Professional Documents
Culture Documents
Electrical Characteristics 1
Electrical Characteristics 1
• When the voltage of the conductors exceeding a certain value, the air around the
conductors get changes
• Certain voltage value is called as critical disruptive voltage
• There’s a violet glow around the conductors
• This may accompany by a hissing noise, production of ozone and power loss
• If the voltage increases, then larger the luminous, hissing noise and power loss
• This effect around the conductors is called as corona effect
• The rough points may brighter
• If the conductor surface is smooth, glow will be uniform
Theoretical aspect
b = pressure in Hgcm
t = temperature in ⁰C
𝑑
Therefore, critical disruptive voltage = 𝑉𝑐 = 𝑔0 δ 𝑟 𝑙𝑜𝑔𝑒 ( )
𝑟
• The minimum phase- neutral voltage at which corona glow appears all along the line
conductors
• In parallel conductors, glow doesn’t begin at critical disruptive voltage
• It will have at visual critical voltage
𝟎.𝟑 𝒅
𝑽𝒗 = 𝒎𝒗 𝒈𝟎 δ 𝒓(𝟏 + )𝒍𝒐𝒈𝒆 ( ) kV/phase
𝜹𝒓 𝒓
𝑓+25 𝑟
𝑃 = 242.2 (𝑉 − 𝑉𝑐 )2 ∗ 10−5 kW/km/phase
𝛿 𝑑
f = supply frequency
V = phase-neutral voltage (rms)
𝑉𝑐 = disruptive voltage per phase (rms)
Q1. A 3-phase line has conductors 2cm in diameter spaced 1m apart from each other.
Dielectric strength of air is 30kV/cm(max) and air density factor and irregularity factors are
0.952 and 0.9, respectively. Find the disruptive critical voltage for the line
Q2. A 3-phase 220kV transmission line consists of 1.5cm radius conductor spaced 2m apart
from each other. If the temperature is 40⁰C and atmospheric pressure is 76Hgcm, Calculate
the corona loss per km of the line.
Take irregular factor as 0.85 and dielectric strength of air is 21.2kV/cm(rms)
Q1.
Conductor radius, r =2/2=1cm
Conductor spacing d = 100cm
g 0 = 30kV/cm (max)= 21.2kV/cm (rms value)
Disruptive critical voltage,
𝑑
𝑉𝑐 = 𝑚0 𝑔0 δ 𝑟 𝑙𝑜𝑔𝑒 ( )
𝑟
100
𝑉𝑐 = 0.9*21.2*0.952*1*𝑙𝑜𝑔𝑒 ( ) = 83.64kV/phase
1
𝑉𝑐 =125.9kV
Supply voltage per phase = 220/ 3= 127kV
𝑓 + 25 𝑟
𝑃 = 242.2 (𝑉 − 𝑉𝑐 )2 ∗ 10−5
𝛿 𝑑
50 + 25 1.5
𝑃 = 242.2 (127 − 125.9)2 ∗ 10−5
0.952 200
P = 0.0199kW/km/phase
Total corona loss per km for three phases
3 x P = 3 x 0.0199 = 0.0599kW
Methods to reduce corona effect
𝑓 + 25 𝑟
𝑃 = 242.2 (𝑉 − 𝑉𝑐 )2 ∗ 10−5
𝛿 𝑑
Power loss at 113kV
At 53kW V= 106/ 3= 61.2kV
V = 113/ 3= 65.2kV
53 = 𝑘(61.2 − 𝑉𝑐 )2 −−−−−−−− −(1)
P = 𝑘(65.2 − 54)2 −−−−−−−−− − 3
(1)/(3)
At 98kW V= 110.9/ 3= 64kV
53/P= (61.2 − 54)2 / (65.2 − 54)2
98 = 𝑘(64 − 𝑉𝑐 )2 −−−−−−−− − 2
P = 128kW
(1)/(2)
53/98= (61.2 − 𝑉𝑐 )2 / (64 − 𝑉𝑐 )2
𝑉𝑐 = 54kV
Classification of overhead transmission lines
▪Short transmission lines
▪ Length of the line up to 50km
▪ Voltage below 20kV
▪Medium transmission lines
▪ Length of the line 50-150km
▪ Voltage 20-100 kV
▪Long transmission lines
▪ Length of the line more than 150km
▪ Voltage more than 100 kV
•When current is passing through the transmission lines, there’s a voltage drop in the
transmission lines
•That is due to resistances and reactance
•Therefore, receiving end voltage is less than the sending end voltage
Voltage regulation
•The ration between this difference to the receiving end voltage
•The difference in voltage at the receiving end of a transmission line between no load
and full load to the receiving end voltage
𝑉𝑆 − 𝑉𝑅
Voltage regulation = ∗ 100%
𝑉𝑅
Transmission line efficiency
•There may be power losses in transmission line due to resistances.
•Therefore, the power at receiving end and sending end will be changed
•Receiving end power is less than the sending end power
•Transmission line efficiency is defined as the ratio between the receiving end power to
sending end power as a percentage.
Transmission line efficiency = Receiving end power / Sending end power *100%
𝑉𝑅 𝐼𝑅 cos( 𝜑𝑅 )
Transmission line efficiency = ∗ 100%
𝑉𝑆 𝐼𝑆 cos( 𝜑𝑆 )
Single phase short transmission lines
𝑉𝑅 cos 𝜑𝑅 + 𝐼𝑅
𝜑𝑆 =
𝑉𝑆
𝑃𝑜𝑢𝑡 = 𝑉𝑅 𝐼 cos 𝜑𝑅
𝑃𝑖𝑛 = 𝑉𝑅 𝐼 cos 𝜑𝑅 + 𝐼 2 𝑅
When considering the complex notations,
𝐼 = 𝐼∠ − 𝜑𝑅
𝑍 = 𝑅 + 𝑗𝑋𝐿
𝑉𝑆 = 𝑉𝑅 + 𝐼𝑍
𝑉𝑆 = 𝑉𝑅 + (𝐼∠ − 𝜑𝑅 )(𝑅 + 𝑗𝑋𝐿 )
𝑉𝑆 = 𝑉𝑅 + (𝐼(cos 𝜑𝑅 − 𝑗 sin 𝜑𝑅 ) ∗ (𝑅 + 𝑗𝑋𝐿 ))
𝑉𝑆 = 𝑉𝑅 + 𝐼𝑅 cos 𝜑𝑅 + 𝐼𝑋𝐿 sin 𝜑𝑅 + 𝑗(𝐼𝑋𝐿 cos 𝜑𝑅 − 𝐼𝑅 sin 𝜑𝑅 )
𝑉𝑆 2 = (𝑉𝑅 + 𝐼𝑅 cos 𝜑𝑅 + 𝐼𝑋𝐿 sin 𝜑𝑅 )2 + (𝐼𝑋𝐿 cos 𝜑𝑅 − 𝐼𝑅 sin 𝜑𝑅 )2
2
Q2. A single-phase transmission line having a cross sectional area of 0.775 𝑐𝑚 delivering
200kW at unity power factor at 3300V. The transmission efficiency is 90%. Take specific
resistance as 1.725μΩcm and find the maximum length of the line.
Q1. Z= 10+j15
P= VI cos(ɸ)
1100=33I *0.8
I = 41.67A
Take voltage as the reference,
𝐼 = 41.67∠ − 36.87∘
𝑉𝑠 = 𝑉𝑅 + 𝐼𝑍
𝑉𝑠
= (33000∠0) + (41.67∠ − 36.87∘ ) ∗ (10 + 𝑗15)
𝑉𝑠 = 33708.39 + 𝑗250.02
𝑉𝑠 = 33709.32∠0.4249∘
𝛼 = 0.4249∘
𝜑𝑆 = 𝜑𝑅 + 𝛼
𝜑𝑆 = 36.87∘ + 0.4249∘ = 37.029∘
cos( 𝜑𝑆 ) = cos( 37.029∘ ) = 0.7956(𝑙𝑎𝑔𝑔𝑖𝑛𝑔)
𝐼2 𝑅 = (41.67)2 ∗ 10 = 17.364𝑘𝑊
𝑃𝑖𝑛 = 1100 + 𝐼2 𝑅
𝑃𝑖𝑛 = 1100 + 17.364 = 1117.364𝑘𝑊
𝑃𝑜𝑢𝑡 = 1100𝑘𝑊
𝑃𝑜𝑢𝑡
𝑒𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 = ∗ 100%
𝑃𝑖𝑛
1100
𝑒𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 = ∗ 100%
1117.364
𝑒𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 = 98.44%
Q2.
P= VI cos(ɸ)
I 2 R = (60.6)2 ∗ R = 22.222 ∗ 1000W
200*1000=3300I *1
R = 6.05Ω
I = 60.60A
ρl
R=
A
𝑃𝑜𝑢𝑡
𝑒𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 = ∗ 100% 1.725∗10−6 l
𝑃𝑖𝑛 6.05 =
0.775
200 ∗ 1000
90% = ∗ 100% Length = 27.18km
𝑃𝑖𝑛
Pin = 222.222kW
Line losses = 222.222-200 kW
Line losses= 22.222kW
Three phase short transmission lines
Q4. A short 3-phase transmission line has the impedance of 6+j8Ω/phase. The sending
end and receiving end voltages are 120kV and 110kV respectively. The receiving end load
at a power factor of 0.9 lagging. Find the power output and sending end power factor.
Q3.
33000
𝑉𝑆 = = 19052𝑉
3
Line losses= 3 * (81.37)*5.31
P= 3VI cos(ɸ)
Line losses = 105.447 kW
360*1000=3 𝑉𝑅 I *0.8
𝑃𝑜𝑢𝑡
1500000
𝑒𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 = ∗ 100%
I= −−−−− −(1) 𝑃𝑖𝑛
𝑉𝑅
360
e𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 = ∗ 100%
360 + 105.45
𝑉𝑆 = 𝑉𝑅 + 𝐼𝑅 cos 𝜑𝑅 + 𝐼𝑋𝐿 sin 𝜑𝑅
Efficiency = 77.34%
1500000 1500000
19052= 𝑉𝑅 + ∗ 5.31 ∗ 0.8 + ∗ 5.54*0.6
𝑉𝑅 𝑉𝑅
𝑉𝑅 2 − 19052𝑉𝑅 + 11,358,000 = 0
𝑉𝑅 = 18.435kV
Line voltage = 3 ∗ 18.435 = 31.93𝑘𝑉
From (1)
1500000 1500000
I= = = 81.37 𝐴 (𝐿𝑖𝑛𝑒 𝑐𝑢𝑟𝑟𝑒𝑛𝑡)
𝑉𝑅 18435
Q4.
120000
𝑉𝑆 = = 69282𝑉
3
𝑉𝑅 cos 𝜑𝑅 + 𝐼𝑅
cos(𝜑𝑆 ) =
110000 𝑉𝑆
𝑉𝑅 = = 63508𝑉 63508 ∗ (0.9) + (650.22 ∗ 6)
3 cos(𝜑𝑆) =
69282
𝑉𝑆 = 𝑉𝑅 + 𝐼𝑅 cos 𝜑𝑅 + 𝐼𝑋𝐿 sin 𝜑𝑅
𝑐𝑜𝑠(𝜑𝑆 ) = 0.88
69282 =63508 + I *6*0.9 + I *8* sin(25.84)
I = 650.22 A
𝑃 = 3𝑉𝐼 cos( 𝜃)
11
1000 = 3 ∗ ∗ 𝐼 ∗ 0.8
3
𝐼 = 65.61𝐴
𝑉𝑆 = 𝑉𝑅 + 𝐼𝑅 cos 𝜑𝑅 + 𝐼𝑋𝐿 sin 𝜑𝑅
11000
𝑉𝑆 = + (65.61 ∗ 0.48 ∗ 0.8) + (65.61 ∗ 3.52 ∗ 0.6)
3
𝑉𝑆 = 6514.62𝑉
𝑉𝑆 − 𝑉𝑅
𝑉𝑜𝑙𝑡𝑎𝑔𝑒 Re 𝑔 𝑢𝑙𝑎𝑡𝑖𝑜𝑛 = ∗ 100%
𝑉𝑅
6514.62 − 6350.85
= ∗ 100% = 2.58%
6350.85
𝑉𝑆 = 𝑉𝑅 + 𝐼𝑆 𝑋𝐿 + 𝐼𝑆 𝑅
𝑉𝑆 = 𝑉𝑅 ∠0 + 𝐼𝑆 (𝑅 + 𝑗𝑋𝐿 )
𝐼𝑆 = 𝐼𝐶 + 𝐼𝑅
𝐼𝑆 = 𝑋𝐶 𝑉𝑅 + 𝐼𝑅 ∠ − 𝜃
𝐼𝑆 = 𝐼𝑅 (cos 𝜃𝑅 − 𝑗 sin 𝜃𝑅 ) + 𝑗(2𝜋𝑓𝐶𝑉𝑅 )
𝐼𝑆 = 𝐼𝑅 (cos 𝜃𝑅 ) + 𝑗[(−𝐼𝑅 sin 𝜃𝑅 ) + (2𝜋𝑓𝐶𝑉𝑅 )]
𝑉𝑆 = 𝑉𝑅 ∠0 + 𝐼𝑆 (𝑅 + 𝑗𝑋𝐿 )
𝐼𝑆 = 𝐼𝐶 + 𝐼𝑅
Q. A single phase transmission line is 100km long. It has the following values
Resistance/km = 0.25Ω Reactance/km = 0.8Ω
Susceptance /km = 14*10−6 Receiving end voltage = 66000V
Line is delivering 15000kW at 0.8 power factor lagging
Using end condenser method,
1. Draw the phasor diagram
2. Find;
1. Sending end current Susceptance= Reciprocal of reactance
𝐼𝐶 = 𝑗𝑌𝑉
𝐼𝐶 = 𝑗(14 ∗ 10−6 ∗ 66000) = 𝑗92
𝐼𝑆 = 𝐼𝐶 + 𝐼𝑅
𝐼𝑆 = 𝑗92 + 284∠ − 36.86∘
𝐼𝑆 = 227.2 − 𝑗78.4 = 240.34∠ − 19.038∘
𝑉𝑆 = 𝑉𝑅 + 𝐼𝑆 𝑍
𝑉𝑆 = 66000∠0 + (227.2 − 𝑗78.4) ∗ (25 + 𝑗80)
𝑉𝑆 = 77952 + 𝑗16216
𝑉𝑆 = 79620.8∠11.75∘ 𝑉
𝑉𝑆 − 𝑉𝑅
𝑉𝑜𝑙𝑡𝑎𝑔𝑒 𝑟𝑒𝑔𝑢𝑙𝑎𝑡𝑖𝑜𝑛 = ∗ 100%
𝑉𝑅
79620 − 66000
𝑉𝑜𝑙𝑡𝑎𝑔𝑒 𝑟𝑒𝑔𝑢𝑙𝑎𝑡𝑖𝑜𝑛 = ∗ 100%
66000
𝑉𝑜𝑙𝑡𝑎𝑔𝑒 𝑟𝑒𝑔𝑢𝑙𝑎𝑡𝑖𝑜𝑛 = 20.63%
𝑅 𝑋𝐿
𝑉1 = 𝑉𝑅 + 𝐼𝑅 (cos 𝜑𝑅 − 𝑗 sin 𝜑𝑅 )( + 𝑗 )
2 2
𝐼𝐶 = 𝑗𝜔𝐶𝑉1
𝐼𝑆 = 𝐼𝑅 + 𝐼𝐶
𝑅 𝑋𝐿
𝑉𝑆 = 𝑉1 + 𝐼𝑆 ( + 𝑗 )
2 2
Q. A three phase, 50Hz overhead transmission line is 100km long. It has the following details.
• Resistance/km/phase = 0.1Ω
• Inductive reactance/km/phase = 0.2Ω
• Capacitive susceptance/km/phase = 0.04*10−4 S
Draw the single-phase equivalent circuit and the phasor diagram and determine
1. Sending end current
2. Sending end voltage
3. Sending end power factor
4. Transmission efficiency using nominal T method
The output power is 10000kW at 66kV and 0.8 power factor lagging
𝑅 = 0.1 ∗ 100 = 10Ω
𝑋𝐿 = 0.2 ∗ 100 = 20Ω
Y = 4 ∗ 10−6 ∗ 100= 4 ∗ 10−4
66000
𝑉𝑅 = = 38105 𝑉
3
𝑃 = 3𝑉𝐼 cos( 𝜃)
66
10000 = 3 ∗ ∗ 𝐼 ∗ 0.8
3
𝐼 = 109𝐴 𝐼𝐶 = 𝑗𝑌𝑉1 = 𝑗 4 ∗ 10−4 ∗ 39195 + 𝑗545
cos( 𝜃) = 0.8--------- 𝜃=36.87 𝐼𝐶 = -0.218 + j15.68
Z = R +j 𝑋𝐿 = 10 + 𝑗20 𝐼𝑆 = 𝐼𝑅 + 𝐼𝐶
𝑉𝑅 = 38105∠0 𝑉 𝐼𝑆 = 109∠ − 36.87 + -0.218 + j15.68
𝐼𝑅 = 109∠ − 36.87 𝐴 𝐼𝑆 = 87 –j 49.7 = 𝟏𝟎𝟎. 𝟏𝟗∠ − 𝟐𝟗. 𝟕𝟓
𝑍
𝑉1 = 𝑉𝑅 + 𝐼𝑅 ( )
2
𝑉1 = 38105∠0 + 109∠ − 36.87 5 + 𝑗10 = 39195 + 𝑗545
𝑍
𝑉𝑆 = 𝑉1 + 𝐼𝑆
2
𝐶
𝐼𝐶2 = 𝑗𝜔( )𝑉𝑆
2
𝐼𝑆 = 𝐼𝐿 + 𝐼𝐶2
𝐶
𝐼𝐶1 = 𝑗𝜔( )𝑉𝑅
2
𝐼𝐿 = 𝐼𝑅 + 𝐼𝐶1
𝑉𝑆 = 𝑉𝑅 + 𝐼𝐿 𝑍
𝑉𝑆 = 𝐼𝐿 (R +j ω𝐿 )
𝐶
𝐼𝐶2 = 𝑗𝜔( )𝑉𝑆
2
𝐼𝑆 = 𝐼𝐿 + 𝐼𝐶2
Q. A 100km long, 3-phase 50Hz transmission line has the following constants.
▪ Resistance/phase/km = 0.1Ω
▪ Inductive reactance/phase/km = 0.5Ω
▪ Susceptance/phase/km = 10*10−6 S
The line is supplying a load of 20MW at 0.9p.f lagging at 66kV at the receiving end.
Calculate;
1. Sending end power factor
2. Voltage regulation
3. Transmission efficiency
𝑅 = 0.1 ∗ 100 = 10Ω
𝑋𝐿 = 0.5 ∗ 100 = 50Ω
Y = 10∗ 10−6 ∗ 100= 10 ∗ 10−4
66000
𝑉𝑅 = = 38105 𝑉
3
𝑃 = 3𝑉𝐼 cos( 𝜃)
66
20000 = 3 ∗ ∗ 𝐼 ∗ 0.9
3
𝐼 = 194.4𝐴 𝑗𝑌
𝐼𝐶1 = 𝑉 = 𝑗 5 ∗ 10−4 ∗ 38105∠0
2 𝑅
cos( 𝜃) = 0.8--------- 𝜃=25.84
𝐼𝐶1 = j19.05
Z = R +j 𝑋𝐿 = 10 + 𝑗50
𝐼𝐿 = 𝐼𝑅 + 𝐼𝐶1
𝑉𝑅 = 38105∠0 𝑉
𝐼𝐿 = 194.4∠ − 25.84 + j19.05
𝐼𝑅 = 194.4∠ − 25.84𝐴
𝐼𝐿 = 186.88∠ − 20.58
𝑉𝑆 = 𝑉𝑅 + 𝐼𝐿 (𝑍)
𝑉𝑆 = 38105∠0 + 186.88∠ − 20.58 10 + 𝑗50
𝑉𝑆 = 𝑉𝑅 + 𝐼𝐿 𝑍
𝑉𝑆 = 38105 + 186.88∠ − 20.58 10 + 𝑗50 = 43890.75 ∠10.62 V
𝑗𝑌
𝐼𝑆 = 𝐼𝐿 + 𝐼𝐶2 𝐼𝐶2 = 𝑉
2 𝑆
𝑉𝑆 − 𝑉𝑅
𝑉𝑜𝑙𝑡𝑎𝑔𝑒 𝑟𝑒𝑔𝑢𝑙𝑎𝑡𝑖𝑜𝑛 = ∗ 100%
𝑉𝑅
43890−38105
𝑉𝑜𝑙𝑡𝑎𝑔𝑒 𝑟𝑒𝑔𝑢𝑙𝑎𝑡𝑖𝑜𝑛 = ∗ 100%= 15.18%
38105
𝑉𝑆 = 𝐴 𝑉𝑅 + 𝐵𝐼𝑅
𝐼𝑆 = 𝐶 𝑉𝑅 + D𝐼𝑅 For a given transmission line
• A, B, C and D are normally complex numbers
𝑉𝑆 = Sending end voltage per phase • A=D
𝐼𝑆 = Sending end current • A*D – B*C = 1
Here ;
𝐼𝑆 = 𝐼𝑅 Hence from (2); D = 1, C = 0
𝑉𝑆 = 𝑉𝑅 + 𝐼𝑅 Z Hence from (1); A =1, B= Z
Therefore ;
A = D =1
A*D – B*C = 1- z*0 =1
Medium transmission lines (Nominal T method)
𝑍
𝑉1 = 𝑉𝑅 + 𝐼𝑅 ( )
2
𝑍
𝑉𝑆 = 𝑉1 + 𝐼𝑆
2
𝑍 Z
𝑉𝑆 = 𝑉𝑅 + 𝐼𝑅 (2)+ IS ----------------(3) From (3) and (4);
2
𝑌𝑍 𝑌𝑍 2
𝑉𝑆 = 𝑉𝑅 (1 + )+ IR 𝑍+ ----------------(5)
𝐼𝐶 = 𝑗𝜔𝐶𝑉1 = 𝑌𝑉1 2 4
𝑍 Therefore ;
𝐼𝐶 = 𝑌𝑉1 = 𝑌 ∗ (𝑉𝑅 + 𝐼𝑅 ( ) A =D = 1 +
𝑌𝑍
2 2
𝐼𝑆 = 𝐼𝐶 + 𝐼𝑅 𝑌𝑍 2
𝑍 B= 𝑍+
𝐼𝑆 = 𝐼𝑅 + 𝑌 ∗ (𝑉𝑅 + 𝐼𝑅 (2) 4
𝑌𝑍
C=Y
𝐼𝑆 = 𝑌 ∗ 𝑉𝑅 + 𝐼𝑅 (1 + ) ------------------(4)
2
Medium transmission lines (Nominal π method)
𝑉𝑆 = 𝐴 𝑉𝑅 + 𝐵𝐼𝑅 −−−−−− −(1)
𝐼𝑆 = 𝐶 𝑉𝑅 + D𝐼𝑅 −−−−−− −(2)
𝐶 𝑌
𝐼𝐶1 = 𝑗𝜔( )𝑉𝑅 = 𝑉𝑅 ( )
2 2
𝑌
𝐼𝐿 = 𝐼𝑅 + 𝐼𝐶1 = 𝐼𝑅 +𝑉𝑅 ( )
2
𝑌 𝑍𝑌
𝑉𝑆 = 𝑉𝑅 + 𝐼𝐿 𝑍= 𝑉𝑅 +[𝐼𝑅 +𝑉𝑅 ( )]*Z= (1+ )𝑉𝑅 + Z 𝐼𝑅 −−−− −(3)
2 2
𝐶 𝑌
𝐼𝐶2 = 𝑗𝜔( )𝑉𝑆 = 𝑉𝑆 ( )
2 2 Therefore ;
𝑌𝑍
𝑌 𝑌 A =D = 1 + 2
𝐼𝑆 = 𝐼𝐿 + 𝐼𝐶2 = 𝐼𝑅 +𝑉𝑅 + 𝑉𝑆 ( )
2 2 B= 𝑍
𝑍𝑌 2
𝑌 𝑌 𝑌 C= Y+
𝐼𝑆 = 𝐼𝑅 +𝑉𝑅 + 𝑉𝑅 +([𝐼𝑅 +𝑉𝑅 ( )]∗Z)( ) 4
2 2 2
𝑍𝑌 𝑍𝑌
𝐼𝑆 = 𝐼𝑅 1 + + 𝑉𝑅 (Y [1+ ]) −−−−−−−− −(4)
2 4
Q. A transmission line is delivering a load of 50MVA at 110kV and 0.8 power factor lagging.
It is given the following constants.
A = D = 0.98∠30 , 𝐵 = 110∠750 , 𝐶 = 0.0005∠800
Find;
i. Sending end voltage
ii. Sending end current
iii. Sending end power factor
110000
𝑉𝑅 = = 63.5∠0𝑘𝑉
3
𝑃 = 3𝑉𝐼
50,000 = 3 ∗ 63.5 ∗ 𝐼
𝐼𝑅 = 262.4∠ − 36.87𝐴
𝑉𝑆 = 𝐴 𝑉𝑅 + 𝐵𝐼𝑅
𝑉𝑆 = 0.98∠30 ∗ (63500∠0) + 110∠750 *(262.4∠ − 36.87) = 87428.56∠13.95 𝑉
𝐼𝑆 = 𝐶 𝑉𝑅 + D𝐼𝑅
𝐼𝑆 = 0.0005∠800 ∗ (63500∠0) +0.98∠30 ∗ (262.4∠ − 36.87) = 246.02 ∠ − 27.09 𝐴
𝑌𝑍 2 𝑗315∗10−6 ∗(20+𝑗52)2
B= 𝑍+ = 20 + 𝑗52 + = 19.84+j51.82 = 55.48∠69.05
4 4
132000
𝑉𝑅 = = 76210.24∠0𝑉
3
𝑃 = 3𝑉𝐼 cos( 𝜃)
30,000,000 = 3 ∗ 76210.24 ∗ 𝐼 ∗ 0.85
𝐼𝑅 = 154.37∠ − 31.78𝐴
𝑉𝑆 = 𝐴 𝑉𝑅 + 𝐵𝐼𝑅
𝑉𝑆 = 0.992∠0.182 ∗ (76210.24∠0) + 55.48∠69.05*(154.37∠ − 31.78) = 82594.14 ∠3.77 𝑉
𝐼𝑆 = 𝐶 𝑉𝑅 + D𝐼𝑅
𝐼𝑆 = 0.000315 ∠90 ∗ (76210.24∠0) +0.992∠0.182 ∗ (154.37∠ − 31.78) = 142.036 ∠ − 23.32 𝐴
Underground Cables Properties of underground cables
Advantages: • Cables should have high conductivity
▪Less liability to damage from storm and • Mostly stranded copper or Aluminium
lightning are used
▪Less maintenance cost •Cables should carry the desired current
▪Less chances to faults without overheating
▪Low voltage drop • Proper thickness of the insulation
▪Armouring
▪ Protect the cable from mechanical injuries while laying and handling
▪ One or two layers of galvanized steel wire
▪Serving
▪ Protect the armouring from atmospheric conditions
Properties of insulation material for conductors
Disadvantages
• Alterations can’t be done easily
• Maintenance cost is high
• Identification of faults is not easy
Draw in system
• Concrete, stones or cast iron is laid in the ground with manholes for cable routes
• Distance between manholes may not be too long to pull the cable
• No need of armouring
• Must have serving to protect when being pulled in ducts
• Used in short length cable routes like workshops, road crossing
Advantages
• Repairs and alterations can be done without opening the ground
• Low maintenance cost
• Have strong mechanical protection; therefore less faults
Disadvantages
• High initial cost