Professional Documents
Culture Documents
Manual Book Soft Starter Renle JJR8000
Manual Book Soft Starter Renle JJR8000
Operation Manual
1
●Please read this operation manual carefully and understand all content in order
to carry out installation, connecting circuit, operation and maintenance
conveniently and correctly.
● Technical specifications will be subject to change without notice.
●This operation manual should be kept till the product has been scrapped.
●This operation manual should be kept in the hand of actual end user.
2
Contents
1 Generalization ........................................................................................................... 5
1.1 Brief Introduction ........................................................................................... 5
1.2 Working principle ........................................................................................... 6
1.3 Protections for motor and related system ..................................................... 8
2 Quick operation......................................................................................................... 9
2.1 Wiring .............................................................................................................. 9
2.2 Keypad ........................................................................................................... 10
2.3 Configuration ................................................................................................ 11
2.4 Motor start ..................................................................................................... 11
3 Descriptions ............................................................................................................. 12
3.1 Brief Introduction ......................................................................................... 12
3.2 Production Generalization (M0/M1/M2/M3 as shape codes) ................... 12
3.3 Control Terminal ........................................................................................... 18
4 Function Instruction ............................................................................................... 23
4.2 Menu instruction ........................................................................................... 25
4.3 Setting............................................................................................................. 27
4.3.1 Application setting .............................................................................. 28
4.3.2 Basic setting ......................................................................................... 29
4.3.3 Function setting ................................................................................... 30
4.3.4 Display setting ..................................................................................... 50
4.3.5 Service setting ...................................................................................... 50
4.4 Local control .................................................................................................. 51
4.5 Events record ................................................................................................. 53
4.6 Status information ........................................................................................ 53
4.7 Events reset .................................................................................................... 54
5 Communication protocol ........................................................................................ 55
5.1 Hardware connection.................................................................................... 55
5.2 Software setting ............................................................................................. 55
5.3 Reading & writing control protocol and related example ......................... 56
5.3.1 Profibus part........................................................................................ 56
5.3.2 Modbus communication rule ............................................................. 59
5.4 Control word and parameter table for bus status...................................... 61
6 Failure analysis........................................................................................................ 66
6.1 Overview ........................................................................................................ 66
6.2 Usual problems and failures......................................................................... 66
6.3 Fault happens when power supply is on ..................................................... 67
6.4 Fault indication ............................................................................................. 67
6.5 Protection indication ..................................................................................... 67
3
Safety precautions
We must be familiar with the content of this operation manual before installation,
connecting circuit, operation and maintenance in order to guarantee its correct
use. We must know well about the information of drive condition and all its
related safety precautions.
Safety
Installation and maintenance operation should strictly comply with this manual,
relative national standard and industry rules. Or manufacturer will not afford
any responsibility for any negative result caused by not following correspondent
operation guide.
All power supply should be turned off before maintaining the soft starter and
related motor.
Please check carefully if there are any components (eg: bolts, washers etc)
dropping into the live parts of the equipment after installation.
Warning
All control parts (including trigger units and CPU control part) are under
hazardous voltage; especially the trigger units have the same high voltage to
main circuit’s. It will be very dangerous if improperly touching it, which may
cause the serious injury and even death.
Even if turning off the control voltage or stopping the soft starter after
connecting the soft starter to the main power supply, it will still display the full
voltage signal for sampling at the output terminal of the soft starter.
The product must make grounding well in order to guarantee safety of the
normal operation so as to prevent from injury of electric shock. It is prohibited
to connect the factor compensation capacitor to the output end of the soft starter.
4
1 Generalization
JJR8000 AC motor soft starter (one full digital intelligent device) is a new soft
starting equipment with adopting electric and electronic technology,
microprocessor technology, and other modern advanced control theory
technology. This product could effectively limit its starting voltage while starting
asynchronous motor, which has been widely applied to fan, pump, transmission,
and compressor and so on. It is one perfect substitute for those equipments by
reducing voltage to soft start motors such as Y/∆ (star/delta) switch, reduction
voltage of auto-transformer, reduction voltage of magnetic control and so on.
Technical characteristics:
1. Main loop circuit working voltage: AC380V/690V/1140 V (+10%~25%);
2. Main loop circuit working current: 13A~1500A;
3. Main loop circuit frequency:50Hz/60Hz(±2%);
4. Control loop circuit power supply:AC/DC 220V ±15%(0.5A);
5. Soft starter rising time: 0~120S;
6. Soft Stop time: 0~100S;
7. Impact time: 0.1~0.3S;
8. Impact voltage: 50%~100%;
9. Limiting current times : 1.5~5.0le;
10. Initial voltage: 25%~80%Ue;
11. Cooling mode: natural cooling;
12. Communication mode: RS485 series communication(Modbus-RTU/Profibus
optional);
13. Start times should be less than 12 times within one hour.
JJR8000 control core is DSP. This microprocessor control system can start and
protect motor. DSP microprocessor can control phase angle triggering of SCR so
as to reduce placed voltage on the motor. The torque of the motor will be
increased smoothly through controlling the voltage and current added on the
motor till accelerating to the full speed operation of the motor. This start mode
can alleviate the start impact current of the motor and then reduce the impact to
the grid and motor. At the same time, it will also reduce mechanical impact on the
mechanical load device connected to the motor so as to prolong the service life of
motor and reduce fault and correspondent stop.
JJR8000 has three start modes: voltage mode, limiting current mode, direct start
mode.
Voltage mode
6
The initial torque can be confirmed (when the frequency is stated, the torque of
motor has direct proportion with the square of added voltage).
Setting range: 25%~80%.We have to put impact current and mechanical impact
into consideration while adjusting its range.
If the setting is too high, It would cause very high initial current impact and
mechanical impact.
Under the voltage mode the current will change in accordance with load change.
When the maximum limiting current is 5 times to the rated current, it could
reduce the start current by adding start time. Because of fast establishment of
motor potential energy, the start process would also be achieved even if it does not
reach the setting rising time when the motor is light loading or free.
7
1.3 Protections for motor and related system
JJR8000 series soft starter provides multiple protection functions to the soft
starter and motor. The main functions are as the following:
1. Phase failure protection for three-phase output. It could only be started when
the main circuit is connected with three-phase input power supply and a load.
2. Over temperature means the SCR group components temperature is too high
(above 80℃) due to frequent starts of the soft starter.
3. Longer start time protection. Longer start time is bad for the soft starter and
the motor. So the longest start time while ex-factory is limited at 30S. This
parameter could be set from 10S to 500S according to its actual load.
4. Big current protection belongs to timing limitation. When the current exceeds
the rated current by 5-8 times (settable), please cut off the output within
20ms-200ms (settable).
5. Overload protection for inverse timing limitation. 4 level curves and stall
protection.
6. Light load alarm, trip protection. Frequency fault.
7. Optional start limitation protection. It would be available for restarting only
when the motor cools down to some extent.
8
2 Quick operation
2.1 Wiring
Instructions:
Main circuit connection: Terminals R-S-T are connected to power supply.
Terminals U-V-W are connected to motor.
Control power connection: It is connected to the terminal P1, P2.
Grounding: It is connected to the circuit P3.
K1 controls bypass contactor, K2, K3 are programmable relay output, all are
passive contact point.
Start and stop circuit connection: It is connected to the control circuit terminals
P4, P5, P6 and P7 according to the diagram.
P9 and P8 are programmable input terminals; P10 is PTC input.
P11 and P12 are 4~20mA analog signal output.
9
2.2 Keypad
NOTE:
1. LED status indication lamp
2. LCD display screen
3. ∧∧←→Adjust the parameter of acceleration or deceleration
4. MENU←→Choose the subentry function for each mode
EXIT←→EXIT key
(The menu with arrow/parameter can roll/modify)
10
2.3 Configuration
Main circuit power-on (check if there is any fault before power-on according
to 2.1)
Deliver start signal to the soft start. (Please enter the menu-setting-site
control-option-start/stop-start if the soft starter needs the soft starter control
pad to run its operation).The motor must stop before exiting the menu.
11
3 Descriptions
12
(2) M1/M2/M3 outline wiring instruction
13
2). Instruction for product model
(1) Product Nameplate
3).Installation
● Installation direction
The soft starter must be installed vertically in order to realize cooling.
● Installation space
In order to guarantee good heat dissipation, there should be enough space for
installation. See following text.
● Circuit installation
The main circuit adopts up input and down output. Meanwhile, the conducting
wire should guarantee enough current-carrying capacity.
14
(2)The distance between M1/M2/M3 and wall/front panel
4) .Size specification
(1) M0 outline size
15
(2)M1/M2/M3 outline sizes
Outline sizes:
16
5). Reference table for JJR8000’s selection
M0 Mode
Rated Current AC380V/Real AC690V/Real Whether
(A) Power Power online or not
13 5.5 1 NO
17 7.5 13 NO
24 11 18.5 NO
32 15 30 NO
38 18.5 37 NO
45 22 45 NO
60 30 55 NO
72 37 75 NO
86 45 90 NO
105 55 110 NO
17
3.3 Control Terminal
18
should be shorter as possible as we can. Reasonable grounding point should be
connected on the installation board of the soft starter which also should be
grounded. (See graphic 3.2)
● Start and Stop. Terminals P4 and P5 (COM), P6 (RUN), P7 (STOP), these four
terminals are used for external buttons to open and stop starter. It must be
selected by programming while using.
Graphic 3.3 offers three wiring methods for the common use of external button.
The dual-wire connection method should be adopted in the following cases. (See
3.4)
(1) When customers need a switch point to control the starter to start and stop, eg
one control point J of PC/PLC.
(2) When using delay function of the soft starter, the starter will begin to start
after one delay time value since the J closes. This delay time value can be
programmable.
19
●Programmable input, terminals P8 and P9
JJR8000 soft starter possesses two programmable inputs.
In0: preset fault/overload reset.
In1: preset fault/overload reset.
See chapter 4 - 4.3.3 (5) to make program.
●Temp input, terminal P10
The thermal sensor PTC integrated in the motor will be connected to the terminal
through P10-COM, See 3.5. The total resistance of the sensor circuit is 2800Ω for
breaking and 1200Ω for connecting. It should be triggered with the program in
the motor protection. See the protection of the reference 4.3.3(2) for the detailed
setting methods.
.Analog current signal output, terminal P11 and P12
The 4~20mA (or 0~20mA) current signal is used to reflect the main circuit current.
The output mode can be selected by the program.(see chapter 4 4.3.3 (9) ).See
reference 3.5.
20
R is load resistor for analog current output end
21
22
4 Function Instruction
4.1 HMI
NOTE:
1. LED status indication lamp
2. LCD display screen
3. ∧∧←→adjust the parameter acceleration or deceleration
4. MENU←→choose the subentry function under each mode
23
EXIT←→EXIT key
(The menu with arrow/parameter can roll/modify)
●LED status indication as follows
LED Color Instruction
Power supply green The control power has
been connected
Fault red Fault display
Protection red Protection function
in effect
When fault or protection LED lamp lights, LCD display screen can display the
corresponding fault description.
LCD display could export two-line description (at most 20 characters per line).
■ The first line will display all kinds of information according to the current status.
The second line shall display function of the current selected key.
■ Turning page arrow will display what parameters or setting values can be
modified under the current status.
■ In different menu the option key owns different functions which are available for
option, modification and record.
See the second line characters on the LCD display screen.
■ The menu key is used for choosing the needed setting in the menu. When
choosing functions in the list table, page turning is under recycling。
● Keypad operation as follows:
Following attached graphic to introduce the Keypad function.
24
Change the motor rated current (Setting current)
1. In the latter chapter, you will find related simple
explanation and route of setting.
Simple route:
Menu-setting-function setting-start/stop-current setting
2. Soft starter menu (graphic1).
Press MENU to enter menu (graphic2)
3. Press MENU to select setting (graphic3)
4. Press two times up or down key till graphic 4
appears.
5. Press MENU to select start/stop (graphic5).
6. Press MENU to enter current setting (graphic6)
current display (graphic 7).
7. Use up and down key to set the rated current, please
select cancel key if you want to exit or press left key
to select storage to store the setting value(graphic 8).
8. Press 4 times back key to return to the main menu.
25
Graphic9: Main menu display
1).Keypad lock/unlock
Keypad lock/unlock
1. Press∧one time to enter Keypad (graphic 10).
If the upper right corner display shows being active, the Keypad unlocks.
2. Press MENU to enter Keypad storage. (Graphic11).
Press up and down key to lock. Select storage to make the Keypad stay in lock
status.
Select back to return the main menu.
3 Keypad unlocks
Carry out its operation the same to lock steps.
Once the Keypad locked, it is never entering the setting submenu.
The soft starter will test whether the input voltage is normal.
Normal: OK; voltage is over lower: LOW-V
The used thermal capacity of motor can be displayed. 0% means that the motor
stays in cooling status. 50% means half of thermal capacity is used, etc. It is only
26
effective when the overload protection has been activated.
The programmable input and output status is shown as”0” and “1”. “0” means no
activation, “1” means activation. The figures own following functions.
In=0100 start signal
In=1000 stop signal
In=0010 programmable input 0
In=0001 programmable input 1
Out=010 programmable relay K2 has been activated.
Out=001 programmable relay K3 has been activated.
4.3 Setting
Press MENU to enter the main menu which includes following submenu.
Menu Set up
Events record
Status information
Events reset
Local control
27
Preset parameters setting to store in the storage unit in order to reset the
parameters to presetting values. When the bus communication is chosen, most
parameters can be modified via communication port.
Note:
All following functions adopt the Keypad method to set. The bus communication
method will be introduced in the communication protocol of chapter 5.
Setting includes application setting, basic setting, function setting, display setting,
and service setting etc.
28
Select application setting to enter this menu.
Choose a good start application mode through the
setting storage. If all the application modes are not in
the list, please press up and down key to choose the
needed application mode, then choose the adjustment
setting for minitrim.
Press next step to confirm option. If the option is wrong,
please press back and then choose the correct
application setting. The setting sequence is shown as the
right graphic.
Basic setting of the menu has included the commonest start/stop parameters
which need to be set. Each parameter can be adjusted separately.
Menu Setting Application setting Current setting
Basic setting Motor overload type
Function setting Start mode
Display setting Voltage acceleration time
Service setting Voltage deceleration time
Initial voltage
Initial time
Current limit times
29
Each application of the function and the detailed
specification instruction of the parameters will refer to the
“function setting” of the manual.
Function setting includes several groups of parameters, they are listed according
to the functions such as protection, alarm, fault, bus communication etc. This
menu can be used to set further.
Menu Setting Application setting
Basic setting
Function setting Start/stop
Display setting Protection
Service setting Alarm
Fault measurement
Input
Output
Bus
Sequent start
Analog current output
30
1) Start /stop
It can be used to set the each parameter for start /stop process of the soft starter.
The menu tree is shown as following graphic.
Function setting Start/stop Setting current
Protection Start mode
Alarm Voltage acceleration time
Fault measurement Voltage deceleration time
Input Initial voltage
Output Initial time
Bus Level fall voltage
Sequent start Limit current times
Analog current output Impact start
Impact voltage
Impact time
Delay start
Delay time
● Setting current
It is used to confirm start current of the soft starter; the detailed setting is the
rated current value of the motor. (Please see the motor nameplate).
Setting range: 1~1500A
● Start mode
It is used to set the choosing mode when the starter begins to start.
Optional mode: voltage, limit current, direct start.
● Voltage acceleration time
It is used to set the time from the start signal to the end of the acceleration time for
the soft starter. The soft starter will trip to cut off the power supply of the motor if
the voltage still could not reach the full voltage after this period. LCD will display
the information of ‘prolong start time’.
Setting range: 1~120s
31
●Voltage deceleration time
It is used to control stop under the high friction load and confirm the time for
reducing voltage to zero. If the voltage deceleration time is 0, once the stop order
is delivered the starter will directly cut off the voltage, which equals to motor free
stop.
Setting range: 0~100s
● Initial voltage
It is used to set the initial voltage level during its starting process of the soft starter.
If the initial voltage setting is too lower, it will cause overlong start time and
unnecessary motor heat.
Setting range: 25%~80%
● Initial time
It is used to set initial time level during its starting process of the soft start. The
voltage will not change during the setting time. Even if it has reached its initial
32
time, the soft starter will still continue to start based on the rising mode until the
start is wholly completed.
Setting range: 1~120s.
● Limit current times
It is used to limit the start current. When the current reaches the limiting value,
the output voltage will keep stable. Until the current is reduced to the level below
the limiting value the voltage rising process will continue. The start current must
be big enough to make the motor reach the rated speed. The allowed minimum
start current is decided by characteristics of the motor and related load.
Setting range: 1.5x~5.0x
● Impact start
It is used to start the high friction load, which needs a bigger start torque within
short time.
Setting range: Allow, Prohibit
● Impact time
It is used to set the requested impact time value.
Setting range: 0.1~0.3s
● Delay start
It is used to set delay start.
33
Setting range: Allow, Prohibit
● Delay time
It is used to set the delay start time value.
Setting range: 0~300s
● Step-down voltage
When the motor stops soft, the rotor speed will not decelerate immediately. The
level fall voltage function can make the speed of the motor decelerate from the
beginning of the soft stop process. It can get an optimized stop through this
function. It is mainly applied to pump load.
Setting range: 25%~80%
2) Protection
Enter the protection menu to carry out the function setting.The menu tree is
shown as graphic 32:
Function setting Start /stop
Protection Motor overload protection
Alarm Motor temperature protection
Fault measurement Reverse phase protection
Input Big current protection
Output Motor phase loss protection
Bus Three-phase imbalance
protection
Sequent start Motor underload protection
Analog current output Motor stall protection
Start limiting time
Thermal melting limit
34
● Motor overload protection
It is used to protect the motor during the start process of the soft starter, which
can prevent from damaging the motor by allowing big running current. This
function has three kinds of modes to be selected.
Selective modes:
Normal: not activate this function
Common: standard protection mode
Dual: this protection has two overload types, one is used for start, and the other is
used during operation.
Motor overload type
It is used to set the requested motor overload protection type.
Setting type:
10A
20
30
10
Start overload type
It is used to set the requested motor overload protection type for the motor start.
When the operation reaches the full voltage, it will switch to its operation
overload type.
Setting type:
10A
20
30
10
● Operation overload type
It is used to set the needed motor overload protection type for the continuous
35
operation of the motor.
Setting type:
10A
20
30
10
Disposal method
When the protection is activated, this parameter is used for selecting the three
different operational modes owned by the soft starter. Only the corresponding
protection is selected, then this function will be activated.
Disposal method:
Manual reset: motor stops; we need to reset before restarting motor.
Automatic reset: motor stops; once faults disappear, it will automatically reset.
Only for indication: motor continues to run when it only send fault indication.
● Motor temperature protection
It is used to protect the motor once the working temperature is over setting
temperature value.
Setting range: Allow, Prohibit
Disposal method
When the protection is activated, this parameter is used for selecting three
different operational modes owned by the soft starter. Only the corresponding
protection is selected, this function will be activated.
Disposal method:
Manual reset: motor stops; we need to reset before restarting motor.
Automatic reset: motor stops; once faults disappear, it will automatically reset.
Only for indication: motor continues to run when it only send fault indication.
● Reverse phase protection
The soft starter could accept any phase sequence but the phase sequence must
follow L1-L2-L3 once we choose this protection function.
Setting range: Non, Positive sequence, Negative sequence
36
Disposal method
When the protection is activated, this parameter is used for selecting three
different operational modes owned by the soft starter. Only the corresponding
protection is selected, this function will be activated.
Disposal method:
Manual reset: motor stops; we need to reset before restarting motor.
Automatic reset: motor stops; once faults disappear, it will automatically reset.
Only for indication: motor continues to run when it only send fault indication.
● Three-phase imbalance protection
If the difference between a phase of current and another phase current exceeds
the setting level, this protection will be activated to monitor after full voltage
lasting for 1 minute.
Setting range: Non, Exist
38
Automatic reset: motor stops; once faults disappear, it will automatically reset.
Only for indication: motor continues to run when it only send fault indication.
3) Alarm
Enter the alarm menu, set its relative parameters to alarm. The menu tree is
shown as graphic 33:
Function setting Start/stop
Protection
Alarm Motor undervoltage alarm
Fault disposal Motor overload alarm
Input SCR overload alarm
Output Big current alarm
Bus
Sequent start
Analog current output
● Motor underload alarm
If this function is selected, once the current is below the setting value under the
full voltage, the alarm signal will be sent. After reaching the full voltage for 60S, it
will begin to monitor.
Setting range: exist, non
● Underload alarm value
Use for setting the underload alarm value.
Setting range:
0.3x~1.0x
● Motor overload alarm
If this function is selected, it will be activated once the motor load exceeds the
specified value. The alarm signal will send out.
Setting range: Exist, Non
41
Overload alarm value
It is used to set the overload alarm value.
Setting range: 1.2x~2.0x
● Big current alarm
If this function is selected, it will be activated once the motor load current exceeds
the specified value. The alarm signal will send out.
Setting range: exist, non
Current alarm value
It is used to set current alarm value.
Setting range: 0.5x~5.0x
● SCR overload alarm
If this function is selected, it will be activated once the SCR temperature exceeds
the specified value. The alarm signal will send out.
Setting range: Exist, Non
SCR overload alarm value
Use for setting SCR alarm value.
Setting range: 40~100℃
4) Fault disposal
It is used to dispose all kinds of faults in the operation process of the soft starter.
The menu tree is shown as graphic 34:
Function setting Start/stop
protection
Alarm
Fault disposal Power phase lost disposal
Input Bus fault disposal,
Output Frequency fault disposal ,
Bus Internal overheat disposal
Sequent start
Analog current output
42
● Power phase lost disposal
If the phase lost fault happens, this parameter is used for selection between the
two different operational modes owned by the motor.
Setting range:
Manual reset: motor stops, it will need to manually reset before restarting the soft
starter.
Automatic reset: motor stops; once faults disappear, it will automatically reset.
● Bus fault disposal
If the bus fault happens, this parameter is used for selection between the two
different operational modes owned by the soft starter
Setting range:
Manual reset: motor stops, it will need to manually reset before restarting the soft
starter.
Automatic reset: motor stops; once faults disappear, it will automatically reset.
● Frequency fault disposal
If the frequency exceeds the range, this parameter is used for selection between
the two different operational modes owned by the soft starter.
Setting range:
Manual reset: motor stops, it will need to manually reset before restarting the soft
starter.
Automatic reset: motor stops; once faults disappear, it will automatically reset.
● Internal overheat disposal
If the internal cooling temperature is too high, this parameter is used for selection
between the two different operational modes owned by the soft starter.
Setting range:
Manual reset: motor stops, it will need to manually reset before restarting the soft
starter.
Automatic reset: motor stops; once faults disappear, it will automatically reset.
5) Programmable input
43
It is used to set the parameters related to the programmable input, the menu tree
is shown as graphic 35:
Function setting Start/stop
Protection
Alarm
Fault disposal
Input Programmable input 0,
Programmable input 1
Output
Bus
Sequent start
Analog current output
● Programmable input 0, 1
The soft starter has two programmable input (0/1), which could be used for
different goals according to the selected function. They are independent from
each other.
Programmable input 0 setting range:
Non: Without indication function (not activated).
Reset: fault or overload reset.
Allowed: In=0 (connection with COM), the soft starter is in the normal working
status; this function is prior to all other inputs.
In=1, the soft start will stop work.
External fault: follow the mode of the soft starter to start. The motor will stop
immediately once releasing the command.
Direct start: open/close the bypass contactor.
Start 2: the start signal for the second parameter setting.
44
status; this function is prior to all other inputs.
In=1, the soft starter will stop work immediately.
External fault: follow the mode of the soft starter to start. The motor will stop
immediately once releasing the command.
Direct start: open/close the bypass contactor.
Start 3: the start signal of the second parameter setting.
6) Output
It is used to set the relative parameters related to the programmable output. The
menu tree is shown as graphic 36:
Input
● The soft starter has two programmable relay outputs (K2, K3), which could
be used for different goals according to the selected function. They are
independent from each other. In the process of voltage rising, operation and
voltage reduction, the signal will send out.
Setting range:
Running
Events
45
Delay
Full voltage
K2,K3 events
Full fault
Motor fault
Equipment fault
Alarm
K2, K3 interlocked time
Set the operation time parameters
Setting range: 0~200S
7) Bus
It is used to set the relative bus parameters. The menu tree is shown as graphic
37:
Function Start/stop
setting
Protection
Alarm
Fault disposal
Input
Output
Bus Bus control;
Bus type;
Bus address;
MOD communication
baud;
PRO type
Sequent start
Analog current output
● Bus control
If we get ready to control the starter through the bus communication, the
communication port must be activated before carrying out any operation.
46
Setting range: non, external control, bus
Non: bus is not activated
External control: bus is activated; the control signal is given by the terminals and
the bus just plays the role of monitoring.
Bus: bus is activated; control permission is given by bus order which carries out
bus monitors at the same time
● Bus type
It is used to select type of the bus.
Setting range: MOD, PRO
MOD: selecting Modbus mode
PRO: selecting Profibus mode.
● Bus address
It is used to select a bus address for the soft starter. We select a suitable, unused
numbers as the address.
Setting range: 0~247
●MOD communication baud
When using the Mod protocol, select a match communication baud for the soft
starter.
Setting range: 1200, 2400, 4800, 9600, 19200
●PRO type
Select the control type for the PRO protocol.
Setting range:
3: Only read status
1: Modify parameter
8) Sequence start
It is used to start several or many motors with different parameters. The menu
tree is shown as graphic 38.
47
Function setting Start/stop
Protection
Alarm
Fault disposal
Input
Output
Bus
Sequence start Sequence start number
Analog current output Sequence 1 parameter
Sequence 2parameter
Sequence 3parameter
Initial voltage:25%~80%
48
Setting range:
Setting current: 0~1500A
Start mode: voltage, current limit
Rising voltage time: 0~100s
Initial voltage:25%~80%
Initial time: 0~120s
Current limit times: 1.5x~5.0x
● Sequence 2 parameter
Enter the sequence 3 parameter group to set the relative parameter.
Setting range:
Setting current: 0~1500A
Start mode: voltage, current limit
Rising voltage time: 0~100s
Initial voltage:25%~80%
Initial time: 0~120s
Current limit times: 1.5x~5.0x
49
● Motor current value
Analog current measuring range can be set from 0.5x to 5.0x.
Service menu includes the parameter setting of the relative maintenance and
repair.
Menu Setting Application setting
Basic setting
Function setting
50
Display setting
Service setting
Graphic 42 Service setting
Menu Setting
Local control Start/stop
Jog
Events record
Status information
Events reset
Local control menu is used to control the motor start/stop through the Keypad.
While selecting one kind of local control type, the soft starter will only be
controlled by the Keypad.
When the sequence start is selected, to enter the local control menu is prohibited.
Once this menu has carried out the motor start, please stop the motor before
exiting this menu. Two ways can be selected. (See graphic below)
51
Function Instruction
Start/stop Start/stop the motor through the
Keypad.
Jog When the jog is pressed, the motor will
run; the motor will stop if the jog is
loosened.
● Start/stop
Menu Setting
Local control Start/stop
Jog
Events record
Status information
Events reset
Graphic 44 start/stop menu
Start
Enter the start/stop menu (graphic 15). Select the start key to start the motor
according to the setting parameters.
Stop
Select the stop key to stop the motor according to the setting parameters. We
could press stop order during the start process if necessary.
● Jog
Menu Setting
Local control Start/stop
Jog
Events record
Status information
Events reset
Graphic 45 Jog menu
Enter the JOG menu (see graphic 16), select JOG. As long as keeping the JOG
order, the motor will accelerate to the rated speed according to setting parameters.
Once the order is canceled, the motor will stop immediately.
52
4.5 Events record
Menu Setting
Local control
Events record
Status record
Events reset
Graphic 46 Events record
The events record menu is used to check the events record of the soft starter.
When entering the menu, the latest 10 events will be displayed. According to the
time sequence, the forefront event is first, the next is second and so on.
These events will be displayed with the events type, the happening date and time.
View all the items in the events record through operation key.
Menu Setting
Local control
Events record
Status record
Events reset
Graphic 47 Status information
The status information menu will be used to display all kinds of different
information. The information will be displayed on the top line by line. Use the
operation key to display all the information.
Display text Function
Frequency Measured frequency
L1 phase current L1 phase current
L2 phase current L2 phase current
L3 phase current L3 phase current
Operation time Total operation time of the motor
Number of start Number of start
Maximum start current Maximum start current
Maximum operation current Maximum operation current
53
4.7 Events reset
Menu Setting
Local control
Events record
Status record
Events reset
Graphic 48 Events reset
When the faults happen or the equipment is in the protection status, it will
automatically enter the events reset menu or enter the reset menu through the
main menu.
54
5 Communication protocol
Connect the soft starter to the upper computer (master) through the bus cable.
The last unit must connect one 2000Ώ terminal resistor if there are several
parallel units .
Menu----Setting----Function setting----Bus
Bus Series No Profibus Modbus Instruction
Bus control External External External control:
control/bus /non control/bus /non terminal start/stop
Bus: Bus
start/stop
Non: Bus close
Bus type PRO MOD PRO: Profibus
MOD: Modbus
Bus address 1-147 1-247 Address for each
soft starter is
unique
MOD 1200-19200 9600 while
communication ex-factory
baud
PRO type 1,3 1: all parameters
control writing
and reading.
3: partial
parameters take
part in monitoring
55
Note:
1: The setting parameter will only be valid after restart powering on.
2: when selecting the Profibus, it will display “communication fault” without
installing the communication board.
Profibus is one express bus with the maximum communication baud 12M. It can
be selected to confirm the value through the upper computer.
Profibus communication protocol is divided into data communication form rule
and application rule. The Profibus communication protocol form is defined by the
GSD file. The application part is open, which is defined by the manufacturer.
1) Communication rule part
Profibus bus controls the JJR8000 through a group of data to complete. It is
totally divided into two data areas namely parameter identification area PKW
and process control PZD, each occupying 2 bytes input/output. The former is used
to read out and modify the function parameter of the soft starter; meanwhile; the
latter is used to control and monitor status current. The master configuration is
given by GSD file.(see graphic 5.1)
IND: high byte INDH means task requirement, low byte INDL is parameter
56
address (see attached table1); used for type 1.
PWE: writing & reading the parameter, see table 5.12; used for type 1.
STW: control word, see table 5.9; used for type 1 and type 3.
ZSW: status word, see table 5.10; used for type 1 and type 3.
ACT: current value (A phase)
Type 1---- It could carry out all operation to the parameter and control monitor of
the soft starter. Check various relative data and control start/stop.Work is in the
PKW and PZD areas.
Type 3----It only carries out the work status monitor. A phase current monitors
and controls of start/stop. Work is in PZD area.
2) Profibus writing & reading protocol
This protocol is given through the table 5.2 and 5.3, which are defined by the
manufacturer.
Table 5.2 the master sends out the task requirements to the slave.
INDH Definition
0 No task
1 Read out one parameter, address is
INDL, see attached table 7
2 Modify one parameter, address is
INDL, write the data into PWE, see
attached table 7
3 Read out status parameter, address is
INDL, see attached table6
57
2 Value exceeds the upper and lower
limit.
3 Can’t modify under live running
4 Don’t support this service
3) Application instance
Use the bus to make the soft starter start.
MASTER: PC or the upper computer master; SLAVE: slave represents that the
address of the soft start is 02.
The PZD control under Profibus: order word is written into the STW of PZD.
MASTER---SLAVE 00 0B 00 00
SLAVE ---MASTER
Normal return 09 00 03 C0 indication for start status, current is 96A.
Fault return 81 01 05 64 indication for phase lost, start current value
is 138A.
Note: return to ZSW+ACT
The following is the operation of type 1 to PKE.
e.g. 1: read out the voltage rising time
To check out an address operation code from table 1, read out INDH=01H
To check out the voltage rising time address from table 7 is 03, so INDL=03H
MASTER---SLAVE 01 03 00 00 Because it is only reading the parameter,
the last four “0” has no meaning.
SLAVE ----MASTER 01 03 00 0c Learning from table 2 PWE=0c, the
voltage rising time is 12s
e.g. 2: modify the limit current to 350%, Hex is 15E.
MASTER----SLAVE 02 07 01 5E
Normal return: SLAVE—MASTER 01 07 01 5E
If return: SLAVE ---MASTER 03 07 00 03
It indicates that this parameter can NOT be modified in running process of the
equipment.
e.g. 3 read out the online B phase current.
See table 5.12 B phase current belongs to the status parameter. The operation
58
code is 03 and its address is 03.
So : MASTER---SLAVE 03 03 00 00
SLAVE----MASTER 01 03 02 64 1b =61.2A decimal system.
Modbus possesses PLC structure characteristics. We could write & read JJR8000
soft starter like one PLC. JJR8000 soft starter reflects start/stop control, status
information(current, fault etc.), function parameters into register(4XXX). The
usage of writing & reading control is realized through the PLC master station.
1) Modbus communication rule
Table5.5 master sends out the data to JJR8000
Address Function code Register Function CRC code
address parameter
BYTE BYTE WORD WORD WORD
The JJR8000 supports the standard Modbus extra case code. (See table 5.8)
Code Name Instruction
01 Illegal function Function code can not be carried out,
JJR8000 does not support
02 Illegal data address The data received address can not be
executed, address overflows
03 Illegal data value The received data can not be carried out
1 parameters exceed the limiting
amplitude
2 parameter can not be modified
59
3) Application instance
e.g.1: Make the soft starter start
MASTER----SLAVE 02 06 00 00 09
SLAVE-----MARSTER 02 06 00 00 00
e.g. 2: Under reading status, operation is carried out to 4002
MASTER----SLAVE 02 03 00 01 00 01
SLAVE----MASTER 02 03 02 01 00
Illustrate the soft starter on starting status.
If SLAVE---MASTER 02 03 02 81 06
Illustrate the motor overload in process of starting
e.g. 3: Read A phase current register 4003
MASTER---SLAVE 02 03 00 02 00 01
SLAVE----MASTER 02 03 02 00 EB
Read A current as 23.5 A
Read & write the function parameter in Modbus.
Operation address =parameter address + 100
Instruction for the below instance.
e.g. 4: Read out the limiting current of the soft starter
MASTER----SLAVE 02 03 01 07 00 01
SLAVE----MASTER 02 03 02 01 5E
Current limit: 350%
e.g. 5: Rewrite the rated current of the motor as 400A
MASTER---SLAVE 02 06 01 00 01 90
SLAVE----MASTER 02 06 02 01 90
e.g. 6: Modify the rising time value as 20s
MASTER----SLAVE 02 06 01 03 00 14
SLAVE----MASTER 02 06 02 00 14
60
5.4 Control word and parameter table for bus status
61
Table5.11 Fault code serial No. and correspondent instruction
Serial No. Fault Serial No. Fault
01 Power phase lost 10 Three phase
imbalance
02 Overheat 11 Motor phase lost
03 Frequency fault 12 Motor underload
04 overlong start 13 SCR over
time temperature
05 External fault 14
06 Motor overload 15
07 Motor stall 16 External fault 2
08 Big current trip 17 Bypass fault
09 Power inverse 18 Parameter fault
sequence
62
1. Profibus A phase current can be read by ACT in PZD.
2. Both address and parameter value adopt Hex.
63
35
36 Motor underload protection No 0 Yes 1
37 Underload trip level 0.4x-0.8x
38 Underload trip time 1-30s
39 Underload handling 0: manual 1: auto 2: tips
40 Motor stall protection No 0 Yes 1
41 Stall trip level 3.0x-8.0x
42 Stall trip time 0.2s-10s
43 Stall trip mode 0: manual 1: auto 2: tips
44 Thermal melting limit No 0 Yes 1
45 Thermal melting level 0%-100%
46 Cooling time 0-600s
47
48
49
50
51 Motor underload alarm No 0 Yes 1
52 Underload alarm value 0.3x-1.0x
53 Motor overload alarm No 0 Yes 1
54 Overload alarm value 1.2x-2.0x
55 SCR overload alarm No 0 Yes 1
56 Phase lost fault handling 1: self-reset 0: manual reset
57
58 Bus failure handling 1: self-reset 0: manual reset
59 Frequency fault handling 1: self-reset 0: manual reset
60 Internal overheat handling 1: self-reset 0: manual reset
61 Overlong time starting handling 1: self-reset 0: manual reset
62 Programmable input 0 0 no 1 reset 2 permit 3 external
fault 4 direct start 5 start 2
63 Programmable input 1 0 no 1 reset 2 permit 3 external
fault 4 direct start 5 start 3
64
65
66 Bus control No 0 external control 1 bus 2
67 Bus type 0 Modbus 1 Profibus
68 Bus address 0-247
69 Baud rate Modbus baud rate
71-75 PRO mode 0:II:III
Reserve
76 Programmable relay K2 0 run 1 full voltage 2 delay 3
events
77 Events 0 full fault 1 motor fault 2
device fault 3 alarm
64
78 Interlock time 0-200s
65
6 Failure analysis
6.1 Overview
When the soft starter or program meets any problem, this section could be used
as a guide to help shoot the fault.
Soft starter adopts LED to indicate fault and fault type will be displayed on the
LCD monitor. When the protection function is activated, LED will show the
working of this function and LCD will instruct protection type.
66
6.3 Fault happens when power supply is on
67
Anti-phase protection
Reset Return
Motor tempreture PTC in the motor detects Check whether the PTC
protection that the motor circuit is closed and
Power temperature is too high. whether the input is
Fault Protection connected.
Motor tempreture Check the reason for its
protection high temperature and
Reset Return correct it.
Cool the motor
sufficiently and then
restart the motor.
Motor overload After a certain time, the During starting:
protection current is still too high, Check the overload
Power which results in motor reason and correct it.
Fault Protection overload. (The load on Check whether the
Motor overload the motor’s bearing is too current limiting times are
Reset Return high.) too small.
Check that the
acceleration time is not
too long when starting.
Check whether the
appropriate motor
overload category is
selected.
Check that the current
setting is correct.
During continuous
working:
Check the reason for the
overload and correct it.
Motor stall protectionSome reasons cause the Check the motor bearing
Power motor running fault. and load.
Fault Protection Damage to the bearings Check whether the load
Motor stall and its adhesion load operation is rigid.
Reset Return may be the reason.
Big current protectionIt generates a fault Check all the lines
Power current which is n times including the motor,
Fault Protection higher than the whether there is the same
Heavy current
soft-starter rated insulation failure or
protection current. grounding fault.
Reset Return Check the heavy current
protection settings.
Three-phase imbalance Three-phase current Check the main circuit
protection imbalance voltage and motor
Power circuit.
Fault Protection Restart the motor and
Three-phase imbalance then check each phase
protection current.
Reset Return
68