KEY PLAN :

GENERAL NOTES:-

LIGHTING: CONTAINMENT SYSTEM: POWER:


1. ALL DIMENSIONS ARE IN MILLIMETRES, UNLESS OTHERWISE STATED. 1. ALL DIMENSIONS ARE IN MILLIMETRES, UNLESS OTHERWISE STATED.
2. ALL CONDUITS ARE Ø25mm PVC, FOR EMBEDDED 25mm EMT FOR EXPOSED. LEGENDS & ABBRIVATION
2. PROVIDE PULL BOX IN EVERY 25M OF CONDUIT RUN.
1. DRAWINGS ARE TO BE READ IN CONJUNCTION WITH OTHER ARCHITECTURAL, 3. PULL BOX FOR CONDUIT RUNS EXCEEDING 25M IN LENGTH.
STRUCTURAL AND MEP DRAWINGS. 4. REFER TO '' MISCELLANEOUS DETAILS '' FOR GUIDLINES TO INSTALLATIONS.
3. USED 100X100X38mm STEEL BACK BOX WHERE 3 OR MORE CONDUITS ARE TERMINATED ON THE
2. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED. 5. ALL POWER CABLES AND WIRES TO BE USED AS PER PROJECT SPECIFICATIONS.
SAME BOX.
3. ALL CABLES ARE CU/XLPE/PVC CABLES,UNLESS INDICATED OTHERWISE. 6. ALL RECEPTACLE OUTLETS ARE GROUNDING TYPE.
4. TERMINATE ALL FEEDER CONDUITS FOR POWER SUPPLY TO LIGHTING CIRCUITS IN A BACK BOX 4. CABLE TRAY ROUTES ARE COORDINATED WITH OTHER SERVICES. 7. ALL RECEPTACLE OUTLETS ARE GROUNDING TYPE.
INSTALLED FLUSH IN CONCRETE WALL ABOVE ASSOCIATED PANEL BOARD AT A MOUNTING 5. EXACT LOCATION OF OUTLETS, ISOLATORS SWITCHES, ETC ARE FULLY 8. THE LENGTH OF FLEXIBLE CONDUITS USED WITH
HEIGHT 1850 AFFL TO BOTTOM OF BOX. (BOX SIZE TO SUIT NUMBER OF CONDUITS) COORDINATED WITH OTHER SERVICES. PRIOR INSTALLATION 9. THE LENGTH OF FLEXIBLE CONDUITS USED WITH
5. USE Ø25mm PVC CONDUITS WITH ALL LIGHTING CIRCUITS 6. CABLE TRAY SIZING EQUIPMENT TERMINATIONS SHALL NOT EXCEED 1800MM.
6. REFER TO SEPARATE SINGLE LINE DIAGRAM FOR THE LIGHTING CONTROL SYSTEM FOR 6.1-ADD UP ALL CABLE DIAMETERS 10. CO-ORDINATE WITH EXACT LOCATION OF MECHANICAL EQUIPMENT FOR
INTERCONNECTION BETWEEN NORMAL LIGHTING DB AND LCP. ACCURATE LAYOUT OF POWER SUPPLY PROVISIONS.
6.2-ALLOW FOR A SPACE BETWEEN CABLES EQUAL TO ONE DIAMETER
7. BOXES FOR OTHER THAN LIGHTING FIXTURE'S OUTLET NOT LESS THAN 100mm SQUARE 11. FOR BRANCH CIRCUIT WIRE SIZES , REFER TO RELAVANT PANELBOARD
OF THE BIGGER CABLE SIZE.
LOAD SCHEDULES UNDER
EXCEPT THAT 100mmX50mm BOXES MAY BE USED WHERE ONLY ONE RACEWAY ENTERS THE 6.3-ALLOW FOR 25% SPARE CAPACITY FOR FUTURE USE.
12. CO-ORDINATE WITH ALL ELV SYSTEM SUPPLIERS FOR SYSTEM
OUTLET. 6.4-ADD UP MEASUREMENTS UNDER ITEM NO'S 6.1,6.2 AND 6.3 ABOVE
POWER REQUIREMENTS.
8. BUILDING WIRES AND CABLES USED IN WIRING LIGHTING SYSTEM AS PER PROJECT 6.5-CONFIRM NEAREST STANDARD TRAY SIZE AVAILABLE IN THE MARKET.
13. REFER TO MECHANICAL DRAWINGS FOR INSTALLATION DETAILS
SPECIFICATION. 6.6-USE MEDIUM DUTY CABLE TRAY HDG.
OF MECHANICAL EQUIPMENT.
6.7-SPECIFY SPACING SUPPORT FOR THE CABLE TRAY (E.G. 1 MTR APART.)
9. LIGHTING FIXTURES IN CAR PARK ARE AS ARE MOUNTED DIRECTLY ON THE UNDER SIDE OF SOFFIT
6.8-SUBMIT SEPARATE ENLARGED, DETAILED PLAN FOR CT - SUPPORTS.
SLAB, EXCEPT WHERE SITE CONDITIONS PREVENT THIS INSTALLATION METHOD. HOWEVER AND
(AFTER APPROVED SUPPORTING MATERIALS).
WHERE IS REQUIRED, LIGHTING FIXTURES ARE SUPPORTED FROM THE SOFFIT SLAB TO AVOID
7. CO-ORDINATE ALL CONTAINMENT ROUTES/LAYOUTS WITH OTHER SERVICES
CLASHES WITH OTHER SERVICES IN THE SAME AREA OF INSTALLATION & TO MAINTAIN UNIFORM
ILLUMINATION LEVELS IN CAR PARK AREAS.
IN THE SAME AREA OF INSTALLATION. PUBLIC ADDRESS & VOICE EVACUATION SYSTEM
10. LIGHTING FIXTURE INSTALLATION DETAILS ARE IN LINE WITH THE APPLICABLE LIGHTING 1. ALL DIMENSIONS ARE IN MILLIMETERS, UNLESS OTHERWISE STATED.
DESIGN STUDY, AND SHALL REFLECT REQUIRED METHOD OF INSTALLATION & MOUNTING HEIGHTS 3. FOR PUBLIC ADDRESS & VOICE EVACUATION SYSTEM SPECIFICATIONS REFER TO
FOR INDIVIDUAL FIXTURE TYPES AND AREAS OF INSTALLATION. SPEC. SECTION 16770.
4. PUBLIC ADDRESS AND VOICE EVACUATION SYSTEM WILL BE INTERFACED WITH
FIRE ALARM SYSTEM TO BE USED FOR VOICE EVACUATION MESSAGE
ANNOUNCEMENT IN CASE OF FIRE AS PER NFPA AND BS STANDARDS.
5. ALL CABLES/WIRES FOR LOW CURRENT SYSTEMS (COMMUNICATIONS, FIRE
ALARM, ETC.) WILL BE FIRE RESISTANT LOW SMOKE ZERO HALOGEN (LSZH).
6. USE A PULL BOX FOR CONDUIT RUNS EXCEEDING 25M IN LENGTH
7. WIRE SIZE: FP-200, 2C X 2.5MM² OR AS OTHERWISE APPROVED BY THE
PUBLIC ADDRESS & VOICE EVACUATION SYSTEM SPECIALIST.
8. EXACT INSTALLATION DETAILS FOR SYSTEM COMPONENTS/DEVICES ARE
CONFORMED BY THE APPROVAL SYSTEM SPECIALIST.
9. FOLLOW RECOMMENDATIONS ISSUED BY ELV SYSTEM'S SPECIALISTS FOR THE
SELECTION OF BACK BOXES USED WITH ALL ELV SYSTEM'S
DEVICES/COMPONENTS.
10. PVC CONDUITS EMBEDDED IN CONCRETE (CEILING) SLAB WILL BE USED FOR
WIRING TO PUBLIC ADDRESS & VOICE EVACUATION SYSTEMS
CABLE TRAYS ALSO BE PROVIDED TO IMPROVE FLEXIBILITY WITH CABLE
DISTRIBUTION & FOR FUTURE USE.
(FOR LOW CURRENT CABLE TRAYS, REFER DWG.NO PD72-WH01_04-EE-121)
SECURITY SYSTEM
1. ALL DIMENSIONS ARE IN MILLIMETERS, UNLESS OTHERWISE STATED.
VOICE & DATA COMMUNICATION SYSTEM 2. FOR GENERAL NOTES & ABBREVIATIONS, LEGEND & SYMBOLS, REFER TO
DWG. NO. PD72-WH 05-EE-001-01.
3. FOR SECURITY SYSTEM SPECIFICATIONS REFER TO SPEC. FIRE ALARM SYSTEM
1. ALL DIMENSIONS ARE IN MILLIMETERS, UNLESS OTHERWISE STATED.
4. INTERFACE BETWEEN FIRE ALARM SYSTEM AND ACCESS CONTROL SYSTEM ARE
2. FOR VOICE AND DATA COMMUNICATION CABLING SPECIFICATIONS REFER TO 1. ALL DIMENSIONS ARE IN MILLIMETERS, UNLESS OTHERWISE STATED.
DONE, THAT IN CASE OF FIRE ALL INTERLOCKING BETWEEN DOOR SETS ARE
SPEC. SECTION 16715. DEACTIVATED. 2. FIRE ALARM SYSTEM WILL MONITOR CLEAN GAS FIRE PROTECTION SYSTEM.
3. ALL TELECOMMUNICATION AND POWER OUTLETS ARE COORDINATED WITH 3. FIRE ALARM SYSTEM WILL INTERFACE WITH THE FOLLOWING SYSTEMS:
5. ALL CABLES/WIRES FOR LOW CURRENT SYSTEMS (COMMUNICATIONS, FIRE ALARM, 00 14/10/21 ISSUED FOR DESIGN APPROVAL
ACTUAL FURNITURE LAYOUT. ETC.) ARE FIRE RESISTANT LOW SMOKE ZERO HALOGEN (LSZH) OR - ELEVATOR CONTROLS FOR FIRE RECALL

D
ED
D

E
NE
N

KE

OV
IEW
AW
4. ALL TELECOM CABLING, CABINETS, RACKS, PATHWAYS, ETC. IN

SIG

EC
- BUILDING MANAGEMENT SYSTEM

PR
PLENUM TYPE.

DR

V
CH

RE
DE

AP
REV.No. DATE REVISIONS

ACCORDANCE WITH TIA/EIA STANDARDS. 6. EXACT LOCATION OF ALL LOW CURRENT EQUIPMENT AND DEVICES LOCATED ON - SECURITY CONTROL SYSTEM
5. MAXIMUM DISTANCE FOR CAT6, UTP HORIZONTAL CABLING WILL NOT EXCEED CEILING COORDINATED & ADJUSTED ON SITE IN ACCORDANCE WITH THE - PUBLIC ADDRESS AND VOICE EVACUATION SYSTEM FOR VOICE
90M. IF DISTANCE BETWEEN FLOOR DISTRIBUTOR AND DATA OUTLET EXCEED FINAL REFLECTED CEILING PLANS. EVACUATION MESSAGE
THE MAX. LIMIT LENGTH, EXTRA SWITCHES OR FIBER OPTIC CABLES WITH 7. SECURITY SYSTEM IP BASED SYSTEM AND USED THE SAME - HVAC AIR HANDLING UNITS
TCP/IP LAN OF THE PROJECT AS A UNIFIED TELECOM NETWORK. 4. ANY FAULT OF THE FIRE ALARM SYSTEM OR FIRE ALARM PANELS WILL NOT
MEDIA CONVERTERS USED.
8.ALL CAT 6A UTP CABLES FOR CCTV & ISC SUBECT OF APPROVAL INADVERTENTLY CAUSE A SHUTDOWN OF THE ENTIRE HVAC SYSTEM.
6. ALL CABLES/WIRES FOR LOW CURRENT SYSTEMS (COMMUNICATIONS, FIRE ALARM, PROJECT
BY IT DEPARTMENT 5. WIRE SIZE: 2C X 2.5MM² OR AS OTHERWISE APPROVED BY THE
ETC.) FIRE RESISTANT LOW SMOKE ZERO HALOGEN (LSZH). RENOVATION
9.STORAGE SYSTEM FOR CCTV CAMERAS ARE CAPABLE FOR 24 HOURS, FIRE ALARM SYSTEM SPECIALIST.
7. EXACT LOCATION OF ALL LOW CURRENT EQUIPMENT AND DEVICES LOCATED ON 60 DAYS, 6 FRAME/SEC RECORDING. 6. ALL CABLES/WIRES FOR LOW CURRENT SYSTEMS (COMMUNICATIONS, FIRE ALARM, Ministry of Municipal and Rural Affairs
CEILING ARE COORDINATED & ADJUSTED ON SITE IN ACCORDANCE WITH THE 10.FOR CCTV CONDUITS REFER TO AS BUILT VOICE & DATA SYSTEM LAYOUT. ETC.) SHALL LOW SMOKE ZERO HALOGEN (LSZH).
OLAYA
FINAL REFLECTED CEILING PLANS. 11.EXACT INSTALLATION DETAILS FOR SYSTEM COMPONENTS/DEVICES ARE 7. EMBEDDED METAL BOXES FOR CEILING MOUNTED DETECTORS WILL BE
PROJECT No. :‫ومقر عورشم‬
8. USE A PULL BOX FOR CONDUIT RUNS EXCEEDING 25m LENGTH. CONFORMED BY THE APPROVAL SYSTEM SPECIALIST. COORDINATED WITH FIRE ALARM SPECIALIST SUPPLIER FOR EXACT DEVICES
TITLE
9. FOLLOW RECOMMENDATIONS ISSUED BY ELV SYSTEM'S SPECIALISTS FOR THE 12.FOLLOW RECOMMENDATIONS ISSUED BY ELV SYSTEM'S SPECIALISTS FOR THE BACK BOX SIZES.
DESIGN DWG
SELECTION OF BACK BOXES USED WITH ALL ELV SYSTEM'S DVICES/COMPONENTS. SELECTION OF BACK BOXES USED WITH ALL ELV SYSTEM'S 8. EXACT LOCATION OF ALL LOW CURRENT EQUIPMENT AND DEVICES LOCATED ON
CEILING WILL BE COORDINATED & ADJUSTED ON SITE IN ACCORDANCE WITH THE
THIRD FLOOR GENERAL
10. PVC CONDUITS EMBEDDED IN CONCRETE (CEILING) SLAB ARE USED FOR DEVICES/COMPONENTS.
FINAL REFLECTED CEILING PLANS. NOTES
WIRING TO VOICE & DATA SYSTEM DEVICES. 13. PVC CONDUITS EMBEDDED IN CONCRETE (CEILING) SLAB ARE USED FOR
WIRING TO INTEGRATED SECURITY SYSTEM DEVICES. 9. USE A PULL BOX FOR CONDUIT RUNS EXCEEDING 25M LENGTH. MAIN CONSULTANT
CONSOLIDATED
CABLE TRAY PROVIDED TO IMPROVE FLEXIBILITY WITH CABLE 10. EXACT INSTALLATION DETAILS FOR SYSTEM COMPONENTS/DEVICES WILL BE
CABLE TRAYS ARE PROVIDED TO IMPROVE FLEXIBILITY WITH CABLE CONSULTANTS
DISTRIBUTION & FOR FUTURE USE. CONFORMED BY THE APPROVAL SYSTEM SPECIALIST. GROUP
DISTRIBUTION & FOR FUTURE USE.

SCALE DRAWING NO. REV.

1:100 07-MRA-DD-3RD-EE-001 00