HV Testing 2

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

HV Testing of Equipments

Testing of transformer

• Transformer is one of the most expensive and


important equipment in power system.
• If it is not suitably designed its failure may cause
a lengthy and costly outage.
• Therefore, it is very important to be cautious
while designing its insulation, so that it can
withstand transient over voltage both due to
switching and lightning.
• Tests include short circuit test, open circuit test,
temperature rise test, impulse test, pd test.
Partial discharge test
• The test is carried out on the windings of the transformer to
assess the magnitude of discharges.
• The transformer is connected as a test specimen and the
discharge measurements are made. The location and
severity of fault is ascertained using the travelling wave
produce due to pd.
• The measurements are to be made at all the terminals of the
transformer and it is estimated that if the apparent measured
charge exceeds 104 Pico-coulombs, the discharge magnitude
is considered to be severe and the transformer insulation
should be so designed that the discharge measurement
should be much below the value of 104 Pico-coulombs.
Impulse Testing of Transformer

• The impulse level of a transformer is determined by


the breakdown voltage of its minor insulation
(Insulation between turn and between windings),
• Breakdown voltage of its major insulation (insulation
between windings and tank) and the flash over
voltage of its bushings or a combination of these.
Test Process

• Impulse testing consists of the following steps:


(i) Application of impulse of magnitude 75% of the Basic
Impulse Level (BIL) of the transformer under test.
(ii) One full wave of 100% of BIL.
(iii) Two chopped wave of 115% of BIL.
(iv) One full wave of 100% BIL and
(v) One full wave of 75% of BIL.
• Usually the chopping time is of 3 to 6µs
• A rod gap is used to chop the impulse wave.
Test results

General observations
• During impulse testing the fault can be located by general
observation like noise in the tank or smoke or bubble in the
breather.
Oscilloscopic observation
• If there is a fault, it appears on the Oscilloscope as a partial
of complete collapse of the applied voltage.
• Study of the wave form of the neutral current also indicated
the type of fault. If an arc occurs between the turns or form
turn to the ground, a train of high frequency pulses are seen
on the oscilloscope and wave shape of impulse changes.
• If it is a partial discharge only, high frequency oscillations
are observed.
Non destructive testing

• Measurement of the insulation resistance under d.c.


voltages.
• Determination of loss factor tan δ and the
capacitance C.
• Measurement of partial discharges.
Losses in a dielectric

(i) Conduction loss Pc by ionic or electronic


conduction. The dielectric, has σ as
conductivity.
(ii) Polarization loss Pp.
(iii) Ionization loss Pi by partial discharges
internal or external zones.
Specimen and electrode

• Normally of 5 to 10 cm length and 3 to 12 mm


thickness.
• Electrode may be aluminum or lead foils usually
pressed on the surface of the specimen by a roller and
made to stick using a conductive adhesive like
silicone grease.
Measurement of resistivity
Measurement of resistivity

If I is the current and V is the voltage applied, then


Dielectric loss factor, tanδ

Iim =VωC
I

IReal

P=VI=VIReal =VIimtanδ
Loss tangent
High voltage Shearing bridge
Bridge balance
Determination of loss tangent
Determination of loss tangent
Determination of loss tangent
Determination of loss tangent
Loss tangent

You might also like