Affect of Thrust Force On Pumps - PMP-116 - 04
Affect of Thrust Force On Pumps - PMP-116 - 04
Anchor supports
Supply Discharge
Untied
bellow
Tied bellow
Pump
Inertia Base with springs
Springs
Node Node
Node Node
PMP-116-01-20 TO PMP-116-05-20
At Node 50890 & 50800 = 23000 N (rated capacity for SLFH 113: 31600 N)
At Node 50900 & 50910 = 14300 N (rated capacity for SLFH 135: 14700 N)
SLFH-113 SLFH-135
23000N 50890 50900 14300N
SLFH-113 SLFH-135
50890 50900
50800 50910
SLFH-113 SLFH-135
Conclusion:
With Nozzle side springs were of SLFH-113 and motor side of SLFH-135, Forces on each spring are within their rated capacity.
Node markup
Vendor Nozzle limits are highlighted in Yellow, All pump Nozzle loads are within vendor specified limits.
Loads on Header supports
‘+’ indicates upward, ‘-’ indicates downward directions for vertical forces
Corrected dimension
updated in line with
supplied pumps
EQUIPMENT BASE
“CS” CAP SCREW
Cap Screw secures Height Saving Bracket (or
“AB” ADJUSTMENT BOLT Equipment Base) to Tapped Concentric Hole in
Turn Counterclockwise Mounting Adjustment Bolt.
to Load Spring and Maintain All springs have additional travel to solid equal to 50%
Free and Operating Height of the rated deflection.
Solid Spring Height = Free Height minus 1.5 times
4 HOLES Rated Deflection.
for 1/2" (13mm) OD/OH = Ratio of Spring Outside Diameter to
Free &&
Free Diameter Bolts Operating Height
Operating
Operating = 0.82 - 1.15
Height
Height 1/4" (6mm)
NON-SKID Holders for mounts SLFH-101 thru SLFH-117 are castings.
NEOPRENE Holders for mounts SLFH-118 are steel.
B C ACOUSTICAL
A D ISOLATION PAD
TYPE SLFH LOAD RATINGS AND DIMENSIONS (American and Metric Units)
Spring Only Adjust- Locking
Rated Rated Spring Spring Free & ment Cap
SLFH Capacity Defl. Constant Color/ Spring Free Oper Bolt Screw
Size (lbs) (kg) (in) (mm) (lbs/in)(kg/mm) Stripe OD Height Ht A B C D AB CS
101 125 57 2.50 64 50 0.89 Purple 33/4 95 53/4 146
102 200 91 2.50 64 80 1.42 Brown 33/4 95 53/4 146
103 310 141 2.50 64 125 2.20 Pink 33/4 95 53/4 146
104 500 227 2.50 64 200 3.55 Green 33/4 95 53/4 146 71/4 184 41/4 108 33/8 86 37/8 98 43/4 121 7/8x53/4 1/2x11/4
105 740 336 2.40 61 310 5.51 Red 33/4 95 53/4 146 x 146 x 32
106 1050 476 2.10 53 500 8.98 White 33/4 95 57/8 149
107 1400 635 2.00 51 700 12.45 Blue 33/4 95 57/8 149
108 1660 753 2.05 52 810 14.48 Silver 41/2 114 63/4 171 83/8 213 5 127 4 102 41/4 108 51/4 133
109 2250 1021 2.00 51 1125 20.02 Orange 41/2 114 71/2 191 9 229 5 127 4 102 41/4 108 51/4 133 7/8x53/4 1/2x11/4
110 3000 1361 2.00 51 1500 26.69 Gray 5 127 71/2 191 9 229 51/2 140 41/4 108 51/4 133 61/2 165 x 146 x 32
111 4000 1814 2.00 51 2000 35.57 Tan 5 127 71/2 191 9 229 51/2 140 41/4 108 51/4 133 61/2 165
112 5300 2404 2.00 51 2665 47.14 Black 51/2 140 81/2 216 101/8 257 6 152 43/4 121 53/4 146 70/ 178
113 7100 3221 2.00 51 3550 63.16 Yellow 6 152 83/4 222 101/2 267 65/8 168 51/4 133 6 152 71/2 191 1 x 6 1/2x11/4
114 9300 4218 2.00 51 4650 82.71 Blu/Orng 63/4 171 100/ 254 12 305 71/2 191 61/4 159 61/4 159 71/2 191 x 152 x 32
51 6300
115 12600 5715 2.00 112.06 Blu/Red 63/4 171 100/ 254 12 305 71/2 191 61/4 159 61/4 159 71/2 191 11/4x6 5/8x11/2 x38
116 16800 7620 2.00 51 8400 149.41 Blu/White 73/4 197 101/8 257 13 330 81/2 216 71/4 184 71/4 184 81/2 216 11/2 x 8 3/4x2
117 28500 12927 2.55 65 11175 198.88 Blu/Silver 83/4 222 131/2 343 16 406 91/2 241 8 203 8 203 91/2 241 x 203 x 51
118 40000 18144 2.10 53 19000 342.34 Blu/Gray 97/8 251 13 330 163/8 416 101/2 267 91/2 241 91/2 241 101/2 267 2 x 8 1x21/2 x64
EQUIPMENT BASE
CAP SCREW
ADJUSTMENT BOLT Cap Screw secures Height Saving Bracket (or Equipment Base)
Turn Counterclockwise to Tapped Concentric Hole in Mounting Adjustment Bolt.
to Load Spring and
Maintain Free and All springs have additional travel to solid equal to 50% of the
Operating Height rated deflection.
Solid Spring Height = Free Height minus 1.5 times Rated
4 HOLES Deflection.
for 1/2” 13mm
Diameter Bolts OD/OH = Ration of Spring Outside Diameter to Operating Height
Free & = 0.82 - 1.15
Operating
NON-SKID Holders for mounts SLFH-126 thru SLFH-140 are castings.
Height
NEOPRENE Holders for mounts SLFH-141-143 are steel.
ACOUSTICAL
C ISOLATION PAD
B
A D
TAG: ________________________________________________________
1: 6:
UNIT:________________________________________________________ 2: 7:
3: 8:
a3
12 * Ø22
3.5 19
This document and all information thereon is the property of BELMAN A/S. It must not be copied, imparted to a third party or used for any other purpose without the consent of BELMAN A/S.
250.7
221.5
478
418
340
295 26
4 1 4
Loose flange Loose flange
12
15
12 15
Tag welded onto the outer edge of flange Flow
TIED BELLOWS
Reac. force: 40.90kN
BC1-PMP116-1-20BC1-PMP116-2-20BC1-PMP116-3-20BC1-PMP116-4-20BC1-PMP116-5-20
Measurements without tolerances acc. EN ISO 14917 table. 7.5.3.1-1, machined parts acc. DS/ EN 22768 class C
3.1 Certificate
Bellow geometry26 16.6 (16.13)
Di = 217.4 mm 19 Spherical washerM16 A4 16
Do = 239 mm 12 Lug 75 * 69 * 15mm - Ø18 1.4307 (304L) 3.1 8
239
10
q = 16.13 mm
4 Flange EN1092-1/01/A/DN200/PN16 1.4307 (304L) 3.1 2
w = 10 mm
e = 0.8 mm (2*0.4mm) 1 Steelbellow 2*0.4mm (1 * 14) 1.4541 (321) 3.1 1
Pos Details Dimension Material Cert. Pcs Pos Details Dimension Material Cert. Pcs
W6 NDT in accordance to + VT PT MT RT UT Design code: EJMA10 (+) (-) Range Spring rate Manufacturer:
EN14917:2009+A1:2012
W1 - - - - -
Design pressure: 3/10 barg Axial: 6 6 6 mm 235 N/mm BELMAN UK +44 (0) 161 491 5515
www.belman.com
Design temperature: 18/120 °C Lat: 8 8 8 mm 369 N/mm Project: Customer:
W6 A-A W2 100 - - - - 46090_DESN_Pipework flexible connectors_220222_DDe
Exyte Northern Europe Ltd.
A W5 W1 Design life time: 7000 cycles Ang: 0 0 0° 27 Nm/° Unit J3
W5 W5 W4 W3 - - - - - W23 AZW4 Co. Kildare
Media: Liquid Mov. in combination Discharge - PMP116-X-20 IRELAND
W4
W4 100 - - - -
Max external force: - Test pressure Drawn Checked by Weight Type
W5
5 min @ 15.00 Barg
A W5 100 - - - - MMC - 31 kg UN1BT-10-0200-006-0
Max velocity: 4.1 m/s Date Date Quantity Drawing No Rev. No.
W3 W1 W2 W6 - - - - -
22-09-22 - 5 5722-03002-050-2 2
Requirement outlined below for the top strap assembly required on the 24” header at the location
indicated below to counteract the upward forces exerted onto the header.
The existing shoe will remain in place with the addition of a top strap assembly consisting of the
following:
Top strap + base welded to the stop strap +PE slide pad +ss sheet metal(slide
surface)+mounting plate
Refer to the screenshots below identifying the location and attached sketch from Pipeshields. A
structural support is to be designed by Hilti for review by Exyte structural team.
DOCUMENT TITLE:
Where this document has been revised it is recorded as indicated below. Please replace all superseded pages of this document with current
version.
Rev Date Description By Checked Approvals
Entire
Document
Issued this
Revision
Bluejay Project Engineering Calculations- Steel Pipe Support 23/11/2022
TABLE OF CONTENTS
1. Introduction 3
2. Basis of Design 4
2.1. Structural Design References & Codes 4
2.2. Structural Design Loading 5
2.2.1. General loading 5
3. Analysis 6
3.1. Weld Verification 6
Bluejay Project Engineering Calculations- Steel Pipe Support 23/11/2022
1. INTRODUCTION
This calc report is to verify the weld requirement of a 24” pipe support which was changed from a guide to an
anchor. This will be achieved by welding the existing pipe support clip to the pipe using a proposed 2x75mm
6mm fillet on each of the support brackets.
Bluejay Project Engineering Calculations- Steel Pipe Support 23/11/2022
2. BASIS OF DESIGN
The loads indicated by the pipe stress report are as follows acting on the pipe c/l:
Maximum Loads of all the load cases: F.O.S. Live load = 1.5
3. ANALYSIS
The total effective weld length is 75mm x 2 welds per bracket = 75mm x 2 x 2 = 300mm
For stability of the connection a minimum of 2no 75mm welds are required on each of the support plates.
All connection elements below the new welded connection have not been validated in this report.
Pipe
Heavy Duty, Shields
Model B3300 Guided Insulated Pipe Support
B3000 Base Mounted Inc.
E 9"
B.O.P.
1/8" CLR
B TYP
T.O.S.
4"
4"
Contact factory for other dimensional, temperature, load, or axial travel requirements. If lateral load is greater than 20% of vertical load, contact factory. Available in
all insulation thickness.
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.
Note: For higher load rating contact factory - For greater axial travel, see: B4300 - For lateral travel, see: B5300
Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 550 4 6 3.375 4 6.5 4.5 4 7 5.5 4 8.5 7.125 6 9 8.125 6 11 10.125 8 12.5 12.25
3/4 700 4 6 3.375 4 6.5 4.5 4 7 5.5 4 8.5 7.125 6 9 8.125 6 11 10.125 8 12.5 12.25
1 900 4 6.5 4 4 7 5 4 7.5 6.062 4 8.5 7.125 6 9 8.125 6 11 10.125 8 12.5 12.25
1 1/2 1300 4 6.5 4.5 4 7 5.5 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1500 4 7 5 4 7.5 6.0625 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1/2 1800 4 7 5.5 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625
3 2100 4 7.5 6.187 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625
4 3350 4 8.5 7.25 4 9 8.25 4 10 9.25 4 11 10.25 6 12 11.375 6 13.5 13.375 8 15 15.625
5 4200 4 10 8.5 4 11 9.5 4 12 10.5 4 13 11.625 6 13.5 12.625 6 15 14.875 8 16.5 16.875
6 5100 4 11 9.5 4 12 10.5 4 13 11.625 4 13.5 12.625 6 14.5 13.625 6 16 15.875 8 17.5 17.875
8 6800 4 13.5 11.625 4 14 12.625 4 15 13.625 6 15.5 14.875 6 16.5 15.875 6 18 18.125 8 19 20.125
10 8000 4 15 13.875 4 15.5 15.125 4 16.5 16.125 6 17 17.125 6 18 18.125 6 19 20.125 8 20.5 22.125
12 8800 4 17 16.125 4 17.5 17.125 4 18.5 18.125 6 19 19.125 6 19.5 20.125 6 21 22.125 8 22.5 24.125
14 10000 4 17.5 17.125 4 18.5 18.125 4 19 19.125 6 19.5 20.125 6 20.5 21.125 6 22 23.125 8 23 25.125
16 11600 4 20.5 19.375 4 21 20.375 6 22 21.375 6 22.5 22.375 6 23.5 23.375 8 24.5 25.375 8 26 27.375
18 12800 4 22 21.375 4 22.5 22.375 6 23.5 23.375 6 24 24.375 6 24.5 25.375 8 26 27.375 8 27.5 29.375
20 13600 4 23.5 23.375 4 24 24.375 6 24.5 25.375 6 25.5 26.375 6 26 27.375 8 27.5 29.375 8 29 31.375
24 14400 4 26 27.375 4 27 28.375 6 27.5 29.375 6 28.5 30.375 6 29 31.375 8 30.5 33.375 8 32 35.375
30 18800 4 32.5 33.625 6 33 34.625 6 34 35.625 6 34.5 36.625 6 35 37.625 8 36.5 39.625 8 38 41.625
36 22000 4 36.5 40.125 6 37.5 41.125 6 38 42.125 6 38.5 43.125 6 39.5 44.125 8 41 46.125 8 42.5 48.125
42 24800 4 41 46.125 6 41.5 47.125 6 42.5 48.125 6 43 49.125 6 43.5 50.125 8 45 52.125 8 46.5 54.125
Model B3300 is designed for use on: · All pipe sizes · B3300: Applicable PSI spec. doc.: No. 209
· Hot water · Steam · Insulation: Calcium Silicate asbestos-free,
· Easy Installation
· Cold water · Air treated with water repellant
· Eliminates welding to pipe · Jackets: Galvanized Steel ASTM A-653
· Chilled water · Gas
· Overlapping galvanized sheet metal jacket · Glue: Industrial contact adhesive
· Dual temperature · Vacuum
· Insulating structural inserts for load transfer · Structural Inserts: High-density calcium silicate
· Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: · Steel Straps/Base: Carbon Steel ASTM A-36
· Other I.D.’s and/or O.D.’s available on request
· Flat Surfaces · Fasteners: ASTM A-307 plated
· Factory mounted polyethylene slide pad on steel
· Slide Pad: UHMW Polyethylene (PTFE Optional)
Temperature Range: mounting plate
Standard: +40°F to +1200°F CalSil Insulation
· Coating: Primer coated or hot dipped galvanized
Note: Up to 1800°F available upon request. Performance Test Results on File: Other coatings available upon request
Cryogenic: -275°F to +275°F Urethane Insulation.
Add U after the model number (i.e., B3300U) Available upon request. Formal Submittal Sheets available
www.pipeshields.com/b3300 51