Ultra

Low

Product Features
Low adjustable pressure ranges
with high working pressures

Explosion-proof or general
purpose enclosures

Corrosion resistant epoxy coated


aluminum sensor housing

Suitable for fluids, air, and


gas media
Highly repeatable
Overview
UE’s new differential pressure switches provide low adjustable ranges with high working (static) pressures. Models 540-543 (K1-K3) utilize a large
diaphragm sensor whose large effective sensing area enables accurate and repeatable performance at low pressures. Models 544-548 (K4-K6) handle
higher pressures with a compact design. The aluminum sensor housings are epoxy-coated for corrosion resistance in harsh environments and are
suitable for use with fluids, air and gas media in a variety of applications in processing, power and OEM markets. Typical services include: monitoring air
or fluid flow, indicating clogged filters and providing alarm/shutdown functions. Vacuum pumps, compressors, purge systems, water injection skids,
scrubbers and burners are some of the equipment frequently requiring differential pressure switches. A wide range of switching options broadens the
applicability of the series.
The H100K is a low cost, NEMA 4X differential pressure switch. The H117K also meets NEMA 4X and is the “Division 2” version of the H100K. Both
series offer a rugged one-piece enclosure and features a slanted cover for wiring accessibility. The J402K provides two, independent switches which may be
separated by as much as 95%. This would allow for alarm AND shutdown of a process. For hazardous locations, the 12K series provides an all stainless
steel, cylindrical body configuration which is critical in compact systems where space is at a premium. Also, for hazardous locations the J120K and
QJ120K meet UL, CSA and CENELEC standards respectively to protect equipment and personnel.

H100K provides cost effective differential


J120K/QJ120 meets requirements of Class 1, pressure control in general purpose and NEMA
Div. 1 and CENELEC hazardous environments 4X/IP65 applications

12K meets requirements of Class 1, Div. 1 and J402K provides cost effective differential
hazardous requirements CENELEC EEx d IIC T6 pressure control and allows for two independent
set points
Model Chart: 12K
Epoxy coated aluminum housing with Kapton™ diaphragm, Buna-N sealing diaphragms and 1/8” NPT Female pressure connections.

Model Adjustable Range Deadband Range Max Working Proof Pressure


Pressure
low end on fall; high end on rise
wcd/psid mbar/bar wc/psi mbar/bar psi bar psi bar
K1 0.7 to 10 "wcd 1,7 to 24,9 mbar 0.2 to 1 "wc 0,5 to 2,5 mbar 200 13,8 400 27,6
K2 2 to 20 "wcd 5,0 to 49,8 mbar 0.3 to 1.5 "wc 0,7 to 3,7 mbar 200 13,8 400 27,6
K3 10 to 150 "wcd 24,9 to 373,4 mbar 0.3 to 5 "wc 0,7 to 12,4 mbar 200 13,8 400 27,6
K4 2 to 20 psid 0,1 to 1,4 bar 0.3 to 1.5 psi 0 to 0,1 bar 1200 82,7 2,500 172,4
K5 5 to 80 psid 0,3 to 5,5 bar 1 to 8 psi 0,1 to 0,6 bar 1200 82,7 2,500 172,4
K6 10 to 150 psid 0,7 to 10,3 bar 1 to 10 psi 0,1 to 0,7 bar 1200 82,7 2,500 172,4

Model Chart: H100K and J120K


Epoxy coated aluminum housing with Kapton™ diaphragm, Buna-N sealing diaphragms and 1/8” NPT Female pressure connections.
Model Adjustable Range Deadband Range Max Working Proof Pressure
Pressure
low end on fall; high end on rise
wcd/psid mbar/bar wc/psi mbar/bar psi bar psi bar
540 0.2 to 7 "wcd 0,5 to 17,4 mbar 0.05 to 0.3 "wc 0,1 to 0,7 mbar 200 13,8 400 27,6
541 1 to 20 "wcd 2,5 to 49,8 mbar 0.1 to 0.5 "wc 0,2 to 1,2 mbar 200 13,8 400 27,6
542 5 to 50 "wcd 12,4 to 124,5 mbar 0.2 to 1.5 "wc 0,5 to 3,7 mbar 200 13,8 400 27,6
543 10 to 200 "wcd 24,9 to 497,8 mbar 0.5 to 4.5 "wc 1,2 to 11,2 mbar 200 13,8 400 27,6
544 2 to 20 psid 0,1 to 1,4 bar 0.1 to 0.6 psi 6 to 41,4 mbar 1200 82,7 2500 172,4
545 5 to 50 psid 0,3 to 3,4 bar 0.2 to 1.2 psi 0 to 0,1 bar 1200 82,7 2500 172,4
546 10 to 125 psid 0,7 to 8,6 bar 0.4 to 2.6 psi 0 to 0,2 bar 1200 82,7 2500 172,4
547 50 to 250 psid 3,4 to 17,2 bar 0.8 to 5.3 psi 0,1 to 0,4 bar 1200 82,7 2500 172,4
548 100 to 500 psid 6,9 to 34,5 bar 2.0 to 9.0 psi 0,1 to 0,6 bar 1200 82,7 2500 172,4

Model Chart: H117K


Epoxy coated alumium housing with Kapton™ diaphragm, Buna-N sealing diaphragms and 1/8”” NPT Female pressure connections
Model Adjustable Range Deadband Range Max Working Proof Pressure
Pressure
low end on fall; high end on rise
wcd/psid mbar/bar wc/psi mbar/bar psi bar bar bar
540 0.8 to 7 "wcd 2 to 17,4 mbar 0.2 to 1.3 "wc 0,5 to 3,2 mbar 200 13,8 400 27,6
541 2 to 20 wcd 5 to 49,8 mbar 0.3 to 1.6 "wc 0,7 to 4 mbar 200 13,8 400 27,6
542 5 to 50 "wcd 12,4 to 124,5 mbar 0.3 to 4 "wc 0,7 to 10 mbar 200 13,8 400 27,6
543 10 to 200 "wcd 24,9 to 497,8 mbar 0.8 to 12 "wc 2 to 29,9 mbar 200 13,8 400 27,6
544 2 to 20 psid 0,1 to 1,4 bar 0.2 to 2 psi 0 to 0,1 bar 1200 82,7 2500 172,4
545 5 to 50 psid 0,3 to 3,4 bar 0.4 to 3.2 psi 0 to 0,2 bar 1200 82,7 2500 172,4
546 10 to 125 psid 0,7 to 8,6 bar 0.5 to 7 psi 0 to 7 bar 1200 82,7 2500 172,4
547 50 to 250 psid 3,4 to 17,2 bar 2 to 15 psi 0,1 to 1 bar 1200 82,7 2500 172,4
548 100 to 500 psid 6,9 to 34,5 bar 2 to 20 psi 0,1 to 1,4 bar 1200 82,7 2500 172,4
Model Chart: J402K
Epoxy coated alumium housing with Kapton diaphragm, Buna-N sealing diaphragms and 1/8”” NPT Female pressure connections.
Model Adjustable Range Deadband Max Working Proof Switch
Range Pressure Pressure Separation
low end on fall; high end on rise
wcd/psid mbar/bar wc/psi mbar/bar psi bar psi bar
540 1 to 7 "wcd 2,5 to 17,4 mbar 0.1 to 1 "wc 0,2 to 2,5 mbar 200 13,8 400 27,6 95%
541 2 to 20 "wcd 5,0 to 49,8 mbar 0.5 to 4 "wc 1,2 to 10 mbar 200 13,8 400 27,6 95%
542 5 to 50 "wcd 12,4 to 124,5 mbar 0.5 to 10 "wc 1,2 to 24,9 mbar 200 13,8 400 2,6 95%
543 15 to 100 "wcd 37,3 to 248,9 mbar 0.5 to 14 "wc 1,2 to 34,8 mbar 200 13,8 400 27,6 95%
544 2 to 20 psid 0,1 to 1,4 bar 1 to 5 psi 0,1 to 0,3 bar 1,200 82,7 2,500 172,4 95%
545 5 to 50 psid 0,3 to 3,4 bar 1 to 6 psi 0,1 to 0,4 bar 1,200 82,7 2,500 172,4 95%
546 10 to 100 psid 0,7 to 6,9 bar 1 to 10 psi 0,1 to 0,7 bar 1,200 82,7 2,500 172,4 95%
547 20 to 200 psid 1,4 to 13,8 bar 1 to 14 psi 0,1 to 1,0 bar 1,200 82,7 2,500 172,4 95%

NOTE: Set point repeats ±1 % of range for start-up vacuum (30” Hg VAC).

Specifications: 12K Series


Storage temperature -65 to 160 (-54 to 71°C) Switch output Either: One, SPDT switch with factory
sealed leadwires.
Ambient Temperature 0° to 160°F (-40 to 71°C); setpoint Two, SPDT switches for DPDT action.
Limits typically shifts less than 1% of range for
a 50°F (28°C) ambient temperature change Electrical Rating Either: 5 amps 250 VAC resistive (choice H)
1 amp 125 VAC resistive (choice L)
Set Point Repeatability Sensor type K1-K3: +/- 1% of adjustable range span
Sensor type K4-K6: +/- 1-1⁄2% of adjustable Approx. Weight Sensor type K1-K3: 5lbs 4 oz (2, 38 kg)
range span Sensor type K4- K6: 3 lbs 6 oz (1, 53 kg)

Shock Set point repeats after 15 G, 10 milli- Electrical Connection ⁄2" NPT, M with 72" leadwires
1

seconds duration
Approvals Class I, Divisions 1 & 2; Groups A, B, C, D
Vibration Set point repeats after 2.5 G, 5-500 Hz Class II, Divisions 1 & 2; Groups E, F, G
Class III
Enclosure 300 series stainless steel Class I, Zone 1, Group IIC
Sensor housing: epoxy coated aluminum UL Listed, file # E40857; cUL certified
with 1⁄8" NPT Female pressure connections. file E40857
Anodized Aluminum internal metallic parts. CENELEC flame proof construction per
Kapton™ and Buna-N internal seals. Viton EEx d IIC T6
DEMKO certificate # 97D.122235
material is optional (replaces Buna-N seals).
Flameproof equipment, EN 50 014 and
Enclosure EN 50 018
Classification Complies with NEMA 4X, 7, 9; IP66 CE compliant to Low voltage directive
Specifications: H100K Series
Storage temperature -65 to 160 (-54 to 71°C)
Enclosure Complies with NEMA 4X;
Ambient Temperature 0° to 160°F (-40 to 71°C); setpoint Classification IP65 requirements
Limits typically shifts less than 1% of range for
a 50°F (28°C) ambient temperature change Switch output One SPDT snap action switch; switch
may be wired “normally open” or
Set Point Repeatability Models 540-543 ± 1% of adjustable range; “normally closed”
models 544-548 ± 11⁄2% of adjustable
range Electrical Rating 15 amps 125/250/480 VAC resistive
Internal set point lock on all models
Approx. Weight H100K models 540-543: 6 lbs (2, 7 kg);
Shock Set point repeats after 15 G, 10 milli- models 544-548: 4 lbs (1, 8 kg)
seconds duration
Electrical Connection ⁄2" NPT; two 7⁄8" diameter
1

Vibration Set point repeats after 2.5 G, 5-500 Hz knockouts

Enclosure Die cast aluminum (max. 0.6% copper), Approvals UL listed


epoxy powder coated, gasketed, captive UL 508,
cover screws file # E42272
Sensor housing: epoxy coated aluminum with CSA certified
1
⁄8" NPT Female pressure connections. C22.2, no 14
Anodized Aluminum internal metallic parts. file # LR39690
Kapton™ and Buna-N-internal seals. Viton CE compliant to Low voltage directive
material is optional (replaces Buna-N seals).

Specifications: J120K Series


Storage temperature -65 to 160 (-54 to 71°C) Switch output One SPDT snap action switch; switch may
be wired “normally open” or “normally
Ambient Temperature 0° to 160°F (-40° to 71°C); set point typically closed”
shifts less than 1%of range for a 50°F (28°C)
ambient temperature change Electrical Rating 15 amps 125/250/480 VAC resistive

Set Point Repeatability Models 540-543 ± 1% of adjustable range; Approx. Weight J120K, QJ120K models 540-543: 8.5 lbs
models 544-548 ± 11⁄2% of adjustable (3, 9 kg)
range models 544-548: 6.5 lbs (3 kg)
Internal set point lock on all models
Electrical Connection 3/4” NPT; terminal block standard
Shock Set point repeats after 15 G, 10 milli-
seconds duration Approvals Class I, Division 1 & 2,
Groups B, C, and D:
Vibration Set point repeats after 2.5 G, 5-500 Hz Class II, Division 1 & 2,
Groups E, F, and G;
Enclosure Die cast aluminum (max. 0.4% copper), Class III
epoxy powder coated; gasketed; UL listed
aluminum nameplate UL 508, UL 698,
Sensor housing: epoxy coated aluminum file # E40857
with 1⁄8" NPT Female pressure connections. CSA certified
Anodized Aluminum internal metallic parts. CSA C22.2 no. 14, 25, 30
Kapton™ and Buna-N-internal seals. Viton file #LR39690
material is optional (replaces Buna-N seals). CENELEC
Flame proof construction
per EEx d IIC T6,IP66
Enclosure Complies with NEMA 4X, 7, 9; IP66 EN 50 014/50 018
Classification requirements (Specify Option “Q”)
CE compliant to Low voltage directive
Specifications: J402K Series
Storage temperature -65 to 160 (-54 to 71°C) Enclosure Complies with NEMA 4X;
Classification IP65 requirements
Ambient Temperature 0° to 160°F (-40 to 71°C); setpoint
Limits typically shifts less than 1% of range for Switch output Two SPDT snap action switches;
a 50°F (28°C) ambient temperature change switches may be wired “normally open”
or “normally closed”. Up to 95% switch
Set Point Repeatability Models 540-543 ± 1% of adjustable range separation may be achieved
span; models 544-547 ± 1 1/2% of adjustable
range span Electrical Rating 15 amps 125/250/480 VAC resistive

Shock Set point repeats after 15 G, 10 milli- Approx. Weight J402K models 540-543: 6 lbs (2, 7 kg);
seconds duration J402K models 544-547: 4 lbs (1, 8 kg)

Vibration Set point repeats after 2.5 G, 5-500 Hz Electrical Connection Three 7⁄8" diameter knockouts

Enclosure Die cast aluminum (max. 0.6% copper), Approvals UL listed


epoxy powder coated, gasketed, captive UL 508, file # E42272
cover screws CSA certified
Sensor housing: epoxy coated aluminum with C22.2, no 14 file # LR39690
1
⁄8" NPT Female pressure connections.
Anodized Aluminum internal metallic parts.
Kapton™ and Buna-N-internal seals. Viton
material is optional (replacing Buna-N Seals).

Drawings
12 Series - *shown with sensor models K1-K3
Drawings

H100K Series - *shown with sensor models 544-548

H117K Series - *shown with sensor models 544-548


Drawings
J120K & QJ120K Series - *shown with sensor models 540-543

J402K Series - *shown with sensor models 540-543

NOTE: *All models are available with all types.


General Options
Code Description
M020 Red status light, 115 VAC only; specify whether light turns on or off with increasing or decreasing pressure. Available on H100K only
M201 Factory set one switch; specify increasing or decreasing pressure and set point
M202 Set two switches (J402K only)
M276 Range indicated on nameplate in bars
M277 Range in KPa on nameplate
M278 Range indicated on nameplate in Kg/cm2
M430 Cover lock (12K series only)
M440 Cover chain (J120K only)
M444 Paper ID tag
M446 Stainless steel ID tag & wire attachment (attachment will vary depending on product)
M450 Breather drain (J120K only)
M460 External grounding screw (12K series only)
M513 Junction box, pre-wired (12K series only)
M540 Viton construction (deadbands will increase approximately 15% and low end of range will increase by 10%)
Wetted parts include Viton sealing diaphragms and O-ring plus Kapton diaphragm
M550 Oxygen service cleaning; (all Buna-N seals changed to Viton similar to option M540)
62169-13 Mounting bracket kit (12K series only)
6361-694 Junction box and terminal kit; not pre-wired
6361-704 Mounting bracket kit (all others)

Switch Options
Code Description
0140 Gold flashed contacts, 1 amp 125 VAC resistive
0500 Close deadband, 5 amp 125/250 VAC resistive
1180 Hermetically sealed, 11 amp 125/250 VAC resistive; deadband and minimum set point will increase. Available on
QJ120K, J120K only
1190 Hermetically sealed, DPDT, 11 amp 125/250 VAC; products set on rising pressure due to inherent. separation of circuits
on falling pressure; specify option 1195 if setting on fall is required; deadband and minimum set point will increase
1195 Hermetically sealed, DPDT, 11 amp 125/250 VAC; products set on falling pressure; specify option 1190 if setting on rise is
required; deadband and minimum set point will increase. Available on H117K, QJ120K, J120K only
1519 Adjustable deadband, 15 amp 125/250/480 VAC resistive; adjustment changes rise setting only
1520 Adjustable deadband 15 amp @ 277VAC resistive,
1530 External manual reset, 15 amp 125/250/480 VAC resistive; reset on increasing pressure. Available on J120K, H100K only
1535 High ambient, 15 amp 125/250 VAC resistive; temperatures up to 250°F/145°C
1537 Vapor seald switch, 15 amp 125/250 VAC resistive. Available on 100K, J120K and QJ120K only
1539 Fungus resistant case, 15 amp 125/250 VAC resistive. Available on QJ120K, J120K only
How To Order
Build a part number by selecting a type, model and options. Choose the Model Type and the Range from the Model Chart .
If options are required, add the code from the option list below. Example: QJ120K 543 * M201.

Select a Type Select a Model Select an Option

❏❏❏❏❏❏ ❏❏❏ ✽ ❏❏❏❏


H100K = NEMA 4X/IP65, general Refer to Model Chart See Previous Page
purpose, internal adjustment
with reference scale
H117K = NEMA 4X/IP65, Division 2,
internal adjustment with
reference scale
J120K = Division 1 approved,
NEMA 4X, 7, 9 internal
adjustment with reference
scale
QJ120K = CENELEC approved, IP66,
internal adjustment with
reference scale

12 Series “WCD Pressure Switch

Housing Electrical Number Electrical Sensor Model


Series Materials Rating of Switches Conduit Type (Range) Options

12 S=Stainless L=1 amp S=SPDT N=1⁄2" NPTM K = Kapton™ diaphragm, 1=0.7 to 10 "WCD
Steel H=5 amp D=DPDT M=M20 Buna-N sealing 2=2 to 20 "WCD
diaphragms, 1⁄8" NPT 3=10 to 150 "WCD
female pressure 4=2 to 20 psid
connections 5=5 to 80 psid
6=10 to 150 psid
Notes: RECOMMENDED PRACTICES AND WARNINGS

United Electric Controls Company recommends careful consideration of the


following factors when specifying and installing UE pressure and temperature
units. Before installing a unit, the Installation and Maintenance instructions
provided with unit must be read and understood.
• To avoid damaging unit, proof pressure and maximum temperature limits
stated in literature and on nameplates must never be exceeded, even by surges in
the system. Operation of the unit up to maximum temperature is acceptable on a
limited basis (i.e., start-up, testing) but continuous operation must be restricted
to the designated adjustable range. Excessive cycling at maximum
temperature limits could reduce sensor life.
• A back-up unit is necessary for applications where damage to a primary
unit could endanger life, limb or property. A high or low limit switch is necessary
for applications where a dangerous runaway condition could result.
• The adjustable range must be selected so that incorrect, inadvertent or
malicious setting at any range point can not result in an unsafe system condition.
• Install unit where shock, vibration and ambient temperature fluctuations will
not damage unit or affect operation. Orient unit so that moisture does not enter
the enclosure via the electrical connection. When appropriate, this entry point
should be sealed to prevent moisture entry.
• Unit must not be altered or modified after shipment. Consult UE if
modification is necessary.
• Monitor operation to observe warning signs of possible damage to unit,
such as drift in set point. Check unit immediately.
• Preventative maintenance and periodic testing is necessary for critical
applications where damage could endanger property or personnel.
• For all applications, a factory set unit should be tested before use.
• Electrical ratings stated in literature and on nameplate must not be exceeded.
Overload on a switch can cause damage, even on the first cycle. Wire unit
according to local and national electrical codes, using wire size recommended in
installation sheet.
• Use only factory authorized replacement parts and procedures.
• Do not mount unit in ambient temp. exceeding published limits.

LIMITED WARRANTY OF REPAIR AND


REPLACEMENT
UE warrants that the product hereby purchased is, upon delivery, free from
defects in material and workmanship and that any such product which is found to
be defective in such workmanship or material will be repaired or replaced by UE
(F.O.B. UE); provided, however, that this warranty applies only to equipment
found to be so defective within a period of 12 months after delivery by the seller.
UE shall not be obligated under this warranty for alleged defects which examina-
tion discloses are due to tampering, misuse, neglect, improper storage, and in
any case where products are disassembled by anyone other than authorized
UE representatives.
EXCEPT FOR THE LIMITED WARRANTY OF REPAIR AND REPLACEMENT
STATED ABOVE, UE DISCLAIMS ALL WARRANTIES WHATSOEVER WITH
RESPECT TO THE PRODUCT, INCLUDING ALL IMPLIED WARRANTIES OF
MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE.
LIABILITY LIMITATION
SELLER’S LIABILITY TO BUYER FOR ANY LOSS OR CLAIM, INCLUDING
LIABILITY INCURRED IN CONNECTION WITH (I) BREACH OF ANY WARRANTY
WHATSOEVER EXPRESSED OR IMPLIED, (II) A BREACH OF CONTRACT, (III) A
NEGLIGENT ACT OR ACTS (OR NEGLIGENT FAILURE TO ACT) COMMITTED BY
SELLER, OR (IV) AN ACT FOR WHICH STRICT LIABILITY WILL BE IMPUTED TO
SELLER, IS LIMITED TO THE LIMITED WARRANTY OF REPAIR AND REPLACE-
MENT STATED HEREIN. IN NO EVENT SHALL THE SELLER BE LIABLE FOR ANY
SPECIAL, INDIRECT, CONSEQUENTIAL OR OTHER DAMAGES OF A LIKE
GENERAL NATURE, INCLUDING, WITHOUT LIMITATION, LOSS OF PROFITS OR
PRODUCTION, OR LOSS OR EXPENSES OF ANY NATURE INCURRED BY THE
BUYER OR ANY THIRD PARTY.
INTERNATIONAL OFFICES U.S. SALES OFFICES

AUSTRALIA United Electric Controls


United Electric Controls 32 Highland Rd.
(Australia) PTY Ltd South Hampton, NH 03827
A.C.N. 004 949 982 Phone: 603-394-0078
Unit 2, 615 Warrigal Road FAX: 603-394-0175
Locked Bag 600
Ashburton, Victoria United Electric Controls
3147, Australia 5 Steeple Chase Court
Phone: 613-9568-6188 Bedminster, NJ 07921
FAX: 613-9569-9742 Phone: 908-781-6967
BELGIUM FAX: 908-781-1003
United Electric Controls-Europe
G. Van Gerven street 19A United Electric Controls
B-9120 Beveren-Waas, Belgium 2520 E. Piedmont Rd.
Phone: 32-37554-383 Suite F-120
FAX: 32-37552-747 Mairetta, GA 30062
Phone: 770-792-8585
CANADA FAX: 770-792-8089
United Electric Controls
(Canada) Ltd United Electric Controls
5320 Bradco Boulevard 28 N. Wise Ave.
Mississauga, Ontario Freeport, IL 61032
L4W 1G7 Canada Phone: 815-235-3501
Phone: 905-625-5082 FAX: 815-235-3847
FAX: 905-625-5709
GERMANY United Electric Controls
United Electric Controls 1022 Vineyard Drive
An Der Zentlinde 21 Conyers, GA 30013
D-64711 Erbach, Germany Phone: 770-483-8400
Phone: 496-062-7400 FAX: 770-929-8716
FAX: 496-062-7501
INDIA United Electric Controls
United Electric Controls 5829 Grazing Court
Amar Hill, Saki Vihar Road Mason, OH 45040
Powai, Mumbai 400 072 Phone: 513-398-3175
Phone: 91-22-857-6921 FAX: 513-398-3076
FAX: 91-22-857-1707
United Electric Controls
MALAYSIA 19335 Hadley
United Electric Controls, Far East Stilwell, KS 66085
No. 16, The Highway Centre Phone: 913-685-2775
Jalan 51/205 FAX: 913-685-2774
46050 Petaling Jaya
Selangor, Malaysia United Electric Controls
Phone: 603-9133-4122 5773 Woodway Drive
FAX: 603-9133-4155 Suite 284
MEXICO Houston, TX 77057
United Electric Controls Phone: 713-974-3417
Chihuahua 129-1 NTE FAX: 713-334-3959
Unidad Nacional 89410
Madero, TAM United Electric Controls
Mexico 1753 Beach Street
Phone: 12/10-0646 San Francisco, CA 94123
FAX: 12/10-5761 Phone: 415-563-5811
FAX: 415-563-5909