Download as pdf or txt
Download as pdf or txt
You are on page 1of 114

Manual

Burner Control FA1

Sensors and Systems for Combustion Engineering www.lamtec.de


Table of Contents

Table of Contents

1 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 Validity of these Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1 For Your Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

3 Brief Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

4 Display and Operational Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8


4.1 Use of the Operating Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.2 Connecting the Burner Control FA1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

5 Operating Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.1 Starting without Pilot Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.2 Starting with Pilot Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.3 Starting without Control Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

6 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.1 Basic Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.2 Password Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.3 Select Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.4 Start with or without Pilot Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6.5 Pre-purge Period . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.6 Deactivate Firing Rate Control Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.7 Running Time of the Regular Firing Rate Input with TPS-Input . . . . . . . . . . . . . . . . . . . 16
6.8 Minimum Running Time of the Fuel/Air Ratio Control . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.9 Post-purge Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6.10 Delaytime of the Air Dampers During Pre-purge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6.11 Parameters of the Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.12 Deactivating Valve Leakage Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.13 Set Pilot Burner (Maintenance Mode) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.14 Automatic Restart after Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.15 Burner Firing Rate Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.15.1 Enter Set Point Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.15.2 Control Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.15.3 Setting the Control Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.15.4 Controller Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.15.5 Outside Temperature Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.15.6 Display of the Units of the Burner Firing Rate Controller Values . . . . . . . . . . . . 23
6.15.7 Display Range in Bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
6.16 Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
6.16.1 Setting the Limit Switches of the Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
6.16.2 Adjusting Control Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
6.16.2.1 Enter the Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6.16.2.2 Clear Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6.16.3 Programming the Ignition Point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6.16.4 Programming the Base Firing Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.16.5 Programming the 3rd up the 10th Point. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.16.6 Saving Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.16.7 Changing Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

2
Table of Contents

6.16.8 Saving Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26


6.17 Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.17.1 Reading Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.17.2 Resetting Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.17.3 Recalling Fault History. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

7 System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7.1 Release Settings by Customer Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7.2 Displaying the Running Time Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
7.3 Displaying Checksums and Safety Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
7.4 Re-enter Range Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

8 Internal Burner Firing Rate Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31


8.1 Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
8.2 Brief Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
8.3 Range Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
8.4 Moving Screen "Actual Temperature is too high" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
8.5 How to Change the Burner-Firing-Rate Controller with the Customer Interface . . . . . . 31
8.6 Changing Setpoint of Burner-Firing-Rate Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
8.7 Input Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
8.8 Operating Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
8.9 Steam Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
8.10 Control by Atmospheric Condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
8.11 Setpoint Changeover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
8.12 Start-up Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
8.13 Thermostat and Control Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
8.14 Manual Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
8.15 How to Adjust the Burner Firing Rate Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
8.16 Control Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
8.17 Checking the Safety Limiter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
8.18 Control Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
8.19 Aides for Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

9 Valve Leakage Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40


9.1 Valve Leakage Test Flow Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
9.2 Calculation Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

10 Standby . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
10.1 Standby mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
10.2 Specification of the burner sequencer function "Standby Mode" . . . . . . . . . . . . . . . . . . 45
10.3 Switching into Standby Mode via LSB module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

11 Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
11.1 Mode Abbreviations Used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
11.2 Flame Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
11.2.1 Integral Flame Monitoring (Option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
11.2.1.1 Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
11.2.1.2 Characteristics flame sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
11.2.1.3 Self Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
11.2.2 General Information of the Optical Flame Monitoring . . . . . . . . . . . . . . . . . . . . 50
11.2.3 Optical Flame Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

3
Table of Contents

11.2.3.1 Switching to Display the Flame Intensity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50


11.3 Avoiding EMC Effects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
11.4 Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
11.5 Calling Up the Condition of the Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
11.6 Tips and Tricks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
11.6.1 Set Pilot Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
11.6.2 Checking the Safety Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
11.7 Process Sequence Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
11.8 Connection Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
11.9 Connection Examples of Firing Rate Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
11.10 Flame Scanner and Sensor Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
11.10.1 Flame Scanner Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
11.10.2 Flame Sensor Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
11.10.2.1 FFS07 Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
11.10.2.2 FFS08 Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
11.11 LAMTEC SYSTEM BUS (LSB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
11.11.1 LSB Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
11.11.2 LSB Cable Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
11.12 Inernal Connecting Diagram of the Control Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
11.13 Valve Leakage Test Venting Over the Roof . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
11.14 Switch- and Key Combinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
11.14.1 Programming Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
11.14.2 Customer Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
11.15 Feedback at Three-Point-Step Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
11.15.1 Connect with Positive Locking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
11.15.2 Fail-Safe Feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
11.15.3 Examples of Potentiometers and Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
11.16 Replacing the Device and Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
11.16.1 Replacing a Burner Control FA1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
11.16.2 How to Replace a Servo Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
11.16.3 How to Replace a Potentiometer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
11.17 Changing EPROMs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
11.18 Wiring Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
11.18.1 Shields Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
11.18.2 PE Busbar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
11.18.3 Control Cabinet Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
11.19 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
11.19.1 FA1 BurnerControl. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
11.19.2 Customer Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
11.19.3 Programming Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
11.20 Burner Control FA1 without integral flame detector . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
11.21 Flame Scanner FFS07/FFS08 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
11.22 Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110

4
1 General Information

1 General Information
1.1 Validity of these Instructions

These instructions apply to the FA1 and in any configuration.


These devices conform to the following standards and regulations:
• DIN EN 298: 2012-11
• DIN EN 1643: 2014-09
• DIN EN 13611:2011-12
• DIN EN 60730-2-5: 2015-10
• DIN EN 60730-1:2012-10
• 2014/35/EU Low Voltage Directive
• 2014/30/EU EMC-Directive
• 2014/68/EU Pressure Equipment Directive
• (EU) 2016/426 Gas Appliance Directive
• 2011/65/EU RoHS

Test symbols: CE-0085 AU 0207

The FA1 is a control unit for combustion systems.

NOTICE
Respect the national safety regulations and standards.

5
2 Safety

2 Safety
2.1 For Your Safety

The following symbols are used in this document to draw the user's attention to important safe-
ty information. They are located at points where the information is required. It is essential that
the safety information is observed and followed, and that applies particularly to the warnings.

DANGER!
This draws the user's attention to imminent danger. If it is not avoided, it will result in death or
very serious injury. The plant including its surroundings could be damaged.

WARNING!
This draws the user's attention to the possibility of imminent danger. If it is not avoided, it may
result in death or very serious injury. The plant including its surroundings could be damaged.

CAUTION!
This draws the user's attention to the possibility of imminent danger. If it is not avoided, it may
result in minor injuries. The plant including its surroundings could be damaged.

NOTICE
This draws the user's attention to important additional information about the system or system
components and offers further tips.

The safety information described above is incorporated into the instructions.


Thus, the operator is requested to:
1 Comply with the accident prevention regulations whenever work is being carried out.
2 Do everything possible within his control to prevent personal injury and damage to prop-
erty.

6
3 Brief Description

3 Brief Description
The Burner Control FA1 is suitable for control of burners and combustion systems for gase-
ous, liquid and solid fuels, with permanent operation, also in hot air generators.
Connections for Interbus-S, PROFIBUS DP, CANopen, TCP/IP (Modbus TCP) and Modbus
RTU are available as optional equipment. The connection of other plant components e.g. O2
trim is by the LAMTEC SYSTEM BUS interface to a 9-pole Sub-D connector.
The operation is via optional PC software or programming unit. As display for end user, a cus-
tomer interface is connectable by LAMTEC SYSTEM BUS. The operation by PC software is
described in a separate manual
The FA1 continuously monitors its own functions and those of the connected control elements.
230 V outputs:
– actuation of the gas valves
– actuation of the oil valves
– actuation of the oil pump/rotary atomiser
– actuation of the ignition valve and the ignition transformer
– fan release
– fault message
– OPEN/CLOSE control signals (three-point-step or 4 ... 20 mA) for the mechanical fuel/air
ratio control
External signals to the FA1 are transmitted via floating contacts or chains of contacts.
The following signals can be pre-set:
– 3 separate safety interlock chains
– gas < max
– air pressure monitor
– pre-purge suppression
– minimum gas pressure monitor (for valve leakage test) gas >min
– flame signal
– burner on
– fuel selection
– oil pressure min / atomiser air pressure
– oil pressure max
– ignition position acknowledgement
– internal burner firing rate controller in combination with the control output

7
4 Display and Operational Controls

4 Display and Operational Controls


Intent of the keys:

 Reset

 Burner firing rate/fault history up

 Burner firing rate/fault history down

Fig. 4-1 Customer interface  MANUAL mode ON/OFF

 Changing display

Display: Status  burner firing rate – Setpoint value/actual value of


firing rate controller (1)
4 = External firing rate – Setpoint external/internal firing rate
23 = Internal firing rate – Flame intensity (1)
– Operating hours

(1) available if activated only

 Changing display
– Status
– Firing rate controller
– O21)
– Flame intensity

Fig. 4-2 Operating Unit

8
4 Display and Operational Controls

4.1 Use of the Operating Unit

With the operating unit you may operate and the program the burner control system.

4.2 Connecting the Burner Control FA1

1. Connect the operating unit to the FA1 by using a 9-pin Cannon connector. To do so, use
the supplied connecting cable, type 663R0430.
Data transmission takes place by the LAMTEC SYSTEM BUS.
2. Alternatively:
Connect the operating unit with the cable of the customer interface. An adapter cable,
type 663R0426, is supplied for this purpose.
Disconnect the 6-pin connector from the customer interface and connect the adapter cable
to the 6-pin connector.

Fig. 4-3 Connection of the operating unit

9
5 Operating Description

5 Operating Description
(see example diagrams in chapter 11.7 Process Sequence Charts)
A signal is first fed to terminal 58 (Burner On) indicating when the burner is to start. The Burner
Control FA1 then interrogates the boiler safety interlock circuit and the air pressure monitor
contact. If it does not detect a proper condition, the text of a corresponding message is indi-
cated and the operating control stops.
If all signals are in proper condition, the fan output is activated and the channel runs to his
bottom stop as a check.
If the channel has reached his bottom stop, it opens for aeration. The valve leakage test runs
in parallel (gas operation only).
In the case of control element the aeration is used to enter and/or test the range limit. After
reaching its top position, the mechanical fuel/air ratio control element remains in the open po-
sition. The FA1 then interrogates the air pressure monitor. If this signal is in proper condtioion,
the parameter set aeration time runs. When this time has expired the channel runs to the pro-
grammed ignition position. Once the channel has reached the ignition position the ignition
transformer is activated on its own for 3 seconds. The oil pump also starts up during oil oper-
ation
Before the valves open the respective fuel safety interlock circuit must be closed.

5.1 Starting without Pilot Burner

The main valves open and together with the ignition transformer remain activated for the du-
ration of the safety time. During this time the flame signal appears.

5.2 Starting with Pilot Burner

The ignition valve and main gas 1 (in gas operation) or the ignition valve alone (in oil operation)
run open. The pilot flame forms and the flame detection detects the flame. The flame detection
sends the signal to the burner control device.
On expiry of the 1st safety time, the ignition transformer switches off. For 3 sec. (stabilisation
time) the pilot burner burns alone. Then main gas 2 or the oil valve opens and remains acti-
vated in parallel with the ignition valve for the duration of the 2nd safety time. The ignition valve
closes again at the end of this period.
3 seconds after ignition, all channels run to the programmed base firing rate point. The FA1
remains in base firing rate position until control release is given.
After control release the FA1 follows the power control unit’s default setting.
A shut off follows the cancelling of the signal of the terminal 58. The main valves close. In gas
operation, first main gas 1 and second main gas 2 closes with a delay of approx. 5 sec., in
order to allow the test line between the solenoid valves to burn out. In the event of a fault shut-
down, both close immediately.
If configured for post-purge, the air channels open again for this period.
Thereafter the FA1 is in the "OFF" mode.

10
6 Commissioning

6 Commissioning
6.1 Basic Settings

First configure the device (FA1) for the requirements of the system.
Therefore set the following parameters.
Recommendation: Use the LAMTEC PC software for Windows (available separately).
The factory standard settings are indicated by an asteriks *.

NOTICE
The parameters of release level 1 must be protected by a password against unauthorised
changes. This password must differ to ’0000’.

6.2 Password Entry

Press key F3
Use keys 6 an 7 to switch to the programming interface.
Confirm with key 11 ENTER.
Confirm the warning with key F3.
Press keys 5, 7 and 8 simultaneously.
Enter the password with keys 2 ... 9 (0000 is set on delivery).
Press key 11 ENTER.
The display shows an arrow to the right and an arrow to the left above
the keys F2 and F3. This means the keys are in function.
Use keys F2 and F3 to set "PARM" in the display.
Use keys 6or 7 to select the desired parameter.
With the keys 9/8 the parameter content can be changed at  1.
With the keys 5/4 the parameter content can be changed at  100.
With the keys 3/2 the parameter content can be changed at  1000.

NOTICE
Changes does not need to be confirmed, they will be saved immediately.

11
6 Commissioning

6.3 Select Language

Select parameter 833

Value Language Value Language Value Language


0 German* 9 Portuguese 17 Slovene
1 English 10 Polish 18 Czech
2 French 11 Turk 19 Coal-Oil-French
3 Italian 12 Croatian 20 Coal-Gas-French
4 Swedish 13 Coal-Oil-German 21 Hungarian
5 Spanish 14 Coal-Oil-English 22 Romanian
6 Dutch 15 Coal-Gas-German 26 Norse
7 Slovak 16 Coal-Gas-English 27 Russian
8 Danish

12
6 Commissioning

6.4 Start with or without Pilot Burner

Select parameter no. 774 and 775 (oil operation, gas operation).
Nr. FMS ETA Short Text Description Min Max Default
/FA1
774 1 1 ZüBr. ÖL Start with (1) or without (0) pilot burner for oil, (2)=oil 0 255 1
with continuous ignition flame
0 = start without pilot burner - oil operation 5.1
1 = start with pilot burner - oil operation 4
2 = pilot burner also active in burner operation with
continuous monitoring of the ignition flame.
Therefore P 788 has to be set to 1
3 = start with pilot burner - oil operation,
only the ignition flame may be present during ignition
(until the 2nd safety time)
4 = pilot burner also active in operation with continuous
operation monitoring of the ignition flame, only the
ignition flame may be present during ignition
(until the 2nd safety time)
(from v. 5.4/510 on)
9 = start with pilot burner - oil operation
You may start the pilot burner with terminal 70 dur-
ing operation.
11 = start with pilot burner - oil operation
only the ignition flame may be present during igni-
tion (until the 2nd safety time).
You may start the pilot burner with terminal 70 dur-
ing operation.
17 = start with pilot burner - oil operation
Before curve set change from solo operation (gas/
fuelA) to mixed mode (+oil), the pilot burner starts
to ignite oil.
19 = start with pilot burner - oil operation,
only the ignition flame may be present during igni-
tion (until the 2nd safety time).
Before curve set change from solo operation (gas/
fuelA) to mixed mode (+oil), the pilot burner starts
to ignite oil.
25 = start with pilot burner - oil operation,
You may start the pilot burner with terminal 70 dur-
ing operation.
Before curve set change from solo operation (gas/
fuelA) to mixed mode (+oil), the pilot burner starts
to ignite oil.
27 = start with pilot burner - oil operation,
only the ignition flame may be present during igni-
tion (until the 2nd safety time).
You may start the pilot burner with terminal 70 dur-
ing operation. Before curve set change from solo
operation (gas/fuelA) to mixed mode (+oil), the pilot
burner starts to ignite oil

NOTICE
2 to 4, 9, 11, 17, 19, 25, 27  The ignition flame input must monitor the ignition flame sep-
arately and P 788 must be set to 1.
9, 11  FMS only
17, 19, 25, 27  FMS with mixed fuel firing only

13
6 Commissioning

Nr. FMS ETA Short Text Description Min Max Default


/FA1
775 1 1 ZüBr.Gas Start with (1) or without (0) pilot burner for gas, (2)=gas 0 255 1
with continuous ignition flame
0 = start without pilot burner - gas operation 5.1
1 = start with pilot burner - gas operation 4
2 = pilot burner also active in burner operation with
continuous monitoring of the ignition flame.
Therefore set P 788 to 1
3 = start with pilot burner - gas operation,
during the ignition (until the 2. safety time) only the
ignition flame may be present
4 = pilot burner also active in operation with continuous
operation monitoring of the ignition flame.
During ignition (until the 2. safety time), only the
ignition flame may be present.For this purpose P
788 has to be 1
(since v. 5.4/5o210)
9 = start with pilot burner - gas operation
You may start the pilot burner with terminal 70 dur-
ing operation.
11 = start with pilot burner - gas operation
only the ignition flame may be present during igni-
tion (until the 2nd safety time).
You may start the pilot burner with terminal 70 dur-
ing operation.
17 = start with pilot burner - gas operation
Before curve set change from solo operation (gas/
fuelA) to mixed mode (+gas), the pilot burner starts
to ignite gas.
19 = start with pilot burner - gas operation,
only the ignition flame may be present during igni-
tion (until the 2nd safety time).
Before curve set change from solo operation (oil/
fuelA) to mixed mode (+gas), the pilot burner starts
to ignite gas.
25 = start with pilot burner - gas operation,
You may start the pilot burner with terminal 70
during operation.
Before curve set change from solo operation (gas/
fuelA) to mixed mode (+gas), the pilot burner starts
to ignite gas.
27 = start with pilot burner - gas operation,
only the ignition flame may be present during igni-
tion (until the 2nd safety time).
You may start the pilot burner with terminal 70 dur-
ing operation.
Before curve set change from solo operation (oil/
fuelA) to mixed mode (+gas), the pilot burner starts
to ignite gas.

NOTICE
2 to 4, 9, 11, 17, 19, 25, 27  The ignition flame input must monitor the ignition flame sep-
arately and P 788 must be set to 1.
9, 11  FMS only
17, 19, 25, 27  FMS with mixed fuel firing only

14
6 Commissioning

6.5 Pre-purge Period

Select parameter no. 785


If an output channel is set to flue gas re-circulation, attention must still be given to P 427.
Nr. FMS ETA Short Text Description Min Max Default
/FA1
785 1 1 ZEIT VO Pre-purge time in seconds 0 999 30
Set the duration of pre-purge in this parameter.
The commissioning engineer sets this value.
P784 sets the lower limit of the pre-purge.

6.6 Deactivate Firing Rate Control Unit

Select parameter no.790 (type of burner firing rate controller).


Nr. FMS ETA Short Text Description Min Max Default
/FA1
790 1 1 Lasttyp Type of firing rate controller. 0-OFF / 1-constant control / 0 3 0/1
2-control by atmospheric conditions
Switch OFF or set the type of the internal firing rate con-
troller
0 = OFF
1 = constant control
2 = control by atmospheric condition 1
3 = control by atmospheric condition 2
This parameter defines the input from which the actual
value is should be taken. If the parameter is set to 1, the
integrated Pt100 input is used, otherwise the firing rate
input is used.
If the Pt100 input is used as the actual value signal for
the internal firing rate controller, the firing rate controller
can be deactivated with a bridge between terminals 19
and 20. In this case the firing rate is indicated by termi-
nals 3 - 6.

NOTICE
These parameters (P 356 - P 359, P 366, P 367, P 427, P 774, P 775 P 785, P 790, P 833)
must be adjusted to the system before commissioning. Further parameters which, although
you can alter them, only need to deviate from the standard setting in exceptional cases, are
given below.

15
6 Commissioning

6.7 Running Time of the Regular Firing Rate Input with TPS-Input

Select parameter no. 718.


If the firing rate default is not provided by TPS signal, the parameter must be set to „0“
Nr. FMS ETA Short Text Description Min Max Default
/FA1
718 1 1 Laufz L Running time in digit/min.. for TPS firing rate input (in 0 1200 0/500
digit/min)
Here, it would be preset on how fast the signal of the
external firing rate should change if the firing rate input
is provided via the TPS signal.
With the TPS signal, external firing rate would be gener-
ated through a counter which counts up or down
depending on the contact.The speed of the counter
would be set through these parameters. Preset values
are in digits per minute. Set the parameter to 0, if the fir-
ing rate input is not TPS. .
With manual mode the default firing rate is treated as
TPS firing rate via redundant feedback channel 2, in
case TPS firing rate (P 718 not equal to 0) is configured.
0 = default firing rate current or potentiometer
500 = default firing rate TPS

6.8 Minimum Running Time of the Fuel/Air Ratio Control

Select parameter no. 729


Nr. FMS ETA Short Text Description Min Max Default
/FA1
729 1 2 stopVERB Minimum running time of fuel/air ratio control 10 999 10
Minimum running time of the fuel/air ratio control (in
seconds)
Set the minimum running time of the fuel/air ratio control
in seconds. This parameter slows down the ramp-up
time or ramp-down time of the burner from base firing
rate to high firing rate.

16
6 Commissioning

6.9 Post-purge Time

Select parameter 758


Nr. FMS ETA Short Text Description Min Max Default
/FA1
758 1 1 ZEIT NA Post-purge time 0 1000 0
Post-purge time (in seconds)
0 = no post-purge
1000 = continuous purge (from 5.0 on)
Set the pre-purge duration after a switch OFF. The air
flaps were opened for this purpose. A fan output runs to
20 mA. The the release signal of the fan remains ON.
No post purge occurs if the parameter content is 0 and
in the case of a fault shutdown.
The actuators are not monitored in post purge mode!
The actuators only open when the flame is extin-
guished. The time begins to run immediately with clos-
ing of the magnetic valves. It may be necessary to add
this post burn time to the required post purge time

6.10 Delaytime of the Air Dampers During Pre-purge

NOTICE
The control output must be active.

Select parameter no. 768.


Nr. FMS ETA Short Text Description Min Max Default
/FA1
768 1 2 KverznLE Damper delay after fan ON in seconds 0 15 5
Delay time for the flaps after switching ON the fan in
seconds (only for FAT)
Enter a delay time for opening the flaps with respect to
the ventilator release. This prevents from increasing the
power consumption of the purge motor in the star/delta
starting phase.
(from 5.4 / 52201 on)
This parameter affects even with continuous purge.

17
6 Commissioning

6.11 Parameters of the Interface

NOTICE
These parameters have to be equal to the settings of the remote control software.
Otherwise no communication is possible.

Nr. FMS ETA Short Text Description Min Max Default


/FA1
822 2 2 Baud S1 Baud rate of serial interface 1 0 5 4
This parameter defines the baud rate for the serial inter-
face. The standard value is parameter content 4 (19,200
baud). If the display shows problems with the serial
transmission (especially with long serial connections), it
may be helpful to drop the baud rate. This must be car-
ried out on the burner control as well as on the operat-
ing device e.g. laptop.

0 = 1200 Baud 3 = 9600 Baud


1 = 2400 Baud 4 = 19 K 2 Baud
2 = 4800 Baud 5 = 38 K 4 Baud
824 2 2 Par. S1 Parity check for serial transfer (ser.1)1 0 2 1
This parameter sets the parity bit for interface transmis-
sion. Standard is even (parameter content: EVEN=0,
NONE=1, ODD=2).
0 = even
1 = none
2 = odd
826 2 2 Adr. S1 Network address _ _ _ (ser.1)1 0 31 1
Network address of the device (serial Interface 1)
Enter the network address for the serial interface. Fac-
tory setting for the network address is 1. If more than
one device is connected via an RS422/RS485 bus, this
network address has to be changed.

6.12 Deactivating Valve Leakage Test

Select parameter no. 772


Nr. FMS ETA Short Text Description Min Max Default
/FA1
772 1 2 Dicht.Zü Valve leakge check before ignition (0-OFF / 1-ON) 0 1 1
Setting of the valve leakage test before ignition:

0 = valve leakage test before ignition is OFF


1 = valve leakage test before ignitionis ON

This parameter is only of significance if the leakage test


is activated. (Parameter 3)

18
6 Commissioning

6.13 Set Pilot Burner (Maintenance Mode)

Select parameter no. 787


Nr. FMS ETA Short Text Description Min Max Default
/FA1
787 1 1 Wartung Maintenance mode (control unit only until stabilization 0 2 0
time)
0 = maintenance mode OFF (main valves are opened)
1 = maintenance mode active
2 = curve set switch allowed in set mode
Set the maintenance mode with this parameter. The
maintenance mode sets the pilot burner or the ignition
flame monitor. It enables to do 5 consecutive ignition
attempts without restarting with pre-purge and the leak-
age test. The burner sequencer only steps up to the
flame stabilisation time. You may not open the main
valves before the reset of this parameter.
After the 5th attempt pre-purge and leakage start auto-
matically.
Note:
A "Total Reset" resets the counter for maintenance
mode automatically i.e. the next cycle is treated as the
first and pre-purge and the leakage test are running.
Therefore, reset faults with a "Partial Reset" wherever
possible (selection switch on "Status", first channel key
2 upwards, then in addition channel key 1 downwards).
Attention: You may not use a partial reset for some
faults.

19
6 Commissioning

6.14 Automatic Restart after Failure

Respect the directives for combustion plants, if you set this parameter.
Nr. FMS ETA Short Text Description Min Max Default
/FA1
836 2 2 AutStart Automatic restart after fault 0 30 0
Automatic restart of the burner on fault condition. In the
case of a fault for which the standards permit an auto-
matic restart, this parameter initiates the restart.
0 = no restart of the burner
1... = automatic restart of the burner for faults, which are
marked in the list of faults. (delay in seconds)
In P 425, select the standard that applies to this error:
0 = TRD
1 = no restart of the burner
2 = EN676 (from 5.4/5f202)

20
6 Commissioning

6.15 Burner Firing Rate Controller

6.15.1 Enter Set Point Values

Select parameter 796 and 798 (setpoint value 1 and setpoint value 2).
With control by atmospheric condition select additionally parameter 797 and 799.

Nr. FMS ETA Short Text Description Min Max Default


/FA1
796 0 0 Soll1min Controller setpoint 1 minimum 0 999 90
Firing rate controller setpoint 1 minimum (setpoint 1) in °
C or bar (xx.x)
Set the minimum value for the first controller setpoint
(active if input "set point switching" = 0) (weather guided
controller) in this parameter. If the firing rate controller is
configured as a constant controller, the set point is set
here.
"Set point input via front panel"
1.Selection switch: firing rate value
2.Display: controller setpoint, controller actual value,
firing rate setpoint, internal firing rate
3.Channel key 3 down and channel key 4 up at the
same time
4.Controller setpoint starts to flash and the setpoint can
be changed with channel key 2
5.Do not save value: channel 3 up and channel 4 down
at the same time or switch off burner
6.Save value: save the setpoint to the minimum value
parameter with the Enter key (in P 796 / P 798
depending on the setpoint switching input)
Saving is only possible with constant controller.
With control by atmospheric conditions you may set the
firing rate controller setpoint value default manually
Activation of the controller setpoint modification is disa-
bled when operating mode is OFF. You may not trigger
the burner start by shifting the switching point.
refer to figure "Control by Atmospheric Conditions / Set-
point Switching of the Firing Rate Controller"
798 0 0 Soll2min Controller setpoint 2 minimum 0 999 70
Firing rate controller setpoint 2 minimum (set point 2)
in ° C or bar (xx.x)
Enter the minimum value for the second controller set
point (active if input "setpoint switching" = 1) (control by
atmospheric condition). Enter the setpoint in this param-
eter, if the firing rate controller is configured to constant
controller,
see P 796
refer to figure "Control by Atmospheric Conditions
/ Setpoint Switching of the Firing Rate Controller"

21
6 Commissioning

6.15.2 Control Range

Select parameter no. 802 and 803


Nr. FMS ETA Short Text Description Min Max Default
/FA1
802 0 0 EinschPt Burner start point 999 999 1
Enter the switching point of the firing rate controller as
the difference to the set point.
[Switching point] = [setpoint] - [parameter content]
e. g. : burner should switch on at 110.
setpoint = 120, parameter content = 10,
110 = 120 - 10
If the burner shall start above the setpoint,
you may enter negative values as well.
Therefore the following values correspond:
-1 = 65535 and -999 = 94537
Parameter content = 65536 - difference
i. e.: burner shall switch on at 125.
setpoint = 120, parameter content = 65536 - 5 = 65531
switching point value= 120 - (-5) = 125
803 0 0 Regelb.O upper Control range 0 999 10
(difference to the set point) in ° C or bar (xx.x)
Enter the upper control range limit.
The entered value corresponds to the difference
between the actual set point and the upper limit of the
control range.
Depending on the content of Parameter 809, the con-
tent of this parameter is interpreted as ° C (directly with-
out decimal point) as bar (resolution 0.1 bar, i.e. range
from 0.1 to 99.9 bar) or in digit.
see figure "Control range of the Firing Rate Controller"

6.15.3 Setting the Control Thermostat

Select parameter no. 804


Nr. FMS ETA Short Text Description Min Max Default
/FA1
804 0 0 Bren.AUS Burner off 0 999 15
Burner off (difference to the set point)
in ° C or bar (xx.x)
Enter the firing rate controller switch off point. The
entered value corresponds to the difference between
the current set point and the value, which shuts down
the burner. The value has to be greater than the
adjusted upper control range.(P 803)
Depending on the content of Parameter 809, the con-
tent of this parameter is interpreted as ° C (directly with-
out decimal point) as bar (resolution 0.1 bar, i.e. range
from 0.1 to 99.9 bar) or in digit
see figure "Control range of the firing rate controller

22
6 Commissioning

6.15.4 Controller Parameters

Select parameter no. 805 - 808.


Nr. FMS ETA Short Text Description Min Max Default
/FA1
806 0 0 I-Factor I - term of the controller 0 999 60
805 0 0 P-Faktor P - term of the power control unit 0 999 120
807 0 0 D-Faktor D - term of the controller 0 999 20
808 0 0 Nachst.z Cycle time 0 60 15
Cyclic control adjustment time
Set the adjustment time in seconds. This time is set
between the individual control steps. The time relates to
the reaction time of the system.

6.15.5 Outside Temperature Limits

Select parameter no. 800 and 801.


Nr. FMS ETA Short Text Description Min Max Default
/FA1
800 0 0 Obergren Firing rate controller: upper limit 0 999 999
Firing rate controller: Upper Limit (for control by atmos-
pheric condition) in ° C or digit
This is the upper limit of the outside temperature for
control by atmospheric condition.
801 0 0 Untergre Firing rate controller: lower limit 0 999 0
Firing rate controller: Lower Limit (for control by atmos-
pheric condition) in ° C or digit
This is the lower limit of the outside temperature for con-
trol by atmospheric condition.

6.15.6 Display of the Units of the Burner Firing Rate Controller Values

Select parameter no. 809


Nr. FMS ETA Short Text Description Min Max Default
/FA1
809 1 1 Leinheit Representation of actual value and setpoint for firing 0 3 0
rate controller
Burner firing rate controller actual input and set point
interpretation
Set how the actual value input of the firing rate controller
is interpreted in the display and in the parameters (defi-
nition of the physical parameters).
0 = display in digit
1 = display in °C (0... 320 °C)
2 = display in bar (P 810 and P 811)
Select also for FA1, from which input the actual
value signal should be taken. If the parameter is
set to 1, the integrated PT100 input is used, other-
wise the firing rate input is used.

23
6 Commissioning

6.15.7 Display Range in Bar

Select parameter no. 810 and 811.


Nr. FMS ETA Short Text Description Min Max Default
/FA1
810 1 1 min.Einh 4 mA corresponds to x units 0 999 0
The lower limit/pressure 4mA at the actual value input
corresponds with x bar.
Enter the lower limit of the display range, which corre-
sponds with 4mA at the input, if the input is configured
as a pressure input (only active when Parameter 809 =
2).
811 1 1 max.Einh 20 mA corresponds to x units 0 999 160
Upper limit pressure equivalent to 20mA actual input
corresponds with x bar.
Enter the upper limit of the display range, which corre-
sponds with 20mA at the input, if the input is configured
as a pressure input (only active when Parameter 809 =
2).

6.16 Setting

6.16.1 Setting the Limit Switches of the Motors

As soon as the FA1 is supplied with voltage, it attempts to drive the actuator motors to the low-
er limit of the factory set curve. If the end-bearing's limit switches are not properly adjusted for
this, the motor may hit the actuator's mechanical stop

NOTICE
This may damage the motor or the valve.

Therefore:
Check the position of the end-bearing limit switches in the motors, taking into account the mo-
tor output shaft's travel.
If in doubt, set a shorter travel. It may be readjusted later.

6.16.2 Adjusting Control Elements

Enter password (see chapter 6.2 Password Entry).


Use F2 and F3 to select ’Set’.
Use the Keys 16 and 17 to set the Setpoint value.
Use the keys 2, 4, 6 and 8 to set all actuators to setpoint value 000.
Press key 16  the display shows the actual feedback value.
The display of ’s. p. feedback’ ≈ 80 ... 200 digit at TPS outputs with feedback potentiometers
of 1 ... 5 kΩ.
The display is ≈ 200 digit with channel 1 with a feedback of 4 ... 20 mA.
When using an integrated speed evaluation the number of points depends on the setting of
the frequency converter (if necessary release fan manually).

24
6 Commissioning

WARNING!
Never change the settings of the frequency converter or the revolution measurement feed-
back after programming the setpoint values at FA1. Otherwise the curves must be entered
again.

Press key 17 to set the display to setpoint.


Use the keys 3, 5, 7 and 9 to set all control elements to 999.
Press key 16  the display shows the actual value feedback.
The display of ’s. p. feedback’ ≈ 800 ... 920 digit when using TPS outputs. If other values are
displayed, set limit switches and/or potentiometers in the motors accordingly.
The display is ≈ 999 digit at channel 1 with a feedback of 4 ... 20 mA.
If other values are displayed, check the 4 ... 20 mA input (terminal 44 and 45) and check the
settings of the frequency converter.

6.16.2.1 Enter the Curve

Fuel selection
0V at terminal 49 = curve set 1 (oil curve)
+24V at terminal 49 = curve set 2 (gas curve)

NOTICE
If the FA1 has 2 oil curves or 2 gas curves (parameter 776 at = 1 (oil) or = 2 (gas), curve set
1 (0 V) or curve set 3 (+24 V) can be chosen for oil and curve set 2 or curve set 4 can be cho-
sen for gas.

NOTICE
If the preset default curve is not suitable for the application, it can be changed.

6.16.2.2 Clear Memory

Press key twice  the display shows ’SL’ in it’s centre.


Press key  the display shows ’cleared’. The old curve is deleted.

6.16.3 Programming the Ignition Point

Press key.  The display shows "El" in the centre.


– Start burner (signal at terminal 58).
Use keys 16 and 17 to switch to ’a.v. feedb’.
– Wait until pre-purge has finished.
Use keys 2 to 9, to run the control elements to ignition position.
Press ENTER key.  The display shows ’Really ignite’.
If not, press key 3 and redefine ignition position.
Press ENTER key again to confirm.  The burner ignites.

25
6 Commissioning

6.16.4 Programming the Base Firing Rate

Press keys 16 and 17 to set to ’firing rate value’.


Press keys 2 and 3 to set to a value of ’200’.
Press keys 16 and 17 to set to ’s. p. feedb.’.
Press keys 2 and 9 to run the actuators to base fire position.
Press key 11 ENTER.

6.16.5 Programming the 3rd up the 10th Point

Proceed as described in "Program base firing rate point", but set each of the firing rate ratings
“250", "300", "400", "500", "600", "700", "800", "900", and "999" one after the other.

6.16.6 Saving Curve

Use the keys to switch from SETTING to AUTOMATIC.  The display shows ’Mem-
ory’.

6.16.7 Changing Points

Change the points by choosing the firing rate value of the desired point and re-entering the
associated actuator position.
Enter password (see chapter 6.2 Password Entry)
Press key  The display shows ’EI’ in it’s center.
Press keys 16 and 17 to ’firing rate value’.
Press keys 2 and 3 to choose the desired firing rate value (point number
is flashing).
Press key 2 twice.  The display shows the actual feedback value.
Press keys 2 and 9 to run the actuators into the desired position.
Press key 11 ENTER.
Proceed with any other point.

6.16.8 Saving Changes

To save the changes:


Press F2  the display shows "Memory".

6.17 Fault

6.17.1 Reading Faults

The display shows this icon upside left.


Press key 17 until the display shows STATUS.  The display shows the error code.

26
6 Commissioning

Press ENTER.  The display shows the plain text message (incl. running time counter
reading)

NOTICE
Press key 16 to read display values up to that moment, the fault occur.
All display values are frozen.

6.17.2 Resetting Faults

press key

6.17.3 Recalling Fault History

The FA1 stores the last 10 faults with the associated running time counter reading.
Prerequisite: FA1 is not in FAULT condition
With programming unit:
Press key until the display shows STATUS.
Press key.  The display shows the latest error code.
Press ENTER key.  The display shows the associated plain text and running time
counter reading.
Press key again.  The display shows the second last error code.
With customer interface:
Press key.
Press key.  The display shows the last error code.
After 3 s, the display automatically shows a scrolling text with error code, plain text
and operating hours.
To terminate press key.

Press keys 3 and 2 to browse through the fault history.

NOTICE
If it is certain that the FA1 is fed with voltage at all the time since the last fault occured, it is
possible to determine at what time the fault occurred from the present running time counter
reading and the current clock time.

27
7 System Operation

7 System Operation
7.1 Release Settings by Customer Interface

Beside terminal 59 FA1 can access the SETTING mode by using the customer interface alter-
natively.
Pre-requisite: The password for release level 1 must be set by the PC Remote Software.

Press keys simultaneously.

With keys 2, 3 and "Change-over", the password for level 1 can be entered.

Confirm with „Hand“ key.

FA1 can be set to SETTING mode using the remote control panel (PC Remote Software).
This function is available independently of the settings in P 869 (beside terminal 59 SETTING
mode requires an additional password):
Available with software version T1s001 and higher.

28
7 System Operation

7.2 Displaying the Running Time Meter

Press F2 (clock). The display shows a running text with the following data:
Total running time
Running time on curve set 1 - start-ups on curve set 1
Running time on curve set 2 - Start-ups on curve set 2
The running times for curve set 1and curve set 2 do not necessarily add up to the displayed
total running time

NOTICE
The total counter refers to the FA1's running time. It starts timing as soon as the unit is con-
nected to a voltage source (this also provides the basis for the fault history).
The individual running time counters refer to the burner's running time. They start timing as
soon as the burner is in operation with the relevant curve set (flame signal is present).

7.3 Displaying Checksums and Safety Times

Press the keys 16 and 17 to select SETPOINT FEEDBACK.


Press key 11 ENTER.
Press key CHANGE DISPLAY at the customer interface 
The display shows the following
CRC 16 for the levels 0, 1and 2  adjustable at commissioning
CRC 16 for level 4  adjustable by LAMTEC only
1. safety time oil in seconds
2. safety time oil in seconds
1. safety time gas in seconds
2. safety time gas in seconds
Pre-purge time in seconds
Press F1 RESET at the display- operating unit or CHANGE DISPLAY at the cus-
tomer interface to aboard.
If changes of parameters was done, restart the FA1 to update the CRC checksum.
If two customer interfaces are connected, calling the checksum is only possible, if the key
CHANGE DISPLAY is pressed simultaneously on both customer interfaces for a long time or
if one customer interface is disconnected temporarily.

29
7 System Operation

7.4 Re-enter Range Limits

NOTICE
At least one actuator must be active.

When changing the limit switch after programming, the range limits must be re-determined.
Enter password (see chapter 6.2 Password Entry).
Press key F3 → until the display shows ’SL’ in it’s centre.
Press key11 ENTER the display shows ’cleared’.
The curves an the range limits are deletet.
Press key F2 twice  the display shows ’Restore previous curve’.
Press key 7.
Since no point has been entered, the old curve is re-activated, but the range limits remain de-
leted.
Let the system pre-purge.
Range limits are re-entered.

NOTICE
This is to be observed on the ’Setpoint’ display. Without limits the setpoint is 0 or 999. Once
the limit is determined, the setpoint skips to the actual value.

30
8 Internal Burner Firing Rate Controller

8 Internal Burner Firing Rate Controller


8.1 Purpose

The internal firing rate controller calculates the burner firing rate against a pre-defined setpoint
value (e.g. as a function of temperature or pressure) by comparison with the actual value. This
position will be transferred to the electronic fuel/air ratio control as a default value.

8.2 Brief Description

The integral firing rate control unit is a PID controller with special combustion engineering
functions. You can use it as a fixed value control or as a control by atmospheric condition. The
following signals can be pre-set:
• Actual value (temperaturePT 100 max 320 °C or steam pressure)
• Outside temperature or another analog signal for setpoint shift (only on control by atmos-
pheric condition). The FA1 must be equipped with the optional hardware for control by at-
mospheric condition.
• Setpoint switching (via floating contact). The burner firing rate controller releases the com-
bustion internally.
Combustion is triggered internally by the power control unit.

8.3 Range Limits

You must set limit values in the parameters, switching the burner on and off. After a burner
shut-down while actual temperature has not reached the switch-on threshold yet, a display will
inform you that firing rate controller is refusing a start-up.

8.4 Moving Screen "Actual Temperature is too high"

Press key F3 MANUAL to start the FA1, even if the display shows the running text,
subject to the condition, that the maximum temperature is not exceeded.
Press key F3 MANUAL again to switch back to AUTOMATIC mode.

NOTICE
The limit values should always be entered in the form of a difference from the setpoint value.

8.5 How to Change the Burner-Firing-Rate Controller with the Customer Interface

This function works only if the burner is in operation.

CAUTION!
If you change the setpoint, regard that also the on and off switchpoints are shifted, since they
are defined as a difference value to the setpoint.

31
8 Internal Burner Firing Rate Controller

8.6 Changing Setpoint of Burner-Firing-Rate Controller

With an activated constant control:


Set the firing rate with keys 16 and 17. On the left side of the display, the actual set-
point 1 or setpoint 2 will be showed depending on the value terminal 50 has (0 V at
terminal 50 = setpoint 1, 24 V on terminal 50 = setpoint 2).
Press key 6 and key 9 simultaneously, left value flashes in display (setpoint).
Setpoint can be changed with keys 4 and 5.
Press key 11 ENTER to save the new setpoint, .
Press keys 7 and 8 simultaneously to end the function ’Set power control unit’ with-
out saving the setpoint.

8.7 Input Signals

The analogue inputs can be preset in various forms.


Actual value:
• as 0/4 ... 20 mA current signal, terminals 4 and 5 (+), 3 (-)
• as non active current signal 4 ... 20 mA (two-wire connection), terminal 23, + 24 V supply,
terminals 4 and 5 input
• as 0 ... 10 V voltage signal
• as 0 ... 5 k resistance signal, terminal 4, 5 and 6
• directly as Pt100 terminal 21, 20, 19 as three-wire connection (0 ... 320 °C/32 ... 608 °F)
Outside temperature (setpoint-shifting) - only available with the option "control by atmospheric
condition"
• as Pt100 (0 ... 320 °C/32 ... 608 °F) as three-wire connection, terminals 39, 40, 41 (de-
fault)
• as 4 ... 20 mA current signal, terminals 39 (-) and 40 (+),
(special option, please order separately)
• as non active current signal 4 ... 20 mA, term. 23 + 24V supply, terminal 40 input

8.8 Operating Description

The burner start-up is carried out as described above. At least ’Burner ON’ signal and ’Re-
lease’ must be sent by firing rate controller.
The burner starts as soon as it is receiving signals ’Burner ON’ and ’Release’ from firing rate
controller. The firing rate controller is in operation not before the burner is running and the sig-
nal ’Control Release’ is pending.

The default value of firing rate for fuel/air ratio control is set via integral firing rate controller.
Depending on the difference between actual and setpoint value and adjusted control param-
eters this default firing rate value is set. When actual value is exceeding to maximum value
the firing rate controller switches OFF combustion.
The firing rate controller is active in AUTOMATIC mode only.

32
8 Internal Burner Firing Rate Controller

8.9 Steam Pressure

If you get a steam-pressure signal from a pressure transmitter on terminal 3, 4 and 5, you must
short-circuit the PT100 input at terminal 20 and 21.

8.10 Control by Atmospheric Condition

If the burner firing rate controller is configured as "controlled by atmospheric conditions" the
setpoint value can be shifted between the parameterised setpoint minimum and setpoint max-
imum by connecting another PT 100 temperature sensor. When utilising control by atmos-
pheric conditions, the outside temperature is a component of setpoint calculation. This allows
the operator to enter a minimum and a maximum setpoint, between which the outside temper-
ature can determine the final setpoint value.

Fig. 8-1 Control by atmospheric conditions

8.11 Setpoint Changeover

You can switch the setpoint with the input "setpoint switchover". If you use a version with fixed
setpoint value it is possible to select one of the two values, which are entered in the parame-
ters 796 and 798 with this contact.
If you have activated the control by atmospheric conditions additionally, you can select be-
tween two pairs of limit values (see control by atmospheric conditions and limit ranges). The
parameters for setpoint 1 (for setpoint switching) and setpoint min. 1 (for control by atmos-
pheric conditions) are equal. Likewise the parameters setpoint 2 and setpoint min. 2. The cor-
responding content is assigned according to the configuration.
When activating the "control by atmospheric conditions” option and setting the adjustable pa-
rameters, you may realise an external setpoint default. In other words, the setpoint can be ad-
justed manually or automatically via a potentiometer (or switched through resistors). By
connecting a change-over switch, you can implement a night-time reduction instead of control
by atmospheric conditions. A control by atmospheric conditions and a night-time reduction can
be realised simultaneously, if you combine the control by atmospheric conditions with the set-
point switching.

33
8 Internal Burner Firing Rate Controller

Nr. FMS ETA Short Text Description Min Max Default


/FA1
796 0 0 Soll1min Controller setpoint 1 minimum 0 999 90
Firing rate controller setpoint 1 minimum (setpoint 1) in °
C or bar (xx.x)
Set the minimum value for the first controller setpoint
(active if input "set point switching" = 0) (weather guided
controller) in this parameter. If the firing rate controller is
configured as a constant controller, the set point is set
here.
"Set point input via front panel"
1.Selection switch: firing rate value
2.Display: controller setpoint, controller actual value,
firing rate setpoint, internal firing rate
3.Channel key 3 down and channel key 4 up at the
same time
4.Controller setpoint starts to flash and the setpoint can
be changed with channel key 2
5.Do not save value: channel 3 up and channel 4 down
at the same time or switch off burner
6.Save value: save the setpoint to the minimum value
parameter with the Enter key (in P 796 / P 798
depending on the setpoint switching input)
Saving is only possible with constant controller.
With control by atmospheric conditions you may set the
firing rate controller setpoint value default manually
Activation of the controller setpoint modification is disa-
bled when operating mode is OFF. You may not trigger
the burner start by shifting the switching point.
refer to figure "Control by Atmospheric Conditions / Set-
point Switching of the Firing Rate Controller"

8.12 Start-up Sequence

The firing rate controller has a startup circuit, in order to slow down the burner's start firing rate.
The startup circuit is run during each new burner start. The internal firing rate is held at a value
P 792 adjustable by the user, for as long as the boiler is cold (actual value is below a user-
adjustable limit, P 791). If the controller’s actual value is equal to or larger than the parame-
terised startup maximum temperature, this startup circuit is cancelled.
In order to prevent a situation where an excessively large demand on system output, the boiler
temperature necessary to cancel the startup circuit is not reached, a startup timer is also trig-
gered in parallel (this timer can also be adjusted by the operator, P 793). Once the internal
firing rate reaches the parameterised startup firing rate, the output is increased linearly step-
wise up to the maximum firing rate. The slope of this linear increase is calculated from the pa-
rameterised startup time.

34
8 Internal Burner Firing Rate Controller

*(1) = P 792
*(2) = P 793

Fig. 8-2 Startup sequence


Nr. FMS ETA Short Text Description Min Max Default
/FA1
791 0 0 Anf.Temp Max. start-up temperature 0 999 0
Maximum start-up temperature or pressure in relation to
the actual value
Start - up circuit parameter:
Enter the actual temperature, up to which the start - up
circuit is active. See fig. Start - up circuit
792 0 0 Anf.Leis Start-up output 0 999 0
Burner start-up firing rate, corresponding to the internal
firing rate (in digit)
Set the firing rate value at which the burner should start.
see fig. start - up circuit
793 0 0 Anf.Zeit Start-up time 0 32767 0
Burner-start-up-time in seconds
The maximum time the start - up circuit is active is set
here.
see fig. start - up circuit

8.13 Thermostat and Control Range

NOTICE
This function can replace the control thermostat, which is required on the plant.
It does not replace a safety thermostat.

The thermostat function switches the burner on and off on the basis of the temperature and/
or pressure value, but only when burner is released by the start signal. The control range is
formed by entering the controller setpoint value and the parameters P 802 (switch-on point),
P803 (upper control range) and P 804 (burner OFF). The cut-off hysteresis is divided into 2
ranges. The first part lies above the setpoint and forms the upper control range. The second
part lies below the setpoint and forms the lower control range.
The control range may lie asymmetrically around the setpoint.
The power control unit functions within the upper and lower control range according to its set-
tings in the parameters and the default values.

35
8 Internal Burner Firing Rate Controller

If the actual value of the control unit reaches the shut-down range, the base firing rate request
is emitted. If the control unit’s setpoint exceed the shut-down range a control shut-off occurs.
This is done by internal processing. If the actual value drops below the lower control range, a
re-start can occur.

Nr. FMS ETA Short Text Description Min Max Default


/FA1
802 0 0 EinschPt Burner start point 999 999 1
Enter the switching point of the firing rate controller as
the difference to the set point.
[Switching point] = [setpoint] - [parameter content]
e. g. : burner should switch on at 110.
setpoint = 120, parameter content = 10,
110 = 120 - 10
If the burner shall start above the setpoint,
you may enter negative values as well.
Therefore the following values correspond:
-1 = 65535 and -999 = 94537
Parameter content = 65536 - difference
i. e.: burner shall switch on at 125.
setpoint = 120, parameter content = 65536 - 5 = 65531
switching point value= 120 - (-5) = 125
803 0 0 Regelb.O upper Control range 0 999 10
(difference to the set point) in ° C or bar (xx.x)
Enter the upper control range limit.
The entered value corresponds to the difference
between the actual set point and the upper limit of the
control range.
Depending on the content of Parameter 809, the con-
tent of this parameter is interpreted as ° C (directly with-
out decimal point) as bar (resolution 0.1 bar, i.e. range
from 0.1 to 99.9 bar) or in digit.
see figure "Control range of the Firing Rate Controller"
804 0 0 Bren.AUS Burner off 0 999 15
Burner off (difference to the set point)
in ° C or bar (xx.x)
Enter the firing rate controller switch off point. The
entered value corresponds to the difference between
the current set point and the value, which shuts down
the burner. The value has to be greater than the
adjusted upper control range.(P 803)
Depending on the content of Parameter 809, the con-
tent of this parameter is interpreted as ° C (directly with-
out decimal point) as bar (resolution 0.1 bar, i.e. range
from 0.1 to 99.9 bar) or in digit
see figure "Control range of the firing rate controller

36
8 Internal Burner Firing Rate Controller

8.14 Manual Control

Press key MANUAL to move the regular firing rate input of the firing rate controller.
Press the keys 2 and 3 to variegate the burner firing rate.
Press key MANUAL again to cancel firing rate controller.
It is also possible to switch the FA1 to "Manual Control" with the terminals. By short-circuiting
the Pt100 signal (e.g. bridge terminal 19 and 20) the burner firing rate controller is switched
off. The fuel/air ratio controller then directly follows the input at the default firing rate input. The
display shows LE instead of HA.

NOTICE
Only use manual control while monitoring the system.

8.15 How to Adjust the Burner Firing Rate Controller

Only adjust the burner firing rate controller with the parameters.

8.16 Control Range

The control range lies around the setpoint. The content of the "Burner on" parameter is sub-
tracted from the setpoint value to form the switch-on value. The value of the "Upper control
range" parameter (P 803) is added to the setpoint value to form the upper limit of the control
range. The control range may therefore lie asymmetrically around the setpoint.The shut-off
range is upwardly limited by the "Burner off" parameter (P 804). The parameter is added to
the setpoint value. If this value is exceeded, the burner is shut off.
The range between "Upper control range" and "Burner off" forms the shut-off range. If the ac-
tual value reaches this range, the to cancel firing rate controller, press key "Manual" again runs
at base firing rate.
It also follows from this that the value in "Burner Off", is generally higher than that in "Upper
control range". Otherwise there is no shut-off range and the burner is shut off on immediately
reaching the limit.
The burner 'ON' switching point also can be located above the setpoint. In this case the pa-
rameter 802 has to be set negative (<0).

*(1) = P 804
*(2) = P 803
*(3) = P 802
*(4) = P 796 - P799
Fig. 8-3 Control range

37
8 Internal Burner Firing Rate Controller

8.17 Checking the Safety Limiter

For testing purposes of the safety limiter change the setpoint. This also causes a change in
shut-off range as well. The safety limiter can therefore be overrun in manual mode.

8.18 Control Mode

The firing rate controller tries to bring the actual value into line with the setpoint value. In doing
so, a direct correlation is assumed between internal firing- ate and boiler temperature, e.g. the
greater the internal firing rate, the faster the boiler temperature rises. Should the curves be
programmed differently, the firing rate controller will not function.
Four parameters determine the control action.
• Adjustment time
The adjustment time determines at what intervals the deviation is checked and the new
adjustment is determined.
• P term
The proportional term acts directly on the deviation, that is the difference between setpoint
value and actual value.
P > → higher step response
• I term
The integral term is calculated from the instantaneous deviation and the previous devia-
tion from the setpoint value.
I > → faster approximation to the setpoint
danger of overshooting!
• D term
The derivative term is calculated from the variation of the actual values. It has acceleration
and respectively slowing effects.
In practice the adjustment of the PID-controller is specified to each controlled system. With
the characteristics of the controlled system you try to deduce acceptable data, i.e. the values
are defined experimentally
• P term, I term, D term are added together and act as adjustment on the firing rate default
for the ratio control. The value is added up, starting from the instantaneous internal firing
rate.
• As long as the actual value is below the setpoint, P term and I term are positive, that is to
say both these term will increase the firing rate default.
• Only the D term is negative in such a case (assuming that the boiler temperature is rising).
Use the D factor sparingly because it leads to a higher burden of the actuators.
• In order to avoid excessive overshoot during burner start-up, the parameters should be
adjusted to achieve a suitably large D-term.
• If, despite a large setpoint deviation, the burner is not running at full firing rate or base firing
rate, the P term should be increased.
• The longer the adjustment time, the quieter the group. However, this also increases the
actual value's deviation from the setpoint value and leads to slower adjustment.

Hot Water Installations Steam Boiler Installations


P term 120* 600
I term 60* 300
D term 20* 25
Adjustment time 15* 20
Values must be adjusted according to the controlled system. * Default value

38
8 Internal Burner Firing Rate Controller

8.19 Aides for Setting

Characteristic Control Process Control Mode Start-up Procedure


P term higher decrease of stronger reaction with faster start-up with
attenuation overshoot overshoot
P term smaller increase of less reaction, less ten- slower startup
attenuation dency to oscillate

Fig. 8-4 Controller operation with P-term too high

Characteristic Control Process Control Mode Start-up Procedure


I term higher decrease of atten- stronger reaction with faster start-up with ten-
uation tendency to oscillate dency to oscillate
I term smaller increase of attenu- less reaction, less ten- slower start-up
ation dency to oscillate

Fig. 8-5 Controller operation with I-term too high

Characteristic Control Process Control Mode Start-up Procedure


D term higher decrease of atten- stronger reaction slower start-up, earlier
uation decrease of power
D term smaller increase of attenu- less reaction faster start-up,
ation decrease of power
later

Fig. 8-6 Controller operation with D-term too high

39
9 Valve Leakage Test

9 Valve Leakage Test


The gas valve leakage test checks the integrity of main gas valves 1 & 2. The supply gas pres-
sure is used to carry out this automatic test procedure. After a controlled burner shutdown, any
gas in test line (the space within the pipework between the two main gas valves) will have
been burnt off and so the pressure in the test section should be atmospheric i.e. gas pressure
> min = 0.
The FA1 checks this and if true then Main gas valve 1 is opened for a short time to allow gas
to flow into the test line.
The FA1 checks that the gas pressure > min value changes to = 1. This pressure condition
must remain for 30 seconds after which the gas valve leakage test is deemed successful and
complete.
If the valve leakage test line is not empty at the start (e.g. as a result of a previous fault shut-
down), main gas valve 2 opens first. The valve leakage test line is vented (into the combustion
chamber or over the roof, depending on the system; for suggested circuit, see Appendix). It is
checked, whether the line remains pressureless for 30 seconds. Otherwise the procedure is,
as described previously.
The valve leakage test is performed before ignition.
The pressure monitor for the valve leakage test line must be connected to ’Gas pressure >min’
input (terminal 47). This also monitors the minimum gas pressure during normal operation. If
there is a requirement for another minimum pressure device to be monitored during normal
operation then this should be incorporated into gas safety interlock for this purpose.
However, the test line must be designed to ensure that the test time of 30 seconds per valve
is sufficient for reliable detection of a 0.1% leak of the fuel gas consumed at maximum com-
bustion heat output, but at least 50 dm3/h.

NOTICE
Respect the national safety regulations and standards.

40
9 Valve Leakage Test

9.1 Valve Leakage Test Flow Chart

Fig. 9-1 Valve leakage test flow chart

41
9 Valve Leakage Test

9.2 Calculation Example

With FA1 the gas pressure monitor is also applicable to the monitoring of minimal gas pres-
sure. Therefore the minimal gas pressure of the burner must be set.
The valve leakage test time t3 (P 311) would be set by FA1. The time t2 for FA1 is fixed to 2s.
The time t3 (P 311) must be set in a way that the maximum allowable leakage rate QLeck can
be securely detected. The maximum leakage rate stated in EN1643 and ISO23551-4 is 0.1%
of the nominal volumetric flow of the gases or a minimum of 50l/h.

Example 1
Burner capacity =1000 KW
Fuel = natural gas H, calorific value = 10 kW/m3
Nominal volumetric flow of the gases = 100 m3/h
Leakage rate max. = 0,1 m3/h or 100l/h

Example 2
Burner capacity =1000 KW
Fuel = propane, calorific value = 25,9 kW/m3
Nominal volumetric flow of propane = 38,6 m3/h
Leakage rate max. = 50 l/h (not 38,6 l/h)

Calculation

Fig. 9-2 Principle scheme


The test volume Vtest must be calculated with tube diameter and valve volume. The value vol-
umes are provided by the valve manufacturer. If valve 1 and valve 2 are be used as a double
valve, the test volume would be provided by the valve manufacturer.
The leakage test VLeak is calculated according to the Boyle-Mariotte principle.

42
9 Valve Leakage Test

p1  V1 = p2  V2
p = absolute pressure
V = gas volume
This is valid for the test of valve 1 V1:

Should t3 be negative, at least 1s must be set.


If the calculation of t3 for valve 2 is higher than t3 for valve 1, the value for the calculation of
valve 2 must be adjusted.

Qleak Leakage rate in l/h


psw Absolute pressure on the switching point of pressure monitor (adjusted over-
pressure + atmosphere pressure)
psw e Adjusted overpressure on switching point of pressure monitor
pout e Output pressure on gas valve V2 during purge
pAtm Atmospheric pressure (average of 101,3 kPa at sea level)
Vtest Test volume between the valves
t2 Settling time is always 2 s
t3 Adjusted leakage check time

NOTICE
pSchalt must always be higher than pout.
Otherwise V1 would be recognised as leaking even if it is not.

This is valid for the test of valve 2 V2:

If t3 is negative, at least 1 s must be set.


If the calculated t3 value of valve 1 is higher than t3 for valve 2, the calculated value of valve
1 must be adjusted.

Qleak Leakage rate in l/h


psw Absolute pressure on switching point of pressure monitor (adjusted overpres-
sure + atmosphere pressure)
psw e Adjusted overpressure on the switching point of pressure monitor
pin Absolute input pressure on gas valve V1
pin e Overpressure at gas valve V1 input
pAtm Atmosphere pressure (average of 101,3 kPa at sea level)
Vtest Test volume between the valves
t2 Settling time is always 2 s
t3 Adjusted leakage check time

43
10 Standby

10 Standby
10.1 Standby mode

In this mode the FA1 enables a switchback to pilot burner mode. The burner re-starts without
pre-purge in the 2nd safety time.
You can activate STANDBY mode, if the internal firing rate controller is active or if an external
input or output command can be connected to LSB module or fieldbus (see parameter 812,
access level 4).
As soon as the burner firing rate controller detects that a shutdown of the burner is necessary,
the burner closes the contact at the LSB or the appropriate bit is set to high by field bus. This
does not lead to a shut down. STANBY mode is activated instead.
The STANDBY mode drives the firing rate value to the ignition point and waits for ignition
acknowledgement. Ignition valve and ignition transformer are switched on first. The recircula-
tion channels run to CLOSE position. Ignition position has to be active. After an idle time (sta-
bilisation time) the valve gas 1 (if fuel = gas) is closed for purging the gas system.
Afterwards all fuel valves but the ignition valve stay closed. If set the performing of a valve
leakage test after operation at fuel gas starts now.
Afterwards the ignition transformer shuts OFF. Only the ignition valve remains open.

Fig. 10-1 Sequence at gas operation


*DK = Valve leakage test after operation. During that time the ignition transformer is active.

44
10 Standby

10.2 Specification of the burner sequencer function "Standby Mode"

Fig. 10-2 Sequence at oil operation


The sequencer is now in STANDBY mode with active pilot flame. Ignition position acknowl-
edgement must apply all the time.
As soon as one of the following incidences happen, the parameter set ignition sequence of
the fuel is executed without switching on the ignition transformer:
– Boiler pressure or boiler temperature have lapsed to that point, where the burner would
start again (with internal firing rate controller)
– As soon as the LSB contact (terminal 1) opens again.
– As soon as the command is transferred by fieldbus.
This may occur after valve leakage test, before operation, with fuel gas and without the trans-
former leading time (analogue changing by pilot burner  ignite the new fuel)

NOTICE
At combustion plants with just one flame detector, ensure, that the main flame is always ignit-
ed by the pilot flame. Otherwise use one flame detector for the main flame and one for the pilot
flame.

If the "Burner ON" signal will be removed during stand-by mode, the FA1 switches OFF. This
shut-off proceeds like a shut-off out of the modes BASE FIRING RATE/CONTROL with all it’s
parameter set procedures.
In oil operation the output for the oil pump stays active.
LSB module address 31 input 1

NOTICE
Since it's not sure how long the STANDBY mode applies, a separate pilot flame monitoring
must be approved for continuous operation, or main flame and pilot flame are monitored to-
gether with one flame scanner, approved for continuous operation.

45
10 Standby

10.3 Switching into Standby Mode via LSB module

Fig. 10-3 Switching in STANDBY mode via LSB module

46
11 Appendix

11 Appendix
11.1 Mode Abbreviations Used

Fig. 11-1 Status display at customer interface Fig. 11-2 Display at programming unit

Short text Description


BE → READY (signal on terminal 58)
ZÜ → IGNITION POSITION or IGNITION
EZ → SETTING/IGNITION position (same as IGNITION, but FA1 on SET-
TING)
GL → BASE FIRING RATE
EG → SETTING/BASE FIRING RATE” (as BASIC FIRING RATE, but FA1 on
SETTING)
NA → POST-PURGE
AU → BURNER OFF (no signal present)
EL → SETTING
SL → CLEAR MEMORY
EV → SETTING/PRE-PURGE" (as "PRE-PURGE", but FA1 on SETTING)
ES → SETTING/CONTROL (as AUTOMATIC but FA1 on SET)
ST → FAULT
VO → PRE-PURGE
HA → MANUAL MODE (burner efficiency may be adjusted manually)
or Hand
no display → Burner set to AUTOMATIC during OPERATION
LE → EXTERNAL FIRING RATE (firing rate controller disabled by digital
input)

47
11 Appendix

11.2 Flame Monitoring

11.2.1 Integral Flame Monitoring (Option)

11.2.1.1 Purpose

The integral flame monitoring system is primarily used for standard applications (e.g. oil or gas
flames at a burner in a combustion chamber) because of it’s limited adjustment possibilities.

NOTICE
We recommend the LAMTEC flame monitoring systems (like F300K, F200K2), if you have
other requirements for the flame monitoring (e.g. combustion of coal dust). You will find infor-
mation on this devices in the corresponding manuals (DLT7650, DLT7600 and DLT7502/
DLT7503).

The task of the flame monitoring device is to scan the burner’s flame in combustion plants un-
affected from any condition in the combustion chamber (e.g. glowing nogging) and to release
the closing of the fuel valves at a flame blow out with an internal control command of the burn-
er control system.
The flame monitoring device has the following tasks:
– Scanning the burner flame unaffected of the conditions in the combustion chamber (e.g.
glowing refractory lining)
– internal release of the control command to close the fuel valves at a flame blow out with
the burner control system
Connect the following LAMTEC flame sensors:
FFS08 IR/UV, FFS07 IR/UV (also in version for Ex zone 1 or Ex zone 2).

11.2.1.2 Characteristics flame sensor

Input variables - optical flame sensor


Required input values from the flame's emitted radiation indication "Flame present”
– Spectral radiation region = 260......400nm (FFS07 UV-1, FFS08 UV-1)
– Spectral radiation region = 215....360 nm (FFS07 UV-4, FFS08 UV-4, replace UV-2)
– Spectral radiation region = 1200....2800 nm (FFS08 IR-1, FFS07 IR-1, FFS07 IR-1 T,
FFS08 IR-1T, FFS08 IR-1 T/S2)
– Pulse frequency ca. 10...200 Hz
– Pulse amplitude 10mV

11.2.1.3 Self Monitoring

– Signal processing with two separately constructed and alternately activated transmission
channels.
– Continuous comparison of the output levels for anticoincidence.
The transmission range of the digital frequency analysis covers signal transmittance between
10Hz or 25Hz (factory configuration) and 200 Hz.
Mains frequency signals and their harmonics are filtered, with a filter bandwidth of 3 Hz.
Setting of the sensitivity of the flame scanner FFS08 IR, FFS07 IR/UV.
Adjust sensitivity with switch S1 and S2. The switches are placed inside the scanner housing.

48
11 Appendix

WARNING!
Do not open FFS08 UV and FFS 06 UV!
Setting of the sensitivity is not possible for FFS08 UV and FFS06 UV.

FFS07

FFS05
(up to January 2014,
replaced by FFS07)

Fig. 11-3 FFS07, FFS 05 Adjusting the flame sensitivity - factory settings IR 50%/UV 100%
FFS08 IR

FFS06
(up to January 2014,
replaced by FFS08)

Fig. 11-4 FFS08 IR, FFS06: Adjusting the flame sensitivity - factory settings IR 50%

NOTICE
S1 and S2 must be set identically.

49
11 Appendix

11.2.2 General Information of the Optical Flame Monitoring

Notes on assembly and installation


The processes that occur during combustion give rise, inter alia, to a pulsing component of
the flame's radiation (flame flickering), whose oscillations (flame frequency) are relatively rap-
id at the flame's root (i.e. near the burner's mouth) and become slower toward is tip.
For individual monitoring, the flame sensor should be aligned in that way, that the first third of
the flame is observed.
The flame sensor's correct alignment is essential for achieving a high degree of availability
and/or selectivity.

WARNING!
We recommend to lay the supply cable, including their extension, on separate cable trays to
keep mains and control lines as well as high-energy power lines and equipment separated
from each other (e.g. ignition lines, ignition transformer, electrical motors, contactors). More-
over, avoid any parallel cable routing together with mains cables in trays

11.2.3 Optical Flame Sensors

11.2.3.1 Switching to Display the Flame Intensity

FFS07, FFS05 (is replaced by FFS07) and subtypes.


The sensor's circuit components are located on printed circuit board (PCBs) in a cylindrical
housing with a spray-proof, axial optical aperture.
The sensor meets the requirements of protection class IP 65.
Optical flame sensor FFS08, FFS06 (is replaced by FFS08) and subtypes (standard sensor
for FA1)
The sensor's circuit components are located on printed circuit boards (PCBs) in a cylindrical
housing with a spray-proof, lateral optical aperture. The sensor meets the requirements of pro-
tection class IP 65.
The computing circuit for the sensor types is located in the FA1.
Cabling from the sensor to the FA1 is 5-pole, static-screened with the sensor housing's poten-
tial (operating earth connection), a sixth cable is for measuring the flame signal during com-
missioning.

WARNING!
If the FA1 is used with an integral flame monitor, terminal 53 may not be connected to any oth-
er components

The optical flame sensors are supplied together with a connecting cable of ca. 2 m length. The
line between the sensor and the flame monitoring unit may be extended up to a distance of
500 m. For implementing an on-site extension we recommend a separate screened, five-wire
extension cable that can be connected to the sensor cable via an FG 24 (with ex-applications)
or FG 21 connector box, e.g.
cable type: LiYCY (blue, red, green, yellow, white) 5 x 1 x 0.5 mm2 (AWG 20)

50
11 Appendix

WARNING!
If the option "integral flame monitoring" is deactivated subsequently in the FA1 (e.g. an exter-
nal flame monitoring should be used), up to base version 4.0 the automatic flame guard plug-
in card has to be removed from the FA1, from base version 5.0 on the bridge 450 (beside the
96-pole plug) has to be switched.

The cable's screening may not be used as a low-frequency carrying operational link. The sen-
sors should be so mounted at the inspection aperture, that the burner's flame is properly vis-
ible across the entire combustion facility's "operating range”. For selective monitoring, the
inspection aperture should be so placed that the sensor covers the monitored flame's root
(near the burner's mouth). Attention should be paid to the fact that with extended tube collars
the part of the flame, which is covered by the sensor, becomes restricted. If necessary, the
inspection aperture should be sealed with a suitable protective glass sheet.
How to switch the display to flame intensity:
Press key F1 RESET.

Press key 15 twice.

Press key 15 again  back to the display of the fuel/air ratio control.

WARNING!
Control of the flame’s fault shut-down:
Emulate a simulation of a flame blow-off or the laps of the flame.
To this end, the fuel supply to the burner monitored by the flame sensor should be shut off.
Check that the safety interlock closing signal is triggered during the period tvAus < 1s after the
flame is extinguished. The FA1 displays the error code 004.

How to switch the display to flame intensity at the customer interface:

Press the selection key as long as the display shows the flame intensity.

WARNING!
Control of the flame’s fault shut-down:
Emulate a simulation of a flame blow-off or the laps of the flame.
To this end, the fuel supply to the burner monitored by the flame sensor should be shut off.
Check that the safety interlock closing signal is triggered during the period tvAus < 1 s, after
the flame is extinguished. The FA1 displays the error code 004.

11.3 Avoiding EMC Effects

The proper installation normally prevents from the EMC-adverse effects. In exceptional cases
it may be necessary by not traceable and /or not removable sources of interference to find an
adequate grounding point for the shielding.
1 In exceptional cases it is possible, that through the protected earth an interference level is
injected into the shielding. Unmotivated fault shut-downs (especially with low wanted sig-
nal) or temporary extraneous light may occur. In this cases the following may help beside
the fault clearance of the protected earth.
– a disconnection of the flame sensor shielding from the protective earth terminal at the
FA1 and the connection with the GND of the flame sensor (terminals 22 or 44)

51
11 Appendix

– In rarely cases the shielding may be disconnected like described in section a) and the
sensor housing may be grounded at the burner plate.
2 Adverse effects through coupling into the laid cable may be eliminated normally only with
the correct laying and in some cases with an adequate grounding point.
3 Adverse effects straight to the flame sensor may be suppressed with the reduction of the
sensitivity when there is a sufficient flame signal.

52
11 Appendix

11.4 Fault Codes

TRD Technical Regulations for Steam Boilers (P425 = 1, P836 = 1)


EN676 European standard 676 ’Automatic Forced Draught Burners for Gaseous Fuels "
(P425 = 1, P836 >1)

Fault Restart according to Description


Code TRD EN676
No.
000 0 0 No fault code available for this fault
001 0 3 Ignition flame does not appear.
H/Ü Check flame stability.
Check wiring.
Check ignition transformer and pilot burner.
Check flame sensor.
Check Parameter 788.
002 0 0 parasitic light failure
H/Ü Check wiring.
Check setting flame sensor.
Check Parameter 788.
003 0 3 Flame fault during ignition
H/Ü Check flame stability.
Check ignition transformer and pilot burner
Check flame sensor settings
004 1 1 Flame fault during operation
H/Ü Check flame stability
The switch off time for digital input "flame signal is <200ms!
For this reason, a flame fault can also have another cause, e.g.:
- The fuel solenoid valves close.(EMV, low voltage))
- "gas pressure < min" switch off time <1s
FMS with 660 R 0016 V4.3 with burner stationary
Check wiring between FMS and 660R0016 V4.3
Change 660 R 0016 V4.3 if wiring is correct.
005 0 3 Flame signal does not appear during 1st safety time
H/Ü Check flame stability.
Check wiring.
Check ignition transformer and pilot burner.
Check flame sensor.
Check Parameter 774, 775 and 788.
006 0 3 Flame signal goes out during stabilising time
H/Ü Check flame stability.
Check set pilot burner.
Check flame sensor.
007 0 3 The flame signal extinguishes during the first safety time
H/Ü Check flame stability.
Check set pilot burner.
Check flame sensor.
ETAMATIC: Check Jumper.

53
11 Appendix

Fault Restart according to Description


Code TRD EN676
No.
008 0 0 The flame signal extinguishes during the second safety time
H/Ü Check flame stability.
Check wiring.
Check flame sensor.
009 0 0 Flame signal does not appear during safety time
H/Ü Check flame stability.
Check wiring.
Check flame sensor.
Check Parameter 774, 775 and 788.
010 0 0 Flame signal goes out immediately after ignition
H/Ü If the flame extinguishes within three seconds after ignition, fault H010 is shown;
after that, fault H004 appears.
Check the flame stability.
Check the flame sensor setting.
Check the sensitivity of the sensor.
The deactivation time for the "Flame signal" digital input amounts to <200ms!
For this reason, a flame fault can also have another cause, e.g.:
- The solenoid fuel valve closes (EMC, low voltage)
- "Gas pressure < min" deactivation time <1s.
011 0 0 Internal fault: 5 sec. outside light monitoring period not kept
The fault can occur during an internal self-test.
Reset the fault. In the process, switch the mains voltage off and on again if neces-
sary.
Check all fuses in the device.
If the fault persists despite reset  exchange the device or respective card
012 0 0 relay module not connected or missing 24V supply for relay
Check the wiring between FMS and relay module 660R0016 and fuse F2 on the
FMS front panel.
FMS with relay module type 660 R 0016 V4.3 when the burner is at a standstill:
Check the wiring between FMS and 660 R 0016 V4.3.
If the wiring has been performed correctly:
Exchange relay module type 660 R 0016 V4.3.
013 1 3 main flame signals appears during ignition
If parameters 774 and 775 are set to value 3 or 4, only the ignition flame may be
present during ignition (up to the beginning of the second safety time). If the main
flame is detected in this time, fault S013 is displayed.
Check the flame sensor setting. The main flame sensor must detect only the main
flame and not the ignition flame.
102 0 0 Internal fault: Internal communication fifo has overflowed
H The fault can occur during an internal self-test.
Reset the fault. In the process, switch the mains voltage off and on again if neces-
sary.
Check all fuses in the device.
If the fault persists despite reset  exchange the device or respective card.

54
11 Appendix

Fault Restart according to Description


Code TRD EN676
No.
103 0 0 Internal fault: Error in misc. data
H/Ü The fault can occur during an internal self-test. A fault was discovered during the
reading of the redundant data in the EEPROM.
Reset the fault. In the process, switch the mains voltage off and on again if neces-
sary.
Check all fuses in the device.
Re-enter the curve.
Import the current data record into the device using the remote control software and
check this data record.
If the fault persists despite reset  the EEPROM is possibly defective:
Exchange the EEPROM.
Import the current data record into the device using the remote control software and
check this data record.
104 0 0 Internal Fault: D/A-Converter faulty
H Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If the fault message continues to persist exchange the device or respective card.
105 >88 3 Curve data faulty! Curve set no.:
H/Ü During an attempt to save the curve to the EEPROM / during the check of the
redundant curves, a fault was discovered.
Repeat the programming.
Reset the fault.
If this fault is still present, proceed as follows:
If this fault occurs after the number of curves has been expanded:
1. Select the corresponding curve set
2. Delete the memory
3. Program a new point
If the data was saved using the remote control software:
Import the curve data of the corresponding curve set into the device.
If this is not possible:
1. Select the corresponding curve set
2. Delete the memory
3. Re-enter the curve
Reset the fault.
If the fault persists  the EEPROM might be defective.
Order a new EEPROM from LAMTEC.
When ordering, enter the original purchase order number, sales order number, and
commission of the device.
Return the defective EEPROM in any case (for the address, see the overleaf of this
publication).
Exchange the EEPROM and import the current data record into the device using
the remote control software and check the result.
When exchanging this component, a basic setting must exist before you can con-
tinue to work with the device.
If you have saved the data of the device using the remote control software, it suf-
fices to reimport this saved data into the new EEPROM.
For more details, see the "Protected data record" description in the remote control
software.
If this is not possible, you must order a preprogrammed EEPROM from LAMTEC.

When ordering, you must enter the device number and software checksums. Only
in this way are mix-ups excluded. For the address, see the overleaf of this publica-
tion.

55
11 Appendix

Fault Restart according to Description


Code TRD EN676
No.
106 0 0 parameters not equal for parameter no.:
Ü Fault during an internal self-test. A fault was discovered during the reading of the
redundant data in the EEPROM.
After a software update:
Import the protected data recording into the device. If that is not possible:
Change the reported parameters once manually.
Reset the fault.
Reset the fault; switch the mains voltage off and on again if pertinent.
Re-enter the curve.
If the fault persists  the EEPROM is possibly defective:
Exchange the EEPROM, import the current data record into the device using the
remote control software, and check the data record.
107 0 0 Invalid configuration
H/Ü Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Using the remote control software, compare the current parameter setting and last
working data record.
108 0 0 Different input signals on main processor and monitoring processor terminal-
H Fault during an internal self-test.
The digital input signals for the main processor (H) and monitoring processor (Ü)
are compared and are not the same.
Reset the fault; switch the mains voltage off and on again if pertinent.
Check all fuses in the device.
A bouncing signal can lead to different states being detected between the main and
monitoring processors.
In the case of the main and monitoring processors, the detection of the digital input
signals takes place at slightly different times. A signal change is present only long
enough for the main processor to detect it, but not the monitoring processor.
Check the signal sequence.
If fault messages are constantly appearing one after the other  exchange the
device or the respective card (processor card).
110 0 0 CRC-16 test had found an error
H/Ü Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If the display remains dark or shows confusing characters, some or all of the LEDs
will light up and faults 111 and 140 will appear.
After the exchange of an EPROM or RAM:
- Remove the processor pc board
Check the components for the correct polarity (all notches point in the same direc-
tion).
Check whether all components are properly inserted (e.g., whether any prongs are
bent), and press them in firmly if necessary.
Check the proper seat of the processor card connection to the backplane.
Check the proper seat of the power supply card connection to the backplane.
If fault messages are constantly appearing one after the other  the EPROM pro-
gramme is possibly defective.
Request a new programme EPROM from LAMTEC with the precise specification of
the respective purchase order number, sales order number, and commission of the
device. Return the defective EPROM in any case (for the address, see the overleaf
of this publication).

56
11 Appendix

Fault Restart according to Description


Code TRD EN676
No.
111 0 0 RAM-Test detected error
H/Ü Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
Check the curve points of the main and monitoring processors for irregularities.
 Remote software: Curve table and/or set value graphic.
If the display remains dark or shows confusing characters, some or all of the LEDs
will light up and faults 111 and 140 will appear.
After the exchange of an EPROM or RAM:
- Remove the processor pc board
Check the components for the correct polarity (all notches point in the same direc-
tion).
Check whether all components are properly inserted (e.g., whether any prongs are
bent), and press them in firmly if necessary.
Check the proper seat of the processor card connection to the backplane.
Check the proper seat of the power supply card connection to the backplane.
If the fault occurs only sporadically, a software update to at least Version 5.7 may
help.
If fault messages are constantly appearing one after the other  exchange the
device or the respective card.
112 0 0 ETAMATICselftest exceeds timeout limit
Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If fault messages are constantly appearing one after the other  exchange the
device or respective card.
120 1 1 Different operating modes for mon. and main processor
H/Ü Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
In the case of the main and monitoring processors, the detection of the digital input
signals takes place at slightly different times.A signal change is present only long
enough for the main processor to detect it, but not the monitoring processor.
Check the signal sequence.
121 0 0 The correction is outside the permissible range. Channel: 1
Ü The monitoring processor checks whether the current correction values lie within
the set range.
Check the correction range.
If fault messages are constantly appearing one after the other → exchange the
device or respective card.
122 0 0 Correction is outside permissible range. Channel : 2
Ü See S121
123 0 0 Correction is outside permissible range. Channel : 3
Ü See S121
124 0 0 Correction is outside permissible range. Channel : 4
Ü See S121
125 0 0 Correction is outside permissible range. Channel : 5
Ü See S121

57
11 Appendix

Fault Restart according to Description


Code TRD EN676
No.
139 0 0 Integr. Flame Detector: selftest fault
H/Ü Especially in the case of oil flames: Reduce the intensity of the flame sensor.
Check the hardware and software configuration:
If the hardware jumper is set to external flame monitoring and parameter 2 is set to
integrated flame monitoring, fault 139 appears as soon as the digital input of the
external flame monitoring becomes active. If the flame signal is detected via the
flame sensor of the integrated flame monitoring in this configuration, the display of
the digital input cycles and a flame fault appears.
140 0 0 The EEPROM is defective.
H/Ü Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If the display remains dark or shows confusing characters, some or all of the LEDs
will light up and faults 111 and 140 will appear.
The EEPROM of the respective processors contains important operating data, the
parameters, and the curves.
During an attempt to save the curve to the EEPROM, a fault was discovered.
Repeat the programming.
After the exchange of an EPROM or RAM:
Remove the processor pc board
Check the components for the correct polarity (all notches point in the same direc-
tion).
Check whether all components are properly inserted (e.g., whether any prongs are
bent), and press them in firmly if necessary.
Check the proper seat of the processor card connection to the backplane.
Check the proper seat of the power supply card connection to the backplane.
Reset the fault if it is still present; the EEPROM is possibly defective.
Request a new EEPROM from LAMTEC with the precise specification of the
respective purchase order number, sales order number, and commission of the
device.
Return the defective EEPROM in any case (for the address, see the overleaf of this
publication).
Exchange the EEPROM, import the current data record into the device using the
remote control software, and check the data record.
When exchanging this component, a basic setting must exist before you can con-
tinue to work with the device.
If you have saved the data of the device using the remote control software, it suf-
fices to reimport this saved data into the new EEPROM.
For more details, see the "Protected data record" description in the remote control
software.
If this is not possible, you must order a preprogrammed EEPROM from LAMTEC.
When ordering, you must enter the device number and software checksums. Only
in this way are mix-ups excluded. For the address, see the overleaf of this publica-
tion.
141 0 0 Potentiometer faulty, feedback changing too quickly: channel 1
H/Ü The return values of a three-point-step servo output change faster than specified as
maximum in parameters 12-16.
Check the wiring; check the potentiometers for short circuit.
It is possible that the range limit switch is set higher than the end of the range of the
potentiometer. The upper value is exceeded and changes quickly towards zero.
Otherwise, exchange the potentiometers.

58
11 Appendix

Fault Restart according to Description


Code TRD EN676
No.
142 0 0 Potentiometer faulty, feedback changing too quickly: channel 2
H/Ü See S141
143 0 0 Potentiometer faulty, feedback changing too quickly: channel 3
H/Ü See S141
144 0 0 Potentiometer faulty, feedback changing too quickly: channel 4
H/Ü See S141
145 0 0 Potentiometer faulty, feedback changing too quickly: channel 5
H/Ü See S141
151 >88 3 Reci damper deactivated, out of time in reaching CLOSED position, channel:1
H/Ü The actuating device may not reach its set value since it is limited by a limit switch:
Check the setting of the set values/limit switches.
The actuating device may not have reached its set value quickly enough.
This is especially possible in the case of actuating devices that are activated sepa-
rately and that must then travel the full distance (e.g., recirculation or exhaust valve
or in case of a floating curve switchover):
Increase the adjusting speed on the motor (if possible)
or
Limit the adjusting range by limit switch (to save runtime)
The return does not move even though the actuating device is moving:
Check the connection of the return to the device (see the connection diagram)
To localise the fault, simulate the return at various points of the return circuit (using
a potentiometer or a current sensor).
The motor does not move:
Check whether "OPEN" or "CLOSED" signals are present on the motor.
Check the voltage supply circuit on the motor.
FMS/VMS:
Check whether the "OPEN" or "CLOSED" relay is actuated.
If yes:
Check the fuse of the relay module.
If no:
Make sure that no fault is present (can be seen on the fault LED).
Check the F2 fuse (on the front panel of the power supply unit).
Check the connection between FMS/VMS and the relay module.
152 >88 3 the same as P 151, but channel: 2
H/Ü See S151
153 >88 3 the same as P 151, but channel: 3
H/Ü See S151
154 >88 3 the same as P 151, but channel: 4
H/Ü See S151
155 >88 3 the same as P 151, but channel: 5
H/Ü See S151
161 >88 3 Monitoring direction of ratation: channel 1
H/Ü The channel is not running or does not start on time. During operation, the channel
briefly changes direction.
Check the servo motor.
162 >88 3 Monitoring direction of ratation: channel 2
H/Ü The channel is not running or does not start on time. During operation, the channel
briefly changes direction.
Check the servo motor.

59
11 Appendix

Fault Restart according to Description


Code TRD EN676
No.
163 >88 3 Monitoring direction of ratation: channel 3
H/Ü The channel is not running or does not start on time. During operation, the channel
briefly changes direction.
Check the servo motor.
165 >88 3 Monitoring direction of ratation: channel 5
H/Ü The channel is not running or does not start on time. During operation, the channel
briefly changes direction.
Check the servo motor.
171 >88 3 Dead band over range too long: channel 1
172 >88 3 Dead band over range too long: channel 2
173 >88 3 Dead band over range too long: channel 3
174 >88 3 Dead band over range too long: channel 4
175 >88 3 Dead band over range too long: channel 5
181 >88 3 Dead band under range too long: channel1
182 >88 3 Dead band under range too long: channel 2
183 >88 3 Dead band under range too long: channel 3
184 >88 3 Dead band under range too long: channel 4
185 >88 3 Dead band under range too long: channel 5
191 1 1 1st monitoring band over range too long: channel 1
192 1 1 1st monitoring band over range too long. Channel: 2
193 1 1 1st monitoring band over range too long. Channel: 3
194 1 1 1st monitoring band over range too long. Channel: 4
195 1 1 1st monitoring band over range too long. Channel: 5
201 1 1 1st monitoring band under range too long. Channel: 1
H/Ü Parameter adjustment for drift compensation P.104 to 16
for prevention of sporadic faults H201 at ETAMATIC / FMS / VMS with constant
control output.
202 1 1 1st monitoring band under range too long. Channel: 2
203 1 1 1st monitoring band under range too long. Channel: 3
204 1 1 1st monitoring band under range too long. Channel: 4
205 1 1 1st monitoring band under range too long. Channel: 5
211 0 0 2nd monitoring band over range too long. Channel: 1
212 0 0 2nd monitoring band over range too long. Channel: 2
213 0 0 2nd monitoring band over range too long. Channel: 3
214 0 0 2nd monitoring band over range too long. Channel: 4
215 0 0 2nd monitoring band over range too long. Channel: 5
221 0 0 2nd monitoring band under range too long. Channel: 1
222 0 0 2nd monitoring band under range too long. Channel: 2
223 0 0 2nd monitoring band under range too long. Channel: 3
224 0 0 2nd monitoring band under range too long. Channel: 4
225 0 0 2nd monitoring band under range too long. Channel: 5

60
11 Appendix

Fault Restart according to Description


Code TRD EN676
No.
231 >88 3 Fuel/air ratio control blocked: channel 1
232 >88 3 Fuel/air ratio control blocked: channel 2
233 >88 3 Fuel/air ratio control blocked: channel 3
234 >88 3 Fuel/air ratio control blocked: channel 4
235 >88 3 Fuel/air ratio control blocked: channel 5
301 1 1 Broken wire at firing rate input -1
H/Ü Check the wiring.
302 1 1 Broken wire at firing rate input-2
H/Ü Check the wiring.
320 1 1 Broken wire at correction input
H/Ü Check the wiring.
321 1 1 Broken wire at feedback channel 1
H/Ü Check the wiring; check the potentiometers for short circuit.
322 1 1 Broken wire at feedback channel 2
H/Ü Check the wiring; check the potentiometers for short circuit.
323 1 1 Broken wire at feedback channel 3
H/Ü Check the wiring; check the potentiometers for short circuit.
324 1 1 Broken wire at feedback channel 4
H/Ü Check the wiring; check the potentiometers for short circuit.
325 1 1 Broken wire at feedback channel 5
H/Ü Check the wiring; check the potentiometers for short circuit.
351 1 1 Different status of ignition position relay
H/Ü Check the signal for curve selection.
Bouncing signal?
Possible bus problems.
352 >88 3 Invalid curve selection (no signals)
H/Ü Check the signal for curve selection.
Possible bus problems.
353 >88 3 Invalid curve selection (several signals)
H/Ü Check the signal for curve selection.
Possible bus problems.
360 0 0 Shut down from O2controller (1) or CO controller (2) :
H Initially, the time from parameter P904 "O2 trim active after ignition in seconds" runs
out before the fault is permitted.
361 1 1 Different status of ignition position relay
S362 1 1 Carry out burner servicing
H/Ü The maintenance counter is reset by changing parameter 713 or 714
363 1 1 permissible O2 value was fallen below
Initially, the time from parameter P904 "O2 trim active after ignition in seconds" runs
out before the fault is permitted. After that, the monitoring time from P966 starts.
Also works without an active O2 controller
(from 5.4):
After ignition, the monitoring time from P966 starts immediately.

61
11 Appendix

Fault Restart according to Description


Code TRD EN676
No.
370 0 0 Internal communication between the processors faulty
H/Ü Different values in the main and monitoring processors. Reimport the curves and/or
parameter set.
A sporadic occurrence of fault H370 is due to EMC interference immunity of the wir-
ing or environment.
If the fault persists, exchange the processor pc board.
371 0 0 Output for internal firing rate faulty
372 0 0 Deviation of the firing rate value between the main processor and the moni-
toring processor is too high.
Ü Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If fault messages are constantly appearing one after the other <Symbol For-
mat="Symbol">→ </Symbol> exchange the device or respective card.
381 0 0 Deviation between main processor and monitoring processor too great: cor-
rection channel 1
Ü Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If fault messages are constantly appearing one after the other  exchange the
device or the respective card.
382 0 0 Deviation between main processor and monitoring processor too great: cor-
rection channel 2
Ü Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If fault messages are constantly appearing one after the other <Symbol For-
mat="Symbol">→</Symbol> exchange the device or the respective card.
391 0 0 Curves sentence does not fit to the chosen fuel.
Ü Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if pertinent.
Check all fuses in the device.
At the curve set selection by BUS, terminal 75 is missing for plausibility check, or
rather terminal 75 can be seen at oil curve.
If fault messages are constantly appearing one after the other <Symbol For-
mat="Symbol">→ </Symbol> exchange the device or the respective card.
392 0 0 Remote not responding (time-out)
393 0 0 Remote shut down triggered.
394 0 0 BURNER-ON/OFF Remote signal missing.
400 0 0 Different point number at programming
Ü Re-enter the curve.
451 1 1 Ignition position was left in ignition mode. Channel: 1
H/Ü In case of a constant output:
Possible EMC influences due to ignition transformer; check the frequency converter
settings
452 1 1 Ignition position was left in ignition mode. Channel: 2
H/Ü In case of a constant output:
Possible EMC influences due to ignition transformer; check the frequency converter
settings

62
11 Appendix

Fault Restart according to Description


Code TRD EN676
No.
453 1 1 Ignition position was left in ignition mode. Channel: 3
H/Ü In case of a constant output:
Possible EMC influences due to ignition transformer; check the frequency converter
settings
454 1 1 Ignition position was left in ignition mode. Channel: 4
H/Ü In case of a constant output:
Possible EMC influences due to ignition transformer; check the frequency converter
settings
455 1 1 Ignition position was left in ignition mode. Channel: 5
H/Ü In case of a constant output:
Possible EMC influences due to ignition transformer; check the frequency converter
settings
500 0 0 Internal comparison: relay out terminal 67 not picking up.
H Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If fault messages are constantly appearing one after the other <Symbol For-
mat="Symbol">→ </Symbol> exchange the device or respective card.
501 0 0 Internal comparison: The relay output terminal 43 or 68 (ETAMATIC) does not
respond.
H See S500
502 0 0 Internal comparison: relay out terminal 16 or 65 (ETAMATIC) not picking up.
H See S500
503 0 0 Internal comparison: relay out terminal 11 or 66 (ETAMATIC) not picking up.
H See S500
504 0 0 Internal comparison: relay out terminal 45 not picking up.
H See S500
505 0 0 Internal comparison: relay out terminal 68 or 61 (ETAMATIC) not picking up.
H See S500
506 0 0 Internal comparison: relay out terminal 36 (ETAMATIC K202) not picking up.
H See S500
507 0 0 Internal comparison: relay out terminal 41 not picking up.
H See S500
508 0 0 Internal comparison: relay out terminal 76 not picking up.
H See S500
509 0 0 Internal comparison: Output K203 not picking up.
See S500
510 0 0 Internal comparison: Output K201 not picking up.
See S500
520 0 0 Internal comparison: relay output terminal 67 not dropping out.
H See S500
521 0 0 Internal comparison: relay output terminal 43 or 68 (ETAMATIC) not dropping
out.
H See S500

63
11 Appendix

Fault Restart according to Description


Code TRD EN676
No.
522 0 0 Internal comparison: relay output terminal 16 or 65 (ETAMATIC) not dropping
out.
H See S500
523 0 0 Internal comparison: relay output terminal 11 or 66 (ETAMATIC) not dropping
out.
H See S500
524 0 0 Internal comparison: relay output terminal 45 not dropping out.
H See S500
525 0 0 Internal comparison: relay output terminal 68 or 61 (ETAMATIC) not dropping
out.
H See S500
526 0 0 Internal comparison: relay output terminal 36 not dropping out.
H See S500
527 0 0 Internal comparison: relay output terminal 41 not dropping out.
H See S500
528 0 0 Internal comparison: relay output terminal 76 not dropping out.
H See S500
529 0 0 Internal comparison: Output K203 not dropping out.
See S500
530 0 0 Internal comparison: Output K201 not dropping out.
See S500
540 0 0 TRIAC selftest : optical couplers are not OFF
See S500
541 0 0 TRIAC selftest : all TRIACS are not supplied with voltage!
Terminal 60 not connected or fuse F5 defective.
Check whether terminals 26 and 60 are supply by the same phase.
See S500
542 0 0 TRIAC selftest : main gas 1 is currentless
See S500
543 0 0 TRIAC selftest: main gas 2 is currentless
If a test current is flowing during the TRIAC self test and no test current is at the ter-
minal for Main Gas 2, the software assumes that a fault is present.
- The connector of Main Gas 2 is not connected
- The solenoid valve is defective
- The TRIAC for Main Gas 2 is defective in ETAMATIC.
If the device only works for oil operation - disconnect Main Gas 1.
544 0 0 TRIAC selftest : oil pump is currentless
See S500
545 0 0 TRIAC selftest : oil valve is currentless
See S500
546 0 0 TRIAC selftest : Ignition transformer is currentless
See S500
547 0 0 TRIAC selftest : ignition valve is currentless
See S500

64
11 Appendix

Fault Restart according to Description


Code TRD EN676
No.
550 0 0 Oil fuel blocked because a required solenoid valve is not connected
The test current for the TRIAC self-test cannot flow.
551 0 0 Gas fuel blocked because a required solenoid valve is not connected
The test current for the TRIAC self-test cannot flow.
552 0 0 No valve connected? Check fuse F3 and F4
The oil and gas valves are not connected.
600 0 0 Programme check time of sequencer expired.
H/Ü If no ignition takes place after starting within this time (parameter 777) after ’Burner
ON,’ a fault is output.
If the parameter is set to 0, no fault appears.
601 0 0 Leak check fault: gas pressure still applied.
602 0 0 Leak check fault: gas pressure missing.
603 0 0 Vent gas line manually.
604 0 0 Flame signal not arriving in time.
605 >88 3 Oil pressure < min !!!
606 1 1 Gas > min appears in oil operation.
607 1 1 Ignition position acknowledgement dropping.
608 0 0 Boiler safety chain dropping.
609 1 1 Gas safety chain dropping.
610 >88 3 Oil safety chain dropping.
611 >88 3 Gas pressure too low
612 1 0 Gas pressure too high.
613 0 0 Air pressure signal missing.
614 1 1 F.A. safety interl. chain gets OFF
615 0 0 Flame is blown away during blow out of oil lance
616 1 1 Ignition flame goes out in standby operation
617 1 1 Continuous ignition flame goes out under operation
618 0 0 Oil circulation: Temperature does not rise up within 45 sec.
620 0 0 Oil lance blow out: Delay for opening not kept
621 0 0 Oil lance blow out: Oil valve actuator not in ignition position
622 0 0 Oil lance blow out: blow out period too long
623 0 0 Atomizer switch-ON-pre-period not kept
624 >88 3 Oil pressure too low
625 >88 3 Oil pressure too high
626 >88 3 Atomizer air pressure too low
627 >88 3 General safety chain missing
700 0 0 Pre-ventilating signal present, without signal on terminal 2.
H VMS, for ETA V Term. 58
701 0 0 Flame signal present, without signal on terminal 2.
H VMS, for ETA V Term. 58
702 0 0 Flame signal appears during pre-ventilating.
H VMS, for ETA V Term. 58

65
11 Appendix

Fault Restart according to Description


Code TRD EN676
No.
703 0 0 Flame signal goes out even though signal on terminal 2 still present.
H VMS, for ETA V Term. 58
711 0 0 Illegal operating mode change
Ü Check the "Burner ON" signal.
Bouncing signal?
712 0 0
713 0 0 Incorrect signal combination in operating mode AU
714 0 0 Incorrect signal combination in operating mode BE
715 0 0 Incorrect signal combination in operating mode VO
716 0 0 Incorrect signal combination in operating mode ZP
717 0 0 Incorrect signal combination in operating mode ZU
718 0 0
719 0 0 Fuel valves open too long without flame
720 0 0 Ignition transformer switched on too long
721 0 0 Ignition valve open too long
722 0 0 Fuel valves open in maintenance mode
723 0 0 Ignition process taking too long
724 0 0 Gas valves open when burning oil
725 0 0 Oil valves open when burning gas
726 0 0 Main gas 2 open without main gas 1
727 0 0 Main gas 1 illegally open
728 0 0 Main gas valves and ignition valve open too long
729 0 0 Ignition process taking too long (without pilot burner)
730 0 0 Maintenance mode without pilot burner
731 0 0 Ignition valve opened without ignition burner
732 0 0 Incorrect signal combination during operation
733 0 0 Incorrect signal combination after operation
734 0 0 Pre-ventilating time not complied with
735 0 0 Fuel safety chain missing
736 0 0 Leak check: both gas valves open
737 0 0 Seal tightness check: Main Gas 2 delayed for too long at deactivation.
738 0 0 Leak check: main gas 2 missing
739 0 0 Seal tightness check: Main Gas 2 open for too long.
740 0 0 Seal tightness check: Main Gas 1 leaky.
741 0 0 Seal tightness check: Main Gas 1 open for too long.
742 0 0 Seal tightness check: Main Gas 2 leaky.
743 0 0 Flame monitoring: flame after-burn too long
Ü Burning duration (parameter 789) set to be too short.
744 0 0 Flame monitoring: flame on again
745 0 0 Programme check time exceeded.
747 0 0 Leak check: ventilating into boiler not allowed
750 0 0 Shut-down on faults via bus.

66
11 Appendix

Fault Restart according to Description


Code TRD EN676
No.
751 >88 3 No data transfer via the bus (time-out).
759 0 0 The "Setting" operating mode exceeded the 24-hour time limit.
760 0 0 Change of curve selection during setting not allowed
761 0 0 Change of curve lasts too long
The curve set change takes too long/could not be performed.
e.g.: The fuel safety chain is missing
763 0 0 different curve selection between the processors
764 1 1 CO-Controller, internal fault no. -
765 0 0 Parameter setting error: The channel for solo-fuel is not to determine.
Check the parametrisation of the channel configuration.

766 0 0 The limited firing rate (maximum firing rate without additional-fuel) does not
exists in the priority curves
Check the programming of the priority curves (assignment of the fuel channels and
their programming).
767 0 0 One parameter of the interpolation type for non-fuels is invalid
Check parameters 390 through 394
769 0 0 Ignition while mixed fuel operation or burner-start with solo fuel-A
770 0 0 Fill-Time for fuel-A too long
791 >88 3 Bus master is in a stop.
792 >88 3 Bus data length incorrectly configured.
793 >88 3 Bus master is decoupled.
800 0 0 Error in parameters, for parameter no.:
888 0 0 Fault block activated !
889 0 0 Time interval between remote-fault-resets is too short.
EN 14459 permits a remote unlocking only 4 x within 15 minutes.
The fault release is monitored by the remote control software, LAMTEC system
bus, and field bus (parameter 19). When exceeded, fault deactivation H889 is gen-
erated and additional remote fault releases are ignored.
After a waiting period, another remote fault release can be performed.
Fault deactivation H889 also takes place if the fault release was sent even though
none is present!
The release is monitored by terminal, while the programming unit and customer
interface are switched of by the standard setting of parameter 19. A release through
the front panel is always possible.
900 0 0 Error in self-test sequencer.
H/Ü Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
If fault messages are constantly appearing one after the other  exchange the
device or respective card.
If the fault appears after a sotware update, the version of the monitoring processor
may be incompatible with the version of the main processor.
901 0 0 Terminal 10 + 24 Volt switch-off faulty.
H/Ü Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If fault messages are constantly appearing one after the other  exchange the
device or respective card.

67
11 Appendix

Fault Restart according to Description


Code TRD EN676
No.
902 0 0 Error in over-voltage self-test.
H/Ü Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If fault messages are constantly appearing one after the other  exchange the
device or respective card.
903 0 0 Error in optical coupler self-test terminal -
H/Ü Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If fault messages are constantly appearing one after the other  exchange the
device or respective card.
For ETAMATIC:
Are another 24V than those of terminal 24 being used?
Check the voltage level.
Short circuit on the 24V
Disconnect 24: no arrow must be pointing at digital inputs.
Connect terminal 24 to only one input
Voltage on
If the fault still occurs: Deactivation in ETAMATIC defective.
904 1 1 Error in reference of firing rate
Ü Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If fault messages are constantly appearing one after the other  exchange the
device or respective card.
Using the device enter the Setting mode for about 3 seconds and then return to the
Automatic mode to reimport the reference voltage.
The potentiometer possibly has the incorrect polarity, is incorrectly connected (cen-
tre pick-up mixed up with the outer one), or is defective.
905 1 1 Error in reference element of main processor
Ü Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If fault messages are constantly appearing one after the other  exchange the
device or respective card.
906 1 1 Error in reference element of monitoring processor
H Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If fault messages are constantly appearing one after the other  exchange the
device or respective card.
907 1 1 Curve set adjustment via LAMTEC SYSTEM BUS, selftest recognizes fault
911 1 1 Error in reference, channel: 1
Ü Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If fault messages are constantly appearing one after the other  exchange the
device or respective card.
Using the device enter the Setting mode for about 3 seconds and then return to the
Automatic mode to reimport the reference voltage.
The potentiometer possibly has the incorrect polarity, is incorrectly connected (cen-
tre pick-up mixed up with the outer one), or is defective.

68
11 Appendix

Fault Restart according to Description


Code TRD EN676
No.
912 1 1 Error in reference, channel: 2
Ü See S911
913 1 1 Error in reference, channel: 3
Ü See S911
914 1 1 Error in reference, channel: 4
Ü See S911
915 1 1 Fault in reference, duct: 5
Ü See S911
921 0 0 Relay driver self-test : output terminal 11 or 66 (ETAMATIC) faulty.
H/Ü Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If fault messages are constantly appearing one after the other  exchange the
device or respective card.
FMS with 660 R 0016 V4.3 when the burner is at a standstill:
Check the wiring between FMS and 660 R 0016 V4.3.
If the wiring has been performed correctly: exchange 660 R 0016 V4.3.
FMS with 660 R 0016 V4.3 at start of burner:
From the start of the burner, relay module type 660 R 0016 V4.3 checks the follow-
ing outputs:
- Ignition transformer (terminal 86)
- Ignition valves (terminal 85)
- Oil valves (terminal 84)
- Main Gas 1 (terminal 82)
- Main Gas 2 (terminal 83)
If faults H921 (in case of starting with gas as the fuel), H923, H924 (in case of start-
ing with O2 as the fuel) occur by the time ignition is completed, the following faults
may be present:
- Lack of or too little firing rates at terminals 82 through 86
- Failure of fuses F1-F4 or F6
- Actual defect in one of the safety-related switching channels
For further troubleshooting, the diagnostic mode can be activated (see DLT6089/
DLT6065).
922 0 0 Relay driver self-test : output terminal 16 or 65 (ETAMATIC) faulty.
H/Ü See S921
923 0 0 Relay driver self-test : output terminal 43 or 68 (ETAMATIC) faulty.
H/Ü See S921
924 0 0 Relay driver self-test : output terminal 67 faulty
H/Ü See S921
925 0 0 Relay driver self-test : output terminal 45 faulty.
H/Ü See S921
926 0 0 Relay driver self-test : output terminal 68 or 61 (ETAMATIC) faulty.
H/Ü See S921
927 0 0 Relay driver self-test : output terminal 36 (ETAMATIC K202) faulty.
H/Ü See S921
929 0 0 Relay driver self-test : output terminal 76 faulty
H/Ü See S921

69
11 Appendix

Fault Restart according to Description


Code TRD EN676
No.
930 0 0 Relay driver self-test : Output K203 defect.
H/Ü See S921
931 0 0 Relay driver self-test : Output K201 defect.
H/Ü See S921
997 >88 3 Default language missing or LANGUAGE-FLASH defect
Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If fault messages are constantly appearing one after the other  exchange the
device or respective card.
998 0 0 Internal fault: main loop is too slow.
H/Ü Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If fault messages are constantly appearing one after the other <Symbol For-
mat="Symbol">→</Symbol> exchange the device or respective card.
999 0 0 Internal fault Number -
H The internal procedure is faulty, and the additional number indicates the position of
the fault within the firmware.
Internal fault number 2:
This fault is triggered by the watchdog processor, when these do not match with the
burner sequencer’s behaviour of the main processor.
Possible cause:
The HP activates the maintenance mode without any permission
The HP changes into a mixed operation without any permission
Internal fault number 3:
If the fault occurs once, it may be caused by EMC interference.
If the fault occurs often, the processor pc board is defective.
Internal fault number 4:
The monitoring processor has not detected a signal change at the "Air pressure
monitor" input. This can occur if the "Air pressure monitor" input is present at
BURNER START and is only briefly deactivated. This fault occurs frequently when
the fan is started by an external control system.
ETAMATIC:
Before A4a4002: the "Air pressure monitor" input appears during the TRIAC self-
test before the fan output is actuated by ETAMATIC!
Internal fault number 7:
This fault occurs when the "Burner On" and "Pre-venting" signals occur in the wrong
order or too quickly in sequence during the postpurge time in the case of devices
without a burner sequencer (VMS / ETAMATIC V).
No fault occurs if the devices switches to the "Ready" (BE) mode downstream of the
"Burner On" input before the "Pre-venting" signal is sent.
Internal fault number 22:
A fault occurred during the assumption of the curve in the EEPROM.
 Check the curve. Re-enter if required. This fault is possible only in connection
with the programming unit!
Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If fault messages are constantly appearing one after the other  exchange the
device or respective card.

70
11 Appendix

11.5 Calling Up the Condition of the Digital Inputs

Mit den Tasten 16 und 17 auf DIGITALE EINGÄNGE schalten.

Bedeutung der digitalen Eingänge FA1

 = Signal liegt an
 = Signal liegt nicht an

71
11 Appendix

11.6 Tips and Tricks

Oil pressure does not build up in time.


Extending the transformer pre-energise time (P 782) starts the pump sooner.

11.6.1 Set Pilot Burner

Setting the "Service mode" parameter (P 787) causes the FA1 operating program to run only
up to the stabilisation time. But up to 5 successive starts can be attempted without pre-purge
and without valve leakage test. After setting the pilot burner, set parameter back to 0

NOTICE
Resetting a fault with a total reset clears the internal counter for the service mode. The next
start-up, pre-purge again.

11.6.2 Checking the Safety Times

If it is required to measure the installation's safety times at a later time (e.g. as part of an in-
stallation's acceptance tests). Do not disconnect the magnetic valves before start-up. This is
monitored by the FA1's self-testing circuit, and results in emergency shut-down.
Disconnect the ignition position's acknowledgement function (term. 46). Start-up and wait until
the ignition position is reached. On the self-test's completion (ca. 5 sec), the magnetic valve
can be disconnected. Reconnect the ignition position acknowledgement function.
The installation starts up.

72
11 Appendix

11.7 Process Sequence Charts

Fig. 11-5 Process sequence chart gas operation with pilot burner and actuator

73
11 Appendix

Fig. 11-6 Process sequence chart gas without pilot burner, with actuator

74
11 Appendix

Fig. 11-7 Process sequence chart oil with pilot burner and actuator

75
11 Appendix

Fig. 11-8 Process sequence chart oil without pilot burner, with actuator

76
11 Appendix

Key to process sequence charts

Any condition
t1 Wait for gas safety interlock circuit air pressure monitor min. scan any
t2 Time for pressure build-up in the gas test line (only with valve leakage test activated) 2 sec.
t3 Servo drive running time 30-60 sec.
t4 Re-circulation damper delay 0-t5
t5 Aeration time 1-999 sec. adjustable
t6 Transformer pre-energise time 3 sec.
t7 1st safety period 4 sec.
t8 Stabilisation period 3 sec.
nd
t9’ 2 safety period 5 sec.
t9’’ 2nd safety period 3 sec.
t9’’’ Safety period 3 sec.
t9’’’’ Safety period 4 sec.
t10 Operating phase any
t11 Control mode any
t12 Time for pressure relief in the gas test line 3 sec.
t13 Post-purge time 0-999 s adjustable
t14 Control elements at base firing rate
t15 Post-combustion time 0-20 s** adjustable
t16 Flame extinguishing check 5 sec.
t17 Valve leakage test, gas valve 2 30 sec.
t18 Triac selftest

77
11 Appendix

Footnote to the Process Sequence Chart FA1


(1) Flame intensity to adjust the flame sensor (not connected during operation)
Here you can measure the flame intensity to adjust the flame sensor.
You can also determine the flame frequency with a multimeter which can determine the frequency with an AC meas-
urement
Because there is a fluctuation in the flame frequency, this is only a rough estimate for the frequency range (Not con-
nect during the operation!).
(2) Module 2 (optional):
Input for PT100 temperature sensor for the option "Control by atmospheric conditions". Sensor cable shielded sepa-
rately on PE or terminal 44.
Alternatively, there is the option (2. correction input current). With this, a current signal of 0/4 ... 20 mA can be used for
correction. Terminal 39- and terminal 40+ (for ETAMATIC S with speed feedback, only 4 ... 20 mA can be set).
(3) Alternatively you may connect the ground to terminal 44 instead of terminal 22.
(4) Burner firing rate controller actual value of int. firing rate
Steam pressure: 0/4-20 mA terminal 3/4/5 (terminal 20/21 connected)
External firing rate input: 0/4-20 mA terminal 3/4/5 (terminal 19/21 connected)
(5) For connection of other LAMTEC devices, e.g. O2 measurement with LAMTEC SYSTEM BUS
(6) For connection of an external control system - for visualisation or laptop
(7) If the recirculation signal is missing during operation, the recirculation channel remains closed or moves to the closed
** position (only valid for ETAMATIC, the internal recirculation signal is always in state 1 at ETAMATIC OEM).
If parameter 427 (VODelR) contains "0" , the recirculation channel remains closed during the pre-purge period.
Alternatively you may use terminal 54 as ignition flame input. In this case you must set P 788 to value 1.
(8) Terminals 1 and 2 at ETAMATIC
*** Extra cost option:
This is a monitor output where different values can be issued (0/4 ... 20 mA) for example: Setpoint of the individual
channels, actual value of the individual channels, actual value of the internal firing rate (chargeable option)
The ETAMATIC S has no monitor output, because the setpoint of channel 1 is preset by terminals 1 and 2.
The output (e.g. internal firing rate) is adjusted via optional LSB module’s.

Parameters for the footnote:


Nr. FMS ETA Short Text Description Min Max Default
/FA1
17 4 4 Etam.OEM ETAMATIC OEM (0=ETAMATIC, 1=ETAMATIC OEM, 0 3 
2=BurnerControl, 3=Special
0 = ETAMATIC
1 = ETAMATIC OEM
2 = BurnerControl FA1
3 = BurnerControl FA1 without continuous output (from
Software version v5.5 on)
Terminal connections:
No. ETAMATIC ETAMATIC OEM Burner Control FA1 Burner Control FA1
Special
59 release setting release setting release setting
58 burner on burner on burner on burner on
57 fault release oil pressure < max oil pressure < max oil pressure < max
56 control release control release pre-purge suppression pre-purge suppression
55 SIC gas SIC gas SIC gas SIC gas
54 P788 P788 P788 P788
0=recirculation on 0=gas pressure<max 0=gas pressure<max 0=gas pressure<max
1=ignition flame signal 1=ignition flame signal 1=ignition flame signal 1=ignition flame signal

78
11 Appendix

53 flame signal flame signal flame signal flame signal


52 SIC boiler SIC common SIC common SIC common
51 SIC oil SIC oil SIC oil SIC oil
50 setpoint switching setpoint switching setpoint switching high fire acknowledge-
ment
49 fuel selection fuel selection fuel selection fuel selection
48 air pressure monitor air pressure monitor air pressure monitor air pressure monitor
47 gas pressure>min gas pressure>min gas pressure>min gas pressure>min
(valve leakage test) (valve leakage test) (valve leakage test) (valve leakage test))
46 ignition position P 762 P 762 ignition position
acknowledgement 0 = no function 0 = no function acknowledgement
1 = oil pressure>min / 1 =oil pressure>min /
atomiser air pressure atomiser air pressure
P 18 P 18
0 = oil pressure>min 0 = oil pressure>min
(atomiser) (atomiser)
1 = atomiser air pres- 1 = atomiser air pres-
sure (rotation atomiser) sure (rotation atomiser)

Nr. FMS ETA Short Text Description Min Max Default


/FA1
18 2 2 ÖlpumpON oil pump ON, 0=standard, 1=together with the fan 0 1 0
From version 4.2 on
0 = pressure atomiser,
ignition transformer switches output OIL PUMP on
and terminal 46 is set to OIL PRESSURE > MIN
(ETAMATIC OEM and FA1 only)
1 = rotation atomiser
fan switches on the output OIL PUMP
and terminal 46 is set to ATOMIZER AIR
PRESSURE (ETAMATIC OEM and FA1 only)
762 2 4 Fkt.Kl.6 Function terminal 6 or 46: 0-recirc. ON signal / 1-oil 0 1 0
pressure > min signal
ETAMATIC (terminal 6):
0 = no function
1 = no function / if P788 = 1, then "recirculation ON"
by PROFIBUS
ETAMATIC OEM or Burner Control FA1 - terminal 46:
0 = no function
1 = ’oil pressure >min’ with pressure atomiser (P 18 = 0)
or ’atomiser air pressure’ when using a rotation
atomiser (P 18 = 1)

WARNING!
P 762 = 0  terminal 46 has no function (ETAMATIC OEM and Burner Control FA1)!
P 17 = 3 (FA1 special)  terminal 46 is set to ’ignition position acknowledgement’!
’Oil pressure > min’ or ’atomiser air pressure’ is not monitored by terminal 46!
Use the safety interlock chain oil via terminal 51 to monitor these signals!

79
11 Appendix

Nr. FMS ETA Short Text Description Min Max Default


/FA1
765 3 4 Irr. Öl Irrelevance time of safety interlock chain oil when ignit- 0 10 0
ing on fuel oil in seconds
Irrelevance time while igniting (longer tolerance) for
safety interlock chain oil
Extend the tolerance time for the safety interlock chain
oil during the ignition process in this parameter. This
avoids fault shut -downs due to pressure impulses by
opening the main valves. Set the values in seconds.
Standard value is 0.
From software version 3i030 on active.
After finished ignition process, this parameter is without
function.
The irrelevance time starts with the opening of the oil
valve (2 nd safety time) and ends after the duration, set
in this parameter has passed.
ETAMATIC OEM  This parameter effects the safety
interlock chain oil as well as the oil pressure min.
788 2 2 Fkt <max Function mode of gas pressure < max. switch 0 1 1
ETAMATIC input terminal 54
0 = recirculation "ON"
If the recirculation signal is missing during opera-
tion,
the recirculation channel remains closed or runs
close (this is valid for ETAMATIC; ETAMATIC OEM
has a static recirculation signal = 1).
If P 427 (VODelR) = 0, the recirculation channel
remains close during the pre-purge period.
1 = ignition flame monitor
the internal recirculation signal is always 1
ETAMATIC OEM terminal 54
0 = gas pressure < max.
1 = ignition flame signal
Burner Control FA1
0 = gas pressure < max.
1 = ignition flame monitor
at input ignition flame signal (see P 728, P 774 and
P 775)

80
11 Appendix

11.8 Connection Diagrams

Fig. 11-9 Connecting diagram of FA1 with pilot flame monitoring and control output for mechanical fuel/
air ratio control or 4 ... 20 mA inverter alternatively (for footnotes refer to the process sequence charts).

81
11 Appendix

Fig. 11-10 Connecting diagram FA1 with pilot flame monitoring, without continuous control output (for
footnotes refer to the process sequence charts)

82
11 Appendix

11.9 Connection Examples of Firing Rate Input

A three-point step signal from the firing rate controller is used as the firing rate input. Use the
contacts instead of the potentiometer as shown below:

Current is used as firing rate default signal instead of a potentiometer:


f.ex. active steam pressure controller

A 4 ... 20 mA unit is supplied with 24 V (e.g. a passive steam pressure controller). The internal
firing rate controller is on.

NOTICE
When using a steam pressure controller: The actual value is pending on terminals 3, 4 and 5
and terminals 20 and 21 must be short-circuited.
To switch off the internal firing rate controller short-circuit terminals 19 and 21.

83
11 Appendix

11.10 Flame Scanner and Sensor Connection

11.10.1 Flame Scanner Connection

Fig. 11-11 Connection flame scanner

(1)
Flame intensity to align the flame sensor (not connected during operation), with delivery of
01.01.2003 on.

Colour coding according to IEC 60757 for Fig. 11-11 Connection flame scanner
BK Black WH White
PK Pink GN Green
RD Red BU Blue
YE Yellow PE PE-bar

84
11 Appendix

11.10.2 Flame Sensor Connection

11.10.2.1FFS07 Assembly

BK Schwarz RD Rot WH Weiß


BU Blau GN Grün YE Gelb
PK Rosa Empfohlener Einbauort 4 Dichtring muss einrasten!

85
11 Appendix

11.10.2.2FFS08 Assembly

BK Black RD Red WH White


BU Blue GN Green YE Yellow
PK Pink Recommended installa- 4 Seal ring must engage!
tion

86
11 Appendix

11.11 LAMTEC SYSTEM BUS (LSB)

The document "LAMTEC SYSTEM BUS technical documentation“ (publication no. DLT6095)
consists of further information with regards to LAMTEC SYSTEM BUS.

11.11.1 LSB Connection

Fig. 11-12 LSB connection FA1 to LT2

Fig. 11-13 LSB connection FA1 - LT2 - other LAMTEC devices

No. Description
1 To other LAMTEC-devices
2 Housing
3 Pre-canned line 2 m
4 PE-bar in housing LT2
5 Terminal resistance passive

87
11 Appendix

Fig. 11-14 LSB connection FA1 o LT1 from SN 600 on

No. Description
1 PE-bar in housing LT1
2 Housing
3 Pre-canned line 2m, 663R0421N
4 LT1 from serial number 0600
5 Terminal resistance active
6 To other LAMTEC- devices

Fig. 11-15 LSB-Connection FA1 - LT 1 to SN 0599

No. Description
1 PE-Track in system-cover LT1
2 Cover
3 Pre-canned line 2 m, 663R0421N
4 LT1 from serial number 0599
5 Terminator enable

88
11 Appendix

Fig. 11-16 LSB Connection ETAMATIC - LT3-F

No. Description
1 LSB connection plug, termination resistor 120 , ON
2 LAMTEC SYSTEM BUS, connection cable 663R0421N

11.11.2 LSB Cable Connection

Devices on LAMTEC SYSTEM BUS (LSB) must be connected in serial/row (see Fig. 11-17
Serial BUS connection). The first and the last participant on LSB must be terminated with a
termination resistor of 120 . All the other BUS participants are not allowed to be connected
to any termination resistor at all. A star wiring is not permitted (see Fig. 11-18 Star BUS con-
nection).
For activation of the termination resistor, see also technical document LAMTEC SYSTEM
BUS (DLT6095).

Correct: Serial Wiring (in a row)

Fig. 11-17 Serial BUS connection

Incorrect: Star Wiring

Fig. 11-18 Star BUS connection

89
11 Appendix

11.12 Inernal Connecting Diagram of the Control Outputs

Fig. 11-19 Internal connecting diagram of the control outputs


Always connect the attached firing rates (valves etc.) to the FA1 (even when the burner is off).
If it is not possible to not ensure this, use an RC combination (ca. 0,15 μF, ca. 220 ) between
the output terminal and neutral to let the testing current flow.

WARNING!
Connect the valves directly to the terminal.
The activating current of the firing rate must be higher than 9 mA.

Fig. 11-20 Example: safety interlock chain wiring via 230 V

No. Description
1 FA1
2 230 V contacts safety interlock chain
3 optional unlocking switch

90
11 Appendix

CAUTION!
If the safety interlock chains run open in BURNER OFF condition, the device doesn’t execute
an interlocking. If you need interlocking in BURNER OFF condition you need to adopt appro-
priate measures on the plant.

11.13 Valve Leakage Test Venting Over the Roof

NOTICE
Check the diameter of the gaspipe when gas will be released above the roof.
Enable terminal no. 67 for 2 sec. to release the gas.
Ensure that this time is long enough, even for mostly used gaspipes with a smaller diameter
to release the gas.

Fig. 11-21 Suggested wiring for venting the gas line over the roof in conjunction with the FA1

91
11 Appendix

11.14 Switch- and Key Combinations

11.14.1 Programming Unit

Action Display Mode Keys


recall correction range status monitoring display
automatic press key 11 (Enter)
setting
reset
press key F1 (Reset)
code entry for parameter set- status automatic
tings press keys 5, 7 and 8 simultaneously
scan fault history status monitoring display press keys 2 or 3
automatic (not in fault mode)
setting
recall correction input value firing rate
press key 11 (Enter)
firing-rate adjustable with automatic
switch 1 (manual mode) press key F3 (manual)
leaving manual mode automatic
press key F3 (manual) again
firing-rate adjustable with firing-rate setting
key 1(internal pre-setting) press key 2 or 3
Modus EG is active firing-rate setting press key 6 Mode GL or RG (EL in dis-
clear memory play) fuel/air ratio control locked (no
indication, ES locked)
Mode EG is terminated setting _
clear memory press key 2.....9 in Mode EG or ES
display of running time automatic
meter / starts counter press key F2 (clock)
store point setpoint setting
feedback press key 11 (Enter)
actual
value
clear actual curve setpoint clear memory
press key 11 (Enter)
display of the acceptance feedback
data, CRCs for all levels, setpoint press key 11 (Enter)
safety time oil/gas, pre-
purge time
traverse channels setpoint setting _
press keys 2.....9
scanning of serial num- feedback
bers and key numbers actual press key 11 (Enter)
value
call up flame intensity press key F4 (M) twice
Without integral flame monitoring, the
display shows "---%"

92
11 Appendix

Action Display Mode Keys


mode switching O2-con- automatic
trol FA1 press key F4 (M) twice
O2 fault reset status O2 control Mode O2 control, press key 11 (Enter),
recall fault history press key 7
call up text messages status O2 control
press key 11 (Enter)
adjusting correction value firing-rate TK press key 2 = excess air
O2 control press key 3 = air deficiency
changing O2 setpoint setpoint T press key 7 = more O2
value O2 control press key 8 = less O2
recall O2 fault history status automatic press key 5 = browse fault history
press key 11 (Enter) = call text
changing firing-rate control- firing-rate operation
ler setpoint press keys 9 and 6 simultaneously,
when display is flashing, press keys 4
and 5 to adjust the setpoint, press key
11 (Enter) to store

11.14.2 Customer Interface

Action Display Mode Keys


Reset RESET key

Calling fault history Status DISPLAY not in MANUAL mode and no fault condi-
MONITORING tion
AUTOMATIC
SETTING
Contrast in the display Contrast +2

Contrast in the display Contrast -2

Display of operating values This key has no effect, if the mode


SETTING FIRING RATE CONTROLLER is
active (LED MANUAL is blinking).
Switching the display to the Press key for 5 s.
2nd level After 10 s without action, the display
switches back automatically
Leaving level 2 RESET key

Switching the display to AUTOMATIC Press key HAND.


manual mode LED in key is ON
Setting the external firing
rate
Setting the firing rate control- AUTOMATIC Press key HAND.
ler LED in key is blinking
Setting the setpoint value

93
11 Appendix

11.15 Feedback at Three-Point-Step Outputs

11.15.1 Connect with Positive Locking

Since the FA1, in the case of three-point step channels, adjusts the damper until the actual
value is equal to the setpoint value, the feedback potentiometer must always reliably corre-
spond to the damper position.
The damper motor potentiometer connections must be positive interlock connections, i.e. not
able to rotate.
In addition you must use potentiometers with high quality standards (see next page). If one of
these two points is not given, you must use two independent potentiometers (not dual-operat-
ed potentiometers) per channel for the feedback.
The motor damper connection must always be a positive interlock.

WARNING!
The connection has to be designed in that way that the maximum torque of the motor could
not break the connection under any condition.

Fig. 11-22 Example of positive potentiometer connection

11.15.2 Fail-Safe Feedback

In the case of single-channel feedback of TPS outputs, only authorised potentiometers may
be used. These must be switched directly.

11.15.3 Examples of Potentiometers and Motors

Example of potentiometers:
The following potentiometers are authorised for use as solo feedback in the case of
FA1, on condition that they are positively connected to the damper:

Manufacturer Type Rating


Novotechnik SP-Serie Rating: 5 kΩ*
Contelec PL 240 Rating: 1 kΩ - 5 kΩ*
Contelec PL 310 Rating: 5 kΩ*

94
11 Appendix

Manufacturer Type Rating


Contelec PL 295 Rating: 5 kΩ*
Bourns 6639S-095-.. Rating: 5 kΩ*
Other potentiometers are permitted only after consulting LAMTEC or the TÜV.

Examples of servomotors
Servomotors with approved potentiometer, fitted with a positive interlock connection:

Manufacturer Description Potentiometer


LAMTEC 662R2111... Novotechnik
662R2112... Novotechnik
662R2121... Novotechnik
662R2127... Novotechnik
663R3100... Megatron
Schimpf All motors with feedback type R01*/type R02*
01-..., 02-... Novotechnik
Haselhofer HD 60 D 2 HD 60 D10 Novotechnik
D1, D2, D3, D10, (Saake HD60...) , SBA12 Contelec
D006, D025, D040, D100, D012 Contelec
Aris WAN 1 - WAN 6 Contelec
WAK..., WAV Contelec
NL6020, NL6040 Contelec, Megatron
N1, N2A Megatron
NK1510, NK3010, NK6010 Megatron
Schneider STM 40 Q15.51 /8 2NL POT Contelec
Electric
Siemens AG SQN..., SQM... Contelec
auma-Werner SA07.1, SA07.5, SA10.1, SA14.1, Contelec
Riester SA14.5, SA16.1, SA25.1, SA30.1, SA35.1,
Gmbh & Co. SA40.1, SA48.1
KG
ARI-Armatur ARI PREMIO Megatron
Albert Richter 2,2 kN, 5,0 kN, 12,0 kN, 15,0kN
GmbH & Co.
KG
Keller GmbH CA 03 AF 325, CA 12 AF 148 Contelec
KFM Rege- 4d124B Novotechnik
lungstechnik
GmbH
Regeltechnik ST 5102, ST5113 Contelec
Kornwestheim
GmbH
* also available at LAMTEC

Other motors are allowable only if the potentiometer connection forms a positive interlock.

95
11 Appendix

11.16 Replacing the Device and Components

11.16.1 Replacing a Burner Control FA1

WARNING!
For replacing a burner control unit you have to take special measures. If you ignore this in-
structions it may cause in dangerous situation or malfunction.

How to upload the data in the new device:


1 You have to ensure, that the hardware configuration of the connected device corresponds
with the configuration of the device, which provides the backup copy. Otherwise it may re-
sult in malfunction. Read the information on the configuration label to check this:
– ID number
– configuration number
– additional notes (i.e. r.p.m. range of the r.p.m. feedback)
2 Make sure that you have selected the protected dataset, which belongs to the actual in-
stallation.
3 After you have uploaded the protected dataset activate the new settings with the interrup-
tion of the power supply and the restarting the new FA1.
4 All device parameters are set in the uploaded dataset. It is important to check all safety
relevant parameters before you put the device into operation on-site.

NOTICE
To verify the actual data, download them from the device and compare them with the protect-
ed dataset.

5 Finally download the actual dataset from the device and send it to support@lamtec.de.

11.16.2 How to Replace a Servo Motor

If you replace a motor without pre-calibration it is necessary to check the burner adjustment
after the change, because the potentiometer value and the position of the switches may differ
a little bit. This may lead to an other position of the damper.

NOTICE
Therefore you must prove the burner adjustment again in all firing rate positions and all oper-
ation modes. If necessary adapt the curves in the FA1.

11.16.3 How to Replace a Potentiometer

NOTICE
Keep switches in the same position.

96
11 Appendix

1 Note actual feedback value at lowest position before changing the potentiometer.
2 Remove old potentiometer.
3 Insert new potentiometer and adjust it so that actual value feedback at lowest position is
the same like noted before.
4 Fix potentiometer in according to the instruction of the motor manufacturer.
5 Verify burner adjustments and change if necessary

NOTICE
Since the normally used potentiometers can have different values, it is possible that the damp-
er has another position than before. Therefore you must prove the burner adjustment n again
after a potentiometer change, at all firing rate points and in all operation modes.

11.17 Changing EPROMs

EPROMS tauschen
 Bevor die Speichererweiterung eingebaut werden kann, muss ein geschützter Datensatz
von dem Gerät erstellt werden.
 Crosstip screw driver size 0
 Crosstip screw driver size 1
 Socket wrensch sizee 5,5
 Extraction tool for EPROMS
1. Removing
a) Switch off power supply
b) Disconnect plugs
c) Take out FA1 ggf. from the control cabinet
2. Open the housing
a) 1 – open screw M2,5
2 – open hex-hat nuts M3 (4 pcs.).
3 – Open screws M3 of side attachements (4 pcs.).

Fig. 11-23 Screw fastening of the housing

97
11 Appendix

b) 1 – Remove cover
2 – Disconnect PE connection

Fig. 11-24 Housing is open


3. Remove base electronic board.
The base electronic board (3) and the rear wall are mounted to one unit (4) and can be
dismounted from the CPU board (1) easily. EPROMs/EEPROM/memory extension are
built in the CPU board (1).

Fig. 11-25 Base electronic board is dismounted


1 – Remove base electronic board.
2 – Disconnect PE connection
4. Replace EPROM.
The software update consists of::
1 EPROM for main processorr ’H’
2 EPROM for communicationn ’B’
3 Memora extension (version 5.0003 and higher)
4 EEPROM for watchdog processor
5 EPROM for watchdog prcessor ’U’

98
11 Appendix

NOTICE
Important: Always pay attention to the direction of the notches before replacing them.
The notches point towards the PE connector.

Fig. 11-26 Tongs to remove EPROM, EE-


PROM and memory extension

Fig. 11-27 Lever out EPROM


- if tongs are not available
a) Lever out the old EPROMs very carefully out of their sockets.
b) Insert new EPROMs in the correct position.
Important: All pins must sit poperly in the sockets.
5. Insert memory extension.
Replace the EEPROM of the main processor with the memory extension. The plug-in di-
rection of the memory extension is clear.

99
11 Appendix

6. Assembly:
a) Re-connect PE connection.
b) Replace the insulating pape ron the CPU board.
c) Insert the base electronic board.
d) Reconnect the side attachements.
e) Re-connect PE connection on the cove.
f) Attach the housing and fasten the screws.
g) Mount FA1 into the control cabinet and connect the plugs.
7. Restor dataset.
Restore the protected dataset
8. Commissioning
a) After replacing of the old software EPROMs and on power ON, a fault message with
error code ’U106’ may be displayed. To clear the fault and/or to set CO control to op-
eration, a password for access level 4 is needed.
b) Set parameters 937 and 976 to the default values when using CO control or 0 if CO
control is not installed.
c) Controll the following parameters or change them if necessary:
Parameter Value
007 11
845 1
846 2
847 1
935 10
d) The new EEPROS are changeing the CRC 4 check sums
e) Correct the software version on the configuration lable. .
f) Send the new CRC check sum and the new software version to LAMTEC for complet-
en the CV of the device.

100
11 Appendix

11.18 Wiring Notes

11.18.1 Shields Connection

All cables from and to the FA1 must be shielded (with the exception of the 230 V cable). Con-
nect the shielding to PE by the shortest possible route.
Right:

shielding terminal
connection terminal

Wrong:

connection terminal
shielding terminal

11.18.2 PE Busbar

Two rails are fitted to the left and right side of the terminal strips and parallel to them on the
unit's rear side. Connect all shieldings to these rails. Also connect the PE to this point from
the outside.

11.18.3 Control Cabinet Wiring

The low-voltage cables from and to the FA1 should not run in parallel to the power electronics'
in and out conductors in one cable duct.
Frequency converter cables and switches/contacts carrying high inductive or capacitive firing
rates are particularly critical. Therefore, avoid routing parallel to the drive cables of solenoid
valves, ignition transformers, servo motors and similar devices.
Although this device exceeds all relevant EMC standards in some respects, suitable wiring is
essential to ensure that the entire system operates smoothly in all conditions.

101
11 Appendix

11.19 Technical Data

11.19.1 FA1 BurnerControl

Fig. 11-28 FA1 ...

Fig. 11-29 Dimensional drawing FA1 ...

Dimension
Dimension (h x w x d) [mm] [in.] 94 x 265 x 144 (3.7 x 10.4 x 5.7)
Weight [kg] [lb] 3,5 (7.7)

Input data
Power supply from 115 V -15 % to 230 V +10 % / 50/60 Hz
Power consumption ca. 50 VA

Characteristics
Inputs (digital/analogue) 14 digital inputs 24V
3 analogue inputs
Digital signal inputs The Burner Control Fa1 self tests will not allow the parasitic
capacitance on the line connected to the digital inputs to
exceed 2,2F.
The length of the cables should not exceed 10 m (32.8 ft.)

102
11 Appendix

Characteristics
Regular firing rate input Selectable:
– Potentiometer mit 1 ... 5 k
– Current signal (0/4 ... 20 mA)
– Three-point-step position output, direct PT100 actuation
(if the load regulator is used)
Analogue inputs Selectable:
– Potentiometer 1 ... 5 k
– Current signal 0/4 ... 20 mA.
Resolution per analogue input 999 digits, 10 Bit
Three-point-step 30 s ... 60 s
– Recommended run time of the positioning distance max. 10 m (32.8 ft.)
drive max. current 50 mA continuous current
Outputs (digital/analogue) 12 digital outputs 230 V
Digital output Main gas 1, Main gas 2, oil valve, fan on, oil pump, ignition
valves
Storage of the set values and variable data In EEPROM, up to 20 (type 11) points per curve with linear
interpolation
Number of programmings Unlimited (EEPROM)
Interfaces – 1 serial 25-pole Sub-D socked
(only addressable with adapter RS 232 (standard
setting 19200 baud, no parity, 8 data bits, 1 stop bit)
– LAMTEC SYSTEM BUS (length max. 500 m (0.3 mile))
Bus coupling LSB- Adapter
BUS card optional for these systems
INTERBUS-S (Phoenix)
PROFIBUS DP
Modbus
Ethernet (Modbus TCP)

Environmental conditions
Ambient temperature
– Operation +0 °C ... +60 °C (32 °F ... 140 °F)
– Transport and storage -25 °C ... +60 °C (-13 °F ... 140 °F)
Permiss. ambient humidity Class F, DIN 40 040

NOTICE
The limits of the technical data must be strictly adhered to.

103
11 Appendix

F1 Gerät
F2 Control elements
F3 Main gas 1, oil, oil pump
F4 Main gas 2, pilot valve, ignition
transformer
F5 Fan, fault indication
F6 24 VDC
S1 9-pole Sub-D connector for
LAMTEC SYSTEM BUS
S2 Communications interface

Fig. 11-30 Rear view FA1

NOTICE
PC connection possible only via LAMTEC interface adapter!

NOTICE
For exchange of the fuses F3, F4, F5 these specifications are to be complied:
- 2A slow blow
- high breaking capacity according to IEC 60127-2, Sheet 5: 1500A @ 250VAC
- melting integral I²t < 40 A²s
- e.g. Littelfuse 0215002.(M)XP
Fuses which fulfills these requirements are ceramic tube fuses with the label T2AH 250V.

104
11 Appendix

11.19.2 Customer Interface

Fig. 11-31 Customer interface

Fig. 11-32 Dimensions of the customer interface

105
11 Appendix

Fig. 11-33 Cut-out for panel board

Dimensions
Dimension (HxWxD) 72 mm x144 mm x56 mm
Weight 1,0 kg

Input data
Spannungsversorgung 24 VDC
Leistungsaufnahme 60 mA

Features
Display Alphanumeric display, 2 x16 digits, switchable to firing rate
value, state, O2 value, flame intenstiy, running text

Environmental conditions
Ambient temperature
– Operation +0 °C ... +60 °C
– Transport and storage -25 °C ... +60 °C
Permissible. ambient humidity Class F, DIN 40 040

NOTICE
The limits of the technical data must be strictly adhered to.

106
11 Appendix

11.19.3 Programming Unit

Length: 180 mm
Width: 94 mm
Depth: 40 mm

Fig. 11-34 Programming Unit Fig. 11-35 Dimensions Programming


Unit

Dimension
Dimension (HxWxD) 180x94x40 mm/7.1x3.7x1.6 in
Weight 0,33 kg/0.7lb

Input data
Power supply 24 VDC
Power consumption 100 mA

Features
Programming unit 4x16 characters can display with softkeys and setup-assistant

Environmental conditions
Ambient temperature
– Operation +0 °C ... +60 °C/32 °F ... 140 °F
– Transport and storage -25 °C ... +60 °C/-13 °F ... 140 °F
Permissible. ambient humidity Class F, DIN 40 040

NOTICE
The limits of the technical data must be strictly adhered to.

107
11 Appendix

11.20 Burner Control FA1 without integral flame detector

Connectable flame detectors: Any tested flame sensor with error-proof floating contact
for flame signalling

WARNING!
If a flame monitor, which is not approved for continuous operation is connected, the entire sys-
tem's approval for continuous operation will loose it’s validation.

11.21 Flame Scanner FFS07/FFS08

Marking Colour
YE yellow
WH white
GN green
RD red
PK pink
BU blue
BK black

Fig. 11-36 Flame sensor FFS08 IR/UV

Fig. 11-37 Mounting clip for FS 60 see the documentation for the desired device Fig. 11-38 Mounting clip for FS60 (DLT7660)

108
11 Appendix

Marking Colour
BK black
BU blue
RD red
GN green
WH white
YE yellow

Fig. 11-39 Flame sensor FFS 07

No. Description
1 Type plate
2 Grounding M4 (Pozidrive 2)
3 Incidence of light
4 Bend radius of the of the FM wire min. 25 mm

109
11 Appendix

11.22 Declaration of Conformity

110
11 Appendix

111
11 Appendix

112
The information in this publication is subject to technical changes.

LAMTEC Meß- und Regeltechnik


für Feuerungen GmbH & Co. KG
Wiesenstraße 6
D-69190 Walldorf
Telefon: +49 (0) 6227 6052-0 info@lamtec.de
Telefax: +49 (0) 6227 6052-57 www.lamtec.de

Printed in Germany | Copyright  2018 Print no. DLT6700-18-aEN-036

You might also like