DAILY CHECKSHEET DAILY CHECKSHEET

EQUIPMENT NAME: DEPARTMENT C/O:


LOCATION: 2F/CHILLER ROOM MONTH:JUNE EQUIPMENT CLASSIFICATION: HVAC
WATER-COOLED CHILLER 1 ENGINEERING DEPT
No. Check Items Standard Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

0900H
1 Chiller Panel(HMI) Functioning
1400H

0900H
No Burns/
2 Chiller Electrical System
Cut/Dirt
1400H

0900H
3 Chilled Water Entering Temp. 6-20 °C
1400H

0900H
4 Chilled Water Leaving Temp. 5-15 °C
1400H

0900H
5 Evaporator Pressure(Chamber 1) 300-450 kPa
1400H

0900H
6 Evaporator Pressure(Chamber 2) 300-450 kPa
1400H

0900H
7 Evaporator Temperature(Chamber 1) 0.7-12.47 °C
1400H

0900H
8 Evaporator Temperature(Chamber 2) 0.7-12.47 °C
1400H

0900H
9 Condenser Pressure(Chamber 1) 784-1275 kPa
1400H

0900H
10 Condenser Pressure(Chamber 2) 784-1275 kPa
1400H

0900H
11 Condenser Temperature(Chamber 1) 30.7-48.7 °C
1400H

0900H
12 Condenser Temperature(Chamber 2) 30.7-48.7 °C
1400H

0900H
13 Compressor 1 (Exhaust Temp) 30.7-48.7°C
1400H

0900H
14 Compressor 1 (Suction Temp) 0.68-12.53 °C
1400H

0900H
15 Compressor 2 (Exhaust Temp) 30.7-48.7°C
1400H

0900H
16 Compressor 2 (Suction Temp) 0.68-12.53 °C
1400H

0900H
17 Compressor 1 Current 0-269 A
1400H

0900H
18 Compressor 2 Currrent 0-269 A
1400H
DAILY CHECKSHEET
DEPARTMENT C/O:
EQUIPMENT NAME: CHILLER 1 LOCATION: 2F/CHILLER ROOM MONTH:JUNE EQUIPMENT CLASSIFICATION: HVAC
ENGINEERING DEPT
No. Check Items Standard Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

0900H
19 Compressor 1 Running Hours x ≮ 1 Hrs
1400H

0900H
20 Compressor 2 Running Hours x ≮ 1 Hrs
1400H

0900H
21 Times Compressor 1 Turned-On x ≮ 1 Times
1400H

0900H
22 Times Compressor 2 Turned-On x ≮ 1 Times
1400H

0900H
23 Unit Running Hours x ≮ 1 Hrs
1400H

0900H
24 Unit Run Count x ≮ 1 Times
1400H

0900H
25 Chilled Water Pressure Leaving 15-20 psig
1400H

0900H
26 Chilled Water Pressure Entering 30-40 psig
1400H

0900H
≥ 1/2 or ≤ 3/4
27 Compressor 1 Oil Level
sight glass
1400H

0900H
≥ 1/2 or ≤ 3/4
28 Compressor 2 Oil Level
sight glass
1400H

0900H
29 Chiller Pump 1(Suction Pressure) 0 psig
1400H

0900H
30 Chiller Pump 1(Discharge Pressure) 40-60 psig
1400H

0900H
31 Chiller Pump 2(Suction Pressure) 0 psig
1400H

0900H
32 Chiller Pump 2(Discharge Pressure) 40-60 psig
1400H

0900H
33 Chiller Pump 3(Suction Pressure) 0 psig
1400H

0900H
34 Chiller Pump 3(Discharge Pressure) 40-60 psig
1400H

Maintenance Technician Daily

Maintenance Engineer Weekly


DAILY CHECKSHEET DAILY CHECKSHEET
EQUIPMENT NAME: DEPARTMENT C/O:
LOCATION: 2F/CHILLER ROOM MONTH:JUNE EQUIPMENT CLASSIFICATION: HVAC
WATER-COOLED CHILLER 1 ENGINEERING DEPT
No. Check Items Standard Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

0900H
1 Chiller Panel(HMI) Functioning
1400H

0900H
No Burns/
2 Chiller Electrical System
Cut/Dirt
1400H

0900H
3 Chilled Water Entering Temp. 6-20 °C
1400H

0900H
4 Chilled Water Leaving Temp. 5-15 °C
1400H

0900H
5 Evaporator Pressure(Chamber 1) 300-450 kPa
1400H

0900H
6 Evaporator Pressure(Chamber 2) 300-450 kPa
1400H

0900H
7 Evaporator Temperature(Chamber 1) 0.7-12.47 °C
1400H

0900H
8 Evaporator Temperature(Chamber 2) 0.7-12.47 °C
1400H

0900H
9 Condenser Pressure(Chamber 1) 784-1275 kPa
1400H

0900H
10 Condenser Pressure(Chamber 2) 784-1275 kPa
1400H

0900H
11 Condenser Temperature(Chamber 1) 30.7-48.7 °C
1400H

0900H
12 Condenser Temperature(Chamber 2) 30.7-48.7 °C
1400H

0900H
13 Compressor 1 (Exhaust Temp) 30.7-48.7°C
1400H

0900H
14 Compressor 1 (Suction Temp) 0.68-12.53 °C
1400H

0900H
15 Compressor 2 (Exhaust Temp) 30.7-48.7°C
1400H

0900H
16 Compressor 2 (Suction Temp) 0.68-12.53 °C
1400H

0900H
17 Unit Running Hours x ≮ 1 Hrs
1400H

0900H
18 Unit Run Count x ≮ 1 Times
1400H
DAILY CHECKSHEET
DEPARTMENT C/O:
EQUIPMENT NAME: CHILLER 1 LOCATION: 2F/CHILLER ROOM MONTH:JUNE EQUIPMENT CLASSIFICATION: HVAC
ENGINEERING DEPT
No. Check Items Standard Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

0900H
19 Compressor 1 Running Hours x ≮ 1 Hrs
1400H

0900H
20 Compressor 2 Running Hours x ≮ 1 Hrs
1400H

0900H
21 Times Compressor 1 Turned-On x ≮ 1 Times
1400H

0900H
22 Times Compressor 2 Turned-On x ≮ 1 Times
1400H

0900H
23 Compressor 1 Current 0-269 A
1400H

0900H
24 Compressor 2 Currrent 0-269 A
1400H

0900H
25 Chilled Water Pressure Leaving 15-20 psig
1400H

0900H
26 Chilled Water Pressure Entering 30-40 psig
1400H

0900H
≥ 1/2 or ≤ 3/4
27 Compressor 1 Oil Level
sight glass
1400H

0900H
≥ 1/2 or ≤ 3/4
28 Compressor 2 Oil Level
sight glass
1400H

0900H
29 Chiller Pump 1(Suction Pressure) 0 psig
1400H

0900H
30 Chiller Pump 1(Discharge Pressure) 40-60 psig
1400H

0900H
31 Chiller Pump 2(Suction Pressure) 0 psig
1400H

0900H
32 Chiller Pump 2(Discharge Pressure) 40-60 psig
1400H

0900H
33 Chiller Pump 3(Suction Pressure) 0 psig
1400H

0900H
34 Chiller Pump 3(Discharge Pressure) 40-60 psig
1400H

Maintenance Technician Daily

Maintenance Engineer Weekly


DAILY CHECKING STANDARD TABLE
No. CHECK ITEMS CHECKING STANDARD
1 Chiller Panel(HMI) Functioning and no physical damage.
2 Chiller Electrical System No damage,discoloration,burns,loosed terminal,cuts,abnormal sound and suspicious smell.
3 Chilled Water Entering Temperature 6 °C to 20 °C reading in HMI display.
4 Chilled Water Leaving Temperature 5 °C to 15 °C reading in HMI display.
5 Evaporator Pressure (Chamber 1&2) 300 kPa to 450 kPa reading in HMI display.
6 Evaporator Temperature (Chamber 1&2) 0.7 °C to 12.47 °C reading in HMI display.
7 Condenser Pressure (Chamber 1&2) 784 kPa to 1275 kPa reading in HMI display.
8 Condenser Temperature (Chamber 1&2) 30.7 °C to 48.7 °C reading in HMI display.
9 Compressor 1&2 (Exhaust Temperature) 30.7 °C to 48.7 °C reading in HMI display.
10 Compressor 1&2 (Suction Temperature) 0.68 °C to 12.5 °C
11 Unit Running Hours Unit Running Hours reading in HMI display.
12 Unit Run Count Unit Running Count reading in HMI display.
13 Compressor 1&2 Running Hours Compressors Running Hours reading in HMI display.
14 Times Compressor 1&2 Turned-On Times Compressors Turned-On reading in HMI display.
15 Compressor 1&2 Current 0 A to 269 A reading in HMI display.
16 Chilled Water Pressure Leaving 15 psig to 20 psig reading in Pressure Gauge in-line.
17 Chilled Water Pressure Entering 30 psig to 40 psig reading in Pressure Gauge in-line.
18 Compressor 1&2 Oil evel 1/2 to 3/4 level in sight glass while in idling state.
19 Chiller Pump 1,2&3 Suction Pressure 0 psig reading in Pressure Gauge in-line.
20 Chiller Pump 1,2&3 Discharge Pressure 40 psig to 60 psig reading in Pressure Gauge in-line.
Working Instruction

1. Draw ( - ) for Sunday and holiday in the check box. 5. Log the actual reading of the specified check items.
2. Draw ( * ) for No Operation in the check box and indicate the date of no operation in the 6. Re-routing of checking will be :
remarks part. Maintenance Technician: Daily
3. Draw ( o ) if there is no trouble and ( x ) if there is trouble and then indicate the trouble Maintenance Engineer: Weekly
in the Remarks check box. 7. If the measured values does not match the standard, report it to your Immediate Superior.
4. Ensure that the unit is checked at the specified time.

SAFETY TIPS
*During checking if you encounter abnormal situation *Avoid contact on energized electrical system.
(i.e loosed wire,suspicious smell,etc.) report immediately it to your immediate superior. *Avoid distraction while conducting checking.
*Must comply with the PPE requirements. *Practical safeguarding of personels arising with the use of
*Wearing practice should be properly observed, avoid wearing electricity.
loose clothing/materials (this can caught in the rotating parts).
REMARKS

Date Trouble/Event Description Action Plan PIC Commitment Date Date Accomplished
DAILY CHECKSHEET DAILY CHECKSHEET
LOCATION:
EQUIPMENT NAME: DEPARTMENT C/O:
MONTH:JUNE EQUIPMENT CLASSIFICATION: HVAC
AIR-COOLED CHILLER 1 ENGINEERING DEPT
2F/CHILLER ROOM SIDE
No. Check Items Standard Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

0900H
1 Chiller Electrical System Functioning
1400H

0900H
No Burns/
2 Supply Terminal Block
Cut/Dirt
1400H

0900H
3 Compressor 1 Breaker 6-20 °C
1400H

0900H
4 Compressor 2 Breaker 5-15 °C
1400H

0900H
5 Condenser Fan Breaker 300-450 kPa
1400H

0900H
6 Pump Breaker 300-450 kPa
1400H

0900H
7 Control/Accessories Ckt. Breaker 0.7-12.47 °C
1400H

0900H
8 Compressor 1 Heater 0.5-0.8A
1400H

0900H
9 Compressor 2 Heater 0.5-0.8A
1400H

0900H
10 Compressor 1 Vibration 784-1275 kPa
1400H

0900H
11 Compressor 2 Vibration 30.7-48.7 °C
1400H

0900H
12 Compressor Lubricating Oil 30.7-48.7 °C
1400H

0900H
13 Condenser Fins&Coil 30.7-48.7°C
1400H

0900H
14 Condenser Fins&Coil 0.68-12.53 °C
1400H

0900H
15 Condenser Fan 30.7-48.7°C
1400H

0900H
16 Condenser Fan Guard 0.68-12.53 °C
1400H

0900H
17 Circulating Pump x ≮ 1 Hrs
1400H

0900H
18 Chiller Tank x ≮ 1 Times
1400H
DAILY CHECKSHEET
DEPARTMENT C/O:
EQUIPMENT NAME: CHILLER 1 LOCATION: 2F/CHILLER ROOM MONTH:JUNE EQUIPMENT CLASSIFICATION: HVAC
ENGINEERING DEPT
No. Check Items Standard Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

0900H
19 Compressor 1 Running Hours x ≮ 1 Hrs
1400H

0900H
20 Compressor 2 Running Hours x ≮ 1 Hrs
1400H

0900H
21 Times Compressor 1 Turned-On x ≮ 1 Times
1400H

0900H
22 Times Compressor 2 Turned-On x ≮ 1 Times
1400H

0900H
23 Compressor 1 Current 0-269 A
1400H

0900H
24 Compressor 2 Currrent 0-269 A
1400H

0900H
25 Chilled Water Pressure Leaving 15-20 psig
1400H

0900H
26 Chilled Water Pressure Entering 30-40 psig
1400H

0900H
≥ 1/2 or ≤ 3/4
27 Compressor 1 Oil Level
sight glass
1400H

0900H
≥ 1/2 or ≤ 3/4
28 Compressor 2 Oil Level
sight glass
1400H

0900H
29 Chiller Pump 1(Suction Pressure) 0 psig
1400H

0900H
30 Chiller Pump 1(Discharge Pressure) 40-60 psig
1400H

0900H
31 Chiller Pump 2(Suction Pressure) 0 psig
1400H

0900H
32 Chiller Pump 2(Discharge Pressure) 40-60 psig
1400H

0900H
33 Chiller Pump 3(Suction Pressure) 0 psig
1400H

0900H
34 Chiller Pump 3(Discharge Pressure) 40-60 psig
1400H

Maintenance Technician Daily

Maintenance Engineer Weekly


DAILY CHECKSHEET LOCATION BUILDING 2

DEPARTMENT: SECTION: MACHINE: MONTH GENERAL MANAGER DGM/M MAINT.ASST. MANAGER


MAINTENANCE UTILITY PACCU 1-1 JANUARY
No. Check Items METHOD SHIFTING TIME 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
DAY SHIFT 0830H
1 PACCU Electrical System VISUAL
NIGHT SHIFT 2030H
DAY SHIFT 0830H
2 Supply Terminal VISUAL
NIGHT SHIFT 2030H
DAY SHIFT 0830H
3 Isolation Breaker VISUAL
NIGHT SHIFT 2030H
DAY SHIFT 0830H
4 Control Panel VISUAL
NIGHT SHIFT 2030H
DAY SHIFT 0830H
5 Lube Oil Pressure Switch VISUAL
NIGHT SHIFT 2030H
Timer Relay
DAY SHIFT 0830H
6 WYE 1 Timer relay VISUAL
NIGHT SHIFT 2030H
DAY SHIFT 0830H
7 WYE 2 Timer relay VISUAL
NIGHT SHIFT 2030H
Running Current
CLAMP DAY SHIFT 0830H
8 L1
METER NIGHT SHIFT 2030H
CLAMP DAY SHIFT 0830H
9 L2
METER NIGHT SHIFT 2030H
CLAMP DAY SHIFT 0830H
10 L3
METER NIGHT SHIFT 2030H
DAY SHIFT 0830H
11 Compresor Vibration VISUAL
NIGHT SHIFT 2030H
DAY SHIFT 0830H
12 Compresor Noise HEARING
NIGHT SHIFT 2030H
DAY SHIFT 0830H
13 Compressor Oil VISUAL
NIGHT SHIFT 2030H
DAY SHIFT 0830H
14 Condenser Fins VISUAL
NIGHT SHIFT 2030H
DAY SHIFT 0830H
15 Condenser Coil VISUAL
NIGHT SHIFT 2030H
DAY SHIFT 0830H
16 Condenser Fan VISUAL
NIGHT SHIFT 2030H
DAY SHIFT 0830H
17 Condenser Fan Guard VISUAL
NIGHT SHIFT 2030H
DAY SHIFT 0830H
18 Compressor Pipe Joints VISUAL
NIGHT SHIFT 2030H
DAY SHIFT 0830H
19 PACCU Area VISUAL
NIGHT SHIFT 2030H
Day Shift Inspector Daily
Night Shift Inspector Daily
Team Leader/Maintenance Engineer Daily
Assistant Manager/DGM/M Weekly
General Manager Monthly
Working Instruction
4. Log the actual value reading of the specified check items.
1. Draw ( * ) for No Operation in the check box and indicate the date of no operation in the 5. If the measured values does not match the standard, report and present checksheet to the team leader.
remarks part. 6. Re-routing of checking will be :
2. Draw ( o ) if there is no trouble and ( x ) if there is trouble and then indicate the trouble
in the Remarks check box located at the back of this sheet. Maintenance Technician: Daily Asst.Manager/Maint.ManagerDGM: Weekly
3. Ensure that the unit is checked at the specified time. Team Leader/Maint. Engineer: Daily General Manager: Monthly
Maintenance Technician: Daily Asst.Manager/Maint.ManagerDGM: Weekly
Team Leader/Maint. Engineer: Daily General Manager: Monthly
DAILY CHECKSHEET INVERTER LOGSHEET
EQUIPMENT NAME: EQUIPMENT CLASSIFICATION: DEPARTMENT C/O:
LOCATION: GF/SOLAR ROOM MONTH:__________
SOLAR INVERTER ELECTRICAL ENGINEERING DEPT
INVERTER NAME TIME 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

0900H
INVERTER 1
0200H

0900H
INVERTER 2
0200H

0900H
INVERTER 3
0200H

0900H
INVERTER 4
0200H

0900H
INVERTER 5
0200H

0900H
INVERTER 6
0200H

0900H
INVERTER 7
0200H

0900H
INVERTER 8
0200H

0900H
INVERTER 9
0200H

0900H
INVERTER 10
0200H

0900H
INVERTER 11
0200H

0900H
INVERTER 12
0200H

0900H
INVERTER 13
0200H

0900H
INVERTER 14
0200H

0900H
INVERTER 15
0200H

0900H
INVERTER 16
0200H

0900H `
INVERTER 17
0200H

0900H
INVERTER 18
0200H

0900H
INVERTER 19
0900H `
DAILY CHECKSHEET INVERTER LOGSHEET
EQUIPMENT NAME: EQUIPMENT CLASSIFICATION: DEPARTMENT C/O:
LOCATION: GF/SOLAR ROOM MONTH:__________
SOLAR INVERTER ELECTRICAL ENGINEERING DEPT
INVERTER NAME TIME 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

0900H
INVERTER 20
0200H

0900H
INVERTER 21
0200H

0900H
INVERTER 22
0200H

0900H
INVERTER 23
0200H

0900H
INVERTER 24
0200H

0900H
INVERTER 25
0200H

0900H
INVERTER 26
0200H

0900H
INVERTER 27
0200H

0900H
INVERTER 28
0200H

0900H
INVERTER 29
0200H

0900H
INVERTER 30
0200H

0900H
INVERTER 31
0200H

0900H
INVERTER 32
0200H

0900H
INVERTER 33
0200H

0900H
INVERTER 34
0200H

0900H
INVERTER 35
0200H

0900H `
INVERTER 36
0200H

0900H
INVERTER 37
0200H

0900H
TECHNICIAN
0200H
DAILY CHECKSHEET DAILY CHECKSHEET
EQUIPENTNAME:
EQUIPENT NAME: LOCATION: MONTH: EQUIPMENT CLASSIFICATION:
DEPARTMENT C/O: ENGINEERING
CHILLERCHILLER 1
1 (SHELL-TUBE) 2F/CHILLER ROOM MAY HVAC
No. Check Items Standard Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
0900H
1 Chiller Panel Functioning
1400H
0900H
2 Chiller Electrical System No Burns/Cut/Dirt
1400H `
0900H
3 Chilled Water Entering Temp. 6-20 °C
1400H
0900H
4 Chilled Water Leaving Temp. 5-15 °C
1400H
0900H
5 Evaporator Pressure(Chamber 1) 300-450 kPa
1400H
0900H
6 Evaporator Pressure(Chamber 2) 300-450 kPa
1400H
0900H
7 Evaporator Temperature(Chamber 1) 0.7-12.47 °C
1400H
1400H
8 Evaporator Temperature(Chamber 2) 0.7-12.47 °C
1400H
1400H
9 Condenser Pressure(Chamber 1) 784-1275 kPa
1400H
1400H
10 Condenser Pressure(Chamber 2) 784-1275 kPa
1400H
1400H
11 Condenser Temperature(Chamber 1) 30.6-48.7 °C
1400H
1400H
12 Condenser Temperature(Chamber 2) 30.6-48.7 °C
1400H
DAILY CHECKSHEET DAY SHIFT LOCATION New Building
DEPARTMENT: SECTION: MONTH MAINT. SUPERVISOR MAINT. MANAGER
MAINTENANCE UTILITY/HVAC KANNETSU ________________ ________________
No. Check Items Standard Method Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
9:00 PM
1 Main Tank Water Level above yellow mark visual
2:00 AM
9:00 PM
2 RO Tank Water Level above yellow mark visual
2:00 AM
9:00 PM
3 Chemical Tank Level above 1/2 level visual
2:00 AM
9:00 PM
4 no damage visual
2:00 AM
9:00 PM
5Condenser Pressure(Chamber 2)less than 40µS/cm visual
2:00 AM
9:00 PM
6 Pre-filter Flow Rate 11 L/min visual
2:00 AM
9:00 PM
7 Post-filter Flow Rate 2.4 L/min visual
2:00 AM
HP: 1.5-3 Mpa 2:00 PM
8 Cooling Unit 1 visual
LP: .45-7 Mpa 2:00 PM
HP: 1.5-3 Mpa 2:00 PM
9 Cooling Unit 2 visual
LP: .45-7 Mpa 2:00 PM
HP: 1.5-3 Mpa 2:00 PM
10 Cooling Unit 3 visual
LP: .45-7 Mpa 2:00 PM
HP: 1.5-3 Mpa 2:00 PM
11 Cooling Unit 4 visual
LP: .45-7 Mpa 2:00 PM
HP: 1.5-3 Mpa 2:00 PM
12 Cooling Unit 5 visual
LP: .45-7 Mpa 2:00 PM
HP: 1.5-3 Mpa 2:00 PM
13 Cooling Unit 6 visual
LP: .45-7 Mpa 2:00 PM
9:00 PM
14 Pressure .25-.27 visual
2:00 AM
9:00 PM
15 Temperature 20-21 visual
2:00 AM
no abnormal 9:00 PM
16 Pumps visual
condition 2:00 AM
First Technician 9:00 PM
Second Technician 2:00 AM
Maintenance Engineer weekly
Working Instruction Remarks :

1. Draw ( - ) for Sunday and holiday in the check box.


2. Draw ( * ) for No Operation in the check box and indicate the date of no operation in the
remarks part.
3. Draw ( o ) if there is no trouble and ( x ) if there is trouble and then indicate the trouble
in the Remarks check box.
4. Ensure that the unit is checked at the specified time.
5. Log the actual reading of the specified check items.
6. Re-routing of checking will be :
Maintenance Technician: Daily
Maintenance Engineer: Twice a Week
7. If the measured values does not match the stadrad, report to Utility/HVAC person in charge.
8. If a cooling unit is off, the values of measured at low and high pressure side must be equal. Record the values.

EMF - 02 -64
October 10, 2016
DAILY CHECKSHEET DAILY CHECKSHEET
EQUIPENT NAME: LOCATION: MONTH: EQUIPMENT CLASSIFICATION: DEPARTMENT C/O:
CHILLER 1 (SHELL-TUBE)
CHILLER 1 2ND MAY HVAC ENGINEERING
FLOOR/CHILLER
No. Check Items Standard Time 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
ROOM
0900H
1 Chiller Panel
1400H
0900H
2 Chiller Electrical System
1400H
0900H
3 Evaporator Water Supply Temp.
1400H
0900H
4 Evaporator Water Return Temp.
1400H
0900H
5 Evaporator Pressure(Chamber 1)
1400H
0900H
6 Evaporator Pressure(Chamber 2)
1400H
0900H
7 Evaporator Temperature(Chamber 1)
1400H
1400H
8 Evaporator Temperature(Chamber 2)
1400H
1400H
9 Condenser Pressure(Chamber 1)
1400H
1400H
10 Condenser Pressure(Chamber 2)
1400H
1400H
11 Condenser Temperature(Chamber 1)
1400H
1400H
12 Condenser Temperature(Chamber 2)
1400H
1400H
13 Compressor 1 (Exhaust Temp)
1400H
0900H
14 Compressor 1 (Suction Temp)
1400H
0900H
15 Compressor 2 (Exhaust Temp)
1400H
0900H
16 Compressor 2 (Suction Temp)
1400H
0900H
17 Anti-Freeze 1 Temperature
1400H
0900H
18 Anti-Freeze 2 Temperature
1400H
0900H
19 Unit Running Hours
1400H
0900H
20 Unit Run Count
1400H
0900H
21 Compressor 1 Running Hours
1400H
0900H
22 Compressor 2 Running Hours
1400H
0900H
23 Times Compressor 1 Turned-On
23 Times Compressor 1 Turned-On
1400H
0900H
24 Times Compressor 2 Turned-On
1400H