Professional Documents
Culture Documents
Page 58
Page 58
(Each Incoming / Outgoing MCCB shall have microprocessor release and variable current setting
from front, adjustable overcurrent, short circuit & earth fault protection, front extended lockable
handle, pad lockable in off position, shrouding on incomer side, termination shall be suitable for
aluminium bus bars / cables and as per specification.)
INSTRUMENTS
4 Nos. 0 to 500 Volt digital voltmeter with Voltmeter Selector Switch & Protective SP MCB
(96mm square) (one for each Incoming Breaker).
4 No. 0 to 1600 Amp digital ammeter (96mm square) with CT's.
4 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).
4 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).
4 Sets trip circuit healthy indicating lamp (one set for each incoming breaker).
4 Sets auto trip indicating lamp (one set for each incoming breaker).
928 INCOMMING / BUSCOUPLER AIR CIRCUIT BREAKER: Each 5
Supplying with fitting and fixing panel mounting open execution 4 pole Air Circuit Breaker type
(MDO/EDO) with guide frame and 4 standard auxillary contacts in the existing cubical panel
board of the following capacity complete with making necessary connection as specified and
directed by the Dept. (ABB Emax/L & T U Power/ Siemens 3 WL/ Schneider Master pact NW)
6A trip system.
1000A Breaking capacity @ Ics=50 KA (EDO)
929 1600A Breaking capacity @ Ics=50 KA (MDO) Each 5
930 OUTGOING MCCB: Each 6
4P MCCB with Microprocessor release (Adj Over Load, Short Ckt & neutral setting incl earth
protection)
Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with
microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, neutral
adjustable with earth fault protection without enclosure of the following capacity complete with
making necessary connection as approved, specified and directed by the dept.
36KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make)
63A
931 50KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make) Each 4
100A
932 160A Each 3
933 250A Each 4
934 400A Each 2
935 630A Each 5
936 EXTERNAL LIGHTING PANEL (OUTDOOR TYPE)- Set 1
Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing &
commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin
proof Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet
complete with following equipments, including digital ammeter with inbuilt ammeter selector
switch, digital voltmeter with inbuilt voltmeter selector switch, indicating lamps, CT's, internal
wiring with suitable size wires / cable, interconnection, painting complete as per specification &
drawing.
INCOMING
1 No. 0 to 500 Volt digital voltmeter with inbuilt selector switch.
1 No. 100 Amp digital ammeter with inbuilt selector switch and CT's.
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
1 Set 24 Hrs TSQ Timer
1 Set 100 Amp, 4P Contactor & A/M switch and Push Button.
BUS BARS
100 Amp TPN aluminium busbar.
Panel described as above. (Incoming / Outgoing MCCB / MCB shall be paid separately. However
the fabrication cost for Incoming / Outgoing MCCB / MCB shall be included in above.)
[58/80]