Professional Documents
Culture Documents
EMCP 3 Control Panel Manual (ENGLISH)
EMCP 3 Control Panel Manual (ENGLISH)
December 2009
Systems Operation
Troubleshooting
Testing and Adjusting
EMCP3
CNB1-Up (Generator Set) NKK1-Up (Generator Set)
D4B1-Up (Machine) YAK1-Up (Generator Set)
G5B1-Up (Generator) CAL1-Up (Generator Set)
X3B1-Up (Generator Set) NKL1-Up (Generator Set)
ZAB1-Up (Generator Set) ZAL1-Up (Generator Set)
CMC1-Up (Generator Set) KNM1-Up (Power Module)
N3C1-Up (Generator Set) NKM1-Up (Generator Set)
NCC1-Up (Generator Set) SLM1-Up (Engine)
NSC1-Up (Generator Set) YAM1-Up (Generator Set)
XYC1-Up (Generator Set) 7RN1-Up (Engine)
D4D1-Up (Machine) FDN1-Up (Generator Set)
GLD1-Up (Generator Set) YAN1-Up (Generator Set)
N4D1-Up (Generator Set) ZAP1-Up (Generator Set)
N6D1-Up (Generator Set) N4R1-Up (Generator Set)
NCD1-Up (Generator Set) PBR1-Up (Generator Set)
XYD1-Up (Generator Set) ZAR1-Up (Generator Set)
ZAD1-Up (Generator Set) YAS1-Up (Generator Set)
GLE1-Up (Generator Set) YAT1-Up (Generator Set)
N4E1-Up (Generator Set) YAW1-Up (Generator Set)
NCE1-Up (Generator Set) N3X1-Up (Generator Set)
ZAF1-Up (Generator Set) N4X1-Up (Generator Set)
ZAH1-Up (Generator Set) G5Y1-Up (Generator)
ZAJ1-Up (Generator Set) 4BZ1-Up (Generator Set)
BRK1-Up (Generator Set) E6M1-Up (Engine)
SAFETY.CAT.COM
i03684547
In the United States, the maintenance, replacement, or repair of the emission control devices and
systems may be performed by any repair establishment or individual of the owner's choosing.
RENR7902-07 3
Table of Contents
Troubleshooting Section
Introduction
General Information .............................................. 89
Service Tools ........................................................ 90
Diagnostic Capabilities ......................................... 91
Diagnostic Trouble Code List ................................ 92
General Information
SMCS Code: 4490
g01237225
Illustration 1
Block diagram of a generator set with EMCP 3 and EUI Engine
RENR7902-07 5
Systems Operation Section
g01237211
Illustration 2
Block diagram of a generator set with EMCP 3 and MUI Engine
6 RENR7902-07
Systems Operation Section
i02989617
Component Location
SMCS Code: 4490
g01228802
Illustration 3
Early Introduction EMCP 3 - Face
(1) Electronic Control Module (ECM) for the (4) Start Aid Switch (SAS) (optional) (8) Alarm Acknowledge/Silence Switch
Generator Set (5) Speed Potentiometer (SP) (optional) (9) Alarm Horn
(2) Panel Lights (6) Emergency Stop Push Button (ESPB) (10) Annunciator Module (ALM)
(3) Panel Light Switch (PLS) (7) Lamp Test Switch
RENR7902-07 7
Systems Operation Section
g01228805
Illustration 4
Early Introduction - EMCP 3 - Subpanel
(11) AC Terminal Strip (14) Discrete Input Output (I/O) Terminal (15) Discrete Input Output (I/O) Module or
(12) DC Terminal Strip Strip Resistive Temperature Device (RTD)
(13) Switchgear Option Terminal Strip Module
8 RENR7902-07
Systems Operation Section
g01589889
Illustration 5
Global Design EMCP 3 - Face
(16) Electronic Control Module (ECM) for (19) Lamp Test Switch (22) Emergency Stop Push Button (ESPB)
the Generator Set (20) Alarm Acknowledge/Silence Switch (23) Panel Light Switch (PLS) (optional)
(18) Annunciator Module (ALM) (21) Alarm Horn
RENR7902-07 9
Systems Operation Section
g01222139
Illustration 6
Global Design - EMCP 3 - Subpanel
(27) AC Terminal Strip (30) Relay for MUI engine with Ether Start (32) Service Connector for CAN 2
(28) DC Terminal Strip Aid option (33) Discrete Input Output (I/O) Terminal
(29) DC Terminal Strip (31) Service Connector for CAN 1 Strip
10 RENR7902-07
Systems Operation Section
g01514733
Illustration 7
In Line Six Cylinder Components
RENR7902-07 11
Systems Operation Section
i02970772
g01211086
Illustration 8
EMCP 3 Control System Panel
(1) Display Screen (7) Auto key (13) Up key
(2) Yellow Warning Lamp (8) Run key (14) Left key
(3) Red Shutdown Lamp (9) Escape key (15) Engine Overview key
(4) Alarm Acknowledge/Silence key (10) Enter key (16) AC Overview key
(5) Lamp Test key (11) Right key
(6) Stop key (12) Down key
(10) Enter Key – The enter key is used during menu (16) AC Overview – Pressing the AC overview
navigation in order to move forward (downward) key displays the first screen of AC information
through the menu/submenu structure. The key is also for the generator set. This initial information page
used during set point programming in order to save contains various AC parameters that summarize the
set points changes. Pressing the Enter key during electrical operation of the generator set. Additional
set point programming causes set point changes to AC parameters can be viewed by pressing the down
be saved to memory. key (12) multiple times.
(11) Right Key – The right key is used during set Data Link
point adjustment. During numeric data entry, the
key is used in order to choose which digit is being SMCS Code: 4490
edited. The key is also used during certain set point
adjustments in order to select a check box or to
deselect a check box. If a box has a check mark Data Links
inside of it, then pressing the key will cause the check
mark to disappear. If the box does not have a check The EMCP 3 has up to three different data links:
mark inside of it, then pressing the key will cause a
check mark to appear inside the box. • Primary Data Link
(12) Down Key – The down key is used in order • Accessory Data Link
to navigate down through the various menus or
monitoring screens. The key is also used during set • System Control And Data Acquisition (SCADA)
point entry. During numeric data entry, the key is Data Link
used in order to decrement the digits (0-9). If the set
point requires selection from a list, then the key is Note: The “EMCP 3.1” has one Primary Data Link.
used to navigate down through the list. The “EMCP 3.2” and “EMCP 3.3” have one Primary
Data Link, one Accessory Data Link, and one SCADA
(13) Up Key – The up key is used in order to Data Link.
navigate up through the various menus or monitoring
screens. The key is also used during set point entry. Primary Data Link - J1939 (CAN 1)
During numeric data entry, the key is used in order
to increment the digits (0-9). If the set point requires The Primary Data Link is used for local communication
selection from a list, then the key is used to navigate among modules associated with a single genset
up through the list. such as the Electronic Control Module (ECM) for
the engine (EUI engines only), Caterpillar Digital
(14) Left Key – The left key is used during set Voltage Regulator (CDVR), and the Thermocouple
point adjustment. During numeric data entry, the Module. On MUI engines, the engine sensors are
key is used in order to choose which digit is being wired directly to the EMCP 3. The Primary Data Link
edited. The key is also used during certain set point utilizes the Society Of Automotive Engineers (SAE)
adjustments in order to select a check box or to J1939 protocol and requires Controller Area Network
deselect a check box. If a box has a check mark (CAN) hardware running at 250k bits per second.
inside of it, then pressing the key will cause the check
mark to disappear. If the box does not have a check The Primary Data Link supports appropriate SAE
mark inside of it, then pressing the key will cause a J1939 Broadcast Parameter Group Numbers (PGN)
check mark to appear inside the box. and Suspect Parameter Numbers (SPN) for engine
and genset data.
System Overview Keys
Accessory Data Link - J1939 (CAN 2)
(15) Engine Overview – Pressing the engine
overview key displays the first screen of engine The Accessory Data Link is used for local
information. This initial information page contains communication among modules associated with a
various engine parameters that summarize the single genset such as Annunciators, RTD Modules
operation of the engine. Additional engine parameters and Discrete Input Output Modules. It utilizes the
can be viewed by pressing the “Down” key (12) Society Of Automotive Engineers (SAE) J1939
multiple times. protocol and requires CAN hardware running at 250k
bits per second.
SCADA Data Link - Modbus RS-485 The engine ECM controls engine speed and also
enables fuel injection on EUI engines in electric
The SCADA Data Link is used for communication power generation applications. Both the fuel enable
with a System Control And Data Acquisition (SCADA) input and the speed input are configurable using the
system. service tool.
The SCADA Data Link uses the Modbus Protocol The fuel enable input to the ECM can be a
with an RS-485 half duplex hardware layer operating “switch-to-ground” or the input can be transmitted
at a minimum of 2.4k bits per second. All data items over the primary J1939 data link from the EMCP 3.
are accessed as Modbus registers. Data that is less
than 16 bits occupies a single register. Larger data The desired engine speed is derived from one of the
occupies consecutive registers in order to allow two following inputs:
access using single request.
• Input from a converter that converts the analog
The SCADA Data Link is a Master/Slave Data Link. speed signal of a speed potentiometer into a pulse
The SCADA controller or customer software will be width modulated signal or directly from EMCP 3
the master and the genset controls will be slaves on over the primary J1939 data link
the Data Link.
• The ECM uses feedback from the engine speed
The SCADA controller can connect directly to the sensors that are mounted on the engine to control
genset control or it may be connected remotely the engine speed
through a modem using an RS-485 to RS-232
converter. Passwords levels are used in order to There are primary and secondary throttle inputs.
restrict access to the genset control. The throttle inputs can be a pulse width modulated
signal or the speed inputs can be transmitted over
Each genset control on the SCADA Data Link has a the primary J1939 link (CAN 1).
unique Modbus Address. A setpoint is available to
select the address for the genset control. Note: The Caterpillar service tool is used in order
to configure the throttle inputs as either primary or
In order to use a modem connection to the SCADA as secondary.
Data Link, the modem must be pre-configured with
all necessary communication parameters and set to If the primary throttle input fails, then the engine ECM
automatically answer. No modem handshaking or will generate a diagnostic, acknowledge the failure,
control is performed by the EMCP 3. and respond to the secondary input. If the primary
throttle input fails and the secondary input is disabled,
Refer to the Application and Installation Guide, then the engine will default to the idle speed setting.
LEBE5255 for more detailed information about the
SCADA data link. The EMCP 3 receives specific information that it
uses in order to monitor the system for events. If a
particular parameter is not supported by the engine
i02972121
ECM, then the EMCP 3.3 displays the parameter
Electronic Control Module name with an associated value of “****”, which
indicates that there is no value associated with that
(Engine) specific parameter.
(EUI Engines Only) Note: Recent versions of software do not display the
SMCS Code: 1901 parameter name for unsupported parameters.
• If warning events are present, that is, the yellow 4. The EMCP 3 cranks the engine for the
warning lamp (2) is lit, then take corrective action if programmed crank time or until the engine starts.
necessary If the engine does not start after the crank time
has elapsed, then the starting motor relay will
• No shutdown events are active, that is, the red de-energize for the programmed rest time. After
shutdown lamp (3) is not lit the rest time has elapsed, then the starting motor
relay will start cranking again for the programmed
• For remote initiate operation, the EMCP 3 must crank time.
be in AUTO mode
A cycle consists of a crank time and a rest time. If
Engine Starting Sequence the engine has not started after the programmed
number of cycles, then the EMCP 3 will abort the
1. The EMCP 3 receives an engine start signal under starting process and will generate an “Engine
one of the following conditions: Failure to Start Shutdown”.
• The operator presses the “RUN” key 5. The EMCP 3 deactivates the starting motor relay
when the engine speed reaches the setpoint for
• The control is in “AUTO” and the remote initiate the crank terminate speed.
input (IC) becomes active
Engine Stopping Sequence
• The operator presses the “AUTO” key and a
start command is sent via the RS-485 SCADA 1. The EMCP 3 will stop the engine under either of
Data Link (Modbus). the following conditions:
• Programmable cycle timer output 1 is “Active” a. The operator presses the “STOP” key.
2. The EMCP 3 checks the following system items b. If the control is in “AUTO” and no longer
before beginning the cranking sequence: receives any of the following:
a. On the MUI engines, the EMCP 3 deactivates Reference: For a full explanation of the use of the
the fuel control relay, which in turn, shuts the function keys (enter, escape) and the navigation keys
engine down. (left, right, up, and down) that are referenced in this
section, refer to the Systems Operation, “Electronic
b. On EUI engines, the EMCP 3 sends a Control Module (Generator Set)” section of this
shutdown signal to the engine ECM over the publication.
primary J1939 data link in order to shut down
the engine. (9) Escape key – Navigate up (backward) through
the menu structure and also used to cancel out of
data entry screens during setpoint programming.
i02973498
The level of password protection that is required for (14) Left key – During numeric data entry, choose
each setpoint is identified on the parameter setpoint the digit to edit. During certain setpoint adjustments,
entry screen. A security level identification number select or deselect a check box.
“1”, “2”, or “3” next to a padlock symbol is displayed
on the parameter setpoint entry screen. Level 3 Drop to Minimum Security Level
security is used for the most secure setpoints and
Level 1 security is used for the least secure setpoints. The first option on the security screen is “DROP
TO MIN LEVEL”. This option refers to a process of
If the EMCP 3 is currently at the required level of placing the EMCP 3 into the lowest level of security
security when viewing a parameter, then the padlock that is authorized. This would be used after the
will not appear. programming of the control is complete. If “DROP TO
MIN LEVEL” is not initiated manually, then the control
If a parameter is displayed with a padlock, but there will automatically revert to the minimum level after
is no security level identification number associated ten minutes of non-activity.
with it, then the parameter cannot be changed from
the EMCP 3 display. 1. From the “MAIN MENU”, press the Up key or the
Down key in order to highlight the “CONFIGURE”
Level 1 and Level 2 passwords are disabled when menu.
shipped from the factory. If desired, Level 1 and Level
2 passwords can be user defined. 2. Press the ENTER key in order to select the
“CONFIGURE” menu. “SECURITY” will be
Function and Navigation Keys highlighted.
Reference: The call outs that are in this section can 3. Press the ENTER key in order to select the
be found on the EMCP 3 control system panel in “SECURITY”. The “DROP TO MIN LEVEL” option
the Systems Operation, “Electronic Control Module will be highlighted.
(Generator Set)” section of this publication.
4. Press the “ENTER” key in order to select the
The keys that are listed below are used for “DROP TO MIN LEVEL” option.
programming the EMCP 3 and for navigating within
the menu structure. 5. The EMCP 3 will now be at the minimum level of
security.
Enter Level 1 or 2 Password 2. Press the Enter key in order to select the
“CONFIGURE” menu. “SECURITY” will be
1. From the “MAIN MENU”, press the Up key or the highlighted.
Down key in order to highlight the “CONFIGURE”
menu. 3. Press the “Enter” key in order to select
“SECURITY”. “DROP TO MIN LEVEL” will be
2. Press the Enter key in order to select the displayed.
“CONFIGURE” menu. “SECURITY” will be
highlighted. 4. Press the Down key in order to highlight “ENTER
LEVEL 3”. Press the Enter key in order to select
3. Press the Enter key in order to select the “ENTER LEVEL 3”.
“SECURITY” menu. “DROP TO MIN LEVEL” will
be highlighted. 5. A sixteen digit number will be displayed and
“ENTER RESPONSE” will be highlighted.
4. Press the Down key in order to highlight “ENTER Make a copy of the sixteen digit number that is
LEVEL 1 OR 2”. displayed. Work through the dealer “Technical
Communicator” to contact the “Dealer Solutions
5. Press the Enter key in order to select the “ENTER Network” (DSN) in order to obtain a factory
LEVEL 1 or 2” menu. “ENTER PASSWORD FOR provided response code. The factory provided
DESIRED LEVEL” is displayed. There is also a 16 response code will be entered into the EMCP 3.
digit entry field with 0 highlighted at the far right.
6. When the factory response is received from the
6. Press the Up key or the Down key in order to factory, press the Enter key in order to select
increment or decrement the highlighted digit to the “ENTER RESPONSE”. “ENTER RESPONSE”
desired number. will be displayed along with a sixteen digit entry
field where the factory provided password will be
7. Press the Left key in order to highlight the next entered.
character to be entered and then press the Up
key or the Down key in order to increment or 7. Use the Up key or the Down key in order to
decrement the highlighted digit to the desired increment or to decrement the highlighted digit
number. to the corresponding digit of the factory provided
password.
8. Continue this process until the correct password
has been entered for the corresponding level. 8. Press the Right key or the Left key in order to
When all digits of the password are correctly highlight the next character that is to be entered,
entered, then press the Enter key. This action will and use the Up or the Down key in order to
display the current level of password protection increment or decrement the highlighted digit to
and the parameters can now be set. the corresponding digit of the DSN provided
password.
Note: The EMCP 3 will go to the highest level of
security authorized by a correctly entered password. 9. Continue the process until all sixteen digits of the
password are entered. Press the “Enter” key after
Note: Level 1 and level 2 passwords are entirely all sixteen digits of the password are entered .
determined by the user and can range from one to After the password has been entered and after
sixteen digits. the “Enter” key has been pressed, the current
level, “LEVEL 3”, of security will be displayed. The
Note: If parameters are being changed using a parameters can be set at this time.
Caterpillar service tool, then a password is not
required. Note: If parameters are being changed using a
Caterpillar service tool, then a password is not
required.
Enter Level 3 Password
The level 3 password is intended for situations where Change Level 1 or Level 2 Password
a customer or a dealer wants to do something that
would typically be done with the service tool, but the 1. From the “MAIN MENU”, press the Up key or the
service tool is not available. Down key in order to highlight the “CONFIGURE”
menu.
1. From the “MAIN MENU”, press the Up key or the
Down key in order to highlight “CONFIGURE”. 2. Press the Enter key in order to select
“CONFIGURE”. “SECURITY” will be highlighted.
RENR7902-07 19
Systems Operation Section
3. Press the Enter key in order to select Note: For external modules such as engine ECM
“SECURITY”. “DROP TO MIN LEVEL” will be thermocouples, RTD, and discrete I/O, there will be
highlighted. only active and inactive events. There are no present
events for optional modules.
4. Ensure that the current level of security is at least
as high as the level of the password that is to be ACTIVE – The event was previously in a “Present”
changed. state, but it is no longer present. It has been latched
by the event system and needs to be reset before the
5. Press the Down key in order to highlight engine can be restarted.
“CHANGE LEVEL 1 PSWD”. Press the Enter key
in order to select “CHANGE LEVEL 1 PSWD”. INACTIVE – The event was previously in an active
“CHANGE LEVEL 1 PSWD” is displayed along or a present state, but it is no longer in an active or a
with a sixteen digit password entry field that has a present state, and it is not affecting system behavior.
zero highlighted in far right of the field.
The “ACTIVE EVENTS” menu is used to display
6. Press the Up key or the Down key in order to active events for ECMs, including those ECMs that
increment or to decrement the highlighted digit are connected to the EMCP 3 over the data link.
to the corresponding number of the desired
password. There is a number in the top right of the “ACTIVE
EVENTS” menu that indicates how many active or
7. Press the Left key in order to highlight the present events are currently in the system. There is
next character that is to be entered. Press the also a number to the right of each listed ECM that
Up key or the Down key in order to increment indicates how many active or present events are
or to decrement the highlighted digit to the currently associated with that particular ECM.
corresponding number of the desired number.
The ECMs listed in Table 1 can have an event log
8. Continue this process until the desired password associated with them:
is displayed and then press the Enter key. The
password is now set. Table 1
ECM Event Type
Note: In order to change a level 2 password,
substitute “CHANGE LEVEL 2 PSWD” for “CHANGE Genset Control EMCP 3
LEVEL 1 PSWD” in step 5 above. Engine Control ADEM
Note: Level 1 and level 2 passwords are entirely AVR (requires CDVR) Voltage Regulator
determined by the user and can range from one to Thermocouple (TC) Module(1) Optional TC
sixteen digits
Resistive Temperature Device Optional RTD
Note: To disable a password, set the password to a (RTD) Module
single zero. Discrete Input/Output (DI/O) Optional DI/O
Module(1)
(1) There may be more than one module.
i02973527
Event Viewing Note: On power up, the EMCP 3 displays the “MAIN
MENU” screen. If the EMCP 3 is currently powered
SMCS Code: 4490 up, and the “MAIN MENU” screen is not displayed,
then press the Escape key (9) as many times as
Reference: Call outs in this section can be found required in order to return to the “MAIN MENU”. Each
on the EMCP 3 Control System Panel Illustration successive press of the Escape key backs you up
in Systems Operation, “Electronic Control Module one level in the menu structure.
(Generator Set)”
Perform the following steps in order to view an event.
Event system information from the EMCP 3 is
displayed on the display screen (1). The event 1. Using the Scroll Down key (12) or the Scroll Up
system uses the following terms to describe the key (13), navigate within the “MAIN MENU” to the
status of an event: “EVENT LOGS” menu and press the Enter key .
The “ACTIVE EVENTS” menu is displayed listing
PRESENT – The condition causing the event is the connected ECM.
present and is affecting the system behavior.
Note: Events are organized by which ECM originated
the event.
20 RENR7902-07
Systems Operation Section
1. Press the STOP key (6). 7. Ensure that the condition which caused the event
is no longer present and then press the Enter key.
Note: The control must be in “STOP” in order to reset
active shutdown events. If the condition that caused the event is no
longer present, and the control is in “STOP”, then
2. Use the Scroll Down key (12) in order to navigate “RESET ALL” will be highlighted.
from the “MAIN MENU” to the “EVENT LOG”
menu.
RENR7902-07 21
Systems Operation Section
g01455527 g01506375
Illustration 12 Illustration 14
8. Press the Enter key again. The fault will clear. If 4. Use the Scroll Down key in order to highlight an
there are no other active shutdown events, then ECM that has active events. Refer to Illustration
the red shutdown lamp will turn off. 14.
Illustration 16
g01506377 Table 3
ECM Functionality
8. Press the Enter key again. The fault will clear. If
there are no other active shutdown events, then Engine Type Engine Control Engine Events
Configuration J1939 Data Functionality
the red shutdown lamp will turn off. Link Support
Configuration
9. Repeat steps 4 through 8 until there are no active
shutdown events remaining. When all active Mechanical None
shutdown events have been reset, then the red No J1939 Can reset all
shutdown lamp will be turned off. Electronic
Support events only
10. Press the Escape key (9) three times in order to Basic J1939 Can view and
Electronic
return to the “MAIN MENU” screen. Support reset all events
Enhanced J1939 Can view and
Resetting All Events for All Modules Electronic
Support reset all and
view additional
event info
1. Ensure that the control is “Stopped”.
2. Execute the following from any screen. Press The EMCP 3 GSC has the ability to reset all events
the “ACKNOWLEDGE” key and hold the for electronic engines with no J1939 support. The
“ACKNOWLEDGE” key for approximately 5 reset is accomplished by the use of a relay output.
seconds.
Three conditions must be satisfied in order for the
3. A confirmation prompt will appear. reset to work.
i02974035
Setpoint Programming
SMCS Code: 4490
g01233459
Illustration 18
The engine and generator setpoints are programmed Reference: For a full explanation of the use of the
in the EMCP 3 at the factory. The setpoints that are Function keys (Enter, Escape) and the Navigation
stored in the EMCP 3 must match the specified keys (Scroll Left, Scroll Right, Scroll Up, Scroll Down)
setpoints of the particular generator set. These that are referenced in this section, see Systems
setpoints, which are programmable, affect the proper Operation, “Electronic Control Module (Generator
operation and serviceability of the engine, as well Set)”
as the accuracy of the information that is shown on
the Display Screen (1). (9) Escape – Navigate up (backward) through the
menu structure and also used to cancel out of data
The setpoints may require modification when the entry screens during setpoint programming.
EMCP 3 is moved from one engine to another engine.
The setpoints may also require modification in order (10) Enter key – Select a highlighted menu item or
to satisfy the requirements of the installation. save a programmed value.
(13) Scroll Up key – Move up through the main c. Scroll through the available digital inputs until
menu or navigate within a list in order to highlight one digital Input 3 is highlighted, and then press the
of the items. Also used to increment digits (0-9). Enter key
(14) Scroll Left key – During numeric data entry, d. Press the Enter key a second time. This action
choose the digit to edit. During certain setpoint highlights the current configuration of the
adjustments, select or deselect a checkbox. “Active” state for digital Input 3.
................. EVENTS
RENR7902-07 25
Systems Operation Section
....................... EVENT I/P FUNCTIONS SELECT a. Using the Scroll Down key, navigate to the
LOW SHUTDOWN parameter, and then press
Note: Event Input Function #1 corresponds to Digital the Enter key in order to select this parameter.
Input #3, Event Input Function #2 corresponds to This setting will generate an FMI of “1”.
Digital Input #4, etc.
In summary, when the fuel level drops below the level
4. Select Event Input Function #1, and then press of the float switch, Digital Input #3 is connected to
the Enter key in order to configure the settings. battery negative through the switch. This generates
Using the navigation keys, scroll through the an SPN-96, with an FMI-1. This code is translated
selections until the setting that is to be configured by the EMCP 3 to shutdown the engine, turn on
is highlighted and then press the Enter again in the shutdown LED, and broadcast the code on the
order to display the current value for that setting. J1939 data link. Any annunciator installed could be
The settings that can be configured include: programmed to have a pair of LED indicators to
detect this code and turn on the red LED.
• Active state
i02974036
• Time delay
Digital Input Programming
• Suspect Parameter Number
SMCS Code: 4490
• Failure Mode Identifier
There are two separate procedures that need to be
5. Set the Active state. This appears in the menu as performed in order to program the EMCP 3 digital
ACTIVE STATE CFG. The Active State should inputs. The first procedure involves programming
always be set to Active HIGH. the Active State of the input as either “Active High”
or as “Active Low”. The second procedure involves
6. Set the Time delay. This appears in the menu as programming the Event Input Functions.
EVENT DELAY TIME. If a time delay is desired
perform the following steps using the navigation
keys in order to adjust the value to the desired Digital Inputs
number of seconds.
The main purpose for the digital inputs is to add
a. Press the Enter key (10) in order to highlight additional monitoring capabilities for the engine
the value. or the generator. The inputs can be configured
by navigating to the “EVENT I/P FUNCTIONS”
b. Using the Scroll Right and Scroll Left parameter under the “SETPOINTS” menu.
navigation keys, highlight each number that is
to be changed. Once the number is highlighted, Note: There are eight digital inputs on “EMCP 3.2”
use the Scroll Up and the Scroll Down and “EMCP 3.3”. There are six digital inputs on
navigation keys in order to change the selected “EMCP 3.1”. On all three levels of controls, the first
value to the desired value. and second digital inputs are dedicated and cannot
be programmed.
c. Press the Enter key again in order to save the
new value. The digital inputs of the EMCP 3 are tied to an
internal pull-up resistor inside the control. Therefore,
7. Set the “Suspect Parameter Number” (SPN). This if there is no connection to a digital input, then the
value appears in the menu as “SUSPECT PARM digital input will read as a logical high. A ground
NUM/”. or battery negative input should be wired to each
EMCP 3 digital input. If an Active High configuration
a. Press “Enter”. is desired, then the ground or battery negative input
should be wired through a normally closed switch.
b. Press the Scroll Down key and navigate to the If an Active Low configuration is desired, then the
LEVELS menu and then press the Enter key in ground or battery negative input should be wired
order to select the menu. through a normally open switch.
Digital Input #1 is dedicated for “Emergency Stop” Activating the Emergency Stop input will either cause
and Digital Input #2 is dedicated for “Remote Initiate”. the generator set to stop immediately or else it will
The other 4 or 6 inputs can be configured to trigger prevent the generator set from starting. Once Digital
alarms or shutdowns in the EMCP 3. In the EMCP Input #1 goes active, the engine will not start until
3 software, Digital Inputs 3 through 8 (3 through 6 the event is reset.
on EMCP 3.1) are linked to functions that are called
“EVENT INPUT FUNCTIONS”. Because Digital Reference: System Operation , “Event Resetting”
Inputs #1 and #2 are dedicated inputs, Digital Input
#3 is linked to Event Input Function #1, Digital Input Digital Input 2 – Digital Input 2 is used for remotely
#4 is linked to Event Input Function #2, and so on. starting and stopping the generator set. This input
See Illustration 19 should be wired to battery negative through a
“Remote Initiate” switch. The input can be set to
activate on an Active High (normally closed contact)
or an Active Low (normally open contact). If the input
is active, and the EMCP 3 is in the “AUTO” mode,
then the engine will attempt to start and run. Once
the input becomes inactive, the engine will enter into
cooldown (if programmed to do so) and will then stop.
.... CONFIGURE
......... SETPOINTS
................. I/O
MAIN MENU
.... CONFIGURE
......... SETPOINTS
................. EVENTS
28 RENR7902-07
Systems Operation Section
Table 4 Table 5
Available Parameters Custom Event Setpoint Value for Event Input
Functions cVue Block
Pressures
Air Filter Differential Pressure Block Setpoint Description
Engine Oil Pressure Instance Value
Fire Extinguisher Pressure
Fuel Filter Differential Pressure 1 701 Custom Event (Instance
Oil Filter Differential Pressure 1 only)
Starting Air Pressure 2 702 Custom Event (Instance
Gas Pressure 2 only)
Temperatures 3 703 Custom Event (Instance
Ambient Air Temperature 3 only)
Engine Coolant Temperature
Engine Oil Temperature 4 704 Custom Event (Instance
Exhaust Temperature 4 only)
Rear Bearing Temperature
Right Exhaust Temperature 5 705 Custom Event (Instance
Left Exhaust Temperature 5 only)
Generator Winding 1 Temperature 6 706 Custom Event (Instance
Generator Winding 2 Temperature 6 only)
Generator Winding 3 Temperature
7 707 Custom Event (Instance
Levels 7 only)
Engine Coolant Level
Engine Oil Level 8 708 Custom Event (Instance
Fuel Level 8 only)
External Tank Fuel Level
Other 5. Set the Failure Mode Identifier (FMI). The
Air Damper Closed following FMI's are available:
ATS in Normal Position
ATS in Emergency Position • High Warning (example: High Temperature
Battery Charger Failure Warning)
Battery Charging System Voltage
Battery Voltage
Fuel Leak Detected • Low Warning (example: Low Temperature
Custom Event Warning)
Earth Fault
Earth Leakage • High Shutdown
Generator Frequency
Generator Voltage • Low Shutdown
Generator Current
Generator Power • Status (Condition Exists)
Generator Circuit Breaker Closed
Utility Breaker Closed
Generator Circuit Breaker Open i02935049
Utility Breaker Open
Loss of Utility Digital Output Programming
Utility to Generator Transfer Failure
Generator to Utility Transfer Failure SMCS Code: 4490
Engine Inlet Manifold Charge Combustion
EPS Supplying Load
Custom Event(1)
Note: The EMCP 3.1 does not have any digital
outputs. The EMCP 3.2 has one digital output. The
(1) For the Input Function setpoint value name “Custom Event”, EMCP 3.3 has two digital outputs.
the corresponding setpoint value will be dictated by the
information in Table 5.
Each digital output is capable of sinking 300 mA.
The outputs have diagnostics for a short to battery
when the driver is on, as well as diagnostics for an
open circuit when the driver is off. If a short to battery
persists for five seconds, then the driver will be
disabled until the condition is no longer present.
RENR7902-07 29
Systems Operation Section
There are two separate procedures that need to be Programming the Active State of
performed in order to program the digital outputs.
The first procedure involves programming the Active
the Digital Output
State of the output as either “Active High” or else
Note: The outputs are internally controlled in the
as “Active Low”. The second procedure involves
EMCP 3. The active state is programmable but
programming the Digital Selectors.
should always be set to “Active High”.
Function and Navigation Keys In order to program the “Active State” of the digital
output, perform the following steps:
Reference: The call outs that are in this section can
be found on the “EMCP 3 Control System Panel” 1. Navigate to the Digital Outputs menu.
in Systems Operation, “Electronic Control Module
(Generator Set)” a. At the “Main Menu”, click “Configure”.
The keys that are listed below are used for b. Select “Setpoints” from the menu.
programming the EMCP 3 and navigating within the
menu structure. c. Click “I/O”.
Note: The “Enter” and “Escape” keys are considered 3. Press the Enter key a second time. The current
as function keys. The “Scroll Left”, “Scroll Right”, configuration will be highlighted.
“Scroll Up”, and “Scroll Down” keys are considered
as navigation keys. 4. Use the navigation keys in order to change the
current configuration to the desired setting.
(9) Escape – The “Escape” key is used in order to
navigate up (backward) through the menu structure. 5. Press the Enter key in order to save the setting.
The “Escape” key is also used in order to back out of
any data entry screen during set point programming
before any changes to the existing data are accepted.
Programming the Digital Selectors
The digital outputs that are available with the
(10) Enter key – The “Enter” key is used in order to
EMCP 3.2 control and the EMCP 3.3 control are
select a highlighted menu item or in order to save a
programmable. The digital outputs can be set to
programmed value.
operate based on different conditions. There are
functions that are called “Digital Selectors”. There
(11) Scroll Right key – Used during numeric data
are digital selectors that are associated with each
entry in order to choose the digit to edit. Also used
digital output. There are eight digital selectors. The
during certain set point adjustments in order to select
digital selectors determine the conditions that are
or deselect a check box.
required in order to cause specific digital outputs to
become “Active”. Only “Digital Selector 7” and “Digital
(12) Scroll Down key – Used in order to move
Selector 8” are associated with digital outputs.
down through the main menu or to navigate within a
list in order to highlight one of the items. Also used
The digital selector is a software function that acts
to decrement digits (0-9).
like a 12 position switch. For each output there are
11 different options or conditions that can make the
(13) Scroll Up key – Used in order to move up
output go active, and one condition to disable the
through the main menu or navigate within a list in
output altogether. The digital selector is used in
order to highlight one of the items. Also used to
order to determine which one of those conditions will
increment digits (0-9).
actually be associated with each digital output. This
relationship is shown in Illustration 20. In addition to
(14) Scroll Left key – Used during numeric data
the ten options shown in the Illustration, the digital
entry in order to choose the digit to edit. Also used
selectors can be configured to receive their activation
during certain set point adjustments in order to select
commands over the SCADA data link.
or deselect a check box.
30 RENR7902-07
Systems Operation Section
g01505580
Illustration 20
“Digital Selector 7” controls “Digital Output 1”. The “Digital Selector 8” controls “Digital Output 2”. The
available configuration options for “Digital Selector available configuration options for “Digital Selector
7” are shown in Table 6. 8” are shown in Table 7.
RENR7902-07 31
Systems Operation Section
Table 7
Digital Selector #8 Configuration Options NOTICE
This output does not control a circuit breaker unless
Display Text Condition the user makes the connections to do so. This output
Disabled(1) Disabled(1) type should be viewed as having a generic name be-
cause the name does not necessarily imply the action
Use Input 1 Breaker Trip 1 that is performed.
Use Input 2 Breaker Trip 2
Use Input 3 Common Alarm Common Alarm
Use Input 4 Auto Mode
• Activated any time that the EMCP 3 initiates and/or
Use Input 5 Run Mode detects either a shutdown event or a warning event
Use Input 6 V & Hz Within Limits
• Deactivates when no warnings or shutdowns are
Use Input 7 Reserved for future use present or active
Use Input 8 Reserved for future use Disable Aux AC Supply
Use Input 9 Reserved for future use
The “Disable Aux AC Supply” is intended to be used
Use Input 10 Reserved for future use in order to disconnect the battery charger, heaters
Use Data Link Input Use SCADA Data Link etc when the engine is running.
Command
(1) Default • Activated when engine start is initiated
• Deactivates when the engine is stopped: RPM=0
Description of Digital Selector Inputs
Used to Activate the Digital Outputs Event Output Function #1
Note: The EMCP 3.1 has six programmable Type (13) Scroll Up key – Move up through the main
A relays. The EMCP 3.2 and EMCP 3.3 have eight menu or navigate within a list in order to highlight one
programmable relays. Six of these are Type A of the items. Also used to increment digits (0-9).
relays and the other two are Type C relays. Type A
relays contain a common and one normally-open (14) Scroll Left key – During numeric data entry,
contact. Type C relays contain a common and two choose the digit to edit. During certain setpoint
contacts, one that is normally-open and one that is adjustments, select or deselect a check box.
normally-closed.
Digital Selector Programming
Each relay is capable of handling 2A @ 30VDC. The
relays are “volt free” meaning that the commons are There are eight digital selectors. The digital selectors
not referenced to anything within the control. The determine which conditions cause the Relay Outputs
relay contacts are not protected against shorts to to become active. Only six of the digital selectors are
battery or ground. Two of the relays are dedicated associated with Relay Outputs.
and cannot be programmed. Relay Output #1 is
dedicated to controlling the starter motor. Relay The digital selector is a software function that acts
Output #2 is dedicated to fuel enable. The six like a 12 position switch. For each output there are
remaining Relay Outputs on the EMCP 3.3 and 11 different options or conditions that can make the
EMCP 3.2 and four remaining Relay Outputs on output go active, and one condition to disable the
the EMCP 3.1 are programmable and can be set to output altogether. The digital selector is used in
operate based on different conditions. order to determine which one of those conditions will
actually be associated with each digital output. This
In order to program the Relay Outputs, the Digital relationship is shown in Illustration 21. In addition to
Selectors must be programmed. the ten options shown in the Illustration, the digital
selectors can be configured to receive their activation
commands over the SCADA data link.
RENR7902-07 33
Systems Operation Section
g01506813
Illustration 21
Digital Selectors being used to program Relay Outputs
34 RENR7902-07
Systems Operation Section
2. Select the digital selector that is to be programmed, • Activated when the engine start is initiated. This
and then press the Enter key. action also starts the timer.
3. Press the Enter key again a second time. The • Deactivates after the Crank Alert Activation Timer
current configuration will be highlighted. expires
4. Use the navigation keys in order to change the Engine Start Initiated
current configuration to the desired setting
• Activates whenever the engine start is initiated
5. Press the Enter key in order to save the setting.
• Deactivates when engine stop is initiated or the
Digital Selector Input Descriptions cool down cycle begins
• Activated by the Emergency Stop condition while • Activated whenever the engine has reached its
the engine is running “crank terminate speed”
• Activated by an Over speed condition • Deactivates when the engine has stopped
• Requires that the setpoint for “Start Aid Activation Note: Intended to provide a rated speed permissive
Time” is to be set greater than zero signal to a governor on an MUI engine
Note: This output is intended for resetting events • Deactivates when either the measured generator
in an ECM when there is no J1939 communication voltage or the frequency are outside the normal
available in the ECM, such as in the case of an operating range.
ADEM II controller. The engine type must be set to
“Electronic” and J1939 support must be set to “No In Cooldown
J1939 Support”.
• Requires that the “Cooldown Duration” setpoint is
Disable Aux AC Supply to be set greater than zero
• Activated when engine start is initiated • Activated when an engine stop has been initiated
and the cooldown cycle begins
• Deactivates when the engine is stopped
• Deactivates when the cooldown timer has expired
Breaker Trip 1
Auto Mode
• Activated when any event occurs that has an event
response configuration set for “breaker trip 1” Activated after the Auto key has been pressed and
while the EMCP 3 remains in the auto mode
• Deactivates when the event is neither present nor
active Run Mode
NOTICE Activated after the Run key has been pressed and
This output does not control a circuit breaker unless while the EMCP 3 remains in the run mode
the user creates the connections for this function. This
output type should be viewed as having a generic Programmable Cycle Timer Output #2
name because the name does not necessarily imply
the action that is performed. The output is activated any time “Output 2” of the
programmable cycle timer is active.
• Activated when any event occurs that has an event High percent kW is activated when “Programmable
response configuration set for “breaker trip 2” Trip Point 1” is active. The “Programmable Trip Point
1” is activated based on the high percent kW. The
• Deactivates when the event is neither present nor high percent kW is determined by the thresholds that
active are configured by the user.
Table 8 Table 10
Digital Selector #1 configuration Options Digital Selector #3 Configuration Options
Display Text Condition Display Text Condition
Disabled Disabled Disabled(1) Disabled(1)
Use Input #1(1) Air Shutoff (1) Use Input #1 Common Alarm
Use Input #2(2) Start Aid (2) Use Input #2 Common Warning
Use Input #3 Common Warning Use Input #3 Overcrank Shutdown
Use Input #4 Common Shutdown Use Input #4 Engine Started
Use Input #5 Crank Alert Use Input #5 Crank Alert
Use Input #6 Auto Mode Use Input #6(2) Rated Speed(2)
Use Input #7 Breaker Trip 1 Use Input #7 Disable Aux AC Supply
Use Input #8 Event Output Function #1 Use Input #8 Auto Mode
Use Input #9 Trip Point #1 Use Input #9 Breaker Trip 1
Use Input #10 Reserved for future use Use Input #10 Reserved for future use
Use Data Link Input Use SCADA Data Link Use Data Link Input Use SCADA Data Link
Command Command
(1) Default for MUI (1) Default for EUI
(2) Default for EUI (2) Default for MUI
Digital Selector #2 controls Relay Output #4. Table Digital Selector #4 controls Relay Output #6. Table
9 lists the configuration options that are available for 11 lists the configuration options that are available for
Digital Selector #2. Digital Selector #4.
Table 9 Table 11
Digital Selector #2 Configuration Options Digital Selector #4 Configuration Options
Display Text Condition Display Text Condition
Disabled Disabled Disabled(1) Disabled(1)
Use Input #1 Horn Control Use Input #1 Common Warning
Use Input #2 Common Alarm Use Input #2 Common Shutdown
Use Input #3 Common Warning Use Input #3 Engine Started
Use Input #4(1) Common Shutdown(1) Use Input #4 Crank Alert
Use Input #5 Engine Started Use Input #5 ECU Fault Reset
Use Input #6 Run Mode Use Input #6 (2) Disable Aux AC Supply (2)
Use Input #7 Breaker Trip 2 Use Input #7 Engine Start Initiated
Use Input #8 In Cooldown Use Input #8 Run Mode
Use Input #9 Reserved for future use Use Input #9 Breaker Trip #2
Use Input #10 Reserved for future use Use Input #10 Reserved for future use
Use Data Link Input Use SCADA Data Link Use Data Link Input Use SCADA Data Link
Command Command
(1) Default (1) Default for EMCP 3.2 and EMCP 3.3
(2) Default for EMCP 3.1
Digital Selector #3
Digital Selector #5
Digital Selector #3 controls Relay Output #5. Table
10 lists the configuration options that are available for Digital Selector #5 controls Relay Output #7. Table
Digital Selector #3. 12 lists the configuration options that are available for
Digital Selector #5
RENR7902-07 37
Systems Operation Section
Table 12 i02978806
1. Ensure the edit box is around the timer that is to The set points of the “Programmable Trip Point” are
be programmed. configured by default. If the %kW exceeds 90 percent
for 10 seconds, then the output of the “Programmable
2. Press the enter key in order to access the timer Trip Point” will become true and remain true until the
information. The EMCP 3 screen will appear with %kW drops below 85 percent for 1 second.
one of the choices as highlighted.
The output of the “Programmable Trip Point” function
3. Use the scroll up key or scroll down key in order can be configured through “Digital Selector 2” to
to highlight the desired choice. For example, if an “Relay output 4” or through “Digital Selector 7” to
output needs to be set, then use the proper scroll “Digital (transistor) Output 1”.
key in order to highlight either of the desired timer
outputs. The set points in the “Programmable Trip Point”
function can be changed with the use of the display.
4. Press the enter key. The EMCP 3 screen will
display the current setting for the output which will Programmable Trip Point Function Trigger
be either “Active” or “Inactive”. The setting will be Condition (Default = Trip Above Threshold) –
highlighted. Selects whether the output will be active if the value
is above or below the threshold.
5. If the output is set to “Inactive” and the desire is
to change the output to “Active”, then press the Programmable Trip Point Function Percentage
scroll down key in order to change the output to Threshold (Default = 90%) – The threshold that the
“Active”. If the output is set to “Active” and the measured parameter must pass in order to change
desire is to change the output to “Inactive”, then the state of the output. In the default case for %kW,
press the scroll up key in order to change the this value is 90 percent of rated kW.
output to “Inactive”.
Programmable Trip Point Function Hysteresis
Note: On the EMCP 3.3, only the specified keys will Percentage (Default = 5%) – Once the output is on,
change the output. the value must exceed the threshold by the default
value before the output turns off again. In the case
6. Press the enter key in order to accept the changes. of the default %kW, the 5 percent value causes the
relay to not turn off again until 85 percent of rated kW
7. Press the escape key in order to navigate back is reached. Therefore, if the rated kW is 90 percent,
to previous menus. then the output will not switch off until 85 percent
is reached. This hysteresis is used to ensure that
After the output has been set, the output status that a value close to the threshold does not cause the
is shown on prog cycle timer screen should change output to toggle on and off.
to reflect the change that was just made for that
specific timer. Programmable Trip Point Function Trip Activation
Delay Time (Default = 10 seconds) – The time
that the value must exceed the threshold before the
i02936504
output of the block becomes active. The activation
Trip Point Programming delay time is used in order to ensure that the
momentary transients do not trip the relay.
SMCS Code: 4490
Programmable Trip Point Function Trip
The standard configuration for the EMCP 3.2 and Deactivation Delay Time (Default = 1 second) –
for the EMCP 3.3 has only one “Programmable Trip The time that the value must return past the
Point” function block. The “Programmable Trip Point” hysteresis threshold before the output of the block
is configured to respond to the %KW of the generator becomes inactive again. The deactivation delay
set. time is used in order to ensure that the momentary
transients do not deactivate the realy.
Note: The “Programmable Trip Point” feature is not
available on the EMCP 3.1 control. The EMCP 3.1
does not monitor power.
i02936488
g01455905
Illustration 24
Illustration 25 shows the “Technician English” version The functionality for the “Modifiable Text Strings”
as “Custom Event #1” and the customized version of differs between the EMCP 3 platforms and the
the event log text string is referred to as “Building language sets. The EMCP 3.1 supports up to six
Fire Detected”. custom events. The EMCP 3.2 and EMCP 3.3
support up to eight custom events. Due to the
Note: The “Technician English” version is the basic differences in screen resolution, the display platforms
version of the text string format before the text string also differ in the number of pixels that are allowed in
is modified. The “Technician English” version is the custom event name.
offered for the use of troubleshooting by a technician.
Different language sets support a different set
of characters. Due to all of the differences, the
“Modifiable Text String” configuration files have
limited portability between the “EMCP 3” modules.
Language Support
The primary language for the “EMCP 3” control will
always be “U.S. (Technician) English”. The user will
always be able to revert back to “Technician English”
from the selected language that is supported by the
flash file. However, if the EMCP 3 display is viewed in
“Technician English”, then the user will not be able to
view the custom text strings. Also, the user will only
be able to view the default strings for a given input.
Refer to the “Before Customizing the Text String”
field information in Illustration 25.
g01456282
Illustration 26
44 RENR7902-07
Systems Operation Section
g01456283
Illustration 27
g01456284
Illustration 28
RENR7902-07 45
Systems Operation Section
• The language ID
• Parameter value name current strings that can be
configured
g01456352
Illustration 29
46 RENR7902-07
Systems Operation Section
g01509224
Illustration 30
g01456367
Illustration 31
The modifiable text strings can be entered after the Note: The modifiable text string parameter value
data from the EMCP 3 is downloaded to the service field is initially blank until it is replaced with a custom
tool. The modifiable text strings are considered to text string parameter value. The custom text string
be a pair of strings for each event. The user has the parameter value entered will replace the default
option to customize the pair of text strings. strings.
Two lines of custom text can be entered as shown in The “Save To ECM” command must be used in order
Illustration 31. The custom text strings can be saved to upload the changes to the EMCP 3 and in order
to the ECM or a file. allow the changes to become effective.
The custom text string parameter value(s) will Note: There is a numbering offset. “Digital Input 3”
be displayed, that are in the flash file secondary triggers “Event Input Function 1”. If “Event Input
language, after the changes have been uploaded to Function 1” is configured properly, then “Custom
the EMCP 3. The custom text string parameter(s) are Event 1” will be triggered. For higher numbered
displayed only when an FMI 31 event for the custom digital inputs, the numbers increase correspondingly.
event is triggered. The user will only have access
to the default strings when viewing the display in a. Expected Result:
“Technician English”. Since the modifiable text strings
are offered as a string pair, the default strings will The “Event Input Function 1” SPN, if using
be displayed as “Custom Event 1” on the first line digital input 3, is configured for “Custom Event”
and as “Status” on the second line. The custom text and that the “Event Input Function 3” FMI code
strings will be displayed in the secondary language. is configured for “Condition Exists” (Status).
If the service tool does not support the secondary
language, then “U.S. English (USA)” will be used. Note: “Status” is referred to as “Condition Exists” by
the Cat Service Tool (CST).
Problems with Modifiable Text Strings
b. Results:
Unable to View the Custom Event
OK - The set points are configured correctly.
1. Check for wiring problems. Proceed to Step 3.
a. At the “Main Menu”, select “I/O Status”. NOT OK - The set points need to be changed.
In order to change the set points, a security
b. Activate the input. Does the appropriate input level 2 access or CST is required. In order
indicator change? If the input indicator does to change the SPN set point from the control
not change, check the wiring. panel display, select the category “Others”,
then click “Custom Event”.
Note: The input should be wired between the
appropriate digital input pin and ground (-BATT). Note: The menu items are not in alphabetical order.
The “I/O Status” should change from a hyphen Each type of event, such as “Custom Event 1
(-) to the number of the input that is being Condition Exists”, has an associated “Event
switched. Response Configuration”. The “Event Response
Configuration” must be enabled in order for the
d. Results: event to appear in the event log.
The Custom Event is Viewable But the Default There is a text string shown to the right of the
Text is Shown on the EMCP 3 Display Instead of custom event that is being configured. For
the Custom String example, in Illustration 28, “Custom Event” 1,
5, and 6 DO NOT have a custom string that is
1. VERIFY THAT THE CONTROL PANEL DISPLAY defined. However, “Custom Event” 2, 3, and 4
IS SET TO THE PRIMARY LANGUAGE. DO have custom strings that are defined.
Note: The “U.S. English (USA)” and “Technician NOT OK - A custom string needs to be entered.
English” look nearly identical. Double click to the right of either line 1 or line
2 of the “Custom Event”. Type in the desired
The language can be changed. In order to change custom string. When finished, press the button
the language from the “Main Menu”, select that is labeled “Save To ECM”. The process will
“Preferences”, then select “Language”. upload the changes to the EMCP 3.
Note: “Preferences” is the bottom item in the “Main 3. VERIFY THAT A STATUS EVENT IS BEING
Menu”. The “Language” choice is the bottom item TRIGGERED
that is in listed in the “Preferences” menu. The menu
structure facilitates the ability to change from a The “Event Input Function” FMI code, that
language the user does not understand to a language corresponds to the “Custom Event” that is being
the user does understand. triggered, should be set to “Condition Exists” or
to “Status”.
a. Expected Result:
Note: The code should be set to “Condition Exists” or
Check the language setting. “Technician to “Status” even though the custom event setting is a
English” should NOT be selected. “High Warning”, a “Low Warning”, or a “Shutdown”.
OK - The language is not set to “Technician Check the event log entry for the “Custom
English”. Proceed to “VERIFY A CUSTOM Event”. Does entry read “Status” on the
STRING”. second line? The other settings such as “Low
Warning”, “Low Shutdown”, “High Warning”, or
NOT OK - Scroll down to the primary language. “High Shutdown” cannot be displayed with the
Press the “Enter” key that is on the EMCP 3 custom text.
display in order to change the language. Go
back into the event log in order verify that Note: This does not mean that a custom event to
the custom string is being displayed for the trigger a warning or shutdown cannot be configured.
“Custom Event” when the corresponding input If needed, configure the “Custom Event” number for
is activated. the “Condition Exists Event Response Configuration”
to trigger a “Warning”, a “Soft Shutdown”, or a “Hard
2. VERIFY A CUSTOM STRING Shutdown”. A user may want to indicate the type
of action taken in a custom text string. “BUILDING
Verify that a custom string was created. Verify that FIRE DETECTED WARNING” or “BUILDING FIRE
a custom string was uploaded by the use of the DETECTED SHUTDOWN” are examples of the types
Caterpillar Service Tool. Verify that the “Modifiable of action that can be described in a custom text string.
Text Strings” command was used. Navigate to the
“Modifiable Text Strings” tool. Press the button Note: The set point name may or may not include the
that is labeled “Load from ECM”. words “Condition Exists”.
Verify that the “Custom Event” that is to be OK - The event does read “Custom Event” on
displayed with a custom text string, has the line 1 and “Status” on line 2. Call the customer
custom string that is to be displayed. support representative for further assistance.
a. Expected Result:
RENR7902-07 49
Systems Operation Section
NOT OK - Configure the desired “Event Input a. Press the Enter key in order to select the
Function” FMI code to “Condition Exists” or CONTROL menu. “SPEED” or “VOLTAGE” will
“Status”. be displayed.
(9) Escape – Navigate up (backward) through the Note: When the scroll left and scroll right keys are
menu structure and also used to cancel out of data used to adjust the frequency, an offset is applied to
entry screens during set point programming. the set point value for “Generator Nominal Output
Frequency”. This data is transmitted over the J1939
(10) Enter key – Select a highlighted menu item or primary data link to the engine controller and is
save a programmed value. retained until battery power is cycled to the EMCP
3. Cycling the battery power to the EMCP 3 will
(11) Scroll Right key – During numeric data entry, remove the offset. Once the offset is removed, the
choose the digit to edit. During certain set point transmitted value reverts back to the set point value
adjustments, select or deselect a check box. for “Generator Nominal Output Frequency”.
(12) Scroll Down key – Move down through the Idle Speed and Rated Speed
main menu or navigate within a list in order to
highlight one of the items. Also used to decrement The engine speed can be toggled between the “LOW
digits (0-9). IDLE” and the “RATED SPEED” with the use of the
control display.
(13) Scroll Up key – Move up through the main
menu or navigate within a list in order to highlight one 1. From the “MAIN MENU”, select “CONTROL”.
of the items. Also used to increment digits (0-9).
2. Press the “DOWN ARROW” in order to highlight
(14) Scroll Left key – During numeric data entry, “IDLE/RATED”.
choose the digit to edit. During certain set point
adjustments, select or deselect a check box. 3. Press the “ENTER” key. The “IDLE/RATED”
screen will be displayed. The current state will be
Adjustment displayed.
Use the following procedure in order to adjust the 4. In order to change the state, press the “Enter” key,
voltage and frequency of the generator output. then press the “UP ARROW” or press the “DOWN
ARROW” in order to select the desired value.
1. From the MAIN MENU, use the Scroll Down key
or the Scroll Up key in order to navigate to the 5. Press the “ENTER” key in order to accept the
“CONTROL” menu. change.
50 RENR7902-07
Systems Operation Section
7. Press the “Enter” key in order to edit the time. 7. Press the Enter key in order to accept the
changes.
8. Use the Scroll Right key or the Scroll Left
key in order to highlight the digit that is to be Note: In order to reject the changes, press the
programmed. The seconds are highlighted in “Escape” key instead of the Enter key.
Illustration 34.
8. Press the Escape key in order to return to the
“MAIN MENU” screen.
1. If the control does not have the “Set Time/Date” 3. Press the Scroll Down key in order to highlight
screen shown, then follow the procedures in Steps “TIME/DATE”.
1 through 4 of the “Change the Time” section in
order to access the “Set Time/Date” screen. 4. Press the Enter key in order to select
“TIME/DATE”. “SET TIME/DATE” is displayed.
2. Press the Scroll Right key in order to place the Also shown is the current time and date
box around the currently programmed date in the that is programmed into the EMCP 3. The
“Set Time/Date” screen. currently programmed time is highlighted on the
“TIME/DATE” screen.
3. Press the Enter key in order to edit the date. An
eight digit display is shown. The year is highlighted 5. Press the Scroll Down key in order to highlight
at the far right. “FORMAT MM/DD/YY”.
Diagnostics
The thermocouple module is capable of generating
events and diagnostics and can store up to twenty
diagnostic log entries that can be viewed from the
EMCP 3. The generated events and diagnostics are
maintained in non-volatile memory in order to ensure
availability after a power loss. The format for each of
g01451712 the log entries is listed in Table 14.
Illustration 35
The display units are selectable at the EMCP 3 1146 Exhaust Gas Port 10 Temperature
controller as either degrees fahrenheit or as celsius. 1147 Exhaust Gas Port 11 Temperature
All monitored values are available on the data link as
read-only information. Temperatures are configured 1148 Exhaust Gas Port 12 Temperature
to indicate the SPN that is transmitted by each 1149 Exhaust Gas Port 13 Temperature
temperature input.
1150 Exhaust Gas Port 14 Temperature
Table 16
1151 Exhaust Gas Port 15 Temperature
SPNs Available for Configuration of
Temperature Inputs 1152 Exhaust Gas Port 16 Temperature
1184 Turbocharger 1 Turbine Outlet Temperature Input #n – Low Temperature −200 °C −200 °C
Warning Threshold (−328 (−328 °F)
1185 Turbocharger 2 Turbine Outlet Temperature °F) to 800 °C
(1472 °F)
1186 Turbocharger 3 Turbine Outlet Temperature
Input #n – High Temperature 1 0 to 120
1187 Turbocharger 4 Turbine Outlet Temperature
Shutdown Delay Time seconds
1212 Engine Auxiliary Coolant Temperature
Input #n – High Temperature 1 0 to 120
1800 Battery 1 Temperature Warning Delay Time seconds
1801 Battery 2 Temperature Input #n – Low Temperature 1 0 to 120
Warning Delay Time seconds
1802 Intake Manifold 5 Temperature
1803 Intake Manifold 6 Temperature
Specifications
2433 Right Manifold Exhaust Gas Temperature
2434 Left Manifold Exhaust Gas Temperature Table 18 lists the specifications for the thermocouple
module.
Configuration Table 18
i02981487 Table 20
Input #nn Suspect Any SPN (see Table N/A 628 Voltage Regulator
X
parameter Number 20 supported by Failure
(SPN) EMCP 3
970 Emergency Stop
X
Input #nn Failure Any FMI supported by N/A Shutdown (1)
Mode Identifier (FMI) EMCP 3
971 Engine Derate
X
Overridden
Table 20 lists the Suspect Parameter Numbers (SPN) 1084 Gen Overexcitation X X
that the EMCP 3 supports for inputs and outputs.
An SPN is an internationally recognized code that is 1122 Generator Bearing
X
assigned a specific meaning. For example, SPN 110 Temperature #1
relates to the Engine Coolant Temperature. 1124 Generator Winding
X
Temperature #1
(continued)
56 RENR7902-07
Systems Operation Section
The RTD Module will read the inputs, apply the Table 24
algorithm, and then calculate the temperature in RTD Module Diagnostics - FMI Codes
degrees celsius. The RTD module will then broadcast
the information onto the J1939 data link. The EMCP FMI Description
3 will read the information from the RTD module and 0 RTD Input #n High Temperature Shutdown
display the information on the display screen.
4 RTD Input Sensor #n Short Circuit
The RTD module is also capable of generating 5 RTD Input Sensor #n Open Circuit
diagnostics. The diagnostics that are generated
by the RTD module are maintained in non-volatile 15 RTD Input #n High Temperature Warning
memory in order to ensure that they are available 17 RTD Input #n Low Temperature Warning
following a power loss.
Table 23 shows the format for the log entries. Table 25 shows the SPNs that are available for
configuration of temperature inputs.
Table 23
Table 25
Diagnostic Log Entry Format Table
SPNs Available for Configuration of
Suspect Parameter Number (SPN)(1) Temperature Inputs
Failure Mode Indicator (FMI )(2) SPN Description
Time of Last Occurrence 52 Engine Intercooler Temperature
Date of Last Occurrence 105 Intake Manifold 1 Temperature
Time of First Occurrence 110 Engine Coolant Temperature
Date of First Occurrence 171 Ambient Air Temperature
Engine Run Hours First Occurrence 172 Air Inlet Temperature
Engine Run Hours Last Occurrence 173 Exhaust Gas Temperature
Number of Occurrences 174 Fuel Temperature
Security to Clear Log Entry 175 Engine Oil Temperature 1
(1)See Table 25 for possible code numbers.
(2) See Table 24 for possible code numbers.
176 Turbo Oil Temperature
441 Auxiliary Temperature 1
Table 24 shows the RTD Module diagnostics.
442 Auxiliary Temperature 2
1122 Alternator Bearing 1 Temperature
1123 Alternator Bearing 2 Temperature
1124 Alternator Winding 1 Temperature
1125 Alternator Winding 2 Temperature
(continued)
RENR7902-07 59
Systems Operation Section
Table 26 Specifications
Configuration Parameters for Each Input
Table 27
Description Range Default RTD Specifications
Value
Operating voltage range 9 VDC to 32 VDC
Input #n Any SPN that is listed
– Suspect in Table 25 Nominal voltage 12 VDC or 24 VDC
0
Parameter
Number (SPN) Overvoltage capability 32 VDC for one hour at
85 °C (185 °F)
Input #n - RTD IEC Platinum (0.00385)
Temperature JIS Platinum Ambient storage −50 °C (−58 °F) to 125 °C
Coefficient (0.003916) temperature (257 °F)
Configuration US Platinum Ambient operating −40 °C (−40 °F) to 120 °C
(0.003902) IEC temperature range (see (248 °F)
Legacy US Platinum notes)
(0.003920)
SAMA Platinum
(0.003923) Note: If the ambient temperatures exceed 85 °C
(185 °F), the RTD module may deviate in accuracy
Input #n – RTD Not Installed
Sensor Type 2-wire RTD Not +/- 1°C
3-wire RTD Installed
4-wire RTD Note: If the ambient temperature exceeds 120 °C
(248 °F), the RTD module may not return to proper
Input #n – High operation.
Temperature 0 °C (32 °F) to 1735 °C 95 °C
Shutdown (3155 °F) (203 °F)
Threshold i02981958
Input #n – High
Temperature 0 °C (32 °F) to 1735 °C 85 °C
Annunciator Module
Warning (3155 °F) (185 °F)
Threshold SMCS Code: 4490
Input #n – Low
Temperature −200 °C (−328 °F) to −200 °C [ OPTIONAL USE]
Warning 800 °C (1472 °F) (−328 °F)
Threshold This module is not required.
Input #n – High
Temperature
0 to 120 seconds 1
General Information
Shutdown Delay
Time The EMCP 3 annunciator module is used in order to
Input #n – High indicate various system events and status conditions.
Temperature The annunciator module uses indicator lights and an
0 to 120 seconds 1 audible horn in order to provide the operator with
Warning Delay
Time information about the current status of the system.
The annunciator module can be used in order to
Input #n - Low announce faults and status signals to the operator.
Temperature
Warning Delay
0 to 120 seconds 1 The annunciator module also allows the operator to
Time silence the horn or to acknowledge the system faults.
Table 28 Table 29
Annunciator Module Status LED Alarm Conditions and System Status LED
Color Combinations
Solid Green Data link is OK
Row LED 1 LED 2
No CAN data link diagnostic, but no
Flashing
communication detected. Hooking the 1 Red Amber
Green
Annunciator up with the power on.
2 Red Amber
CAN data link diagnostic. For example:
Solid Red the module is wired wrong (Data Link), 3 Red Amber
wrong cable, or no terminating resistor. 4 Red Amber
Red/Green No application software loaded 5 Red Amber
Flashing
6 Red Amber
7 Red Amber
8 Red Amber
8 Red Amber
9 Red Amber
11 Red Amber
12 Red Amber
13 Green Amber
14 Green Amber
15 Red Green
Illustration 36
g01509455 16 Red Green
17 Amber Green
Basic Operation
Each pair of LED indicators on the annunciator Configuration
consist of two of the following three colors: green,
amber, and red. The color choices allow for custom The annunciator is field programmable with the use
configuration of Status, Warning, and Shutdown the CST. The annunciator is also flash programmable
indicators. For example, a pair of red and amber LED in order to update the software with the use of CST.
indicators may be configured for engine oil pressure. The service tool software must be installed on a
If a low engine oil pressure Warning is read over the Windows based PC. The Caterpillar communication
data link, the Annunciator will flash the amber LED adapter must be connected between the PC and
and the audible horn will sound. If the low engine oil the J1939 data link that the target annunciator is
pressure shutdown is read over the data link, the connected to. When the PC is connecting to the
annunciator will flash the Red LED and the audible annunciator, the user will first see the “Module
horn will sound. Summary” screen. Refer to Illustration 37.
In order to acknowledge the shutdown and alarm Note: The service tool may be connected to the
conditions or to silence the horn, press the Alarm EMCP 3 accessory data link service connector.
Acknowledge button that is located near the middle
of the annunciator. Illustration 37 shows the module information such as
serial number, part number, software group number,
In order to test the LED indicators, or in order to test and software release date.
the horn, press the Lamp Test button and hold the
Lamp Test button that is located near the top of the
annunciator.
g01510103
Illustration 37
The annunciator module can be customized in order Electronic Control Unit (ECU) Instance
to signal many different system related conditions. Number
The supported data link parameters are shown in
Table 30 in the form of “J1939 Suspect Parameter The module description possesses the capability to
Numbers” (SPNs). indicate a number that identifies the annunciator
uniquely from any other annunciator modules that are
Global Acknowledge on the primary or accessory J1939 data link. In the
example that is shown in Illustration 38, the service
The annunciator can be configured to initiate an tool is connected to “Alarm Module 2”.
event acknowledge message and to respond to an
event acknowledge message over the J1939 data The unique number that identifies the annunciator is
link. If the “Global Acknowledge” set point is enabled, called the “Electronic Control Unit (ECU) Instance”.
then the annunciator events may be acknowledged The “ECU Instance” is programmable. In order to
directly on the annunciator. The annunciator events program the annunciator to a different ECU instance
may be acknowledged by pressing the: number:
g01510429
Illustration 38
The Cat ET configuration screen shows the desired Configuring the Annunciator LED
ECU instance and the actual hardware, “Aarm Module Behavior
2”, that is related to the specific ECU instance. In
Illustration 38, the annunciator will be programmed to Each LED pair has four parameters that are required
ECU instance 1. Perform the following steps in order in order to configure each LED pair. The best practice
to program the desired instance. is to configure the four columns in order from left to
right, that is, first configure “Trigger Condition”, next
1. Select the desired ECU instance row. configure “Severity Level”, then configure “Suspect
Parameter Number”, and finally configure “Failure
2. Double click on the current ECU instance. A dialog Mode Identifier” (FIM), if required. The reason for
box will open that allows entry of the new ECU the order is because the value that is set in one
instance. column does affect the choices that are available in
the subsequent columns. If a field is grayed out, that
3. Type a numeric value such as 1, 2, 3, or 4. Click particular field is not available due to conditions set
“OK”. in the previous columns.
When the “OK” button is clicked, the service Perform the following steps in order to configure the
tool software will automatically restart and will behavior of the LED pairs.
automatically reconnect to the data link. After the
service tool software has connected once again, 1. Select “Service” in order to enter the “LED Pair
the summary screen will now show the new module Configuration” dialog.
name, based on the ECU instance.
2. Select “LED Pair Configuration”.
g01510553
Illustration 39
Since the FMI codes are implied by this column, the Exhaust Temperature 173
FMI column is grayed out for any of these selections. Engine Oil Temperature 175
Only the “Specific” option will allow an FMI to be
configured. Engine Speed 190
SCADA Data Link Fault 625
Suspect Parameter Number
Primary Data Link (J1939 #1) 639
The “Suspect Parameter Number” column is used Event Input Function #1 701
in order to select or in order to type in the SPN for
Event Input Function #2 702
the parameter that is assigned to the LED pair. Most
supported SPNs can be selected from the list. Refer Event Input Function #3 703
to the “SAE J1939” literature or Systems Operation
Testing and Adjusting Manual, RENR7902 for a Event Input Function #4 704
complete list of supported SPNs. Event Input Function #5 705
Note: Remember to click the “Submit” button that Event Input Function #6 706
is at the bottom of the LED “Pair Configuration” tool Event Input Function #7 707
after the selections for each LED pair has been
made. Only after the “Submit” button has been Event Input Function #8 708
pressed, will the new settings take effect. If selections Event Input Function #9 709
are made and an attempt is made to leave the LED
“Pair Configuration” tool before the “Submit” button Event Input Function #10 710
has been pressed, then a prompt will ask if the user Event Input Function #11 711
wishes to have the changes take effect. If the user
declines, then the changes will be lost. Event Input Function #12 712
Event Input Function #13 713
Table 30
Event Input Function #14 714
Supported SPNs
Event Input Function #15 715
SPN Description SPN
Event Input Function #16 716
Fuel Level (External Tank) 38
Emergency Stop Shutdown 970
Aftercooler Temperature 52
Generator Bearing Temperature #1 1122
Starting Air Pressure 82
Generator Bearing Temperature #2 1123
Fuel Filter Differential Pressure 95
Generator Winding Temperature #1 1124
Fuel Level (Local Tank) 96
Generator Winding Temperature #2 1125
Engine Oil Level 98
Generator Winding Temperature #3 1126
Oil Filter Differential Pressure 99
Exhaust Gas Port 1 Temperature 1137
Engine Oil Pressure 100
Exhaust Gas Port 2 Temperature 1138
Crankcase Pressure 101
Exhaust Gas Port 3 Temperature 1139
Air Filter Differential Pressure 107
Exhaust Gas Port 4 Temperature 1140
Atmospheric Pressure 108
Exhaust Gas Port 5 Temperature 1141
Engine Coolant Temperature 110
Exhaust Gas Port 6 Temperature 1142
Engine Coolant Level 111
Exhaust Gas Port 7 Temperature 1143
Fire Extinguisher Pressure 137
Exhaust Gas Port 8 Temperature 1144
Battery Voltage (switched) 158
(continued)
(continued)
66 RENR7902-07
Systems Operation Section
Table 31
Failure Mode Identifier (FMI) Codes
FMI Description Short Description
0 Data Valid but Above Normal Operational Range - Most Severe Level High Shutdown
1 Data Valid but Below Normal Operational Range - Most Severe Level Low Shutdown
2 Data Erratic, Intermittent or Incorrect N/A
3 Voltage Above Normal or Shorted to High Source N/A
4 Voltage Below Normal or Shorted to Low Source N/A
5 Current Below Normal or Grounded Circuit N/A
6 Current Above Normal or Grounded Circuit N/A
7 Mechanical System Not Responding or Out of Adjustment N/A
8 Abnormal Frequency, Pulse Width or Period N/A
9 Abnormal Update Rate N/A
10 Abnormal Rate of Change N/A
g01093231
Illustration 40
Adding additional remote annunciator
g01093228
Illustration 41
Connection details for devices in parallel with remote annunciator
i02936516
g01457718
Illustration 42
Default Control Panel that is Provided with the EMCP 3 Monitoring Software
Software Set Up
Connect a computer to the EMCP 3. The SCADA
data link must be used. Follow the instructions that
are located in the “EMCP 3 Monitoring Software
Quick Start Guide” section of this publication. After
the program launched, a login dialog will appear. A
user name and a password are required. Use the
default user name “administrator”. Enter “admin” for
the password. Refer to Illustration 43.
g01457841
Illustration 43
Log On Screen
Add Device
1. Click on “Network”.
RENR7902-07 71
Systems Operation Section
2. Select “Add Device” or right click on the cable 3. Click “Set Points”.
symbol that is located at the top left corner of the
dialog. The symbol is located near the “Offline” 4. Select “Network”
text that is on the dialog.
5. Select “Data Link – SCADA”.
3. Select “Add Device”. The “Add a Device” dialog
will appear. Refer to Illustration 44. Check the Online Configuration Settings
Use the following steps in order to check the online
configuration settings:
1. Select “Network”.
Device Name
Access the SCADA Data Link Slave Address Set 2. Select “Control Panel Configuration”.
Point
Add a Control
Perform the following steps in order to access the
SCADA data link slave address set point. 1. Select “Edit”.
1. Begin at the main menu. 2. Select “Add Control”.
2. Select “Configure”.
72 RENR7902-07
Systems Operation Section
3. Click “Digital Display” or click the “Digital Display” 5. Click on a previously defined device name that is
button that is on the tool bar. In order to add the listed in the “Device/Group” field of the dialog. For
control, double click on the desired location within this example, “ENG” has been selected.
the control panel (77). The process will add the
digital display as shown in Illustration 46. All of the possible parameters for the digital
display will be shown in the “Parameter List”.
g01457844
Illustration 46
Digital Display Added to Control Panel
g01457845
Illustration 47
RENR7902-07 73
Systems Operation Section
g01457846
Illustration 48
g01457849
Illustration 49
1. Select “View”.
74 RENR7902-07
Systems Operation Section
g01457851
Illustration 51
Perform the following steps in order to test the If the battery voltage is not reading correctly, then
connection: insure that the dialog that is being displayed is the
“Control Panel View” dialog and not the “Control
1. Click “Network” or right click on the cable symbol Panel Edit” dialog.
that is in the top left corner of the dialog where the
dialog displays “Offline”. Also, recheck all of the settings that are mentioned at
the beginning of this software setup section. Finally,
2. Click “Go Online”. check the wiring for any possible problems.
The procedure instructs the computer to begin Click the “View Current Events” button that is located
the connection. The battery voltage should on the tool bar in order to perform another simple
be displayed within a few seconds. Refer to test. The dialog should display all of the events that
Illustration 51. are currently listed in the EMCP 3.
g01457873
Illustration 52
g01457874
Illustration 53
3. Use the scroll bar that is on the right of the 4. Click on the “EMCP Monitoring Software –
screen in order to scroll down until “EMCP QUICKSTART ver1_ 0.doc” link in order to start
Monitoring Software” is found in the left column. the download. The “File Download” dialog will
The second column from the left contains the open.
“EMCP Monitoring Software.zip” file. The far right
column shows the “Additional Info” link. Click on
the “Additional Info” link in order to access the
“Quick Start Guide”. Refer to Illustration 53.
76 RENR7902-07
Systems Operation Section
g01457875
Illustration 54
g01457876
Illustration 55
RENR7902-07 77
Systems Operation Section
Creating a Control Panel View Note: The monitoring software provides the
option to create new control panel views. A new
In the “Software Set Up” section, a control panel view control panel view can be defined by selecting the
was created in order to display the battery voltage. A desired parameters and by selecting the desired
control panel view can be created in order to serve format for the parameters. The types of parameter
other purposes. This section will provide an overview formats include, but are not limited to, circular
of the steps that are necessary in order to design a gauge and numeric display. After the parameter
control panel view. and the parameter format has been selected, the
configuration should be saved to a file. A default
Add Controls configuration file is supplied with the monitoring
software. The file name, “default.pvc”, contains the
1. Access the control panel edit dialog. Refer to basic screens that have the standard parameters
Illustration 56. already configured. The user can modify the file. The
modified file can be save as a new file if desired.
Note: The entire control panel can be created from
within the control panel edit dialog. 2. New controls can be added by two different
methods.
• Displays
• Switches
• Indicators
The display controls consist of:
• Circular gauge
g01457877
Illustration 56 • Digital display
a. Click “Edit”. • Thermometer
b. Click “Control Panel Configuration”. • Linear gauge
Note: If the “Control Panel Edit” option is unavailable, The displays can be used in order to display
close out of the “Control Panel View” dialog. The the information about the generator set. Some
“Control Panel View” dialog and the “Control Panel examples include engine coolant temperature,
Edit” dialog cannot be open at the same time. Also, it generator total real power, engine RPM, and
is recommended that the control be “offline” before battery voltage. Refer to Illustration 57.
any attempt is made to edit the “Control Panel View”.
In order to place the control offline, click “Network”,
then click “Go Offline” or right click on the cable
symbol, then click “Go Offline”.
78 RENR7902-07
Systems Operation Section
g01457878
Illustration 57
• Sliding switch
• Panel switch
• Lever switch
• Rocker switch
• Single button
• Rotary switch
The rotary knob and the multiple button switch
are included in this category. These switches
can be used in order to control something that
is either “off” or “on”. Some of the examples
include the emergency stop switch, the remote
initiate command, and the digital selectors. The
multiple button switch can also control the engine
operating mode command. Refer to Illustration 58.
g01457880
Illustration 58
RENR7902-07 79
Systems Operation Section
g01457881
Illustration 59
g01457883
Illustration 60
80 RENR7902-07
Systems Operation Section
g01457885
Illustration 61
g01457887
Illustration 62
g01457898
Illustration 63
9. The displayed text (51) can be changed after the a. Right click on the text box.
desired parameter has been selected.
82 RENR7902-07
Systems Operation Section
g01457899
Illustration 64
g01457900
Illustration 65
1. Select “Edit”.
3. Select “Edit”.
a. Click “Edit”.
g01457914
Illustration 67
g01457915
Illustration 68
g01457916
Illustration 69
6. Select the “Triggering” tab in order to configure The text file can be opened after the data has been
when events should start and in order to configure collected. Locate the saved file. Open the saved
when events should stop. file with a text editor such as Notepad. The file will
contain a timestamp from the start of data logging.
a. In order to start an event, select “On Arm”, The file will also contain data that was captured
“Manual Trigger” , or “Absolute Time”. according to the “Base Scan Rate” setting that is in
the “Data Log Configuration” dialog that is shown
On Arm will start the data collection in Illustration 69. The file should look similar to
immediately after “Arm” has been selected or Illustration 70.
after clicking the “Play” button.
g01457917
Illustration 70
RENR7902-07 89
Troubleshooting Section
Troubleshooting Section
Do not connect generator to a utility electrical dis-
Introduction tribution system unless it is isolated from the sys-
tem. Electrical feedback into the distribution sys-
tem can occur and could cause personal injury or
i02464576 death.
i02464702
The Caterpillar Electronic • The failures of the ECM system are displayed.
Technician • The status of most of the inputs and the outputs
are displayed.
• View the status of parameters. • A time stamp will display the last occurrence of the
problem.
• Clear active diagnostic codes and clear logged
diagnostic codes Status Groups For The Caterpillar
• Program the ECM (Flash). This is done with the Electronic Technician
“WINflash” program. See Testing and Adjusting,
“Electronic Control Module (Generator Set) - Flash The Status Groups are lists of ECM parameters. The
Program”. status of the parameters are shown in real time.
92 RENR7902-07
Troubleshooting Section
i03206911
Table 33
Trouble Codes
Suspect Parameter Failure Mode Code Description Display Text Troubleshooting
Number (SPN) Identifier (FMI) String Topic
38 0 External Tank High Fuel EXT TANK HIGH Digital Input Circuit
Level Shutdown FUEL LEVEL Fault and Analog Input
SHUTDOWN Circuit Fault
38 1 External Tank Low Fuel EXT TANK LOW Digital Input Circuit
Level Shutdown FUEL LEVEL Fault and Analog Input
SHUTDOWN Circuit Fault
38 3 External Tank Fuel Level EXT TANK FUEL Analog Input Circuit
Sensor Short High LEVEL SENSOR Fault
SHORT HIGH
38 4 External Tank Fuel Level EXT TANK FUEL Analog Input Circuit
Sensor Short Low LEVEL SENSOR Fault
SHORT LOW
38 15 External Tank High Fuel EXT TANK Digital Input Circuit
Level Warning HIGH FUEL LVL Fault and Analog Input
WARNING Circuit Fault
38 17 External Tank Low Fuel EXT TANK Digital Input Circuit
Level Warning LOW FUEL LVL Fault and Analog Input
WARNING Circuit Fault
(continued)
RENR7902-07 93
Troubleshooting Section
• Activation of the stop signal input Note: Refer to the engine Troubleshooting
manual for more information on engine starting
• A data link message calling for a engine shutdown and engine cranking for your particular genset.
If the engine is running, the engine will continue to run Conditions Which Generate This Code:
in cooldown. When the cooldown interval is complete,
the engine will stop. An immediate shutdown due to The code for the engine overcrank is generated when
a critical fault will cause the engine to shutdown and the EMCP 3 determines that an engine overcrank
the Cooldown Timer to be bypassed. condition has occurred.
Reference: For more information on setting the Test Step 1. PERFORM THE INITIAL
cooldown duration setpoint, see Testing and CHECK.
Adjusting, “Electronic Control Module (Generator
Set) - Configure”, A. Check for active diagnostic codes on the engine
ECM and the EMCP 3. If any codes are present,
Conditions Which Generate This Code: correct the diagnostic codes first.
The code for the engine cooldown is generated when Expected Result:
the EMCP 3 determines that an engine cooldown is
in progress. The engine will continue to run until the No other diagnostic codes or indicators are active.
cooldown duration time has expired.
Results:
Talk to the Operator
• OK – No other diagnostic codes or indicators are
Note: No repair to the engine is necessary. active. Proceed to Test Step 2
A. Determine the conditions that caused the • NOT OK – Another diagnostic code is active or an
diagnostic code. indicator is active.
Expected Result: Repair: Exit this procedure. Troubleshoot the
active code or indicator. Resume normal operation
A shutdown was initiated by the operator or by the and verify that the problem has been corrected.
software that caused the engine to enter into the
cooldown mode. STOP.
Results: Test Step 2. CHECK THE SETPOINTS.
• OK – STOP. A. View the setpoints (Crank Duration, Crank
Cycle Rest Interval, and Maximum Number of
Crank Cycles). Make a note of the setpoints.
See Testing and Adjusting, “Electronic Control
Module (Generator Set) - Configure”. Compare
the setpoints against the default setpoints of the
particular generator set.
RENR7902-07 109
Troubleshooting Section
Results: STOP.
• OK – The setpoints are correct for your particular Test Step 4. Check communications
genset. Proceed to Test Step 3 for MUI engines. between EMCP 3 and Engine ECM. (EUI
Proceed to Test step 4 for EUI engines. Engines Only)
• NOT OK – The setpoints are NOT correct. A. Use the Caterpillar Electronic Technician in order
to verify that the fuel enable input on the Engine
Repair: Reprogram the setpoints. Reset the ECM is configured for “CAN Input”.
genset. Resume normal operation and verify that
the problem has been corrected. B. Refer to the Genset Electrical System Schematic
in the Service Manual and check the Data Link
STOP. wiring between the EMCP and the Engine ECM.
See Troubleshooting, “Data Link Circuit Fault”
Test Step 3. Inspect the 2301A Governor
Power Source and Wiring. (MUI Engines Results:
Only)
• OK – The Data Link wiring is correct. The EMCP
Refer to the Genset Electrical System Schematic in 3 may have failed.
the Service Manual for an accurate representation of
the genset that is being serviced. Repair: It is unlikely that the EMCP 3 has failed.
Exit this procedure and perform this procedure
A. Verify the Emergency Stop Push Button is not again. If the failure is not found, replace the EMCP
pressed 3.
Note: Refer to the engine Troubleshooting manual Repair: Reprogram the setpoints. Reset the
for more information regarding engine speed for genset. Resume normal operation and verify that
your particular genset. the problem has been corrected.
Test Step 2. CHECK THE SETPOINTS. Test Step 4. CHECK THE SYSTEM BY
USING THE SPEED POTENTIOMETER.
A. View the Engine Speed Monitor and Generator (MUI ENGINES ONLY)
Desired Engine Speed Request setpoints. Make a
note of the setpoints. See Testing and Adjusting, A. With the engine running, adjust the speed of the
“Electronic Control Module (Generator Set) - engine by turning the speed potentiometer.
Configure”. Compare the setpoints against the
default setpoints of the particular generator set. Expected Result:
Repair: Reprogram the setpoints. Reset the • NOT OK – The engine speed cannot be adjusted
genset. Resume normal operation and verify that with the speed potentiometer. Proceed to test step
the problem has been corrected. 5
Verify the engine speed can be viewed and adjusted B. Disconnect the speed potentiometer from the
from the EMCP 3 Display Screen. terminals “11” and “12” on the 2301A Governor.
Repair: Adjust the engine speed to meet site • OK – The resistance of the sensor is correct.
requirements. Resume normal operation and verify Proceed to Test Step 6.
that the problem has been corrected.
• NOT OK – The resistance of the speed
STOP. potentiometer is not correct.
• NOT OK – The engine speed cannot be adjusted. Repair: Replace the speed potentiometer. Resume
Proceed to test step 7 normal operation and verify that the problem has
been corrected.
• NOT OK – The engine speed reads zero on the
EMCP Display Screen. STOP.
Repair: The Engine Speed Sensor may have Test Step 6. CHECK THE SPEED
failed or needs to be adjusted. See Testing And POTENTIOMETER HARNESS FOR A
Adjusting, “Speed Sensor (Engine) - Adjust”. If OPEN CIRCUIT. (MUI ENGINES ONLY)
the problem remains, replace the Engine Speed
Sensor. A. Disconnect the speed potentiometer harness from
the 2301A governor.
STOP.
112 RENR7902-07
Troubleshooting Section
B. Check for an open circuit. Check the resistance Repair: The EMCP 3 may have failed. It is unlikely
from the wire connected to terminal “11” of the that the EMCP 3 has failed. Exit this procedure and
2301A governor to the same wire number at the perform this entire procedure again. If the problem
speed potentiometer. The resistance should be 5 remains, replace the EMCP 3. See Testing And
ohms or less. Adjusting, “ Electronic Control Module (Generator
Set) - Replace”.
C. Check for an open circuit. Check the resistance
from the wire connected to terminal “12” of the STOP.
2301A governor to the same wire number at the
speed potentiometer. The resistance should be 5 • NOT OK – The wiring is not correct
ohms or less
Repair: Repair the Data Link wiring or Replace the
Expected Result: Data Link wiring. Resume normal operation and
verify the problem has been corrected.
When the resistance is measured between the wire
connected to terminal “11” of the 2301A governor to STOP.
the same wire number at the speed potentiometer
connector, the resistance should be 5 ohms or less.
i02461493
Repair: Replace the speed potentiometer. Resume Test Step 7. CHECK THE J1939 DATA
normal operation and verify that the problem has LINK BETWEEN THE EMCP 3 AND THE
been corrected. ENGINE ECM (EUI ENGINES ONLY)
STOP. Refer to the Genset Electrical System Schematic in
the Service Manual and check the Data Link wiring
Test Step 6. CHECK THE SPEED between the EMCP 3 and the Engine ECM. For more
POTENTIOMETER HARNESS FOR A information on troubleshooting the Data Link, see
OPEN CIRCUIT. (MUI ENGINES ONLY) Troubleshooting, “Data Link Circuit Fault ”.
Repair: The EMCP 3 may have failed. It is unlikely Pressing the Auto Key or a Modbus RS-485 SCADA
that the EMCP 3 has failed. Exit this procedure and Data Link message causes the engine to enter AUTO
perform this entire procedure again. If the problem mode. When the engine is in AUTO mode and no
remains, replace the EMCP 3. See Testing And shutdowns are active, then continuous activation of
Adjusting, “ Electronic Control Module (Generator the Remote Initiate input causes the engine to start
Set) - Replace”. and to run (after a programmed Start Aid Activation
delay and Crank Alert interval). When the Remote
STOP. Initiate signal is removed, then the engine will cool
down and then stop. When the genset control is not
• NOT OK – The harness wiring with the incorrect in AUTO mode, "GEN CONTROL NOT IN AUTO
resistance measurement has failed. WARNING" will be displayed on the EMCP 3 in order
to inform the operator of the not in auto condition.
RENR7902-07 115
Troubleshooting Section
Results:
STOP.
116 RENR7902-07
Troubleshooting Section
• NOT OK – The overcurrent condition was not If an overfrequency condition is detected, then
caused by an occurrence known to the operator. “GEN OVERFREQUENCY SHUTDOWN” or “GEN
Proceed to Test Step 2 OVERFREQUENCY WARNING” will be displayed
on the EMCP 3 in order to inform the operator of an
Test Step 2. CHECK THE SETPOINTS. overfrequency condition.
A. View the setpoints (Generator Current Transformer Note: The severity of the overfrequency condition will
Primary Winding Rating), (Generator Current determine if a warning or shutdown event occurs.
Transformer Secondary Winding Rating), and
all of the overcurrent setpoints. Make a note Conditions Which Generate This Code:
of the setpoints. See Testing and Adjusting,
“Electronic Control Module (Generator Set) - The code for generator overfrequency is generated
Configure”. Compare the setpoints against the when the EMCP 3 determines that a generator
default setpoints of the particular generator set. overfrequency condition has occurred.
STOP.
i02464697
• NOT OK – The setpoints are NOT correct. • NOT OK – The generator output frequency cannot
be adjusted with the speed potentiometer. Proceed
Repair: Reprogram the setpoints. Reset the to test step 5
genset. Resume normal operation and verify that
the problem has been corrected. Test Step 5. CHECK THE RESISTANCE OF
THE ENGINE SPEED POTENTIOMETER.
STOP. (MUI ENGINES ONLY)
Test Step 3. VERIFY FREQUENCY CAN A. Shut down the engine.
BE VIEWED AND ADJUSTED FROM THE
EMCP 3 (EUI ENGINES ONLY) B. Disconnect the speed potentiometer from the
terminals “11” and “12” on the 2301A Governor.
Verify the generator output frequency can be viewed
and adjusted from the EMCP 3 Display Screen. C. At the speed potentiometer, measure the
resistance of the speed potentiometer.
Expected Result:
Expected Result:
The generator output frequency can be viewed and
adjusted from the EMCP 3 Display Screen. The resistance should be adjustable between 0 and
100 ohms.
Results:
Results:
• OK – The generator output frequency can be
viewed and adjusted from the EMCP 3 Display • OK – The resistance of the sensor is correct.
Screen. Proceed to Test Step 6.
Repair: Adjust the generator output frequency to • NOT OK – The resistance of the speed
meet site requirements. Resume normal operation potentiometer is not correct.
and verify that the problem has been corrected.
Repair: Replace the speed potentiometer. Resume
STOP. normal operation and verify that the problem has
been corrected.
• NOT OK – The generator output frequency cannot
be adjusted. Proceed to test step 7 STOP.
• NOT OK – The generator frequency reads zero on Test Step 6. CHECK THE SPEED
the EMCP Display Screen. Proceed to test step 8 POTENTIOMETER HARNESS FOR AN
OPEN CIRCUIT. (MUI ENGINES ONLY)
Test Step 4. CHECK THE SYSTEM BY
USING THE SPEED POTENTIOMETER. A. Disconnect the speed potentiometer harness from
(MUI ENGINES ONLY) the 2301A governor.
A. With the engine running, adjust the generator B. Check for an open circuit. Check the resistance
output frequency by turning the speed from the wire connected to terminal “11” of the
potentiometer. 2301A governor to the same wire number at the
speed potentiometer. The resistance should be 5
Expected Result: ohms or less.
The generator output frequency can be adjusted to C. Check for an open circuit. Check the resistance
the desired frequency. from the wire connected to terminal “12” of the
2301A governor to the same wire number at the
Results: speed potentiometer. The resistance should be 5
ohms or less
• OK – The generator output frequency can be
adjusted. Expected Result:
Repair: Adjust the generator output frequency to When the resistance is measured between the wire
meet site requirements. Resume normal operation connected to terminal “11” of the 2301A governor to
and verify that the problem has been corrected. the same wire number at the speed potentiometer
connector, the resistance should be 5 ohms or less.
STOP.
118 RENR7902-07
Troubleshooting Section
When the resistance is measured between the wire Repair: Check for a shorted component or
connected to terminal “12” of the 2301A governor to damaged wiring. Troubleshoot and repair the
the same wire number at the speed potentiometer problem. See the Generator Set Wiring Diagram
connector, the resistance should be 5 ohms or less. for your particular genset. After the problem has
been repaired, replace the fuses.
Results:
STOP.
• OK – The harness functions properly. Proceed to
test step 8 Test Step 9. CHECK THE GENERATOR
VOLTAGE OUTPUT.
• NOT OK – The harness wiring with the incorrect
resistance measurement has failed. Replace A. Open the circuit breaker or remove the load.
the failed harness from the 2301A governor
to the speed potentiometer or repair the failed B. Start the engine and run the genset.
harness from the 2301A governor to the speed
potentiometer. Resume normal operation and C. Measure the voltage between all three AC input
verify that the problem has been corrected. STOP. fuses.
STOP. STOP.
Test Step 8. CHECK THE VOLTAGE Test Step 10. CHECK THE VOLTAGE
INPUT FUSES. INPUT CONNECTIONS
A. Check the three fuses on the AC voltage inputs of A. Shut down the engine.
the EMCP 3.
B. Remove the EMCP 3 harness connector from the
Expected Result: EMCP 3.
The fuses should not be open. C. Check the EMCP 3 harness connector. See
Testing And Adjusting, “Electrical Connector -
Results: Inspect”.
• OK – The fuses are not open. Proceed to test step D. Check for one or more damaged wires between
9 the EMCP 3 voltage inputs and the voltage input
fuses. See the Generator Set Wiring Diagram for
• NOT OK – One or more of the fuses are open. your particular genset.
Expected Result:
• OK – NO problem was found with the connectors An overvoltage was caused by an occurrence that is
or with the wiring. known to the operator and the operator would like to
put the genset back into service.
Repair: The EMCP 3 may have failed. It is unlikely
that the EMCP 3 has failed. Exit this procedure and Results:
perform this entire procedure again. If the problem
remains, replace the EMCP 3. See Testing And • OK – The operator can determine the cause for
Adjusting, “ Electronic Control Module (Generator the overvoltage condition, the condition has been
Set) - Replace”. repaired and the operator wants to put the genset
back into service.
STOP.
Repair: Reset the genset. Resume normal
• NOT OK – The problem was with the connectors operation and verify that the problem has been
or with the wiring. corrected.
If the voltage rises above the Generator Overvoltage The setpoints are correct.
Percentage Threshold setpoint value, then the
overvoltage timer will begin timing. When the timer Results:
expires, the Generator Overvoltage event is made
active (if the voltage has been above the threshold • OK – The setpoints are correct for your particular
level continuously while timing). If the voltage genset.
drops below the Generator Overvoltage Percentage
Threshold, then the Generator Overvoltage event will Repair: Reset the genset. Resume normal
be made inactive and the timer will be reset. operation and verify that the problem has been
corrected.
If an overvoltage condition is detected, then
“GEN OVERVOLTAGE SHUTDOWN” or “GEN STOP.
OVERVOLTAGE WARNING” will be displayed on
the EMCP 3 in order to inform the operator of an • NOT OK – The setpoints are NOT correct.
overvoltage condition.
Repair: Reprogram the setpoints. Reset the
Note: The severity of the overvoltage condition will genset. Resume normal operation and verify that
determine if a warning or shutdown event occurs. the problem has been corrected.
The code for generator overvoltage is generated Test Step 3. VERIFY VOLTAGE CAN BE
when the EMCP 3 determines that a generator ADJUSTED
overvoltage condition has occurred.
Verify the generator output voltage can be adjusted
Test Step 1. TALK TO THE OPERATOR from the EMCP 3 Display Screen.
The generator output voltage can be adjusted from Generator Reverse Power
the EMCP 3 Display Screen. Warning
Results: SMCS Code: 4490
• NOT OK – The wiring is not correct A reverse power was caused by an occurrence
known to the operator and the operator would like to
Repair: Repair the Data Link wiring or Replace the put the genset back into service.
Data Link wiring. Resume normal operation and
verify that the problem has been corrected. Results:
STOP. • OK – The operator can determine the cause for
the reverse power condition, the condition has
been repaired and the operator wants to put the
genset back into service.
STOP.
A. View the Generator Reverse Power setpoints. The polarity of the current transformers should be
Make a note of the setpoints. See Testing and correct.
Adjusting, “Electronic Control Module (Generator
Set) - Configure”. Compare the setpoints against Results:
the default setpoints of the particular generator
set. • OK – The polarity of the current transformers is
correct.
Expected Result:
Repair: It is unlikely that the EMCP 3 has failed.
The setpoints are correct. Exit this procedure and perform this procedure
again. If the diagnostic code is still present,
Results: then replace the EMCP 3. Refer to Testing and
Adjusting, “ Electronic Control Module (Generator
• OK – The setpoints are correct for your particular Set) - Replace”.
genset. Proceed to Test Step 3.
STOP.
• NOT OK – The setpoints are NOT correct.
• NOT OK – The polarity of the current transformers
Repair: Reprogram the setpoints. Reset the is NOT correct.
genset. Resume normal operation and verify that
the problem has been corrected. Repair: Install the current transformers as shown
on the wiring diagram for your particular genset.
STOP. Reset the genset. Resume normal operation and
verify that the problem has been corrected.
Test Step 3. CHECK THE POLARITY OF
THE CURRENT TRANSFORMERS STOP.
i02464681
Generator Underfrequency
Warning
SMCS Code: 4490
The code for generator underfrequency is generated Test Step 3. VERIFY FREQUENCY CAN
when the EMCP 3 determines that a generator BE VIEWED AND ADJUSTED FROM THE
underfrequency condition has occurred. EMCP 3 (EUI ENGINES ONLY)
Test Step 1. TALK TO THE OPERATOR Verify the generator output frequency can be viewed
and adjusted from the EMCP 3 Display Screen.
A. Determine the conditions that caused the
underfrequency condition. Expected Result:
• OK – The operator can determine the cause for Repair: Adjust the generator output frequency to
the underfrequency condition, the condition has meet site requirements. Resume normal operation
been repaired and the operator wants to put the and verify that the problem has been corrected.
genset back into service.
STOP.
Repair: Reset the genset. Resume normal
operation and verify that the problem has been • NOT OK – The generator output frequency cannot
corrected. be adjusted. Proceed to test step 7
STOP.
RENR7902-07 123
Troubleshooting Section
B. Check for an open circuit. Check the resistance Test Step 8. CHECK THE VOLTAGE
from the wire connected to terminal “11” of the INPUT FUSES.
2301A governor to the same wire number at the
speed potentiometer. The resistance should be 5 A. Check the three fuses on the AC voltage inputs of
ohms or less. the EMCP 3.
Expected Result: • OK – The fuses are not open. Proceed to test step
9
When the resistance is measured between the wire
connected to terminal “11” of the 2301A governor to • NOT OK – One or more of the fuses are open.
the same wire number at the speed potentiometer
connector, the resistance should be 5 ohms or less. Repair: Check for a shorted component or
damaged wiring. Troubleshoot and repair the
When the resistance is measured between the wire problem. See the Generator Set Wiring Diagram
connected to terminal “12” of the 2301A governor to for your particular genset. After the problem has
the same wire number at the speed potentiometer been repaired, replace the fuses.
connector, the resistance should be 5 ohms or less.
STOP.
124 RENR7902-07
Troubleshooting Section
Test Step 9. CHECK THE GENERATOR Repair: The EMCP 3 may have failed. It is unlikely
VOLTAGE OUTPUT. that the EMCP 3 has failed. Exit this procedure and
perform this entire procedure again. If the problem
A. Open the circuit breaker or remove the load. remains, replace the EMCP 3. See Testing And
Adjusting, “ Electronic Control Module (Generator
B. Start the engine and run the genset. Set) - Replace”.
The line to line voltage should measure the rated Repair: Repair the connectors or replace the
voltage of the genset. wiring harness. Resume normal operation and
verify that the problem has been corrected.
Results:
STOP.
• OK – The voltages are correct and the problem
remains. Proceed to Test Step 10.
i02464667
D. Check for one or more damaged wires between Note: The severity of the undervoltage condition will
the EMCP 3 voltage inputs and the voltage input determine if a warning or shutdown event occurs.
fuses. See the Generator Set Wiring Diagram for
your particular genset. Conditions Which Generate This Code:
Repair: Reprogram the setpoints. Reset the All three phases of generator output voltage are
genset. Resume normal operation and verify that shown on the EMCP 3 Display Screen
the problem has been corrected.
Results:
STOP.
• OK – All three phases of generator output voltage
Test Step 3. VERIFY VOLTAGE CAN BE are shown on the EMCP 3 Display Screen
ADJUSTED
Repair: Refer to appropriate voltage regulator
Verify the generator output voltage can be adjusted service manual and perform an operational check
from the EMCP 3 Display Screen. of the voltage regulator. Resume normal operation
and verify that the problem has been corrected.
Expected Result:
STOP.
The generator output voltage can be adjusted from
the EMCP 3 Display Screen. • NOT OK – All phases of voltage are not shown on
display. Proceed to test step 6
126 RENR7902-07
Troubleshooting Section
Test Step 6. CHECK THE VOLTAGE B. Remove the EMCP 3 harness connector from the
INPUT FUSES. EMCP 3.
A. Check the three fuses on the AC voltage inputs of C. Check the EMCP 3 harness connector. See
the EMCP 3. Testing And Adjusting, “Electrical Connector -
Inspect”.
Expected Result:
D. Check for one or more damaged wires between
The fuses should not be open. the EMCP 3 voltage inputs and the voltage input
fuses. See the Generator Set Wiring Diagram for
Results: your particular genset.
• OK – The fuses are not open. Proceed to test step Expected Result:
7
The wiring and the connectors should have been
• NOT OK – One or more of the fuses are open. good.
Results:
i02464635
Repair: The wiring or the connections the are System Operation Description:
damaged. Check for damaged wiring between
the fuses and the generator output bus. See the A Service Maintenance Interval Warning event is
Generator Set Wiring Diagram for your particular detected when the number of engine hours or the
genset. Repair the wiring or replace the wiring. number of days since the previous alarm occurrence
Resume normal operation and verify that the was reset exceeds the number of hours or days
problem has been corrected. specified by the Service Interval Setpoints. Once the
event is active, it will not become inactive until a
STOP. Reset Service Interval Counter Command is received
over the data link or from the display.
Test Step 8. CHECK THE VOLTAGE
INPUT CONNECTIONS Conditions Which Generate This Code:
Test Step 2. CHECK THE SETPOINTS. Conditions Which Generate This Code:
A. View the setpoints (Service Maintenance Interval This code is generated when the measured Spare
Hours), and (Service Maintenance Interval Days) Analog Input value goes above or below the
and make note of the setpoints. See Testing and programmed threshold for a configurable duration.
Adjusting, “Electronic Control Module (Generator
Set) - Configure”. Compare the setpoints against Test Step 1. PERFORM THE INITIAL
the default setpoints of the particular generator CHECK.
set.
A. Use the Caterpillar Electronic Technician in order
Expected Result: to check for active diagnostic codes on the Engine
ECM. If any codes are present, then correct the
The setpoints are correct for your particular genset diagnostic codes first.
and application.
Expected Result:
Results:
No other diagnostic codes or indicators are active
• OK – The setpoints are correct for your particular on the engine ECM.
genset and application.
Results:
Repair: It is possible the Service Maintenance
Interval was not reset when the genset was last • OK – No other diagnostic codes or indicators are
serviced. Reset the Service Maintenance Interval active. Proceed to Test Step 2
in order to indicate when the genset will need to be
serviced again. Resume normal operation. • NOT OK – Another Engine ECM diagnostic code
is active.
STOP.
Repair: Exit this procedure. Troubleshoot the
• NOT OK – The setpoints are NOT correct for your active code or indicator. Refer to the engine
particular genset and application. Troubleshooting manual for your particular genset.
STOP.
128 RENR7902-07
Troubleshooting Section
A. View the Spare Analog Input setpoints. Make a D. Operate the genset.
note of the setpoints. See Testing and Adjusting,
“Electronic Control Module (Generator Set) - E. Check the status of the diagnostic code.
Configure”. Compare the setpoints against the
default setpoints of the particular generator set. Expected Result:
Repair: Reprogram the setpoints. Reset the • NOT OK – The code is active. The diagnostic code
genset. Resume normal operation and verify that has not been corrected. The ECM may have failed.
the problem has been corrected.
Repair: It is unlikely that the ECM has failed. Exit
STOP. this procedure and perform this procedure again.
If the cause of the failure is not found, replace
Test Step 3. CHECK THE ANALOG INPUT the ECM. See Testing and Adjusting, “Electronic
DEVICE WIRING Control Module (Generator Set) - Replace”.
If the battery voltage drops below the Low Battery Expected Result:
Voltage Warning Threshold setpoint value, the low
battery voltage event timer will begin timing. When The setpoints are correct.
the low battery voltage event timer expires, the Low
Battery Voltage event is made active (if the battery Results:
voltage has been below the event threshold level
continuously while timing). If the battery voltage rises • OK – The setpoints are correct for your particular
above the Low Battery Voltage Event Threshold, the genset. Proceed to test step 3
Low Battery Voltage event will be made inactive and
the timer will be reset. • NOT OK – The setpoints are NOT correct.
If a battery undervoltage condition is detected, “LOW Repair: Reprogram the setpoints. Reset the
BATTERY CHARGING SYS VOLT WARN” or “LOW genset. Resume normal operation and verify that
BATTERY VOLTAGE WARNING” will be displayed the problem has been corrected.
on the EMCP 3 in order to inform the operator of an
undervoltage condition. STOP.
Note: The severity of the battery over/under voltage Test Step 3. COMPARE ACTUAL
condition will determine if a warning or shutdown BATTERY VOLTAGE TO THE VOLTAGE
event occurs. DISPLAYED ON THE EMCP 3 DISPLAY
Conditions Which Generate This Code: A. Shut down the engine.
This code is generated when the measured battery B. Disconnect the harness connector from the EMCP
voltage value goes above or below the programmed 3.
thresholds for a configurable duration.
C. At the harness connector, measure the battery
Test Step 1. PERFORM THE INITIAL voltage between pin number 52 and pin number
CHECK. 65.
No other diagnostic codes or indicators are active • OK – The measured battery voltage is the same
on the Engine ECM. as the battery voltage displayed on the EMCP 3
Display Screen. Proceed to test step 4
Results:
• NOT OK – The measured battery voltage is not
• OK – No other diagnostic codes or indicators are the same as the battery voltage displayed on the
active. 2 EMCP 3 Display Screen. The EMCP 3 may have
failed.
• NOT OK – Another Engine ECM diagnostic code
is active. Repair: It is unlikely that the EMCP 3 has failed.
Exit this procedure and perform this procedure
Repair: Exit this procedure. Troubleshoot the again. If the cause of the failure is not found,
active code or indicator. Refer to the engine replace the EMCP 3. See Testing and Adjusting,
Troubleshooting manual for your particular genset. “Electronic Control Module (Generator Set) -
Replace”.
STOP.
STOP.
Test Step 2. CHECK THE SETPOINTS.
A. View the Battery Voltage Monitor setpoints. Make
a note of the setpoints. See Testing and Adjusting,
“Electronic Control Module (Generator Set) -
Configure”. Compare the setpoints against the
default setpoints of the particular generator set.
130 RENR7902-07
Troubleshooting Section
Test Step 4. CHECK THE BATTERY Repair: It is unlikely that the ECM has failed. Exit
VOLTAGE WIRING BETWEEN THE EMCP this procedure and perform this procedure again.
3 AND THE BATTERY SOURCE If the cause of the failure is not found, replace
the ECM. See Testing and Adjusting, “Electronic
A. Check the battery negative (“B-”) wiring to the Control Module (Generator Set) - Replace”.
battery negative input for a short circuit or open
circuit. Check the battery positive (“B+”) wiring to STOP.
the battery positive input for a short circuit or open
circuit. Check the wires in the generator control
i02463551
panel. Check the wires in the engine harness.
Refer to the appropriate wiring diagrams for the
circuit that is being checked.
Data Link Circuit Fault
SMCS Code: 4490
Expected Result:
System Operation Description:
The wiring is correct.
This procedure checks for an open circuit or a short
Results: circuit in a Data Link. There are three data links
associated with the EMCP 3.
• OK – No problems can be found with the battery
voltage supply wiring. Proceed to test step 5 • J1939 Accessory Data Link
• NOT OK – The battery voltage supply wiring is • J1939 Primary Data Link
defective.
• Modbus RS-485 SCADA Data Link
Repair: Repair the wiring or replace the wiring.
Refer to Systems Operation, “General Information”
Proceed to test step 5 for details on each data link.
Test Step 5. CHECK IF THE DIAGNOSTIC Note: Use the wiring diagram for your particular
CODE REMAINS genset in order to troubleshoot the Data Links.
A. Inspect the harness connectors and clean the Test Step 1. Inspect the Electrical
contacts of the harness connectors. Connectors and the Wiring
B. Reconnect all harness connectors. A. Turn the keyswitch to the OFF position.
C. Reset the genset. B. Thoroughly inspect the EMCP 3 connector, the
service tool connector, and all other connectors in
D. Operate the genset. the circuit for the data link.
E. Check the status of the diagnostic code. Reference: Refer to Troubleshooting, “Electrical
Connectors - Inspect” for details.
Expected Result:
Expected Result:
The diagnostic code is not active.
All connectors, pins, and sockets are completely
Results: inserted and coupled. The harness and wiring are
free of corrosion, of abrasion, and of pinch points.
• OK – The diagnostic code is not active. The
diagnostic code does not exist at this time. The Results:
initial diagnostic code was probably caused by a
poor connection or a short at one of the connectors
• OK – In order to troubleshoot the Modbus RS-485
that was disconnected and reconnected. Resume SCADA Data Link, proceed to Test Step 2
normal operation. STOP.
• OK – In order to troubleshoot the J1939 Primary
• NOT OK – The code is active. The diagnostic code or the J1939 Accessory Data Link, proceed to Test
has not been corrected. The ECM may have failed. Step 4
• Not OK
RENR7902-07 131
Troubleshooting Section
Repair: Repair the wiring or replace the wiring. Repair: Repair the wiring or replace the wiring.
Test Step 2. Check for Shorts in the Test Step 4. Check for Shorts in the J1939
Modbus RS-485 SCADA Data Link Data Link Harness
Harness
A. Disconnect all connectors from the suspected
A. Disconnect all connectors from the suspected data link.
data link.
B. Measure the resistance between (data link +) and
B. Measure the resistance between (data link +) and data link −).
data link −).
Expected Result:
C. Measure the resistance between ( data link +) and
chassis ground. The resistance is approximately 60 Ohms.
Repair: Repair the wiring or replace the wiring. Test Step 5. CHECK IF THE DIAGNOSTIC
CODE REMAINS
Proceed to Test Step 5
A. Inspect the Data Link harness connectors and
Test Step 3. Check the Resistance clean the contacts of the harness connectors.
through the Modbus RS-485 SCADA Data
Link Harness B. Reconnect all Data Link harness connectors.
The resistance is less than 10 Ohms. • OK – The diagnostic code is not active. The
diagnostic code does not exist at this time. The
Results: initial diagnostic code was probably caused by a
poor connection or a short at one of the connectors
• OK – The Data Link is OK. Proceed to test step 5 that was disconnected and reconnected. Resume
normal operation. STOP.
• Not OK – There is an open circuit or excessive
resistance in the harness or connectors. • NOT OK – The code is active. The diagnostic code
has not been corrected. The ECM may have failed.
132 RENR7902-07
Troubleshooting Section
Repair: It is unlikely that the ECM has failed. Exit Test Step 2. CHECK THE SETPOINTS.
this procedure and perform this procedure again.
If the cause of the failure is not found, replace A. View the Digital Input setpoints. Make a note
the ECM. See Testing and Adjusting, “Electronic of the setpoints. See Testing and Adjusting,
Control Module (Generator Set) - Replace”. “Electronic Control Module (Generator Set) -
Configure”. Compare the setpoints against the
STOP. default setpoints of the particular generator set.
Expected Result:
i02463502
System Operation Description: • OK – The setpoints are correct for your particular
genset. Proceed to Test Step 3
Digital inputs are used to bring on/off information,
such as switch closures, to the Genset Control. • NOT OK – The setpoints are NOT correct.
Depending on how the input is programmed,
the EMCP 3 associates the inputs with levels, Repair: Reprogram the setpoints. Reset the
temperatures, pressures, and status conditions . genset. Resume normal operation and verify that
Two of the Digital Inputs, which are programmed the problem has been corrected.
at the factory, are used by the EMCP 3 to control
Emergency Stop and Remote Initiate functions. The STOP.
spare digital inputs must be programmed before use.
Test Step 3. CHECK THE DIGITAL INPUT
For additional information on programming digital WIRING
inputs, see System Operation, “Digital Input
Programming” A. Check the wiring to the corresponding digital
inputs for an unwanted short circuit. The short can
Conditions Which Generate This Code: be to the battery negative (“B-”). Carefully check
ALL wires that are connected to the appropriate
This code is generated when the digital input is digital input for abrasion or worn spots in the
active. The code may indicate that a problem exists insulation that could be causing the short. Check
with the genset, or the code may indicate a status the wires in the generator control panel. Check
that does not need to be repaired. the wires in the engine harness. Refer to the
appropriate wiring diagrams for the circuit that is
Test Step 1. PERFORM THE INITIAL being checked.
CHECK.
Expected Result:
A. Use the Caterpillar Electronic Technician in
order to check for active diagnostic codes on the The wiring is correct.
Engine ECM. If any codes are present, correct the
diagnostic codes first. Results:
E. Check the status of the diagnostic code. Each resistance measurement is greater than 5000
ohms.
Expected Result:
Results:
The diagnostic code is not active.
• OK – Each resistance measurement is greater
Results: than 5000 ohms. The harness is correct. Proceed
to Test Step 2
• OK – The diagnostic code is not active. The
diagnostic code does not exist at this time. The • NOT OK – Each resistance measurement is
initial diagnostic code was probably caused by a not greater than 5000 ohms. There is a short in
poor connection or a short at one of the connectors the harness on the wire that has that has a low
that was disconnected and reconnected. Resume resistance measurement.
normal operation. STOP.
Repair: Repair the harness or replace the harness.
• NOT OK – The code is active. The diagnostic code
has not been corrected. The ECM may have failed. STOP.
Repair: It is unlikely that the ECM has failed. Exit Test Step 2. CHECK THE DEVICE
this procedure and perform this procedure again. If CONNECTED TO THE DIGITAL OUTPUT
the cause of the failure is not found, then replace CIRCUIT WIRING FOR SHORT TO THE
the ECM. See Testing and Adjusting, “Electronic +BATTERY CIRCUIT.
Control Module (Generator Set) - Replace”.
A. In order to prevent the engine from running while
STOP. performing this procedure, press the Emergency
Stop Push Button and turn the battery disconnect
switch to the ON position.
i02464600
Digital Output Circuit Fault B. At the digital output device, measure the DC
voltage on the wire connected to the failed digital
SMCS Code: 4490 output.
Digital Outputs are used to convey on/off information The voltage is at or near 0 volts DC and not shorted
from the Genset Control for energizing loads such as to battery positive (B+).
relays, solenoids, and indicator lamps. The digital
output must not be connected directly to battery Results:
positive (B+).
• OK – The digital output device is not shorted to
Conditions Which Generate This Code: battery positive (B+). Proceed to Test Step 3
This code is occurs when the digital output wiring is • NOT OK – The digital output device is shorted to
shorted to battery positive (B+). battery positive (B+)
Test Step 1. CHECK FOR A SHORTED Repair: Repair the digital output device or replace
HARNESS the digital output device.
E. Check the status of the diagnostic code. Refer to the engine Troubleshooting manual to
for more information on engine over/under speed
Expected Result: conditions for your particular genset.
Results:
The sensor creates a sine wave signal. The signal Test Step 2. CHECK THE SETPOINTS.
is created from passing ring gear teeth. The rate of
the signal is one pulse per tooth. The sensor sends A. View the Engine Speed Monitor Setpoints. Make
the sine wave signal to the EMCP 3. The frequency a note of all the setpoints. See Testing and
of the signal is directly proportional to the speed of Adjusting, “Electronic Control Module (Generator
the engine. Set) - Configure”. Compare the setpoints against
the default setpoints of the particular generator
Conditions Which Generate This Code: set.
B. Disconnect the harness connector from the EMCP • NOT OK – Replace the sensor.
3.
Repair: Refer to Testing And Adjusting, “Speed
C. At the EMCP 3 harness connector, measure the Sensor (Engine) - Adjust”.
resistance from contact “66” to contact “67”.
STOP.
Expected Result:
Test Step 6. CHECK THE HARNESS FOR
The resistance should be from 100 to 350 ohms. AN OPEN OR A SHORT.
Results: A. Press the Stop key on the EMCP 3 control.
• OK – There is probably an intermittent problem. B. Disconnect the sensor from the engine harness.
Proceed to Test Step 4. The sensor remains fastened to the engine.
• NOT OK – The harness wiring or the speed sensor C. Disconnect the harness connector from the EMCP
has failed. Proceed to Test Step 4. 3.
Test Step 4. CHECK FOR AN D. Check for an open circuit. Check the resistance
INTERMITTENT FAULT. from contact “1” of the sensor harness connector
to contact “66” of the EMCP 3 harness connector.
A. Press the Stop key on the EMCP 3 control. The resistance should be 5 ohms or less.
B. Check the EMCP 3 display for a speed sensor E. Check for an open circuit. Check the resistance
diagnostic code. from contact “2” of the sensor harness connector
to contact “67” of the EMCP 3 harness connector.
Expected Result: The resistance should be 5 ohms or less.
A speed sensor diagnostic code should not appear F. Check for a short circuit. Check the resistance
on the upper display. from contact “66” to contact “67” of the EMCP
3 harness connector. The resistance should be
Results: greater than 5000 ohms.
Results: Results:
• OK – The harness functions properly. Proceed to • OK – No damage is present. Reinstall the engine
Test Step 7. speed sensor. Adjust the sensor.
• NOT OK – The circuit with the incorrect resistance Repair: For more information, refer to Testing And
measurement has failed. Replace the failed Adjusting, “Speed Sensor (Engine) - Adjust”.
harness from the sensor to the EMCP 3 connector
or repair the failed harness from the sensor to the Proceed to Test Step 9.
EMCP 3 connector. STOP.
• NOT OK – Damage is present. Replace the engine
Test Step 7. CHECK THE SHIELD AND speed sensor.
THE CONNECTORS.
Repair: Refer to Testing And Adjusting, “Speed
A. Press the Stop key on the EMCP 3 control. Sensor (Engine) - Adjust”.
F. Check the connection between the sensor and the A speed sensor diagnostic code should still be active.
mating harness connector. Refer to Testing and
Adjusting, “Electrical Connector - Inspect”. Results:
B. Use a multimeter and 7x-1710 Multimeter Test Step 1. TALK TO THE OPERATOR
Probes in order to measure the AC signal voltage.
Measure the AC signal voltage between contact A. Determine the conditions that caused the
“66” and contact “67” of the EMCP 3 connector. unexpected shutdown.
C. Start the engine and run the engine at the rated Expected Result:
speed.
A unexpected shutdown was caused by an
D. Measure the AC signal voltage of the engine occurrence known to the operator and the operator
speed sensor. would like to put the genset back into service.
The voltage should be equal to 2 VAC or greater. • OK – The operator can determine the cause for
the “UNEXPECTED ENGINE SHUTDOWN”, the
Results: condition has been repaired and the operator
wants to put the genset back into service.
• OK – The voltage is equal to 2 VAC or greater.
The speed sensor circuit is correct. STOP. Repair: Reset the genset. Resume normal
operation and verify that the problem has been
• NOT OK – The voltage is not equal to 2 VAC or corrected.
greater. The most likely cause is improper air gap
of the pickup. STOP.
Repair: For more information, refer to Testing And • NOT OK – The “UNEXPECTED ENGINE
Adjusting, “Speed Sensor (Engine) - Adjust”. SHUTDOWN” was not caused by a occurrence
known to the operator. Proceed to Test Step 2
STOP.
Test Step 2. CHECK FOR OTHER
DIAGNOSTIC CODES.
i02464587
Unexpected Engine Shutdown A. Check for active diagnostic codes on the engine
ECM and the EMCP 3. If any codes are present,
SMCS Code: 4490 correct the diagnostic codes first.
While the engine is running, if engine speed suddenly No other diagnostic codes or indicators are active.
becomes zero and the Auto Start/Stop function block
has not initiated a shutdown, an “UNEXPECTED Results:
ENGINE SHUTDOWN” event will be activated.
• OK – No other diagnostic codes or indicators are
The EMCP 3 performs the following using an active.
independent engine speed sensor that is dedicated
to EMCP 3 use only Repair: Refer to the engine Troubleshooting
manual for more information on engine unexpected
engine shutdowns for your particular genset.
• Determines the engine speed, in rpm, from the
Magnetic Pickup (Engine Speed Sensor) input pins
STOP.
• Detects diagnostics on the sensor
• NOT OK – Another diagnostic code is active or an
indicator is active.
• Annunciates an engine over/under speed condition
Conditions Which Generate This Code: Repair: Exit this procedure. Troubleshoot the
active code or indicator. Resume normal operation
While the engine is running, if engine speed suddenly and verify that the problem has been corrected.
becomes zero and the Auto Start/Stop function block
has not initiated a shutdown, an “UNEXPECTED STOP.
ENGINE SHUTDOWN” event will be activated.
138 RENR7902-07
Testing and Adjusting Section
Testing and Adjusting • Moisture can enter the connector through the
wire insulation.
Section
5. Check for dirty contacts or corroded contacts.
Electrical Connector - Inspect • Check each contact of the connector for a snug
fit by using a new pin and socket. The new
SMCS Code: 7553-040 contact should stay connected if the connector
is held with the contacts that are facing down.
Intermittent electrical problems are often caused by
poor connections. Use the following checks as a i02985222
reference for inspecting connectors.
Wiring Harness (Open Circuit)
1. Check the connection of the connectors.
- Test
• Ensure that the locking rings are properly SMCS Code: 1408-081
locked.
An open is a failure of an electrical circuit that results
• Ensure that locking clips are used on Sure Seal in no flow of electrical current. An open circuit is
connectors.
usually caused by failed electrical wires or a poor
connection of electrical connectors. If an electrical
• Ensure that the center of the connector is tight. wire or a connection is broken, then the flow of
electrical current through the circuit is interrupted. A
• Ensure that the connector pins and sockets normally closed circuit will have less than 5 ohms of
align properly.
resistance. The following procedure explains the test
for an open circuit:
2. Check the wires at the connector.
Reference: For a complete electrical schematic,
• Ensure that the wires are straight as they enter refer to Electrical System Schematic for the genset
the back of the connector.
that is being serviced.
• Ensure that each wire is properly crimped into TEST FOR AN OPEN CIRCUIT.
the proper connector contact.
1. Identify the connectors and the wire numbers of
• Ensure that each connector contact is properly the suspect circuits. Use the Electrical System
locked into the connector contact. When the
Schematic of the genset to identify the circuits.
connector contact is locked properly, the contact
(wire) cannot be pulled out of the connector
2. Turn the disconnect switch to the OFF position.
body without excessive force.
3. Disconnect the components and the ECM from
3. Check each wire for nicks or signs of abrasion
the wiring harness.
in the insulation.
4. At one of the disconnected harness connections,
4. Check for moisture at the connector.
place a jumper wire from the contact of the
suspect wire to frame ground.
• Check for damaged connector seals or lost
connector seals.
5. At the other connector of the genset harness, use
the multimeter probes to measure the resistance
• Check for missing or loose wire hole plugs. from the contact of the suspect wire to frame
ground.
• Check for wires that do not enter the connector
properly.
Expected Result: The resistance is less than 5
ohms.
• If the wires enter the connector at an angle,
there may not be a good seal between the
OK – The resistance is less than 5 ohms. The
connector and the wire insulation.
harness circuit is correct.
RENR7902-07 139
Testing and Adjusting Section
Repair: Repair the genset harness or replace the Repair: Repair the genset harness or replace the
genset harness. genset harness.
Stop. Stop.
i02464705 i02985320
Stop.
140 RENR7902-07
Testing and Adjusting Section
g01512173
Illustration 76
Three Phase Four Wire (Series or Parallel) Wye (Star)
g01512193
Illustration 77
Three Phase Four Wire Delta
RENR7902-07 141
Testing and Adjusting Section
g01512213
Illustration 78
Three Phase Three Wire Delta
g01512215
Illustration 79
Single Phase Three Wire (Double Delta)
142 RENR7902-07
Testing and Adjusting Section
g01512236
Illustration 80
Single Phase Two Wire (Double Delta)
Transformer Connections
In order to monitor the generator output voltages
greater than 600 Volts, potential transformers (PTs)
must be used.
g01228369
Illustration 81
Wye configuration of external potential transformers on the 4-wire Wye Generator
This configuration allows the accurate measurement of all power parameters by the EMCP 3 including when the loads are unbalanced and
neutral current is present. All power parameters are shown on the display of the EMCP 3. The EMCP 3 configuration parameter“ Generator
Connection Configuration” should be set to WYE (or STAR).
g01228370
Illustration 82
Open Delta Configuration of external potential transformers on the 3-wire Delta Generator
This configuration allows the accurate measurement of power parameters by the EMCP 3 including when the loads are unbalanced and
circulating current is present. The real power phase A, B and C cannot be determined. The power factor phase A, B and C cannot be
determined. The phases are not shown on the EMCP 3 display. The EMCP 3 configuration parameter “Generator Connection Configuration”
should be set to DELTA (3 WIRE).
g01228371
Illustration 83
Open Delta configuration of external potential transformers on the 4-wire Wye Generator
This configuration results in less accurate measurement of all power parameters by the “EMCP 3” when the loads are unbalanced and neutral
current is present. Real power phase A, B, C and power factor phase A, B, C cannot be determined and are not shown on the “EMCP 3”
display. The EMCP 3 configuration parameter “Generator Connection Configuration” should be set to DELTA (3 WIRE).
144 RENR7902-07
Testing and Adjusting Section
Table 34
Transformer Connections
Parameter Star 3-WIRE DELTA 4-WIRE DELTA 2-WIRE 1-PHASE 3-WIRE 1-PHASE
Gen Freq OK OK OK OK OK
VL-L AVG OK OK OK OK OK
VA-B OK OK OK OK OK
VB-C OK OK OK Invalid Invalid
VC-A OK OK OK Invalid Invalid
VL-N AVG OK Invalid OK Invalid OK
VA OK Invalid OK Invalid OK
VB OK Invalid OK Invalid OK
VC OK Invalid OK Invalid Invalid
IAVG OK OK OK OK OK
IA OK OK OK OK OK
IB OK OK OK OK OK
IC OK OK OK Invalid Invalid
SMCS Code: 1912-587 If there is not a device that is supplying the PWM
signal and the engine speed bias is controlled
The following procedure describes the adjustments from the EMCP 3, then go to Step 3.
that are required if an “Engine Speed Timing
Calibration” is performed. After this procedure has 3. Use the EMCP 3 control screen in order to go to
been completed, the engine can be started and the idle. Refer to the “Idle Speed and Rated Speed”
engine can be run at rated speed. information that is in the “Voltage and Frequency
Adjustment” section of this publication. Go to Step
Note: This procedure does not include the 5.
instructions for performing the actual calibration.
4. Set the “Engine Start Fault Protection Activation
Note: Before changing any value per this procedure, Delay Time” setpoint in the EMCP 3 to 90 seconds.
record the original value. Use the Cat ET in order to set the “Secondary
Desired Speed Input Configuration” set point in
1. Stop the engine. the engine ECM to “DISABLED”.
8. Use Cat ET in order to return the set points that Engine Setpoint Verification -
were modified in Step 2 through Step 4 to the Test
original values. Navigate to the “Control” screen,
then go to the “Rated” screen. SMCS Code: 4490-081
9. Reconnect any wires that were disconnected in The Engine setpoint verification procedure verifies
Step 2. that the EMCP 3 operates correctly when one of the
following faults occurs:
i02464712
Engine overspeed – Causes the EMCP 3 to shut
Speed Sensor (Engine) - Adjust the engine down
1. Remove the speed sensor (1) from the flywheel During the procedure, each configuration setpoint
housing. Remove all debris from the tip of the that is to be adjusted should be recorded, and then
speed sensor. Align a ring gear tooth directly in returned to the original setting after the setpoint has
the center of the threaded sensor opening. been verified.
2. By hand, screw the speed sensor (1) into the hole Note: Prior to performing this procedure, a service
until the end of the sensor contacts the gear tooth. replacement file can be saved using the Caterpillar
service tool. The replacement file is used in order to
3. Turn the sensor (1) in the counterclockwise record the configuration to allow reprogramming the
direction through 270 degrees (three-fourths turn). control with the original setpoints after the procedure
has been completed.
4. Tighten locknut (2) to 25 ± 5 N·m (18 ± 4 lb ft).
Engine Protection Events Configuration
Note: Do not allow speed sensor (1) to turn as
locknut (2) is tightened.
• High Engine Coolant Temperature Shutdown
Event Response Configuration (Hard Shutdown
Enable/Disable)
146 RENR7902-07
Testing and Adjusting Section
• Low Engine Oil Pressure Shutdown Event Reference: For details on changing the EMCP 3
Response Configuration (Hard Shutdown security level, see Systems Operation, “Password
Enable/Disable) Entry”.
Engine Speed Monitor 1. Start the engine and run the engine at its rated
speed.
Table 35
2. Adjust the setpoint value to a value that is below
Engine Over Speed Shutdown Threshold
(adjust value)
the speed that the engine is running, and then
press the ENTER key. An Engine Overspeed
Adjustment 400 to 4330 RPM in 1 RPM increments Shutdown event will immediately occur.
Range
Default 2120 RPM (or 1.18 times the rated speed) 3. View the event in the Genset Control event log.
value
Reference: Systems Operation, “Event Viewing”
g01211086
Illustration 85
(1) Display Screen (7) Auto key (13) Scroll Up key
(2) Yellow Warning Lamp (8) Run key (14) Scroll Left key
(3) Red Shutdown Lamp (9) Escape key (15) Engine Overview key
(4) Alarm Acknowledge/Silence key (10) Enter key (16) AC Overview key
(5) Lamp Test key (11) Scroll Right key
(6) Stop key (12) Scroll Down key
(12) Scroll Down – Move down through the main The keypad is also used in order to change the
menu or navigate within a list in order to highlight one setpoints. Press the Enter key in order to change a
of the items. Also used to decrement digits (0-9). setpoint. Press the Scroll Up key or the Scroll Down
key in order to increase or decrease the value. Press
(13) Scroll Up – Move up through the main menu or the Scroll Left key or the Scroll Right key in order
navigate within a list in order to highlight one of the to change the digit that is to be adjusted.
items. Also used to increment digits (0-9)
Note: The EMCP 3 panel will power up to the MAIN • Generator AC Power Monitor
MENU screen. If the EMCP 3 panel is already
powered up, press the Escape key in order to return • Generator Over Current
to the main menu. Each press of the Escape key
moves you back one level in the menu structure, • Generator Over/Under Frequency
Within each setpoint category there are one or more • Generator Reverse Power
function blocks. Each of those function blocks may
contain one or more setpoints. Each of these setpoint Input/Output (I/O)
categories and its corresponding function blocks are
shown below. • Digital Inputs
Events
• Diagnostics Conguration
• Engine protection Events Conguration
• Generator Protection Events Conguration
• Other System Events Conguration
• Custom Events
• Event Output Function
• Event System
Generator Monitor/Protect
• Enhanced Generator Monitor
• Generator AC Monitor
EMCP 3.1 Generator Set Control Menu Structure
sample screen
SETPOINTS
CONTROL CONTROL
ENGINE MON/PROTECT AUTOMATIC START/STOP
GOV DESIRED ENG SPD *1
EVENTS
GEN MON/PROTECT
I/O
OTHER
ENG MONITOR/PROTECT
BATTERY VOLT MON
ENG COOL TEMP MON
ENG OIL PRES MON *1
ENG SPEED MON
Illustration 86
ENG PROTECT CONFIG TEMPERATURES *1
GEN PROTECT CONFIG LEVELS
OTHER SYSTEM CONFIG OTHERS
GEN MON/PROTECT
GEN AC MONITOR *1
RELAY OUTPUTS
OUTPUT #1
OUTPUT #2
OUTPUT #3
OUTPUT #4 *1
OUTPUT #5
OUTPUT #6
sample screen
OTHER DIGITAL SELECTORS
DIGITAL SELECTORS DIGITAL SELECTORS #1
Digital I/P - 2 - 4 - -
REDUCED PWR MODE DIGITAL SELECTORS #2
Relay O/P 1 - - - 5 6
DIGITAL SELECTORS #3
DIGITAL SELECTORS #4 *1
*1
PREFERENCES
CONTRAST
BACKLIGHT
PRESSURE *1
TEMPERATURE
LANGUAGE
g01231819
RENR7902-07
RENR7902-07 151
Testing and Adjusting Section
EMCP 3.2 Generator Set Control Menu Structure
sample screen
SETPOINTS
CONTROL
CONTROL
AUTOMATIC START/STOP
ENGINE MON/PROTECT GOV DESIRED ENG SPD *1
EVENTS
GEN MON/PROTECT
I/O
NETWORK ENG MONITOR/PROTECT
BATTERY VOLT MON
OTHER
ENG COOL TEMP MON
CRANK/START CTRS *1
ENG OIL PRES MON
ENG SPEED MON
SERVICE MAINT INTERVAL
Illustration 87
*1
ENG PROTECT CONFIG
PRESSURES
TEMPERATURES *1
LEVELS
OTHERS
GEN MON/PROTECT
GEN AC MONITOR
GEN AC PWR MONITOR *1
GEN OVER CURRENT
GEN OVER/UNDER FREQ
GEN OVER/UNDER VOLT
DIGITAL OUTPUTS
NETWORK *1
DATALINK- SCADA OUTPUT #1
RELAY OUTPUTS
OUTPUT #1
OUTPUT #2
sample screen OUTPUT #3
OUTPUT #4 *1
Digital I/P - 2 - 4 - - - 8 OUTPUT #5
Relay O/P 1 - - - 5 6 7- OUTPUT #6
OUTPUT #7
OUTPUT #8
sample screen
CONTROL OR AVG: 481 V L-L 324A Active, Inactive. Only SHUTDOWN events can be reset; some events can
60.2Hz 0.82 LAGGING be set as a SHUTDOWN. To reset an event, the control must be in STOP.
TOTAL kW 216 48%
PREFERENCES
All other events will become INACTIVE once the condition goes away.
*3. To RESET : press the ENTER key to get to the details of the event, and
CONFIGURE CURRENT LEVEL = 2 then press the ENTER key again.
SECURITY DROP TO MIN LEVEL *4. To get back to the MAIN MENU at any time, press or and
SETPOINTS ENTER LEVEL 1 OR 2
ENTER LEVEL 3
TIME DATE CHANGE LVL 1 PSWD 5. When unsure about your location on the screen, press the ESCAPE key and
ENG OPERATE HRS CHANGE LVL 2 PSWD
CHANGE SCADA PSWD then refer to this menu map to navigate to the correct location.
SETPOINTS CONTROL
CONTROL AUTOMATIC START/STOP
ENG MONITOR/PROTECT AVR DESIRED VOLTAGE
EVENTS GOV DESIRED ENG SPD
*1
GEN MONITOR/PROTECT
I/O
NETWORK ENG MONITOR/PROTECT
OTHER BATTERY VOLT MONITOR
CRANK/START CNTRS
ENG COOLANT TEMP MON *1
ENG OIL PRES MONITOR
ENG SPEED MON
ENHANCED ENG MONITOR
SERVICE MAINT INTERVAL
Illustration 88
OTHER SYSTEM CONFIG OTHERS
RELAY OUTPUTS
OUTPUT #1
OUTPUT #2
OUTPUT #3
OUTPUT #4 *1
OUTPUT #5
OUTPUT #6
OUTPUT #7
OUTPUT #8
Programming the Display f. Press the Scroll Down key in order to highlight
TEMPERATURE and then press the Enter key
Preferences in order to select the temperature function. The
available options for temperature measurement
The preferences affect the way data is viewed on the
are “°C” or “°F”. The display will list both
display screen. The configuration may need to be
options, with the current option highlighted.
changed in order to meet local requirements.
g. Adjust the temperature to the desired
In order to program the display preferences, perform
measurement scale using the Scroll Right
the following menu options.
key or the Scroll Left key , and then press the
Enter key in order to save the temperature
1. Press the Escape key as many times as
measurement unit.
necessary in order to go back to the “MAIN
MENU” display.
h. Press the Scroll Down key in order to highlight
VOLUME and then press the Enter key in order
2. From the “MAIN MENU”, press the Scroll Down
to select the volume function. The available
key or the Scroll Up key in order to highlight
options for volume measurement are “LITERS”,
the “PREFERENCES” option. The following
“US GAL”, or “IMP GAL”. The display will
parameters can be changed or viewed:
list all three options, with the current option
highlighted.
• CONTRAST
i. Highlight the desired volume measurement unit
• PRESSURE using the Scroll Right key or the Scroll Left
key , and then press the Enter key in order to
• TEMPERATURE save the volume measurement unit.
• VOLUME j. Press the Scroll Down key in order to highlight
LANGUAGE and then press the Enter key
• LANGUAGE in order to select the language function.
Language does not display a value to the
a. Press the Enter key in order to select
right. The display will show one or two options.
PREFERENCES. CONTRAST will be
TECHNICIAN ENGLISH will always be shown
highlighted.
and, if another language is available on the
flash file, that language will also be shown as
b. Press the Enter key in order to select the
an options.
contrast level. The contrast can be adjusted
between 1 and 100, with 1 being the least
k. Highlight the desired language that is to be
contrast and 100 being the greatest contrast.
used for display on the EMCP 3 using the
The display will show a status bar and a
Scroll Right key or the Scroll Left key , and
number representing the current contrast level.
then press the Enter key (10) in order to save
the desired language selection
c. Use the Scroll Right key or the Scroll Left key
in order to adjust the contrast to the desired
l. Press the Escape key as required in order to
level, and then press the Enter key in order to
step back up to the MAIN MENU.
save the new contrast setting.
d. Press the Scroll Down key in order to highlight Programming the Setpoints
PRESSURE, and then press the Enter key
in order to select the pressure function. The The engine/generator setpoints affect the proper
available options for pressure measurement operation and serviceability of the engine, and the
are “kPa”, “PSI”, and “BAR”. The display will accuracy of information shown on the display screen.
list all three options, with the current option The EMCP 3 setpoints are programmed at the
highlighted. factory.
e. Adjust the pressure to the desired The setpoints may require changing when the EMCP
measurement unit using the Scroll Right 3 is moved from one engine to another engine.
key or the Scroll Left key , and then press The setpoints may also require changing in order
the Enter key in order to save the pressure to satisfy the site requirements. The setpoints that
measurement unit. are stored in the EMCP 3 must match the specified
setpoints of the particular generator set.
156 RENR7902-07
Testing and Adjusting Section
See the Setpoint tables following these procedures 13. Press the Escape key twice in order to back up to
for a complete list of all the setpoint blocks. All of the the SETPOINTS menu.
setpoints listed in the tables should be verified and
reprogrammed if required. 14. Press the Scroll Down key in order to scroll
through the setpoint options until ENGINE
The first setpoint block to program is the Automatic MONITOR/PROTECT is highlighted.
Start/Stop Block. The Automatic Start/Stop Block is
part of the Control Category. In order program the 15. Press the Enter key in order to select the ENGINE
Automatic Start/Stop Setpoints, perform the following: MONITOR/PROTECT menu and then program all
of the function blocks in this menu.
1. Press the Escape key as required in order to step
back to the MAIN MENU. 16. Continue to program the remaining setpoints until
each setpoint in every setpoint category has been
2. From the MAIN MENU, press the Scroll Down checked and programmed as required.
key until CONFIGURE is highlighted and then
press the Enter key in order to select the menu.
Setpoint Tables
3. Press the Scroll Down key until SETPOINTS is
All of the available setpoints on the EMCP 3 are
highlighted, and then press the Enter key in order
listed in the following tables. Refer to these tables
to select the menu. while programming the setpoints.
4. Press the Scroll Down key in order to scroll
through the setpoint options until CONTROL is Control
highlighted, and then press the Enter key in order
to select the menu. The AUTOMATIC START / Automatic Start/Stop
STOP menu is highlighted.
The Automatic Start/Stop block receives starting
5. Press the Enter Key in order to select the and stopping requests from various sources (local,
AUTOMATIC START / STOP menu and then use remote, internal), arbitrates between them and then
the Scroll Down key and the Scroll Up key in cranks or shuts down the engine in an orderly fashion.
order to highlight the next setpoint that is to be
programmed.
Table 38
Setpoints - Automatic Start/Stop(1)
Setpoint Min Max Factory
Units Description
Name Value Value Default
Fault protection time delay prevents shut
Engine start fault protection sec
0 300 30 down during start up from low oil pressure
activation delay time
etc.
Table 39
Maximum Generator Output Voltage Bias Percent 5. Press the Scroll Down key or the Scroll Up key
in order to decrement or increment the highlighted
The following settings will only apply if there is a digit to the desired value and then press the
CDVR installed on the generator. Scroll Right key or the Scroll Left key in order to
highlight the next character that is to be entered.
Note: It is possible to set the “MAXIMUM GEN
OUTPUT VOLTAGE BIAS PERCENT” from 0 to 6. Continue this process until the desired current
100% but the CDVR will only allow the voltage to voltage bias percent has been entered and then
change by a maximum of 15%. press the Enter key in order to save the new
value.
1. From the MAIN MENU, press the Scroll Down
key or the Scroll Up key in order to highlight the Generator Desired Engine Speed Request
CONFIGURE menu, and then press the Enter
key in order to select the menu. “SECURITY” will The Generator Desired Engine Speed Request block
be highlighted. generates a data link request over the J1939 data
link in order to request a desired generator frequency
2. Press the Scroll Down key in order to highlight from a generator.
the SETPOINTS menu, and then press the Enter
key in order to select the menu. AUTOMATIC
START/STOP will be highlighted.
Table 40
Setpoints - Generator Desired Engine Speed Request(27)
Setpoint Min Max Factory
Units Description
Name Value Value Default
The Maximum Engine Speed Range is the maximum
Maximum Engine rpm value above and below the Nominal Engine Speed
0 2000 100
Speed Range that the EMCP 3 will send a request for when
adjusting the speed from the control screen
Generator Nominal This value is set to match the generator rated
40 500 Hz 50
Output Frequency frequency
(27) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular generator set.
Engine Monitor/Protect
Battery Voltage Monitor
Table 41
Table 42
Setpoints - Crank Attempt / Successful Start Counter(31)
Setpoint Min Max Factory
Units Description
Name Value Value Default
Customer Security Password
Password level required in order to reset
Level to Reset Crank/Start 0 4 n/a 3
the Crank/Start Counters
Counters
(31) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular generator set.
Table 43
Table 44
Setpoints - Engine Oil Pressure Monitor(11)
Setpoint Min Factory
Max Value Units Description
Name Value Default
Select “Sensor” or “Data Link”. Set
Engine Oil Pressure Sensor
Setpoint Value List 0 to Sensor for MUI Engines or set
Configuration
to Data Link for EUI engines.
Low Engine Oil Pressure 34 kPa 690 kPa 160 kPa
kPa
Warning Event Threshold (5 psi) (100 psi) (23 psi)
Low Idle Low Engine Oil Pressure 34 kPa 690 kPa 160 kPa
kPa
Warning Event Threshold (5 psi) (100 psi) (23 psi)
Low Engine Oil Pressure
Warning Event Notification Delay 0 30 sec. 10
Time
Low Engine Oil Pressure 34 kPa 690 kPa 34 kPa
kPa
Shutdown Event Threshold (5 psi) (100 psi) (5 psi)
Low Idle Low Engine Oil Pressure 34 kPa 690 kPa 160 kPa
kPa
Shutdown Event Threshold (5 psi) (100 psi) (23 psi)
Table 45
Setpoints - Engine Speed Monitor(12)
Setpoint Min
Max Value Units Factory Default Description
Name Value
Flywheel Teeth 95 350 N/A 95
Table 46
Setpoints - Enhanced Engine Monitor (31)
Table 47
EVENTS
Table 48
Description of Event Response Selections
Active Only Only displays event in the event log (no history on the event)
Warning Event logged, amber warning status LED
Audible Alert Activates relay output configured as “horn control”
Soft Shutdown Shutdown event allows cooldown cycle
Hard Shutdown Shutdown event skips cooldown cycle for fast engine shutdown
Breaker 1 Trip Activates relay output configured as “breaker 1 trip”
Breaker 2 Trip Activates relay output configured as “breaker 2 trip”
FTP Suppress the event until the engine is running and the fault protection timer has expired
Diagnostics Configuration
Table 49
“PRESSURE” Setpoints - Diagnostics Configuration(15)
Setpoint Audible Soft Hard Loss of Breaker Breaker Active
Warning FPT
Name Alert Shutdown Shutdown Utility Trip #1 Trip #2 Only
Air Filter
Differential
Pressure Sensor
X X X X X X
Diagnostic
Response
Configuration
Engine Oil
Pressure Sensor
Diagnostic X X X X X X
Response
Configuration
Fire Extinguisher
Pressure Sensor
Diagnostic X X X X X X
Response
Configuration
Fuel Filter
Differential
Pressure Sensor
X X X X X X
Diagnostic
Response
Configuration
Engine Oil
Filter Differential
Pressure Sensor
X X X X X X
Diagnostic
Response
Configuration
Starting Air
Pressure Sensor
Diagnostic X X X X X X
Response
Configuration
(15)Each setpoint in the Diagnostics Configuration block is used in order to program a system response to the associated Suspect Parameter
Number/Failure Mode Identifier (SPN/FMI) for any internal source.
Table 50
“TEMPERATURE” Setpoints - Diagnostics Configuration(15)
Loss
Setpoint Audible Soft Hard Breaker Breaker Active
Warning of FPT
Name Alert Shutdown Shutdown Trip #1 Trip #2 Only
Utility
Ambient Air
Temperature
Sensor
X X X X X X
Diagnostic
Response
Configuration
Engine
Coolant
Temperature
Sensor X X X X X X
Diagnostic
Response
Configuration
Engine Oil
Temperature
Sensor
X X X X X X
Diagnostic
Response
Configuration
Exhaust
Temperature
Sensor
X X X X X X
Diagnostic
Response
Configuration
Right Exhaust
Temperature
Sensor
X X X X X X
Diagnostic
Response
Configuration
Left Exhaust
Temperature
Sensor
X X X X X X
Diagnostic
Response
Configuration
Generator
Bearing #1
Temperature
Sensor X X X X X X
Diagnostic
Response
Configuration
(15)Each setpoint in the Diagnostics Configuration block is used in order to program a system response to the associated Suspect Parameter
Number/Failure Mode Identifier (SPN/FMI) for any internal source.
Table 51
“LEVEL” Setpoints - Diagnostics Configuration(15)
Setpoint Audible Soft Hard Loss of Breaker Breaker Active
Warning FPT
Name Alert Shutdown Shutdown Utility Trip #1 Trip #2 Only
Engine
Coolant
Level Sensor
X X X X X X
Diagnostic
Response
Configuration
Engine Oil
Level Sensor
Diagnostic X X X X X X
Response
Configuration
Fuel Level
Sensor
Diagnostic X X X X X X
Response
Configuration
External
Tank Fuel
Level Sensor
X X X X X X
Diagnostic
Response
Configuration
(15)Each setpoint in the Diagnostics Configuration block is used in order to program a system response to the associated Suspect Parameter
Number/Failure Mode Identifier (SPN/FMI) for any internal source.
Table 52
“OTHER” Setpoints - Diagnostics Configuration(15)
Setpoint Audible Soft Hard Loss of Breaker Breaker Active
Warning FPT
Name Alert Shutdown Shutdown Utility Trip #1 Trip #2 Only
Accessory
Data Link
Diagnostic X X X X X X
Response
Configuration
Digital Output
#1 Diagnostic
X X X X X X
Response
Configuration
Digital Output
#2 Diagnostic
X X X X X X
Response
Configuration
Engine Speed
Sensor
Diagnostic X X(16) X X
Response
Configuration
Generator
Output
Sensing
System X X X X X X
Diagnostic
Response
Configuration
Primary
Data Link
Diagnostic X X X X X X
Response
Configuration
SCADA
Data Link
Diagnostic X X X X X X X
Response
Configuration
(15) Each setpoint in the Diagnostics Configuration block is used in order to program a system response to the associated Suspect Parameter
Number/Failure Mode Identifier (SPN/FMI) for any internal source.
(16) Setpoint Is not adjustable
Engine Protection Events Configuration The Engine Protection events Configuration block is
subdivided into 4 categories as follows: Pressures,
Temperatures, Levels, and Others. Each of the
Diagnostics Configuration subcategories is shown in
it's own table.
Warning and/or shutdown events should not be
disabled. If warning or shutdown events are dis- Note: Table 53 lists the available options for each
abled, the user may not be aware of conditions “PRESSURE” setpoint. The options that are available
that could cause damage to the engine, generator, for each setpoint are designated by an “X” in the
or electrical loads. If warning or shutdown events option column.
are disabled, make sure that there is another con-
trol that is set up that can diagnose the event, and
if necessary, will shut the engine down.
Table 53
“PRESSURE” Setpoints - Engine Protection Events Configuration(17)
Loss
Setpoint Audible Soft Hard Breaker Breaker Trip Active
Warning of FPT
Name Alert Shutdown Shutdown Trip #1 #2 Only
Utility
High Air Filter
Differential
Pressure
X X X X
Warning Event
Response
Configuration
High Air Filter
Differential
Pressure
Shutdown X X X X X
Event
Response
Configuration
Table 54
Table 55
Table 56
“OTHER” Setpoints - Engine Protection Events Configuration(17)
Setpoint Audible Soft Hard Loss of Breaker Breaker Active
Warning FPT
Name Alert Shutdown Shutdown Utility Trip #1 Trip #2 Only
Air Damper
Closed Event
X X X
Response
Configuration
Emergency
Stop
Shutdown
X X(16) X X
Event
Response
Configuration
Engine Failure
to Start
Shutdown
X X(16) X X
Event
Response
Configuration
Unexpected
Engine
Shutdown
X X(16) X X
Event
Response
Configuration
Engine
Over Speed
Shutdown
X X(16) X X
Event
Response
Configuration
Engine
Under Speed
Warning Event X X X X X
Response
Configuration
Engine
Under Speed
Shutdown
X X X X X X
Event
Response
Configuration
Fuel Tank
Leak Event
X X X X X X
Response
Configuration
Service
Maintenance
Interval
X X
Warning Event
Response
Configuration
(17) Each setpoint in the Engine Protection Events Configuration block is used in order to program a system response to the associated
Suspect Parameter Number/Failure Mode Identifier (SPN/FMI) for any internal source.
(16) Setpoint Is not adjustable
176 RENR7902-07
Testing and Adjusting Section
Table 57
Setpoints - Generator Protection Events Configuration(18)
Setpoint Audible Soft Hard Loss of Breaker Breaker Active
Warning FPT
Name Alert Shutdown Shutdown Utility Trip #1 Trip #2 Only
Earth Fault
Event
X X X X X X
Response
Configuration
High
Generator
Winding #1
Temperature X X X X X
Warning Event
Response
Configuration
High
Generator
Winding #1
Temperature
X X X X X X
Shutdown
Event
Response
Configuration
High
Generator
Winding #2
Temperature X X X X X
Warning Event
Response
Configuration
(continued)
RENR7902-07 177
Testing and Adjusting Section
Table 58
Setpoints - Other System Events Configuration(19)
Loss
Setpoint Audible Soft Hard Breaker Breaker Active
Warning of FPT
Name Alert Shutdown Shutdown Trip #1 Trip #2 Only
Utility
(continued)
180 RENR7902-07
Testing and Adjusting Section
Loss
Setpoint Audible Soft Hard Breaker Breaker Active
Warning of FPT
Name Alert Shutdown Shutdown Trip #1 Trip #2 Only
Utility
High
Ambient Air
Temperature
X X X X X
Warning Event
Response
Configuration
High
Ambient Air
Temperature
Shutdown X X X X X X
Event
Response
Configuration
Low
Ambient Air
Temperature
X X X X
Warning Event
Response
Configuration
Low
Ambient Air
Temperature
Shutdown X X X X X
Event
Response
Configuration
Automatic
Transfer
Switch in
Normal X X X
Position Event
Response
Configuration
Automatic
Transfer
Switch in
Emergency X X X
Position Event
Response
Configuration
Battery
Charger
Failure
X X X
Diagnostic
Response
Configuration
High Battery
Voltage
Warning Event X X X X
Response
Configuration
(continued)
RENR7902-07 181
Testing and Adjusting Section
Loss
Setpoint Audible Soft Hard Breaker Breaker Active
Warning of FPT
Name Alert Shutdown Shutdown Trip #1 Trip #2 Only
Utility
High Battery
Voltage
Shutdown
X X X X X
Event
Response
Configuration
Low Battery
Voltage
Warning Event X X X X X
Response
Configuration
Low Battery
Charging
System
Voltage X X X X X
Warning Event
Response
Configuration
Generator
Breaker
Failure to
X X X X X
Open Event
Response
Configuration
Generator
Breaker
Failure to x
X X X X
Close Event
Response
Configuration
Generator
Breaker
Open Event X X X
Response
Configuration
Generator
Breaker
Closed Event X X X
Response
Configuration
Utility Breaker
Failure to
Open Event X X X X X
Response
Configuration
Utility Breaker
Failure to
Close Event X X X X X
Response
Configuration
(continued)
182 RENR7902-07
Testing and Adjusting Section
Loss
Setpoint Audible Soft Hard Breaker Breaker Active
Warning of FPT
Name Alert Shutdown Shutdown Trip #1 Trip #2 Only
Utility
Utility Breaker
Open Event
X X X
Response
Configuration
Utility Breaker
Closed Event
X X X
Response
Configuration
Emergency
Shutdown
Override
Mode Active X(16) X
Warning Event
Response
Configuration
Engine in
Cooldown
Event X X X
Response
Configuration
Engine Speed-
Generator
Output
Frequency
X X X X
Mismatch
Warning Event
Response
Configuration
Custom Event
#1 High
Warning Event X X X X X
Response
Configuration
Custom Event
#1 High
Shutdown
X X X X X X
Event
Response
Configuration
Custom Event
#1 Low
Warning Event X X X X X
Response
Configuration
Custom Event
#1 Low
Shutdown
X X X X X X
Event
Response
Configuration
(continued)
RENR7902-07 183
Testing and Adjusting Section
Loss
Setpoint Audible Soft Hard Breaker Breaker Active
Warning of FPT
Name Alert Shutdown Shutdown Trip #1 Trip #2 Only
Utility
Custom Event
#1 Event
X X X X X X X X X
Response
Configuration
Custom Event
#2 High
Warning Event X X X X x
Response
Configuration
Custom Event
#2 High
Shutdown
X X X X X X
Event
Response
Configuration
Custom Event
#2 Low
Warning Event X X X X X
Response
Configuration
Custom Event
#2 Low
Shutdown
X X X X X X
Event
Response
Configuration
Custom Event
#2 Event
X X X X X X X X X
Response
Configuration
Custom Event
#3 High
Warning Event X X X X X
Response
Configuration
Custom Event
#3 High
Shutdown
X X X X X X
Event
Response
Configuration
Custom Event
#3 Low
Warning Event X X X X X
Response
Configuration
Custom Event
#3 Low
Shutdown
X X X X X X
Event
Response
Configuration
(continued)
184 RENR7902-07
Testing and Adjusting Section
Loss
Setpoint Audible Soft Hard Breaker Breaker Active
Warning of FPT
Name Alert Shutdown Shutdown Trip #1 Trip #2 Only
Utility
Custom Event
#3 Event
X X X X X X X X X
Response
Configuration
Custom Event
#4 High
Warning Event X X X X X
Response
Configuration
Custom Event
#4 High
Shutdown
X X X X X X
Event
Response
Configuration
Custom Event
#4 Low
Warning Event X X X X X
Response
Configuration
Custom Event
#4 Low
Shutdown
X X X X X X
Event
Response
Configuration
Custom Event
#4 Event
X X X X X X X X X
Response
Configuration
Custom Event
#5 High
Warning Event X X X X X
Response
Configuration
Custom Event
#5 High
Shutdown
X X X X X X
Event
Response
Configuration
Custom Event
#5 Low
Warning Event X X X X X
Response
Configuration
Custom Event
#5 Low
Shutdown
X X X X X X
Event
Response
Configuration
(continued)
RENR7902-07 185
Testing and Adjusting Section
Loss
Setpoint Audible Soft Hard Breaker Breaker Active
Warning of FPT
Name Alert Shutdown Shutdown Trip #1 Trip #2 Only
Utility
Custom Event
#5 Event
X X X X X X X X X
Response
Configuration
Custom Event
#6 High
Warning Event X X X X X
Response
Configuration
Custom Event
#6 High
Shutdown
X X X X X X
Event
Response
Configuration
Custom Event
#6 Low
Warning Event X X X X X
Response
Configuration
Custom Event
#6 Low
Shutdown
X X X X X X
Event
Response
Configuration
Custom Event
#6 Event
X X X X X X X X X
Response
Configuration
Custom Event
#7 High
Warning Event X X X X X
Response
Configuration
Custom Event
#7 High
Shutdown
X X X X X X
Event
Response
Configuration
Custom Event
#7 Low
Warning Event X X X X X
Response
Configuration
Custom Event
#7 Low
Shutdown
X X X X X X
Event
Response
Configuration
(continued)
186 RENR7902-07
Testing and Adjusting Section
Loss
Setpoint Audible Soft Hard Breaker Breaker Active
Warning of FPT
Name Alert Shutdown Shutdown Trip #1 Trip #2 Only
Utility
Custom Event
#7 Event
X X X X X X X X X
Response
Configuration
Custom Event
#8 High
Warning Event X X X X X
Response
Configuration
Custom Event
#8 High
Shutdown
X X X X X X
Event
Response
Configuration
Custom Event
#8 Low
Warning Event X X X X X
Response
Configuration
Custom Event
#8 Low
Shutdown
X X X X X X
Event
Response
Configuration
Custom Event
#8 Event
X X X X X X X X X
Response
Configuration
High Fire
Extinguisher
Pressure
X X X X
Warning Event
Response
Configuration
High Fire
Extinguisher
Pressure
Shutdown X X X X X
Event
Response
Configuration
Low Fire
Extinguisher
Pressure
X X X X X
Warning Event
Response
Configuration
(continued)
RENR7902-07 187
Testing and Adjusting Section
Loss
Setpoint Audible Soft Hard Breaker Breaker Active
Warning of FPT
Name Alert Shutdown Shutdown Trip #1 Trip #2 Only
Utility
Low Fire
Extinguisher
Pressure
Shutdown X X X X X X
Event
Response
Configuration
Generator
Control Not
in Automatic
X X X
Warning Event
Response
Configuration
Loss of
Utility Event
X X X
Response
Configuration
Utility to
Generator
Transfer
Failure X X X X
Warning Event
Response
Configuration
Utility to
Generator
Transfer
Failure
X X X X
Shutdown
Event
Response
Configuration
Generator to
Utility Transfer
Failure
X X X X
Warning Event
Response
Configuration
(19) Each setpoint in the “Other System Events Configuration” block is used in order to program a system response to the associated Suspect
Parameter Number/Failure Mode Identifier (SPN/FMI) for any internal source.
(16) Setpoint Is not adjustable
Table 59
Setpoints - Event Input Functions (13)
Table 60
Setpoints - Event Output Functions(14)
Setpoint Min Factory
Max Value Units Description
Name Value Default
Event Output Function #NN Trigger Settings for event output functions
N/A N/A N/A Disabled
Condition #1- #30
Event Output Function #NN Suspect Settings for event output functions
N/A N/A N/A 100
Parameter Number #1- #30
(14) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular generator set.
Event System
Table 61
Setpoints - Event System(20)
Setpoint Max Factory
Min Value Units Description
Name Value Default
Event Warning Condition Response Auto
Setpoint Value List 1
Reset Enable Status
Event Audible Alert Response Auto Reset
Setpoint Value List 1
Enable Status
Event Loss of Utility Response Auto Reset
Setpoint Value List 1
Enable Status
Event Breaker #1 Trip Response Auto Reset
Setpoint Value List 1
Enable Status
Event Breaker #2 Trip Response Auto Reset
Setpoint Value List 1
Enable Status
(20) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular generator set.
RENR7902-07 189
Testing and Adjusting Section
Generator Monitor/Protect
Enhanced Generator Monitor
Generator AC Monitor
Table 63
Setpoints - Generator AC Monitor(21)
Setpoint Min Max Factory
Units Description
Name Value Value Default
Configurations can be:
“Star/Wye”,
Generator Connection “Delta/3 Wire”
Setpoint Value List 0
Configuration “Delta/4 Wire”
“Single Phase 2 Wire”
“Single Phase 3 Wire”
Generator Potential For direct sensing, leave at default value. For an
Transformer Primary 1 50000 V 1 application requiring a potential transformer, set to
Winding Rating transformer primary winding value.
Generator Potential For direct sensing, leave at default value. For an
Transformer Secondary 1 240 V 1 application requiring a potential transformer, set to
Winding Rating transformer secondary winding value
Generator Current
Transformer Primary 1 7000 A 75 Set to current transformer primary winding value
Winding Rating
Generator Current
Transformer Secondary 1 5 A 5 Can only be set to 1 or 5
Winding Rating
Number of Generator
0 200 N/A 4
Poles
Generator Rated
Setpoint Value List 0
Frequency
Generator Rated Voltage 100 50000 V 100
Generator Rated Power 1 50000 kW 1
Generator Rated Apparent
1 50000 kVA 1
Power
(21) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular generator set.
• Total kW hours exported Note: Per phase quantities (kW, kVAr, KVA, and
Power Factor) will be monitored for 3-phase, 4-wire
• Percent kW output star-connected configurations)
Table 64
Setpoints - Generator AC Power Monitor(31)
Setpoint
Min Value Max Value Units Factory Default Description
Name
Customer Password Security Level to
0 3 N/A 3
Reset Generator Energy Meters
(31) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular generator set.
Table 65
g01239796
Illustration 89
192 RENR7902-07
Testing and Adjusting Section
Table 66
Setpoints - Generator Over / Under Frequency(24)
Setpoint Min Max Factory
Units Description
Name Value Value Default
Generator Over Frequency Warning Event
80 120 % 105
Percentage Threshold
Generator Over Frequency Warning Event sec.
0 120 10
Notification Delay Time
Generator Over Frequency Shutdown Event
80.0 120 % 110
Percentage Threshold
Generator Over Frequency Shutdown Event sec.
0 120 2
Notification Delay Time
Generator Under Frequency Warning Event
80.0 120.0 % 95.0
Percentage Threshold
Generator Under Frequency Warning Event sec.
0 120 10
Notification Delay Time
Generator Under Frequency Shutdown Event
80.0 120.0 % 90.0
Percentage Threshold
Generator Under Frequency Shutdown Event sec.
0 120 4
Notification Delay Time
(24) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular generator set.
Table 67
Setpoints - Generator Over / Under Voltage(25)
Setpoint Min Max
Units Factory Default Description
Name Value Value
Generator Over Voltage Warning
100 125 % 105
Event Percentage Threshold
Generator Over Voltage Warning sec.
0 120 10
Event Notification Delay Time
Generator Over Voltage Shutdown
100 125 % 110
Event Percentage Threshold
Generator Over Voltage Shutdown sec.
0 120 2
Event Notification Delay Time
Generator Under Voltage Warning
60 100 % 95
Event Percentage Threshold
Generator Under Voltage Warning sec.
0 120 10
Event Notification Delay Time
Generator Under Voltage
60 100 % 90
Shutdown Event Threshold
Generator Under Voltage
Shutdown Event Notification 0 120 sec. 4
Delay Time
(25) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular generator set.
RENR7902-07 193
Testing and Adjusting Section
Table 68
Table 69
Setpoints - Digital Inputs(5)
Setpoint Min Max
Units Factory Default Description
Name Value Value
Active Active Activating the E-STOP input will cause the
E-STOP N/A Active High
Low High generator set to stop immediately.
Setpoint allows for starting and stopping the
genset from a remote location.
If input is active and the engine mode switch
Active Active
REMOTE INITIATE N/A Active Low is in “AUTO”, the engine will attempt to start
Low High
and run. Once the input becomes inactive, the
engine will enter into cooldown (if programmed)
and then STOP.
Active Active
Digital #3(6) N/A Active Low
Low High
Active Active
Digital #4(6) N/A Active Low
Low High
Active Active
Digital #5(6) N/A Active Low
Low High
Active Active
Digital #6(6) N/A Active Low
Low High
Active Active
Digital #7(6) N/A Active Low
Low High
Active Active
Digital #8(6) N/A Active Low
Low High
(5) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular generator set.
(6) The “Digital Inputs” parameter can only be set to “Active High” or “Active Low” in order to initiate a High Warning, Low Warning, High
Shutdown. Low Shutdown, or Status.
RENR7902-07 195
Testing and Adjusting Section
Table 70
Available Digital Inputs
Pressures Other
Air Filter Differential Pressure Air Damper Closed
Engine Oil Pressure ATS in Normal Position
Fire Extinguisher Pressure ATS in Emergency Position
Fuel Filter Differential Pressure Battery Charger Failure
Engine Oil Filter Differential Pressure Battery Charging System Voltage
Starting Air Pressure Battery Voltage
Gas Pressure Fuel Leak
Custom Event
Temperatures Earth Fault
Ambient Air Temperature Earth Leakage
Engine Coolant Temperature Engine Inlet Manifold Charge Combustion
Engine Oil Temperature EPS Supplying Load
Exhaust Temperature Generator Circuit Breaker Closed
Generator Rear Bearing Temperature Generator Circuit Breaker Open
Right Exhaust Temperature Generator Frequency
Left Exhaust Temperature Generator Voltage
Generator Winding #1 Temperature Generator Current
Generator Winding #2 Temperature Generator Power
Generator Winding #3 Temperature Loss of Utility
Levels Utility Breaker Closed
Engine Coolant Level Utility Breaker Open
Engine Oil Level Utility to Generator Transfer Failure
Fuel Level Generator to Utility Transfer Failure
External Tank Fuel Level
Table 71
Custom Event Setpoint Value for Event Input
Functions cVue Block
Block Setpoint Description
Instance# Value
1 701 Custom Event (Instance
#1 only)
2 702 Custom Event (Instance
#2 only)
3 703 Custom Event (Instance
#3 only)
4 704 Custom Event (Instance
#4 only)
5 705 Custom Event (Instance
#5 only)
6 706 Custom Event (Instance
#6 only)
7 707 Custom Event (Instance
#7 only)
8 708 Custom Event (Instance
#8 only)
Digital Outputs
Table 72
Setpoints - Digital Outputs(7)
Setpoint Max Factory
Min Value Units Description
Name Value Default
Digital Output #1 Active State Configuration Low High N/A Low
Digital Output #2 Active State Configuration Low High N/A Low
(7) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular generator set.
Relay Outputs
Table 73
Table 74
Setpoints - Spare Analog Input(29)
Setpoint Min Factory
Max Value Units Description
Name Value Default
Set to “Enabled” for
MUI engines and set
Spare Analog Input Enable Status N/A N/A N/A Enabled
to “Disabled” for EUI
engines
Select
“Temperature”,
Spare Analog Input Type Configuration N/A N/A N/A Temperature
“Pressure”, or “Level”
.
Spare Analog Input Suspect Parameter
N/A N/A N/A 175 Oil temperature
Number (SPN)
Spare Analog Input High Percentage Warning
0 100 % 0
Event Threshold
Spare Analog Input High Temperature Deg.
-273 1,735 102 °C (216 °F)
Warning Event Threshold C
Spare Analog Input High Pressure Warning
-250 10,000 kPa -250
Event Threshold
Spare Analog Input High Warning Event sec.
0 60 2
Notification Delay Time
Spare Analog Input High Percentage
0 100 % 0
Shutdown Event Threshold
Spare Analog Input High Temperature Deg.
-273 1,735 107 °C (225 °F)
Shutdown Event Threshold C
Spare Analog Input High Pressure Shutdown
-250 10,000 kPa -250
Event Threshold
Spare Analog Input High Shutdown Event sec.
0 60 10
Notification Delay Time
Spare Analog Input Low Percentage Warning
0 100 % 100
Event Threshold
Spare Analog Input Low Temperature Deg.
-273 1735 1735
Warning Event Threshold C
Spare Analog Input Low Warning Event
-250 10000 kPa 10000
Threshold
Spare Analog Input Low Warning Event sec.
0 60 0
Notification Delay Time
Spare Analog Input Low Percentage
0 100 % 100
Shutdown Event Threshold
Spare Analog Input Low Temperature Deg.
-273 1735 1735
Shutdown Event Threshold C
Spare Analog Input Low Pressure Shutdown
-250 10000 kPa 10000
Event Threshold
Spare Analog Input Low Shutdown Event sec.
0 60 0
Notification Delay Time
(29) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular generator set.
RENR7902-07 199
Testing and Adjusting Section
NETWORK
Data Link - SCADA
Table 75
Setpoints - Data Link - SCADA(4)
Setpoint Factory
Min Value Max Value Units Description
Name Default
SCADA Data Link Baud Rate 2400 57600 N/A 19200
Select “None”,
SCADA Data Link Parity N/A N/A N/A None
“Odd”, or “Even”
SCADA Data Link Slave Address 1 247 N/A 1
SCADA Data Link Access Password 0 0xfffff N/A 0
SCADA Data Link Connection Timeout sec.
0.1 3600.0 30
Interval
RS-485 Bias Resistor Enable Status Disabled Enabled N/A Enabled
(4) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular generator set.
OTHER
Digital Selectors
Table 76
Setpoints - Digital Selectors(8)
Setpoint
Min Value Max Value Units Factory Default Description
Name
Digital Selector #1 controls Relay
Output #3
Configuration Options are:
Disabled
Digital Selector
Use Input #1
#1 Source Input #1
Use Input #2
Configuration
Use Input #3
Use Input #4
Use Input #5
Use Data Link Input
Digital Selector #2 controls Relay
Output #4
Configuration Options are:
Disabled
Digital Selector
Use Input #1
#2 Source Input #4
Use Input #2
Configuration
Use Input #3
Use Input #4
Use Input #5
Use Data Link Input
(continued)
200 RENR7902-07
Testing and Adjusting Section
Table 77
ECLC – Engine Coolant Loss Sensor Connector GSC – Generator Set Control
EGR – Electronic Governor Relay LFLAS – Low Fuel Level Alarm Switch
EHS – Ether Hold-In Switch LOLAS – Low Oil Level Alarm Switch
ENFR – Engine Failure Relay LWLAS – Low Water Level Alarm Switch
EOTC – Engine Oil Temperature Sensor Connector LWTL – Low Water Temperature Light
g01309357
Illustration 90
206 RENR7902-07
Testing and Adjusting Section
g01514111
Illustration 91
RENR7902-07 207
Testing and Adjusting Section
g01514113
Illustration 92
208 RENR7902-07
Index Section
Index
A Electronic Control Module (Generator Set) -
Configure ........................................................... 147
Analog Input Circuit Fault .................................... 127 Function Keys and Navigation Keys ................ 147
Annunciator Module............................................... 60 Initial Setup ...................................................... 148
[ OPTIONAL USE] ............................................. 60 Menu Maps ...................................................... 149
Adding Additional Remote Annunciator ............. 67 Programming the Display Preferences ............ 155
Basic Operation ................................................. 61 Programming the Setpoints ............................. 155
Configuration...................................................... 61 Setpoint Tables ................................................ 156
General Information ........................................... 60 Setpoints .......................................................... 149
Electronic Control Module (Generator Set) - Flash
Program ............................................................. 147
C Electronic Control Module (Generator Set) -
Replace.............................................................. 147
Charging System ................................................. 128 Replacement Procedure .................................. 147
Component Location ............................................... 6 Engine Cooldown Warning .................................. 108
Cycle Timer Programming..................................... 38 Engine Overcrank Warning ................................. 108
Outputs .............................................................. 39 Engine Overspeed Warning ................................. 110
Engine Setpoint Verification - Test....................... 145
Relevant Engine Parameter Group Setpoints.. 145
D Verification Procedures .................................... 146
Engine Speed Circuit Fault.................................. 134
Data Link ............................................................... 13 Engine Speed Timing Calibration - Setup ........... 144
Data Links .......................................................... 13 Engine Speed Warning........................................ 109
Data Link Circuit Fault ......................................... 130 Engine Underspeed Warning ............................... 112
Diagnostic Capabilities .......................................... 91 Event Resetting ..................................................... 20
The Caterpillar Electronic Technician................. 91 Reset Individual Events from the Generator Set
Diagnostic System Procedures ........................... 108 Control.............................................................. 21
Diagnostic Trouble Code List ................................ 92 Resetting All Events for a Single Module........... 20
Digital Input Circuit Fault ..................................... 132 Resetting All Events for All Modules .................. 22
Digital Input Programming ..................................... 25 Resetting Events for Engines Without J1939
Digital Inputs ...................................................... 25 Support............................................................. 22
Function and Navigation Keys ........................... 26 Event Viewing........................................................ 19
Programming the Active State of the Digital External Potential Transformer Connections ....... 139
Input ................................................................. 27 Transformer Connections ................................ 142
Programming the Event Input Functions............ 27 Winding Connections ....................................... 139
Digital Output Circuit Fault................................... 133
Digital Output Programming .................................. 28
Function and Navigation Keys ........................... 29 G
Programming the Active State of the Digital
Output .............................................................. 29 General Information........................................... 4, 89
Programming the Digital Selectors .................... 29 Generator Control Not in Automatic Warning ....... 114
Discrete Input/Output Module................................ 55 Generator Output Sensing Circuit Fault ............... 115
[ OPTIONAL USE ] ............................................ 55 Generator Overcurrent Warning ........................... 115
Configuration Behaviors..................................... 57 Generator Overfrequency Warning ...................... 116
General Information ........................................... 55 Generator Overvoltage Warning........................... 119
Inputs ................................................................. 55 Generator Reverse Power Warning .................... 120
Outputs .............................................................. 56 Generator Underfrequency Warning ................... 121
Specifications..................................................... 57 Generator Undervoltage Warning........................ 124
E I
M Thermocouple Module........................................... 52
[ OPTIONAL USE] ............................................. 52
Monitoring Software for Computer......................... 69 Configuration...................................................... 54
Creating a Control Panel View........................... 77 Diagnostics ........................................................ 52
Logging Data to a File........................................ 84 General Information ........................................... 52
Quick Start Guide............................................... 74 Monitoring Features ........................................... 53
Software Set Up................................................. 70 Specifications..................................................... 54
MUI Engine Monitoring and Control ...................... 15 Trip Point Programming......................................... 40
Troubleshooting Section........................................ 89
Typical Generator Abbreviations ......................... 201
P
Table of Contents..................................................... 3
Testing and Adjusting .......................................... 138
Testing and Adjusting Section ............................. 138
Text String Programming ....................................... 41
Text String Programming ................................... 41
210 RENR7902-07
Index Section
RENR7902-07 211
Index Section
©2009 Caterpillar Cat, Caterpillar, their respective logos, “Caterpillar Yellow” and the Power edge Printed in U.S.A.
All Rights Reserved trade dress, as well as corporate and product identity used herein, are trademarks
of Caterpillar and may not be used without permission.