Professional Documents
Culture Documents
هندسه قدره
هندسه قدره
Scientific Research
Southern Technical University
Engineering Technical College/Basrah
Department of Elect. Power Eng.
Hassan Al-Ajwad
Power Engineering
Third Stage
Chapter Three
Inductance of Transmission Line
1
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
2
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
2
𝑃2
𝑊=𝐼 𝑅= 2 𝑅
𝑉 𝑐𝑜𝑠 2 𝜑
If ρ, l and a denote the resistivity of conductors, length of the line and the
area of cross -section of the conductor, respectively; then:
𝑅 = ρ 𝑙/𝑎
So:
𝑃2 𝜌 𝑙
𝑊= 2 … (1)
𝑉 𝑐𝑜𝑠 2 𝜑 𝑎
Also, the cross-section area of conductor (a) is:
𝐼 𝑃
𝑎= =
𝛿 𝑉 cos 𝜑 𝛿
𝑃2 𝜌 𝑙 𝑉 cos ∅ 𝛿 𝑃𝜌𝑙𝛿 𝑊 𝑉 cos ∅
𝑊= 2 × = 𝑜𝑟 𝛿 =
𝑉 𝑐𝑜𝑠 2 φ 𝑃 𝑉 cos ∅ 𝑃𝜌𝑙
Now, Efficiency:
𝑂𝑢𝑡𝑝𝑢𝑡 𝑂𝑢𝑡𝑝𝑢𝑡
ŋ= =
𝐼𝑛𝑝𝑢𝑡 𝑂𝑢𝑡𝑝𝑢𝑡 + 𝑙𝑖𝑛𝑒 𝑙𝑜𝑠𝑠𝑒𝑠
P 𝜌𝑙𝛿
= = 1− … (2)
𝑃𝜌𝑙𝛿 𝑉 cos 𝜑 + 𝜌 𝑙 𝛿
𝑃+
𝑉 cos 𝜑
𝑊 𝑊
𝑅𝑒𝑠𝑖𝑠𝑡𝑎𝑛𝑐𝑒 𝑑𝑟𝑜𝑝 𝑝𝑒𝑟 𝑙𝑖𝑛𝑒 = 𝐼 𝑅 = 𝐼 = =𝜌𝑙𝛿 … (3)
𝐼2 𝐼
Volume of conductor required per phase is:
𝑃𝑙 𝑃2 𝜌 𝑙2
𝑉=𝑎𝑙= = … (4)
𝑉 cos 𝜑 𝛿 𝑊 𝑉 2 𝑐𝑜𝑠 2 φ
3
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
3𝑃
𝑉 = 5.5√𝑙 +
100
where:
P: is the estimated maximum kW per Fig. 2: The optimum voltage
from the economy point of
phase as to be delivered over a single view.
circuit.
4
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
𝑘𝑉𝐴
𝑉 = 5.5√𝑙 +
150
where:
kVA: is the total power.
l: is the distance of transmission in miles.
5
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
𝑃3
∴𝑎=√
𝑃2
6
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
𝑃3
𝑎=√
𝑃2
7
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
𝑃3 1080.6
𝑎=√ =√ = 1.69 𝑐𝑚2
𝑃2 375
8
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
36 × 103
= 𝑘𝑊ℎ
𝑎
𝑃3 36 × 103 2880
= 0.08 × =
𝑎 𝑎 𝑎
𝑃3 2880
∴𝑎=√ =√ = 1.9 𝑐𝑚2
𝑃2 800
9
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
10
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
11
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
B. Phase advancer
CD = additional of new plant
CD = kVA2 cos 𝜑2 − kVA1 cos 𝜑1
P2 − P1 = kVA(cos 𝜑2 − cos 𝜑1 )
BE = kVAR of necessary new plant
BE = OD(tan 𝜑1 − tan 𝜑2 )
Q 𝑠 = P2 (tan 𝜑1 − tan 𝜑2 )
For case 1:
Reduction in kVA = kVA1 − kVA2
𝑃 𝑃
= −
cos 𝜑1 cos 𝜑2
If the cost kVA equals to x (I. D.) then, the saving in demand:
1 1
𝑆𝑎𝑣𝑖𝑛𝑔 = 𝑥 𝑃 ( − )
cos 𝜑1 cos 𝜑2
Against this saving, the kVAR has been provided by power factor
improvement plant (static capacitor) is:
12
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
Q = P (tan 𝜑1 − tan 𝜑2 )
If y (I. D.) is the cost per kVAR of improvement plant
∴ cost of condencer = y P (tan 𝜑1 − tan 𝜑2 )
1 1
Net Saving (S) = 𝑥 𝑃 ( − ) − y P(tan 𝜑1 − tan 𝜑2 )
cos 𝜑1 cos 𝜑2
For maximum saving:
𝑑𝑠 𝑦
= 0 → sin 𝜑2 =
𝑑𝜑2 𝑥
13
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
14
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
15
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
H. W.: A 35 kW induction motor has power factor 0.9 and efficiency 0.9
at full-load, power factor 0.6 and efficiency 0.7 at half full-load. At no
load the current is 25% of full-load current and power factor is 0.1.
Capacitors are supplied to make the line power factor 0.8 at half full-
load. With these capacitors in circuit, find the line power factor at: (i) full
load, and (ii) no load.
[Ans: (i) 0.994 lagging and (ii) 0.272 leading]
16
Chapter Two
Overhead Line Insulators
2.1 Introduction
Transmission line conductors are bare and do not have any
insulated coating over it. To maintain safety and necessary clearance
between live conductors and metal structure of the support, insulators are
mounted. These insulators provide insulation of high voltage wire with
the metal structure and also provide support to the conductor. Insulators
are also used in providing support to bus-bar conductors and other live
high voltage equipment terminals.
17
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
18
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
19
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
capacitance between metal fitting of each unit and the earthed pole or
tower. The capacitance so formed is known as shunt capacitance.
Let the mutual capacitance between the links be C' and shunt capacitance
between links and earth be C, voltage across the first unit (nearest the
cross-arm) be E1, voltage across the second unit be E2, voltage across the
third unit be E3, voltage across the fourth unit (nearest the line conductor)
be E4, and voltage between conductor and earth be E volts.
𝐶′
𝐿𝑒𝑡 = 𝑚 𝑜𝑟 𝐶′ = 𝑚𝐶
𝐶
20
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
21
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
capacitances are greater for lower units thus voltages across them are
reduced.
22
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
𝐶2′ = 10𝐶 + 𝐶
∴ 𝐶2′ = 11𝐶
𝐴𝑡 𝑝𝑜𝑖𝑛𝑡 𝑏:
𝐶2 ′ = 10𝐶
𝐼3 = 𝐼2 + 𝐼𝑏
𝐶3′ 𝐸 = 𝐶2 ′𝐸 + 𝐶(𝐸 + 𝐸 )
𝐶3′ = 11𝐶 + 2𝐶
∴ 𝐶3′ = 13𝐶
𝐴𝑡 𝑝𝑜𝑖𝑛𝑡 𝑐:
𝐶3 ′ = 10𝐶
𝐼4 = 𝐼3 + 𝐼𝑐
𝐶4′ 𝐸 = 𝐶3 ′𝐸 + 𝐶(𝐸 + 𝐸 + 𝐸)
𝐶4′ = 13𝐶 + 3𝐶
∴ 𝐶4′ = 16𝐶
𝐴𝑡 𝑝𝑜𝑖𝑛𝑡 𝑑:
𝐶4 ′ = 10𝐶
𝐼5 = 𝐼4 + 𝐼𝑑
𝐶5′ 𝐸 = 𝐶4 ′𝐸 + 𝐶(𝐸 + 𝐸 + 𝐸 + 𝐸)
𝐶5′ = 16𝐶 + 4𝐶
∴ 𝐶5′ = 20𝐶
𝐴𝑡 𝑝𝑜𝑖𝑛𝑡 𝑒:
𝐶5 ′ = 10𝐶
𝐼6 = 𝐼5 + 𝐼𝑒
𝐶6′ 𝐸 = 𝐶5 ′𝐸 + 𝐶(𝐸 + 𝐸 + 𝐸 + 𝐸 + 𝐸)
𝐶6′ = 20𝐶 + 5𝐶
∴ 𝐶6′ = 25𝐶
23
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
24
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
25
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
26
Chapter Three
Electrical Design of Overhead Lines
(Inductance of Transmission Lines)
3.1 Introduction
When a current is passed through electrical circuit, this current will
generate a flux. When this current changes with time in this circuit, the
flux will change and generate e.m.f. The absolute value of this e.m.f is
directly proportional to the rate of changes of flux, then:
𝑑∅ 𝑑∅ 𝑑𝜓
|𝑒| ∝ → |𝑒| = 𝑁 =
𝑑𝑡 𝑑𝑡 𝑑𝑡
𝑑𝜓 𝑑𝜓 𝑑𝑖 𝑑𝑖
= × =𝐿
𝑑𝑡 𝑑𝑖 𝑑𝑡 𝑑𝑡
𝑑𝜓
∴𝐿=
𝑑𝑖
ψ: flux linkage (Wb.T); i: current (A); L: inductance (H);
e: induced voltage (V); di/dt: rate of change of current (A/Second).
If the flux linkages of the circuit vary linearly with current, in other
words, this means that the magnetic circuit has constant permeability,
then:
𝜓
𝐿=
𝐼
Thus, the inductance of a circuit is defined as the flux linkage per
unit current.
27
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
𝑚. 𝑚. 𝑓 = ∮ 𝐻𝑥 𝑑𝑠 = 𝐼𝑥
28
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
𝜓𝑖𝑛𝑡 𝜇 𝐻
∴ 𝐿𝑖𝑛𝑡 = = ( )
𝐼 8𝜋 𝑚
If the relative permeability (μr) of the conductor is taken "1";
𝐻
𝜇 = 𝜇0 𝜇𝑟 = 4𝜋 × 10−7 ( )
𝑚
1 𝐻
∴ 𝐿𝑖𝑛𝑡 = × 10−7 ( )
2 𝑚
29
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
𝐷1 𝐻
= 2 × 10−7 𝑙𝑛 ( )
𝑟1́ 𝑚
−1
𝑤ℎ𝑒𝑟𝑒: 𝑟1́ = 𝑟1 𝑒 4
𝐷2 𝐻
𝐴𝑙𝑠𝑜: 𝐿2 = 2 × 10−7 𝑙𝑛 ( )
𝑟2́ 𝑚
𝐷1 𝐷2
𝐿 = 𝐿1 + 𝐿2 = 2 × 10−7 (𝑙𝑛 + 𝑙𝑛 )
𝑟1́ 𝑟2́
If 𝑟1́ = 𝑟2́ = 𝑟́ ; 𝐷1 = 𝐷2 = 𝐷
𝐷 𝐻
∴ 𝑇ℎ𝑒 𝑡𝑜𝑡𝑎𝑙 𝑖𝑛𝑑𝑢𝑐𝑡𝑎𝑛𝑐𝑒 𝑖𝑠 𝑔𝑖𝑣𝑒𝑛 𝑏𝑦: 𝐿 = 4 × 10−7 𝑙𝑛 ( )
𝑟́ 𝑚
30
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
∑𝐼 = 0
𝐼1 + 𝐼2 + 𝐼3 + ⋯ + 𝐼𝑛 = 0
If 𝜓1𝑝1 denotes all the flux linkages of conductor 1 due to its own current
I1, then:
𝐷1𝑝 𝑇
𝜓1𝑝1 = 2 × 10−7 𝐼1 (𝑙𝑛 ) (𝑊𝑏. )
𝑟1́ 𝑚
Consider 𝜓1𝑝2 the flux linkages with conductor 1 due to current in
conductor 2:
𝐷2𝑝
𝜓1𝑝2 = 2 × 10−7 𝐼2 (𝑙𝑛 )
𝐷12
Also:
𝐷𝑛𝑝
𝜓1𝑝𝑛 = 2 × 10−7 𝐼𝑛 (𝑙𝑛 )
𝐷1𝑛
∴ 𝜓1𝑝 = 𝜓1𝑝1 + 𝜓1𝑝2 + 𝜓1𝑝3 + ⋯ + 𝜓1𝑝𝑛
𝐷1𝑝 𝐷2𝑝 𝐷3𝑝 𝐷𝑛𝑝
= 2 × 10−7 [𝐼1 𝑙𝑛 + 𝐼2 𝑙𝑛 + 𝐼3 𝑙𝑛 + ⋯ + 𝐼𝑛 𝑙𝑛 ]
𝑟1́ 𝐷12 𝐷13 𝐷1𝑛
So that:
1 1 1 1
𝜓1𝑝 = 2 × 10−7 [𝐼1 𝑙𝑛 + 𝐼2 𝑙𝑛 + 𝐼3 𝑙𝑛 + ⋯ + 𝐼𝑛 𝑙𝑛 ]
𝑟1́ 𝐷12 𝐷13 𝐷1𝑛
+ 2 × 10−7 [𝐼1 𝑙𝑛𝐷1𝑝 + 𝐼2 𝑙𝑛𝐷2𝑝 + 𝐼3 𝑙𝑛𝐷3𝑝 + ⋯ + 𝐼𝑛 𝑙𝑛𝐷𝑛𝑝 ]
To account for the total flux linkages to conductor 1, the point P must
approach infinity, and in this condition:
𝐷1𝑝 ≈ 𝐷2𝑝 ≈ 𝐷3𝑝 … 𝐷𝑛𝑝 = 𝐷𝑝 then:
1 1 1 1 𝑇
𝜓1𝑝 = 2 × 10−7 [𝐼1 𝑙𝑛 + 𝐼2 𝑙𝑛 + 𝐼3 𝑙𝑛 +. . +𝐼𝑛 𝑙𝑛 ] (𝑊𝑏. )
𝑟1́ 𝐷12 𝐷13 𝐷1𝑛 𝑚
31
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
32
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
𝑚
−7
√𝐷𝑏𝑎́ 𝐷𝑏𝑏́ 𝐷𝑏𝑐́ … 𝐷𝑏𝑚
𝐿𝑏 = 2 × 10 𝑛 𝑙𝑛 { }
𝑛
́
√𝐷𝑏𝑎 𝑟𝑏 𝐷𝑏𝑐 … 𝐷𝑏𝑛
Thus, average inductance of strands (segments) of conductor x is:
𝐿𝑎 + 𝐿𝑏 + 𝐿𝑐 + ⋯ + 𝐿𝑛
𝐿𝑎𝑣 =
𝑛
For calculating inductance of conductor x, it is clear that n such strands
are electrically in parallel, so that:
𝐿𝑎𝑣 𝐿𝑎 + 𝐿𝑏 + 𝐿𝑐 + ⋯ + 𝐿𝑛
𝐿𝑥 = =
𝑛 𝑛2
𝑚𝑛
−7 √(𝐷𝑎𝑎́ 𝐷𝑎𝑏́ . . 𝐷𝑎𝑚 )(𝐷𝑏𝑎́ 𝐷𝑏𝑏́ . . 𝐷𝑏𝑚 ). . (𝐷𝑛𝑎́ 𝐷𝑛𝑏́ . . 𝐷𝑛𝑚 )
= 2 × 10 𝑙𝑛 { 𝑛2
}
√(𝐷𝑎𝑎 𝐷𝑎𝑏 . . 𝐷𝑎𝑛 )(𝐷𝑏𝑎 𝐷𝑏𝑏 . . 𝐷𝑏𝑛 ). . (𝐷𝑛𝑎 𝐷𝑛𝑏 . . 𝐷𝑛𝑛 )
where 𝑟́𝑎 , 𝑟́𝑏 , … , 𝑟́𝑛 are replaced by 𝐷𝑎𝑎 , 𝐷𝑏𝑏 , 𝐷𝑛𝑛 respectively.
In this expression the numerator of argument of ln is called GMD
(Geometric Mean Distance) and often called (Mutual GMD) between
conductors x and y:
𝑚𝑛
𝐺𝑀𝐷 = 𝐷𝑚 = √(𝐷𝑎𝑎́ 𝐷𝑎𝑏́ . . 𝐷𝑎𝑚 )(𝐷𝑏𝑎́ 𝐷𝑏𝑏́ . . 𝐷𝑏𝑚 ). . (𝐷𝑛𝑎́ 𝐷𝑛𝑏́ . . 𝐷𝑛𝑚 )
Also, the denominator of argument of ln is called GMR (Geometric Mean
Radius)and often called (Self GMR):
𝑛2
𝐺𝑀𝑅 = 𝐷𝑠 = √(𝐷𝑎𝑎 𝐷𝑎𝑏 . . 𝐷𝑎𝑛 )(𝐷𝑏𝑎 𝐷𝑏𝑏 . . 𝐷𝑏𝑛 ). . (𝐷𝑛𝑎 𝐷𝑛𝑏 . . 𝐷𝑛𝑛 )
𝐷𝑚 𝐻
∴ 𝐿𝑥 = 2 × 10−7 𝑙𝑛 ( )
𝐷𝑠 𝑚
In a similar way, we can find Ly. Then, the total inductance is:
𝐿 = 𝐿𝑥 + 𝐿𝑦
If conductors x and y are identical, then:
𝐿𝑥 = 𝐿𝑦 = 𝐿́
𝐷𝑚 𝐻
∴ 𝐿 = 2𝐿́ = 4 × 10−7 𝑙𝑛 ( )
𝐷𝑠 𝑚
33
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
119 𝑚𝐻
𝐿 = 4 × 10−4 𝑙𝑛 = 1.36 ( )
3.94 𝑘𝑚
H.W.: The Fig. below shows the arrangement of a double circuit single
phase line. Conductors 𝑎, 𝑎́ from one connection and conductors 𝑏, 𝑏́
from return connection. The distance between 𝑎 and 𝑎́ is 90 cm and
between a and b is 175 cm as shown. Calculate the inductance per km of
the line (lead and return). The diameter of each conductor is 2.5 cm.
35
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
36
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
1 1 1
𝜓𝑎3 = 2 × 10−7 [𝐼𝑎 𝑙𝑛 + 𝐼𝑏 𝑙𝑛 + 𝐼𝑐 𝑙𝑛 ]
𝑟́ 𝐷13 𝐷23
The average flux linkages of conductor a is:
𝜓𝑎1 + 𝜓𝑎2 + 𝜓𝑎3
𝜓𝑎 =
3
1 1 1 1
𝜓𝑎 = × 2 × 10−7 [3𝐼𝑎 𝑙𝑛 + 𝐼𝑏 𝑙𝑛 + 𝐼𝑐 𝑙𝑛 ]
3 𝑟́ 𝐷12 𝐷23 𝐷13 𝐷13 𝐷12 𝐷23
𝐴𝑡 𝑏𝑎𝑙𝑎𝑛𝑐𝑒: (𝐼𝑏 + 𝐼𝑐 ) = −𝐼𝑎
3
−7 √𝐷12 𝐷23 𝐷13
𝜓𝑎 = 2 × 10 𝐼𝑎 𝑙𝑛 ; 𝑤ℎ𝑒𝑟𝑒 𝐷𝑒𝑞 = 3√𝐷12 𝐷23 𝐷13
𝑟́
𝐷𝑒𝑞
∴ 𝜓𝑎 = 2 × 10−7 𝐼𝑎 𝑙𝑛
𝑟́
𝜓𝑎 𝐷𝑒𝑞 𝐻
𝐿𝑎 = = 2 × 10−7 𝑙𝑛 ( ⁄𝑝ℎ𝑎𝑠𝑒)
𝐼𝑎 𝑟́ 𝑚
4
𝐷𝑎𝑏 = 4√𝑑𝑎𝑏 𝑑𝑎𝑏́ 𝑑𝑎́ 𝑏 𝑑𝑎́ 𝑏́ = √𝑑 2 𝑔2 = √𝑑𝑔
37
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
6
1 1 1
𝐷𝑚 𝑒𝑞 = 𝐷𝑒𝑞 = 3√𝐷𝑎𝑏 𝐷𝑏𝑐 𝐷𝑐𝑎 = √2ℎ𝑑 3 𝑔2 = (2ℎ)6 (𝑑)2 (𝑔)3
The self GMR for the phase which consists of 𝑎𝑎́ is:
At position 1:
4
𝐷𝑠1 = 4√𝑑𝑎𝑎 𝑑𝑎𝑎́ 𝑑𝑎́ 𝑎 𝑑𝑎́ 𝑎́ = √(𝑟́ 𝑓)2 = √𝑟́ 𝑓
At position 2:
4
𝐷𝑠2 = √(𝑟́ ℎ)2 = √𝑟́ ℎ
At position 3:
4
𝐷𝑠3 = √(𝑟́ 𝑓)2 = √𝑟́ 𝑓
1 1 1
3
𝐷𝑠 𝑒𝑞 = 𝐷𝑒𝑞 = √𝐷𝑠1 𝐷𝑠2 𝐷𝑠3 = (𝑟́ )2 (𝑓)3 (ℎ)6
1 1
−7
𝐷𝑚 𝑒𝑞 −7
1 𝑑 2 𝑔 3 𝐻
𝐿𝑎 = 2 × 10 𝑙𝑛 = 2 × 10 ln[26 ( ) ( ) ] ( ⁄𝑝ℎ𝑎𝑠𝑒)
𝐷𝑠 𝑒𝑞 𝑟́ 𝑓 𝑚
38
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
loads are balanced and the line is transposed. Find the inductance of the
line per km per phase.
Solution:
𝐷𝑒𝑞 𝐻
𝐿 = 2 × 10−4 𝑙𝑛 ( )
𝑟́ 𝑘𝑚
3
𝐷𝑒𝑞 = √4 × 6 × 9 = 6 𝑚
1.8
𝑟́ = 0.7788 × = 0.701 𝑐𝑚
2
6 × 100 𝑚𝐻
∴ 𝐿 𝑝𝑒𝑟 𝑝ℎ𝑎𝑠𝑒 𝑝𝑒𝑟 𝑘𝑚 = 2 × 10−4 𝑙𝑛 = 1.35
0.701 𝑘𝑚
Solution:
𝑆𝑒𝑙𝑓 𝐺. 𝑀. 𝐷 𝑜𝑓 𝑐𝑜𝑛𝑑𝑢𝑐𝑡𝑜𝑟 = 𝐷𝑎𝑎 = 0.9 𝑐𝑚
4
𝐷𝑠1 = 4√𝐷𝑎𝑎 𝐷𝑎𝑎́ 𝐷𝑎́ 𝑎 𝐷𝑎́ 𝑎́ = √(0.9)2 (40)2 = 6 𝑐𝑚
𝐷𝑠2 = 𝐷𝑠3 = 𝐷𝑠1 = 6 𝑐𝑚
𝐷𝑠 = 3√𝐷𝑠1 𝐷𝑠2 𝐷𝑠3 = 6 𝑐𝑚
39
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
H. W:. Find the inductance per phase per km of double circuit 3 phase
line which is shown in Fig. below. The line is completely transposed and
operates at a frequency of 50 Hz. Take the conductors dia. 6 mm.
40
Chapter Four
Electrical Design of Overhead Lines
(Capacitance of Transmission Lines)
4.1 Introduction
We know that any two conductors separated by an insulating
medium constitute a condenser or a capacitor. In case of an overhead line,
two conductors form the two plates of a capacitor and the air between the
conductors behaves as the dielectric medium. When an alternating p.d. is
applied across a transmission line, it draws a leading current, even when
supplying no load. This leading current is termed as the charging current.
It must be noted that the charging current is due to the capacitive effect
between the conductors of the line and is not in any way dependent on the
load. The strength of the charging current depends upon the voltage of
transmission, the capacitance of the line and the frequency of the ac
supply and is given by:
𝐼𝑐 = 2𝜋𝑓𝐶𝑉
If the capacitance of an overhead line is high, the line draws more
charging current, which compensates or cancels the lagging component of
load current (under the normal load conditions, the load is inductive one).
Hence the resultant current flowing in the line is reduced. The reduction
in resultant current results in:
a. Reduction of line losses and so increase of transmission efficiency.
b. Improvement of voltage regulation.
c. Improvement of power factor.
However, capacitance is defined as charge per unit of p.d., thus
capacitance per unit length of the line is:
41
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
𝑞
𝐶=
𝑉
where C is the capacitance (F/m), V is the p.d. between the conductors
(V) and q is thr charge on the line (Coulombs/m).
42
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
43
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
At position 1:
1 𝐷12 𝑟 𝐷23
𝑉𝑎𝑏1 = [𝑞𝑎 𝑙𝑛 + 𝑞𝑏 𝑙𝑛 + 𝑞𝑐 𝑙𝑛 ]
2𝜋 ∈0 𝑟 𝐷12 𝐷31
At position 2:
1 𝐷23 𝑟 𝐷31
𝑉𝑎𝑏2 = [𝑞𝑎 𝑙𝑛 + 𝑞𝑏 𝑙𝑛 + 𝑞𝑐 𝑙𝑛 ]
2𝜋 ∈0 𝑟 𝐷23 𝐷12
44
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
At position 3:
1 𝐷31 𝑟 𝐷12
𝑉𝑎𝑏3 = [𝑞𝑎 𝑙𝑛 + 𝑞𝑏 𝑙𝑛 + 𝑞𝑐 𝑙𝑛 ]
2𝜋 ∈0 𝑟 𝐷31 𝐷23
Assume (qa, qb, qc) are the same in spite of transposed during one
transposition cycle. Then, the average voltage between conductors a and
b is:
𝑉𝑎𝑏1 + 𝑉𝑎𝑏2 + 𝑉𝑎𝑏3
𝑉𝑎𝑏 =
3
1 𝐷12 𝐷23 𝐷31 𝑟3 𝐷12 𝐷23 𝐷31
= [𝑞𝑎 𝑙𝑛 + 𝑞𝑏 𝑙𝑛 + 𝑞𝑐 𝑙𝑛 ]
2𝜋 ∈0 𝑟3 𝐷12 𝐷23 𝐷31 𝐷12 𝐷23 𝐷31
1 𝐷𝑒𝑞 𝑟
= [𝑞𝑎 𝑙𝑛 + 𝑞𝑏 𝑙𝑛 ]
2𝜋 ∈0 𝑟 𝐷𝑒𝑞
45
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
46
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
1 𝐷 𝑟
𝑉𝑎𝑏 = [𝑞𝑎 𝑙𝑛 + 𝑞𝑏 𝑙𝑛 ]
2𝜋 ∈ 𝑟 𝐷
1 √𝐷2 + 4ℎ2 2ℎ
+ [−𝑞𝑎 𝑙𝑛 − 𝑞𝑏 𝑙𝑛 ]
2𝜋 ∈ 2ℎ √𝐷2 + 4ℎ2
1 2ℎ𝐷 𝑟√𝐷2 + 4ℎ2
= [𝑞 𝑙𝑛 ( ) + 𝑞 𝑙𝑛 ( )]
2𝜋 ∈ 𝑎 𝑟√𝐷2 + 4ℎ2 𝑏
2ℎ𝐷
But, since 𝑞𝑎 = −𝑞𝑏
1 2ℎ𝐷 1 2ℎ𝐷
∴ 𝑉𝑎𝑏 = [𝑞𝑎 (𝑙𝑛 )2 ] = [𝑞𝑎 𝑙𝑛( )]
2𝜋 ∈ 𝑟√𝐷2 + 4ℎ2 𝜋∈ 𝑟√𝐷2 + 4ℎ2
𝑞𝑎 𝜋∈ 𝐹
𝐶𝑎𝑏 = = ( )
𝑉𝑎𝑏 𝑙𝑛( 𝐷 𝑚
)
𝑟√1 + 𝐷2 ⁄4ℎ2
𝐷
Comparison with expression (𝐶𝑎𝑏 = 𝜋 ∈⁄𝑙𝑛 ) shows that earth
𝑟
47
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
1 𝐷 √3𝐷 𝑟 2𝐷
∴ 𝑉𝑎𝑏 = [𝑞𝑎 (𝑙𝑛 + 𝑙𝑛 ) + 𝑞𝑏 (𝑙𝑛 + 𝑙𝑛 )
2𝜋 ∈ 𝑟 2𝐷 𝐷 √3𝐷
𝐷 √3𝐷
+ 𝑞𝑐 (𝑙𝑛 + 𝑙𝑛 )]
√3𝐷 𝐷
1 √3𝐷
= (𝑞𝑎 − 𝑞𝑏 )𝑙𝑛
2𝜋 ∈ 2𝑟
Similarly:
1 √3𝐷
𝑉𝑎𝑐 = (𝑞𝑎 − 𝑞𝑐 )𝑙𝑛
2𝜋 ∈ 2𝑟
1 √3𝐷
𝑉𝑎𝑏 + 𝑉𝑎𝑐 = 3𝑉𝑎𝑛 = (2𝑞𝑎 − 𝑞𝑏 − 𝑞𝑐 )𝑙𝑛
2𝜋 ∈ 2𝑟
3𝑞𝑎 √3𝐷
𝑞𝑎 + 𝑞𝑏 + 𝑞𝑐 = 0 → 𝑞𝑎 = −(𝑞𝑏 + 𝑞𝑐 ), 𝑡ℎ𝑒𝑛: 3𝑉𝑎𝑛 = 𝑙𝑛
2𝜋 ∈ 2𝑟
𝑞𝑎 2𝜋 ∈ 𝐹
∴ 𝐶𝑎𝑛 = = ( ) (𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑎𝑛𝑐𝑒 𝑜𝑓 𝑐𝑜𝑛𝑑𝑢𝑐𝑡𝑜𝑟 𝑡𝑜 𝑛𝑒𝑢𝑡𝑟𝑎𝑙)
𝑉𝑎𝑛 √3𝐷 𝑚
𝑙𝑛 2𝑟
2𝜋 ∈ 𝐹
𝐶𝑛 = 2𝐶𝑎𝑛 = 2 × ( ) (𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑎𝑛𝑐𝑒 𝑜𝑓 𝑝ℎ𝑎𝑠𝑒 𝑡𝑜 𝑛𝑒𝑢𝑡𝑟𝑎𝑙)
√3𝐷 𝑚
𝑙𝑛 2𝑟
48
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
49
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
3𝑞𝑎 2𝑑 3 𝑔2
𝑉𝑎𝑏 + 𝑉𝑎𝑐 = 3𝑉𝑎𝑛 = 𝑙𝑛 3 2
6𝜋 ∈ 𝑟 𝑓
𝑞𝑎 2𝑑 3 𝑔2 𝑞𝑎 3 𝑑 𝑔 2⁄3
∴ 𝑉𝑎𝑛 = 𝑙𝑛 3 2 = 𝑙𝑛[√2 ( ) ( ) ]
6𝜋 ∈ 𝑟 𝑓 2𝜋 ∈ 𝑟 𝑓
𝑞𝑎
∴ 𝐶𝑎𝑛 =
𝑉𝑎𝑛
2𝜋 ∈ 𝐹
= (𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑎𝑛𝑐𝑒 𝑜𝑓 𝑐𝑜𝑛𝑑𝑢𝑐𝑡𝑜𝑟 𝑡𝑜 𝑛𝑒𝑢𝑡𝑟𝑎𝑙 𝑖𝑛 )
3 𝑑 𝑔 2⁄3 𝑚
𝑙𝑛[√2 ( ) ( ) ]
𝑟 𝑓
𝐶𝑛 = 2𝐶𝑎𝑛
2𝜋 ∈ 𝐹
=2× (𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑎𝑛𝑐𝑒 𝑜𝑓 𝑝ℎ𝑎𝑠𝑒 𝑡𝑜 𝑛𝑒𝑢𝑡𝑟𝑎𝑙 𝑖𝑛 )
3 𝑑 𝑔 2⁄3 𝑚
𝑙𝑛[√2 ( ) ( ) ]
𝑟 𝑓
𝜋∈ 𝜋 × 10−9 −12
𝐹
𝐶𝑎𝑏 = = = 4.34 × 10
𝐷 36𝜋𝑙𝑛(1.5⁄2.5 × 10−3 ) 𝑚
𝑙𝑛
𝑟
𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑎𝑛𝑐𝑒 𝑓𝑜𝑟 40 𝑘𝑚 = 4.34 × 10−12 × 40 × 103 = 0.174 𝜇𝐹
50
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
b. with ground:
𝜋∈ 10−9
𝐶𝑎𝑏 = =
𝐷 1.5
𝑙𝑛( ) 36 𝑙𝑛( )
√ 𝐷2 2.25
𝑟 1+ 2 2.5 × 10−3 √1 + 196
4ℎ
𝐹
= 4.4 × 10−12
𝑚
𝐶𝑎𝑏 𝑓𝑜𝑟 40 𝑘𝑚 = 4.4 × 10−12 × 40 × 103 = 0.176 𝜇𝐹
51
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
Solution:
2𝜋 ∈ 𝐹
𝐶𝑎𝑛 = ( ) (𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑎𝑛𝑐𝑒 𝑜𝑓 𝑜𝑛𝑒 𝑐𝑜𝑛𝑑𝑢𝑐𝑡𝑜𝑟 𝑡𝑜 𝑛𝑒𝑢𝑡𝑟𝑎𝑙)
√3𝐷 𝑚
𝑙𝑛 2𝑟
2𝜋 ∈ 𝐹
𝐶𝑛 = 2𝐶𝑎𝑛 = 2 × ( ) (𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑎𝑛𝑐𝑒 𝑜𝑓 𝑝ℎ𝑎𝑠𝑒 𝑡𝑜 𝑛𝑒𝑢𝑡𝑟𝑎𝑙)
√3𝐷 𝑚
𝑙𝑛 2𝑟
2𝜋 ∈ 2𝜋 ∈
= = = 2.26 𝜇𝐹
√3𝐷 1 √3 × 200 12
ln( 2𝑟 )2 ln( )
2.5
Solution:
2𝜋 ∈
𝐶𝑎𝑛 = 3
𝑙𝑛[√2(𝑑⁄𝑟)(𝑔⁄𝑓)2⁄3 ]
2𝜋 ∈
𝐶𝑛 = 2 × 3
𝑙𝑛[√2(𝑑⁄𝑟)(𝑔⁄𝑓)2⁄3 ]
𝑔 = √52 + 22 = √29
𝑓 = √52 + 42 = √41
4𝜋 ∈
∴ 𝐶𝑛 = 3 = 0.02 𝜇𝐹/𝑘𝑚
𝑙𝑛[√2(200⁄1.25)(29⁄41)2⁄6 ]
52
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
H.W.: Find the capacitance per km per phase to neutral of a 3-phase line
arranged as shown in Fig. The outside dia. of conductors is 2.60 cm. The
line is transposed. Take the effect of ground into account.
53
Chapter Five
Underground Cables
5.1 Introduction
Insulated conductors those are usually laid underground are called
“Cables”. External protection against mechanical injury, moisture and
chemical reaction is provided on the cable. Cable is more expensive than
overhead lines, particularly at high voltages. Also, temperature rise is
high in cables. There is limitation of raising the operating voltage. In low
and medium voltage distribution in urban areas, cables are more
widespread.
54
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
The resistance of this cylindrical shell for length l of the cable is:
𝑙
𝑅𝑖 = 𝜌 𝑤ℎ𝑒𝑟𝑒 𝜌 𝑖𝑠 𝑡ℎ𝑒 𝑟𝑒𝑠𝑖𝑠𝑡𝑖𝑣𝑖𝑡𝑦 𝑜𝑓 𝑖𝑛𝑠𝑢𝑙𝑎𝑡𝑖𝑜𝑛
𝐴
𝑑𝑥
𝑑𝑅𝑖 = 𝜌
2𝜋𝑥𝑙
𝐷 ⁄2
𝜌 𝑑𝑥 𝜌 𝐷
𝑅𝑖 = ∫ ∙ → 𝑅𝑖 = 𝑙𝑛 𝑜ℎ𝑚𝑠
𝑑 ⁄2 2𝜋𝑙 𝑥 2𝜋𝑙 𝑑
55
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
Therefore, capacitance:
𝑞 2𝜋 ∈ 𝐹
𝐶= = ( )
𝑉 𝑙𝑛 𝐷 𝑚
𝑑
2𝜋 ∈ 𝑉
𝑞= ;
𝐷
𝑙𝑛
𝑑
𝐷
2𝜋 ∈ 𝑉⁄𝑙𝑛 𝑉
𝑎𝑛𝑑 𝑔 = 𝑑=
2𝜋 ∈ 𝑥 𝐷
𝑥𝑙𝑛
𝑑
The stress is maximum at the surface of the conductor, i.e. when x = r
𝑉 2𝑉 𝑘𝑉
𝑔𝑚𝑎𝑥 = = ( )
𝐷 𝐷 𝑚
𝑟𝑙𝑛 𝑑𝑙𝑛
𝑑 𝑑
The stress is minimum at the sheath of cable.
2𝑉 𝑘𝑉
𝑔𝑚𝑖𝑛 = ( )
𝐷 𝑚
𝐷𝑙𝑛
𝑑
Therefore, the stress is a maximum at the conductor and a minimum at
the sheath. In order to avoid breakdown of the insulation it would be
advisable to have a more uniform stress distribution. This may be done by
“Capacitance Grading”.
Example 1: A single core cable has a core diameter of 2.5 cm, insulation
thickness of 1,25 cm and resistivity of the insulation is 4.5 × 1014 Ω.cm.
Calculate the insulation resistance per km.
Solution:
𝜌 𝐷
𝑅𝑖 = 𝑙𝑛
2𝜋𝑙 𝑑
𝜌 = 4.5 × 1014 Ω. 𝑐𝑚; 𝐷 = 2.5 + (2 × 1.25) = 5 𝑐𝑚
𝑙 = 1 𝑘𝑚 = 105 𝑐𝑚; 𝑑 = 2.5 𝑐𝑚
56
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
4.5 × 1014 5
∴ 𝑅𝑖 = 𝑙𝑛 = 495 𝑀Ω
2𝜋 × 105 2.5
H.W.: Find the most economical value of the diameter of a single core
cable to be used on a 132 kV, 3 phase system. Find also the overall
diameter of the insulation if the peak permissible stress is not to exceed
60 kV per cm.
[Ans: 3.6 cm, 9.786 cm]
57
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
𝑞
𝑇ℎ𝑒 𝑠𝑡𝑟𝑒𝑠𝑠 𝑖𝑛 𝑡ℎ𝑒 𝑖𝑛𝑛𝑒𝑟 𝑑𝑖𝑒𝑙𝑒𝑐𝑡𝑟𝑖𝑐 𝑎𝑡 𝑎 𝑟𝑎𝑑𝑖𝑢𝑠 𝑥 𝑖𝑠: 𝑔1 =
2𝜋 ∈1 𝑥
𝑞
𝐷𝑖𝑒𝑙𝑒𝑐𝑡𝑟𝑖𝑐 𝑠𝑡𝑟𝑒𝑠𝑠 𝑖𝑛 𝑡ℎ𝑒 𝑜𝑢𝑡𝑒𝑟 𝑑𝑖𝑒𝑙𝑒𝑐𝑡𝑟𝑖𝑐 𝑖𝑠: 𝑔2 =
2𝜋 ∈2 𝑥
𝑑1 ⁄2 𝐷 ⁄2
𝑞 1 𝑑1 1 𝐷
𝑉=∫ 𝑔1 𝑑𝑥 + ∫ 𝑔2 𝑑𝑥 = [ 𝑙𝑛 + 𝑙𝑛 ]
𝑑 ⁄2 𝑑1 ⁄2 2𝜋 ∈1 𝑑 ∈2 𝑑1
𝑞 2𝜋
𝐶= =
𝑉 [ 1 𝑙𝑛 𝑑1 + 1 𝑙𝑛 𝐷 ]
∈1 𝑑 ∈2 𝑑1
𝑑 𝑑1
𝐸𝑙𝑒𝑐𝑡𝑟𝑖𝑐𝑎𝑙 𝑠𝑡𝑟𝑒𝑠𝑠 𝑤𝑖𝑙𝑙 𝑏𝑒 𝑚𝑎𝑥𝑖𝑚𝑢𝑚 𝑎𝑡 𝑥 = 𝑎𝑛𝑑 𝑎𝑡 𝑥 = :
2 2
𝑞 𝑞
𝑔1𝑚𝑎𝑥 = =
2𝜋 ∈1 𝑑/2 𝜋 ∈1 𝑑
𝑆𝑢𝑏𝑠𝑡𝑖𝑡𝑢𝑡𝑖𝑛𝑔 𝑡ℎ𝑒 𝑣𝑎𝑙𝑢𝑒 𝑜𝑓 𝑞 𝑖𝑛 𝑡𝑒𝑟𝑚𝑠 𝑜𝑓 𝑉:
58
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
2𝑉
𝑔1𝑚𝑎𝑥 =
𝑑 ∈ 𝐷
𝑑[𝑙𝑛 1 + 1 𝑙𝑛 ]
𝑑 ∈2 𝑑1
2𝑉
𝑔2𝑚𝑎𝑥 =
∈ 𝑑 𝐷
𝑑1 [ 2 𝑙𝑛 1 + 𝑙𝑛 ]
∈1 𝑑 𝑑1
The impedance between core 1 and the star point must be equal to (1/3)
times the impedance of each branch of the delta. This gives:
59
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
1 1
= 𝑜𝑟 𝐶1 = 3𝐶𝑐
𝜔𝐶1 3𝜔𝐶𝑐
The star may be assumed to be at zero potential and if the sheath is also at
zero potential, the capacitance of each conductor to neutral is:
𝐶0 = 𝐶1 + 𝐶𝑠 = 3𝐶𝑐 + 𝐶𝑠
The values of Cc and Cs may be found by actual measurement as
explained:
1. Connect conductors 2 and 3 to the sheath. Capacitances Cc between
conductors 2 and 3 and Cs of conductors 2 and 3 with respect to the
sheath are eliminated.
Capacitances Cc and Cs are now in parallel across core 1 and the sheath
and they add up. Measure the capacitance between core 1 and the sheath.
Let this be Ca, then:
𝐶𝑎 = 2𝐶𝑐 + 𝐶𝑠
2. Next, join all cores and measure the capacitance with respect to the
sheath. Let this be Cb, then:
1
𝐶𝑏 = 3𝐶𝑠 𝑜𝑟 𝐶𝑠 = 𝐶𝑏
3
1
𝐶𝑎 = 2𝐶𝑐 + 𝐶𝑏
3
1 1
𝐶𝑐 = 𝐶𝑎 − 𝐶𝑏
2 6
60
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
3 1 1
𝐶0 = 𝐶𝑎 − 𝐶𝑏 + 𝐶𝑏
2 2 3
3 1
∴ 𝐶0 = 𝐶𝑎 − 𝐶𝑏
2 6
61
Power Engineering Third Stage
Dr. Dhyaa Kamml M.Sc. Hiba Abdulkareem M.Sc. Hassan Al-Ajwad
H.W.: For the graded cable with permittivity ∈1 and ∈2 , obtain the
condition under which the maximum values of the electric fields in the
two regions are equal. [Ans: ∈𝟏 𝒅 =∈𝟐 𝒅𝟏 ]
62