17 Continuous Current carrying capacities :- (a) In Ground at 30°C (A) 31 (b) In Air at 40°C (A) 27 18 Minimum bending radius 12 times Overall diameter 19 Max. Tensile strength (i) for Cables pulled with stocking (Newtons) 7x D2 where D is the overall diameter of the cable ii) for Cables pulled with pulling eyes (N) 15 YEAR of Manufacture POLYCAB ELECTRIC 0.6/1 (1.2)kV 20 Printing GRADE LSZH FIRE RESISTANT, CABLE SIZE WITH SEQUENTIAL MARKING at every one meter interval. Note:-The values given above are subject to tolerances as per the relevant standards. TDS.190731-4261 PRAVEEN S