Professional Documents
Culture Documents
Nx700-Mwlink Nplus Sereis
Nx700-Mwlink Nplus Sereis
Nx700-Mwlink Nplus Sereis
NX70-CPU70P2, NX-CPU700P
Multi Wire Link Unit
User's Manual
CONTENTS
1-5. Specification.....................................................................
1-5-1. General Specification.....................................................
1-5-2. Performance Specification...............................................
1-5-3. Transmission Cable Specification.....................................
1 System Configurations and Specification
1-1. Features
● Realization of communication among PLCs with ease
As wire cables are used in transmission lines, it is easy to wire and install them.
As NX700/NX70 PLC are connected on Multi-drop mode, it is easy to
communicate among PLCs.
MW-Link System can offer three kinds of communication functions among PLCs,such as
① PLC Link function ② Data transmission ③ Remote programming
By using link register(W) x 128 words and link relay (L, M) x 1024 points transmitted to cyclic,
PLC Link communication can freely and easily share data among PLCs connected with MW-Link
unit (for NX70, NX700).
NOTES :
·It can be used only among MW-Link Units(16 units in the maximum) set to PLC Link mode.
("Mode selector switch No.1" in front of MW-Link unit. must be OFF to use PLC Link mode )
·One CPU can control a maximum of 2 Link units. (MW-Link).
·The units in PLC Link mode are designated as PLC LINK0 and PLC LINK1 starting
with the unit which is closest the CPU.
● In accordance with ON/OFF status of link relay L0.0 in "station 02 PLC", the contents
of "station 01 PLC" control can be changed.
● If you input [data of M0] into [link register W0] in "station 02 PLC", "station 01 PLC"
reads [the data of W0] and inputs them into [M0].
In accordance with [SEND] and [RECV] programs, which are ladder commands of PLC, data
transmission functions can transmit or receive contact(bit)/ data(word) information of 16 words in
the maximum. (You can set any of NX70, NX700 MW-Link)
Ladder programs on the other PLCs are not needed, and data transmission function can be
used among the units connected with W-Link,MW-Link unit (for NX70, NX700)
(Regardless of PLC link mode, it can use all of 16 units in the maximum.)
NOTES :
● This function can be performed between all of the stations(Max. 16) in the same loop.
● This function is available for all of the MW-Link units installed in a single CPU unit.
● For more details, see「3-3. Data Transmission」.
(EXAMPLE 1)
R0.0
SEND
NT = 1:4
TO = 6:200
FROM = 1:W100
"station No.1 PLC" sends the data, stored in the data registers starting with W100, to
the data registers starting with W200 of "station No.4 PLC".
1 System Configurations and Specification
NOTES :
● This function can be performed between all of the stations(Max. 16) in the same loop.
● This function is available for all of the MW-Link units installed in a single CPU unit.
● For more details, see「3-4. Remote programming」.
● This function can be performed in only WinGPC
WinGPC
Power unit
CPU unit
h In the network connected with MW-Link unit( for NX70, NX700), PLC NX Series
are handled in the same way.
h As maximum as 2 MW-link units can be installed to a CPU unit.
(The unit which has link function such as MW-link unit are included to
2 units in the maximum)
● One CPU unit with 2 MW-link units installed can configure three networks with Loops.
(Enable to configure 2-LOOPS)
● In System B in the below figure, network Station No.1∼ Station No.4 and Station No.1
∼ Station No.3 are configured in 2 Loops.
● System B can send/ receive data transmitted between two Loops(networks) to PLC of
the other Loop by the commands of [SEND] and [RECV] from Ladder program.
Station No.3
Station No.1 Station No.2
System A Station No.2 System B
System C
NX-CPU NX-MWL NX-MWL NX-X16 NX-X32 NX-X64
Twisted-Pair Cable
(2-Wire) Twisted-Pair Cable
(2-Wire)
③ ④
5
4
3
2
1
ON
1 System Configurations and Specification
NX70-MWLINK
Display of operation modes
MWLINK
2
1
ON
1 System Configurations and Specification
NX70/NX700
MW-LinkUnit
NX70-MWLINK NX-MWLINK
MWLINK
MWLINK
○ : Turn ON, ◑ : Fast flashing (T=0.2s), ◐ : Slow flashing (T=1.0s), ● : Turn Off
Operation status
LEDs Description
W-Mode
○ : Normal
Communication
COM.
status
● : Comm. error (cannot transfer)
(Note 1) Examples of other errors: transfer error, out of the range of link unit numbers, duplicated station
number, and duplicated link area allocation.
(Note 2) PLUS CPU don't support W2-MODE.
1 System Configurations and Specification
LINK NO.
· Set the switches in upper digits(10 digit) and low digit(1 digit)
to the number you want by turing the dial in the center, using
(+) screw driver. For example, if you set station number(Link
no.) to 13, set upper digits to "1", and low digit to "3".
Notes
● Select operation mode and set terminal station by using this DIP switch.
·In operation of MW-LINK unit, there are two ways. One is that the operation is done in PLC Link
mode,
and the other is that the operation is not done in PLC Link mode.
(It is determined by mode selector switch No.1.)
·Station number which operate in PLC Link mode must be assigned station number(Link no.) within
the range of 01 to 16.
·If you change the switch and supply power turns ON, the selected mode will operate.
● When operating in PLC Link mode ( only 01 - 16 units) (Switch No.1 : OFF)
You can operate 1) PLC link function
2) Data transmission function
3) Remote programming function
* PLC LINK LED will turn ON.
● When not operating in PLC Link mode ( 01 - 16 units) (Switch No.1 : ON)
You can operate 1) Data transmission function
2) Remote programming function
* PLC LINK LED will turn OFF.
·When the settings of terminal station is not correct, it can cause transmission errors.
MODE SW.
Switch No. Description
1 ON -- Not PLC link mode
1
(PLC Link mode setting) OFF -- PLC link mode
2 2 Not used
3 ,4 ON -- Terminal station
3 (Terminal station setting) OFF -- Not terminal station
● Select operation mode and set terminal station by using this DIP switch.
·In operation of MW-LINK unit, there are two ways. One is that the operation is done in PLC Link
mode,
and the other is that the operation is not done in PLC Link mode.
(It is determined by mode selector switch No.5.)
·Station number which operate in PLC Link mode must be assigned station number(Link no.) within
the range of 01 to 16.
·If you change the switch and supply power turns ON, the selected mode will operate.
● When operating in PLC Link mode ( only 01 - 16 units) (Switch No.5 : OFF)
You can operate 1) PLC link function
2) Data transmission function
3) Remote programming function
* PLC LINK LED will turn ON.
● When not operating in PLC Link mode ( 01 - 16 units) (Switch No.5 : ON)
You can operate 1) Data transmission function
2) Remote programming function
* PLC LINK LED will turn OFF.
·When the settings of terminal station is not correct, it can cause transmission errors.
5 Funtion Mode setting (W/ W2-Mode setting) (You must set to W MODE.)
4 Communication Speed setting (W2-Mode Used)
3 PLC Link mode setting (ON -- Not PLC link mode
2 OFF -- PLC link mode)
1
Terminal station setting : (ON -- Terminal station
OFF -- Not terminal station )
ON
Setting contents
No. Item
W-MODE W2-MODE
Set to terminal 1
1 전부 ON 2
station
Terminal OFF ON
station
Not Set to 1
2 전부 OFF 2
terminal station
OFF ON
※ Notes
* The settings of the mode selector switches (1) and (2) should always be changed with the power off. The setting will
be effective the next time that the power is turned on.(if the setting is changed with the power on, be aware that the
setting in effect when the power was turned on will remain effective.)
* Only the settings of the mode selector switches (1) No. 1 and No. 2(terminal station settings) will be effective at the
instant that they are changed.
1 System Configurations and Specification
Transmission Transmission
cable cable
+ +
+
- -
-
F.G F.G F.G
Shield Shield
Notes
● Refer to " 1-5-3. Transmission Cable Specification" details about the transmission cables.
● The total length of the transmission Cable in a single network should not be more than
800m (2624.67ft) .
● In W-Link Unit, you can communicate by connecting up to 32 stations in the maximum.
● Transmission guaranteed distance is the maximum distance between MW-link units of
two end terminals. There is no special restriction for distance in the middle between MW-link
units if it is in the range of distance.of transmission guaranteed.
● You should be careful not to connect units in a star-burst arrangement as shown below.
X
1 System Configurations and Specification
(Example)
●
●
UNIT No. 0 6
MODE SW.
5 W mode
4
3 PLC LINK mode
2
1 Terminal station
OFF ON
1 System Configurations and Specification
1-5. Specification
Conductor
Resistance Max 16.8 Ω/km (at 20℃)
For 800m
Insulation material Polyethylene
distance
Cable Insulation thickness Min 0.5mm (0.020inch)
Jacket diameter Min 8.5mm (0.335inch)
Size Min 0.5mm2 (AWG20 or larger)
Conductor
Resistance Max 34.4 Ω/km (at 20℃)
For 700m
Insulation material Polyethylene
distance
Cable Insulation thickness Min 0.5mm (0.020inch)
Jacket diameter Min 7.8mm (0.307inch)
● Crimp Terminal
Be sure to connect the cables and the transmission terminals correctly using crimp terminals.
2-1. Dimensions................................................................
2-2. Installation Procedure................................................
2-3. Installing MW-Link Units..............................................
2-3-1. Location of MW-Link Units........................................
2-3-2. Installation Example................................................
2-3-3. How to Install MW-Link units....................................
2-1. Dimensions
NX-MWLINK
MWLINK
COM. PLC
ERR. Link
W-Mode SPEED
W2-Mode TERM
115.5
35.0
104.0
NX70-MWLINK
MWLINK
105.0
35.0
87.0
2 Dimensions & Installation
● However, PLC Link function available up to 2 units for one CPU unit.
The units are designated as 「PLC LINK0」 and 「PLC LINK1」 starting with the unit which is
closest the CPU.
(Slot No.) 0 1 2 3 4 5 6 7
Master
backplane Unit ● You can install up to 2 Link units to any Slot from
SLOT 0 ~ SLOT 7. The Link units are designated
Power Unit
as「LINK 1」,「LINK 2」starting with
the unit which is closest the CPU unit.
CPU Unit
● In addition, you can use 2 Link units out of them as
PLC Link mode.
They are called「PLC LINK 0」and「PLC LINK 1」
starting with the unit which is closest the CPU unit.
2 Dimensions & Installation
(Slot No.) 0
[ Sample 1 ] Installed at slot 0
1. Insert fixing projection into the unit 1. Remove screw fixed on mother
hanging chin. board with driver.
『PUSH』
push device
1 screw
2 Dimensions & Installation
· Install and remove the MW-Link Unit only when all of the power is turned OFF.
· Be sure to install the MW-Link Unit securely in the Master Backplane.
· Do not drop the MW-Link Unit or apply excessive force to it.
· Do not allow pieces of wire or other objects to fall into the unit when making the wiring
connections.
· The system should only be used within the conditions for which it is rated.
See the specifications.
● However, PLC Link function is available only in PLC which is set to PLC Link mode
● When set to PLC Link mode (Mode Selector Switch No.1 : OFF )
1) PLC Link communication is available. Station No. should be selected within
No. 01 ~ No. 16.
2) Data transmission function is available.
3) Remote programming function is available.
● When Not set to PLC Link mode (Mode Selector Switch No.1 : ON )
1) Data transmission function is available.
2) Remote programming function is available.
(PLC Link communication is not available in the this mode)
● You can communicate between stations with the functions which lines show as in the figure below.
PLC Link
communication
Data transmission
Remote programming
If it is CPU unit in the same LOOP, connect the programming For more
Remote
Tool(WinGPC) to CPU unit nearby. details,
programming function
You can operate programs of PLC in the remote place see 3 - 4
5
○ Use to PLC Link mode……………… Turn OFF.
4
○ Not use to PLC Link mode………… Turn ON.
3
2
※ In the shipping of them, all of them are set to OFF
(PLC Link mode). 1
※ The figure on the right side shows that the Mode OFF ON
selector switch No.3 is OFF.
Notes
1. Before you set the "Mode Selector Switch", turn OFF the power.
· When power turned ON, it runs in the operation mode which was set before.
(Therefor The Link unit's mode are activated when the Power is turned ON.)
· If you change "the Mode Slelector Switch No. 3" while the Power is ON, its operation
mode doesn't change.
2. When the MW-Link Unit is set for "PLC Link mode" ,「PLC LINK LED」will be turn ON.
NX70-MWLINK
「PLC LINK LED」turns ON
MWLINK
( when "the Mode Slelector Switch No. 3" is set to OFF) COM.
ERR.
PLC Link
SPEED
W-Mode TERM
W2-Mode
3 Link System Function
OFF
PLC Link mode ● PLC Link………ON
ON
Not PLC Link mode ○ PLC Link ……OFF
● STEP 1
Check the setting for station No.(Unit No.), terminal station and PLC Link mode.
1) Check if the station No. exceeds the allowed range(01-16), or if it is overlapped.
2) Check if the Link units of both ends are set to terminal.
3) Check if the Link unit for PLC Link communication is set to「PLC Link mode」, or if the station No.
is set within range of No. 1 ~ No. 16.
● STEP 2
Turns ON Power.
● STEP 3
● STEP 4
● PLC Link communication is one of the functions available with a MW-Link System.
● In a PLC Link communication, data is shared between PLCs connected with Link units by writing
or reading data in memory areas called Link register (W) and Link relay(L, M) which exist in
each PLC.
● Since no special instruction for data communication are required when using the PLC Link
function, you can create programs without needing complicated procedures.
● PLC link communication is the data sharing communication by transmitting Link register(W) and
Link relay(L, M) between PLCs connected with Link units with cyclic
● They are called「PLC Link 0」and「PLC Link 1」starting with the unit which is closest the
CPU unit.
● Turning ON the external output relay R3.0 in station No.06, when the external input
relay R0.0 in station No.1 is turned ON. (by using the Link relay L0.0)
R0.0 : ON
R3.0 : ON
Station 01 Station 06
L0.0 : ON
● The contents of data register M0 in station No.1 will be transferred to the data
register M1 in station No.6. (by using the Link register W0)
W0
M0 $ 1234 $ 1234
M1
Station 01 Station 06
● The send area relative addresses in the PLC Link Area should not be overlapped in one network
(Loop). If the send area addresses overlap each other in the same loop, an error will occur.
● Allocation of link area should be set by ladder program.
63 127
0 128
M0.0 ~ M63.15
PLC PLC W128 ~ W255
Link 1 : 1,024 points Link 1 : 128 words
63 255
● PLC Link communication is one of the functions available with a MW-Link System.
● Each CPU has 2 PLC Link Areas available for :
· PLC Link 0
· PLC Link 1
● Each PLC Link Area is composed of 2 types of areas (a Link relay area and a Link register
area) and the following areas are available as PLC Link Areas :
·PLC Link 0 :
Link relay area .... Max. 1,024 points for link relays (L00.00 to L63.15)
Link register area ...... Max. 128 words for Link registers (W0 to W127)
·PLC Link 1 :
Link relay area .... Max. 1,024 points for Link relays (M00.00 to M63.15)
Link register area ...... Max. 128 words for Link registers (W128 to W255)
3 Link System Function
Notes
● One CPU can control a maximum of 2 PLC Link units for PLC Link function.
● The units in PLC Link Mode are designated as "PLC LINK0" and "PLC LINK1" starting with
the unit which is closest the CPU unit.
● Any area which is not used as a part of the PLC Link can be used as normal internal relays
and data registers.
● When only one Link unit is installed, the area「for PLC Link1」can't be used.
● In case of only one Link unit is installed, Link relay available is 1024 points in the maximum
and Link register available is 128 word in the maximum.
Example of Link area Allocation * <for PLC Link1> is all the same.
L30.0 50
Sending area Sending area
L40.0 90
Receiving area
Receiving area
L63.15 127
L63 W127
3 Link System Function
hThe data in the ˝Send 1˝area is transferred to the ˝Receive 1˝area in stations 2, 3 and 4.
hThe data in the ˝Send 2˝area is transferred to the ˝Receive 2˝area in stations 1, 3 and 4.
hThe data in the ˝Send 3˝area is transferred to the ˝Receive 3˝area in stations 1, 2 and 4.
hThere is no send area in the station number 04 (Link No. 04) in this loop.
hThe send and receive area settings must be assigned for both the Link relays (L) and the Link
data registers(W)
hThe send area addresses in each PLC Link Area (PLC Link0 and PLC Link1) should not be
overlapped in the same loop. If the send area relative addresses are overlapped, an error will
occur. Be sure to allocate non-overlapping the send areas.
Receive
Send
Receive
Receive
3 Link System Function
● In PLC Link communication, allocates Link areas in accordance with its using conditions.
Sending area allocation of Link areas should be set by the LADDER program.
● Setting should be made by words. Allocates Link relay(L) by 1 word(16 points).
Notes
0 :individual renewal
F2.2 Set Link data(relay/ register) renewal mode (Note 1)
1 :batch renewal
0 :individual renewal
F 2. 10 Set Link data(relay/ register) renewal mode (Note 1)
1 :batch renewal
F 2. 11 Use system
for
F 2. 12 Permit Link data(relay/ register) sending 1 :permit sending PLC Link2
Note 1:
2) Batch renewal : Data is renewed when data is received from all link modes registered to
LINK Network.
3 Link System Function
F1.0
LET F1.0 : ON for the first scan
LET : command for WORD data change
D = SR252
S = $040A
F2.0
(SET) Request to set Link sending area
F2.4
(SET) Request to permit
Link data(relay /register) sending
F2.5
(SET) Request to permit
Link data(relay /register) receiving
F2.2
(RST) Set Link data(relay /register) renewal
mode to individual renewal mode
Description
● First, set 7 words from L4.0 to L10.0 of the link area from SR252 (sending area setting
register in Link0) to the sending area and then set F2.0 in the first scan.
● Second, Set sending area of the Link data(relay /register) and start sending/ receiving by
requesting not only to set CPU unit to perform it (when CPU unit finishes it, the system will
initialize it into '0') ,but also to permit sending (F2.4) and receiving(F2.5).
3 Link System Function
● The following special relays can be used for checking whether each MW-Link
Unit in a loop is in PLC Link Mode or not.
● The CPU mode(RUN or PROG.) for each station in the PLC Link is checked
using the special relays.
● Turn ON when it is in [RUN mode]. ● Turn OFF when it is in [PROG. mode].
● It is convenient to use it when checking in remote programming.
● When you use each contact relay in the program, shift it to BIT register area.
2) When station No. doesn't overlapped, read the status of the special data register in the
Loop where errors occurred, and check if there is any Link unit where link area(sending
area) is overlapped.
3 Link System Function
F3.0 When overlap error occurred in the Link LOOP1, turn ON. 1: errors occurred
- station number
F3.1 When overlap error occurred in the Link LOOP2, turn ON. overlapped
- problem in
F3.2 NOT USED. communication cables
F3.3 When the first Link Unit was installed, turn ON. 1: installed
F3.4 When the second Link Unit was installed, turn ON. 1: installed
F3.5 N/A
Display that data was received through the first Link unit from
F3.6 1: data receiving completed
the other Link Units
Display that data was received through the second Link Unit
F3.7 1: data receiving completed
from the other Link Units
F3.8 N/A
Display that Link area was overlapped
F3.9 1: LINK area overlapped
- Error regardless of LINK ERROR MODE(F2.3) setting
Display that the first Link Unit run to SEND and RECV 0: running completed,
F3.10
commands sending available
Display that the first Link Unit failed to SEND and RECV
F3.11 1: running failed re-sending
commands
Display that the second Link Unit run to SEND and 0: running completed,
F3.12
RECV commands sending available
Display that the second Link Unit failed to SEND and
F3.13 1: running failed, re-sending
RECV commands
F3.14 N/A
F3.15 N/A
3 Link System Function
2) When a "send area overlap error" occur within a Loop, the contents of special data
register write overlapped station No.
SR377(LOOP1), SR378(LOOP2)
● In case of「send area overlap errors」, CPU will stop operating the program and
turn ON ERROR LED of CPU unit.
LINK 1
LINK 1
C P U
C P U
C P U
MSB LSB
SR377
0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
SR378
Station NO.1
PLC Link 1 PLC Link 0
Station NO.2
C C
P P
U U
PLC Link 0
In order to handle data from「PLC Link 1」when you operate PLC Link communication between
PLCs connected as in the above figure, it is necessary to withdraw those numbers as many as
areas in「PLC link 0」.
Example 1) If you transmit Link relay L10.15 in station No.2 in the above figure by station No.1, the data will be
saved to Link relay M10.15 in station No.1.
Example 2) If you transmit Link register W130 in station No.1 in the above figure, the data will be saved to Link
register W2 in station No.2.
3 Link System Function
SEND
Basic Instruction format NN? : Number
R NT=NN1:NN2
TO=NN3:NR4 NR? : Register or Number
FR=NR5:RR6 RR? : Register
Read the designated words (NR5) from register (RR6), and write it orderly to
designated position(NR4) of register type (NN3) for station (NN2) on designated Link Network(NN1).
Description
1. NN1 : Link Network number (1,2) ex. Network using first installed Link unit is "1")
NN2 : Station number connected to the Link network (1~16)
NN3 : Register type you want to write
( 0:L register, 1:M register, 2:R register, 3:K register, 4:T/C setting value, 5:T/C present
value, 6:W register, 7:F register)
NR4 : Start address of the designated register
NR5 : Data length to send (1~16 words)
RR6 : Start address of register to send
2. Take caution in programming not to duplicate it in the Link network within 1 scan by execu t i n g
after completing scan.
Station 01 Station 04
3 Link System Function
Send the value of bit register(NB5) to designated bit location(NR4) of register type
(NN3) for station(NN2) on the designated Link Network(NN1)
Description
1. NN1 : Link Network Loop number (1,2) ex. Network using first installed Link unit is "1")
NN2 : Station number connected to the Link network ( 1~16)
NN3 : Register type you would write
(0 :L register, 1 :M register, 2 :R register, 3 :K register, 4 :T/C setting value,5 :T/C
present value, 6 :W register, 7 :F register)
NR4 : Bit location to specify, display in hexadecimal
ex) If you want to specify 5th bit of 3rd word
NR4 == $ 0 0 3 5
BR5 : Bit address to send
2. Take caution in programming not to duplicate it in the Link network within 1 scan by
execu t i n g after completing scan.
SENDB
command
When the first Link unit is installed(F3.3)
and sending is completed through the Fr To
first unit(F3.10), Bit data
the "station No.1 PLC" sends the bit value
of F1.3 to R0.1 (2:$0001) of "station No.3
PLC" connected to Loop 1.
Station 01 Station 03
3 Link System Function
Read the designated word number (NR1) from the designated position(NR6) of register
type(NN5) for the station(NN4) on the designated Link Network(NN3) and write it into
register(RR2) orderly.
Description
RECV
When the first Link unit is installed(F3.3) command
and sending is completed through the first
unit(F3.10), To Fr
Word data
the "station No.1 PLC" receives the word
value of F1 register of "station No.3 PLC"
connected to Loop 1 and saves into R2
register
Station 01 Station 03
3 Link System Function
Read the value of bit position(NR6) of register type(NN5) for station (NN4) on the
designated link network(NN3) and write it into bit register(BR1)
Description
RECVB
When the first Link unit is installed(F3.3) command
and sending is completed through the first
unit(F3.10), To Fr
Bit data
the "station No.1 PLC" receives the bit
value of F1.2 (7:$0012) of "station
No.4 PLC" connected to Loop 1 and saves
the value into R2.0 .
Station 01 Station 04
3 Link System Function
● Commands of data sending(SEND) and data receiving(RECV) can be run only one at
a time. In addition, as it requires data sending and receiving in running the commands,
actual sending and receiving should be done after finishing program scan.
● In order to check the status of running the commands when you transmit data,
use special relay (Flag) or data register.
* When you run several commands of data sending and receiving, make sequence
programs which will avoid running simultaneously by using special relay as follows.
Special relay and data register for checking the status of running data transmission
● When data is not transmitted within a normal time, there will happen「abnormal completion」
with detection of time-out error.
● Limitation time for running data transmission will be set automatically by CPU unit, and its
time is mostly 1 second. If it doesn't have any response from the other within a second,
CPU unit will set
● F3.11 (LOOP1), F3.13(LOOP2), and continue retry periodically.
3 Link System Function
Notes :
WinGPC
■ Checking-methods
LSB(bit)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Abnormal transmission
(Link impossible)
Station No.overlap error
Overlap error in Link sending area
Supply power
NX70-MWLINK
MWLINK
Yes
Initial setting
No
② Read the status of special data register on the LOOP checked in special relay,
and check the overlapped station No. of the Link area
In case of LOOP No.1 SR377
In case of LOOP No.2 SR378
MSB LSB
SR377
0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
SR378
4-2. Troubleshooting
No1.
Check to see whether all of the units are corrected installed on the backplane.
No2.
Check to see if the POWER LED on the power supply unit is lighted. if not, refer to
the NX PLC hardware manual
No3.
Check to see if the ALARM and ERROR LEDs on the CPU are lighted
To see if the mode being used is appropriate for the objective, check the mode
selector switches on the rear panel
Appendix
Special
Contents Remarks
relay
F 2. 0 Request to set Link relay for sending 1 :request setting
0 :individual renewal
F 2. 2 Set Link data(relay/ register) renewal mode (Note 1)
1 :batch renewal
0 :individual renewal
F 2. 10 Set Link data(relay/ register) renewal mode (Note 1)
1 :batch renewal
F 2. 11 Use system
for
F 2. 12 Permit Link data(relay/ register) sending 1 :permit sending PLC Link1
F 2. 13 Permit Link data(relay/ register) receiving 1 :permit receiving
F3.0 When overlap error occurred in the Link LOOP1, turn ON. 1: errors occurred
- station number
F3.1 When overlap error occurred in the Link LOOP2, turn ON. overlapped
- problem in
F3.2 NOT USED.
F3.3 When the first Link Unit was installed, turn ON. 1: installed
F3.4 When the second Link Unit was installed, turn ON. 1: installed
F3.5 When the third Link Unit was installed, turn ON. 1: installed
Display that data was received through the first Link unit from 1: data receiving
F3.6
the other Link Units completed
Display that data was received through the second Link Unit 1: data receiving
F3.7
from the other Link Units completed
Display that data was received through the third Link Unit from 1: data receiving
F3.8
the other Link Units completed
Display that the first Link Unit run to SEND and RECV 0: running completed,
F3.10
commands sending available
Display that the first Link Unit failed to SEND and RECV 1: running failed,
F3.11
commands re-sending
Display that the second Link Unit run to SEND and RECV 0: running completed,
F3.12
commands sending available
Display that the second Link Unit failed to SEND and RECV 1: running failed,
F3.13
commands re-sending
Display that the third Link Unit run SEND to and RECV 0: running completed,
F3.14
commands sending available
Display that the third Link Unit failed to SEND and RECV 1: running failed,
F3.15
commands re-sending
Appendix1 Special Relay & Special Data Register
■ Flag which displays station number in Link and receiving status : F4, F5, F6, F7
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0 0 1 0 0 0 1 0 0 0 0 0 0 0 0 1
[Description]
Link station No.1,No.10 and No.14 display the Link operation with the first Link unit(Loop1).
● Flag which displays sending source of the received link data (F4,F5)
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0 0 1 0 0 0 1 0 0 0 0 0 0 0 0 1
[Description]
Display that the receiving is completed through Link station No.1, No.10 and
No.14.
Appendix1 Special Relay & Special Data Register
1~64 words
SR254 Set the sending area for Link relay (M0~M63)
PLC (0~1024 points)
Link 1
SR255 Set the sending area for Link register(W128~W255) 1~128 words
08 0A
The first No. of register to transmit The last No. of register to transmit
[Description]
If the contents of SR252 is '080AH' as shown in the example above, it means to set
three words of its Link relay(word) L8, L9 and L10 to the sending area.
Appendix1 Special Relay & Special Data Register
■ Display the status of the other CPU operation connected with Link unit
: SR256, SR257, SR258, SR259
Status of the other station connected to If the related bit is '1', it means the
SR256
LINK NETWORK 1 (Loop1) status of RUN operation
Status of the other station connected to If the related bit is '1', it means the
SR257
LINK NETWORK 2 (Loop2) status of RUN operation
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 1
[Description]
Display that Link station No.11, No.10 and No.1 participate in the related network.
■ Display the status of the other CPU operation connected with Link unit
: SR377, SR378
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0
[Description]
Display that Link station No.10 is overlapped in the related network
Appendix2 Communication Times
Notes
● The time needed for one transmission cycle is called the transmission cycle time.
The total transmission cycle time ″Ttc″is calculated by adding the time needed for
each station token processing cycle as shown in the following equation.
Tsti = Time needed for token processing at station i (UNIT NO. i).
Tdti = Time needed for Data Transfer processing at station i (UNIT NO. i).
Tmg = Time needed for basic token management at each station after transmission
operation
·When 2 to 31 stations are linked in the loop
The Tmg value at each station should be calculated as : Tmg = 0.4 ms
·When 32 stations are linked in the loop
The Tmg value at each station should be calculated as : Tmg = 0 ms
Appendix2 Communication Times
Tpci = 0 ms
Where :
Bdti = Number of bytes needed for Data Transfer instruction.
One instruction consists of one command and one response message.
The number of bytes for each message is calculated as :
·SEND Command Message : 6 bytes + (Number of data sent) × 2
·SEND Response Message : 3 bytes
·RECV Command Message : 7 bytes
·RECV Response Message : 3 bytes + (Number of data received) × 2
Tadi = Time additionally needed for the Data Transfer operation when the station is in
PLC Link Mode.
·When the station is not in PLC Link Mode
Tadi = 0 ms
·When the station is in PLC Link Mode
Tadi = 1.0 ms
Appendix2 Communication Times
Station number 01 (UNIT No. 01) Station number 02 (UNIT NO. 02)
of Optical-Link Unit of Optical-Link Unit
Program Program
·In the above example, the operation flow from an input transition to an output
transition is explained as follows :
I/O Update :
At the time of I/O update in the CPU scan[station
number 01], the R0.0 status is taken
into CPU.
Program execution :
The external input relay R0.0 turns ON and the
L0.0 turns ON.
1
Appendix2 Communication Times
Token reception :
When the first token is passed after the reception of the buffer update signal, the send area data in
the buffer is prepared for transfer.
Data distribution :
The data are actually distributed during one transmission cycle time plus the transmission time
needed for next station after the buffer update signal only when the buffer is ready to receive the
data.
Program execution :
The Link relay L0.0 turns ON and R2.0
turns ON.
I/O Update :
At the time of I/O update in the CPU scan
[station number 02 (UNIT NO. 02)], the
R2.0status is updated.
Output transition :
The external output relay R2.0 in the station
number 02 (UNIT NO. 02) is turned ON.
Appendix2 Communication Times
Since the actual PLC Link Response Time depends upon the transmission cycle time, the
transmission timing and the time needed for CPU processing(CPU scan time) etc., the PLC Link
Response Time will deviate between the minimum and the maximum possible PLC Link Response
Times. When installing the network, these values should be taken into consideration.
where :
TidA = Input delay time of the input transition at PLC ″A″.
TscA = Scan time of PLC ″A″.
TstA = Time needed for the PLC Link processing by ″A″.
Tsti min. = Time needed for the PLC Link processing by station ″i
(UNIT NO.i)″. Here, the Tsti min. is supposed to be the shortest
time needed for processing by one station.
TscB = Scan time of PLC ″B″.
TodB = Output delay time for the output transition of PLC ″B″.
Station A
Input
(UNIT NO.A) I/O update
delay
Input
transition
TidA Buffer update I/O update
CPU scan
Station B
(UNIT NO.B)
TscB
(Approx. one scan time)
Buffer
CPU scan
Output delay
Output
transition
TodB
Appendix2 Communication Times
where :
TidA = Input delay time of the input transition at PLC ″A″.
TscA = Scan time of the PLC ″A″.
T1 = Time needed between the I/O update and the Optical-Link Unit's buffer
update.
Ttc
T1 = (1 + ) × TscA
TscA
Ttc = Time needed for one transmission cycle.
TscB = Scan time of Programmable Controller ″B″.
T2 = Time needed from the buffer update signal reception and the CPU
memory update at station ″B″.
where :
TstA = Time needed for PLC Link processing by station ″A″.
TscB = Scan time of PLC″B″.
TstB = Time needed for PLC Link processing by station ″B″.
CPU scan
CPU scan
Appendix2 Communication Times
where :
Ttc = Time needed for one transmission cycle
TscA = Scan time of PLC ″A″.
TscB = Scan time of PLC ″B″.
CPU scan
Command Response
Buffer message message
Command
message Response
Buffer message
(Approx. 2 scan time)
CPU scan