1 AIM
The aim of this document is to define the configurations and setting of all devices assembled in the electrical
cabinets of SG 4.X.
2 SCOPE
To ensure that the devices are configurated correctly, during the fabrication, assembly and commissioning of
the cabinets/switchgear, the settings will be adjusted and checked by different groups.
The checks / adjustments that must be done by each of the groups in the devices are marked in this document
with an “X” in each component.
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
4 COMUNICATIONS
For PxC components, name assignment can be done by Netnames or PCWorkx software.
X= WTG number.
AA2401 CONVERTER
TAG Module IP (SGIPE<2.3) IP (Other SCADAs) Fast architecture
IP: NA IP: 192.168.11.X IP: NA
-AA0004 CCU Subnet Mask: NA Subnet Mask:255.255.224.0 Subnet Mask: NA
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
AA2401 CONVERTER
TAG Module IP
IP: 192.168.250.20
-AA0004 CCU Subnet Mask:255.255.255.0
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
5 MV PROTECTIONS SETTINGS
5.1 SWITCHGEAR
The switchgear settings are all included in the document GD279373 “RD RELAY SETTINGS FOR WTG MV
SWITCHGEAR”.
The settings are defined based on switchgear type, windfarm voltage (Kv) and WTG main transformer power
(kVA).
Perform the next procedure to access to the relay in order to connect to the web server of the SEL-849, the
relay and your PC must be connected to the same Ethernet network (192.168.9.X by default) Where X shall be
different to station number within the wind farm
In example; a Wind farm of 49 WTGs with IP domain 192.168.1.X. then PC shall be configured with IP address
192.168.1.50 as following picture.
o Connect a standard Ethernet cable to the port 2 of APTIF relay (KR849). Connector is located at
one side of the relay body:
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
o Type at URL bar following IP address: 169.254.0.Y and press ENTER, Where Y is the station
number defined as per wind turbine number
Relay will open its own web page. It´s an interface to access to relay settings without installing any
dedicated software.
The Login page of the web server allows you to access either ACC, 2AC, or CAL level. The menu item
you select under Access Level determines the access level at which you enter the web server.
additional level access is required in order to update settings use the following passwords as
below table
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
o for view settings. Select with the mouse pointer the menu SETTINGS:
o Logging in to the web server with 2AC access allows you to modify relay
o settings (with ACC access, you can only view settings). When you select
o Settings from the navigation pane, the screen displays all available classes of settings in the
SEL-849
Note: settings can be modified at this point. Since there are a lot of settings to be submitted, A preload
configuration shall be included for each wind farm to be imported following instruction in point 4.2
The web server is a convenient way to both export settings from a relay and import settings to a relay. Each
settings class is saved in a separate .7z file according to frequency and voltage WF level.
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
Located on the navigation pane, System consists of four categories (File Management, passwords, Date/Time,
and Device Reset). Use File Management to export and import settings from the relay.
Decompress the attached file to obtain all settings in separated *.txt files. Each file shall be imported into relay via
Web server.
Select the class of settings you want to import from pre-configurated Settings (.txt files)... Then, you can click
Import Settings to upload configuration.
Repeat the import procedure for all .txt files.
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
6 CABINET SETTINGS
Depending of the motor supplier the figure of the current could deviate.
For breakers 5% is admitted.
Nevertheless, frequency drive parameters shall be confirmed with the nameplate of the motor, in terms of rated
speed and current in 50Hz, and set up according these values.
G1 G2 G3 DEVICE SETTING
X BT001G 0ºC
X BT002 5ºC Heating
X BT002 15ºC Cooling
X BH003 90%
KR330G
- RELECO
(only off-delay)
- ROCKWELL
- FINDER
X
(off-delay and on-delay)
Units:
Time: 2
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
- FINDER 83.02
1m
10
1b
CE
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
Protections settings:
SETTING STATUS
G1 G2 G3 DEVICE AFTER
G1 G2 G3
SETTING
L: L:
CONVERTIDOR
MKI (SG 4.5): MKI (SG 4.5):
GAMESA ELECTRIC
I1 = 0.85 I1 = 0.85
FG005 (ABB) T1 = 12 s T1 = 12 s
MKI: MKII (SG 5.0): MKII (SG 5.0):
Emax2 E1.2N 1250 I1 = 0.9 I1 = 0.9
Relay Ekip Dip LSI 3p T1 = 12 s T1 = 12 s
X X MKII: DOESN`T APPLY OPEN
S: (I2t) S: (I2t)
Emax2 E1.2N 1250/E9 I2 = 1.5 I2 = 1.5
800Vac
T2 = 0.1 s T2 = 0.1 s
Relay Ekip Dip LSI 3p
------------------- -------------------
I=10xIn I=10xIn
I: I:
I3 = 2 I3 = 2
N= OFF N= OFF
L: L:
CONVERTIDOR Ir=In*(L=0.9) Ir=In*(L=0.9)
INGETEAM Ir=1125A Ir=1125A
S: S:
FG005 (SIEMENS)
3WL1112-3CB32-4AN2-Z
Isd=In*(S=1.5) Isd=In*(S=1.5)
C01+K07+F31 Isd=1875A Isd=1875A
3P 690V 1250A B 50KA Tsd=0 Tsd=0
I: I:
Ii≥In*20 Ii≥In*20
X X DOESN`T APPLY OPEN
Other settings:
G1 G2 G3 DEVICE SETTING
X BT001 -10ºC
X BT002 +10ºC
X BM001 90%
X BM002 90%
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
SETTING STATUS
G1 G2 G3 DEVICE AFTER
G1 G2 G3
SETTING
FG008 L: L: L:
Emax2 E6.2H/E9 6300 MK I (SG 4.5): MK I (SG 4.5): MK I (SG 4.5):
Relay Ekip Dip LSI 3p I1 = 0.7 I1 = 0.7 I1 = 0.7
T1 = 48 s T1 = 48 s T1 = 48 s
MK II (SG 5.0): MK II (SG 5.0):
I1 = 0.72 I1 = 0.72
T1 = 48 s T1 = 48 s
S: (I2t) S: (I2t) S: (I2t)
MK I (SG 4.5): MK I (SG 4.5): MK I (SG 4.5):
I2 = 0.8 I2 = 0.8 I2 = 0.8
X X X T2 = 0.1 s T2 = 0.1 s T2 = 0.1 s OPEN
------------------- ------------------- -------------------
I=10xIn I=10xIn I=10xIn
MK II (SG 5.0): MK II (SG 5.0):
I2 = 1 I2 = 1
T2 = 0.1 s T2 = 0.1 s
------------------- -------------------
I=10xIn I=10xIn
I: I: I:
I3 = 4 I3 = 4 I3 = 4
N= OFF N= OFF N= OFF
Other settings:
G1 G2 G3 DEVICE SETTING
X BT101 -10ºC
X BM101 90%
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
SETTING STATUS
G1 G2 G3 DEVICE AFTER
G1 G2 G3 SETTING
FG001
XT1B 160A with TMD
relay
X X L: I1 = Max DOESN`T APPLY L: I1 = Max OPEN
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
DOESN`T CLOSED
X FG400 (MS132-6.3) (VHC) 13A (50Hz) DOESN`T APPLY
APPLY
DOESN`T CLOSED
X FG401 (MS132-10) (VHC) 7.2A (50Hz) DOESN`T APPLY
APPLY
DOESN`T CLOSED
X FG402 (MS132-10) (VHC) 7.2A (50Hz) DOESN`T APPLY
APPLY
Other settings:
G1 G2 G3 DEVICE SETTING
X BT016A 5ºC
X BT016B 15ºC
X BT017A 5ºC
X BT017B 15ºC
X BH016 90%
X BT001 0ºC
KR330
- RELECO
(only off-delay)
- ROCKWELL
- FINDER
Units:
Time: 3
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
- FINDER 83.02
1m
10
1b
CE
G1 G2 G3 DEVICE SETTING
UC611
I= 3A
Delay= 0,3s
X X
SV620
Sensor adjust = MAX
Key position = Active
X X
KR214 NOTE:
(ROG) The ROG is configured in different way depending on the WTG type. In
the present document and only for information purpose, the ROG
configuration is depicted for SG 4.X WTG.
Therefore, for other WTG type consult engineering department.
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
DISPLAY
SETUP
TA ratio
200/5
1) 2 seconds.
2) 3 times
3) 1 time
SETUP
Communication
MODBUS
(default)
1) 2 seconds.
2) 4 times
3) 1 time
4) MODBUS
SETUP
Communication
ADDRESS 31
(default)
1) 2 seconds.
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
2) 4 times
3) 1 time
4) 1 time
5) ADDR 31
SETUP
Communication
SPEED 9600
1) 2 seconds.
2) 4 times
3) 1 time
4) 2 times
5) Speed 9600
SETUP
Communication
PARITY “NONE”
(default)
1) 2 seconds.
2) 4 times
3) 1 time
4) 3 times
5) Pty “NONE”
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
SETUP
Communication
STOP BIT “1”
(default)
1) 2 seconds.
2) 4 times
3) 1 time
4) 4 times
5) Sb “1”
LENGUAGE
English
1) 2 seconds.
2) 3 times
3) 1 time
4) →English
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
DISPLAY
2. Select , press .
4. Press for two seconds. Press once. The display will show the
quantity Voltage ( on the display) and the ratio. To change the ratio, press
and hold .
If not required, then press and hold to step back to the previous menu.
5. Press once to get to the next menu. The display will show the baudrate
6. Press once to get to the next menu. The display will show the address
( ). Set address: 31.
7. Press once to get to the next menu. The display will show the parity
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
ESC
ENTER
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
NOTE: The speed drive configuration is always configured as if it is connected at 50Hz grid independently the real
grid frequency.
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
Configuration 50Hz/60Hz
UF380 UF480
(Schneider → ATV320D15N4B) (Schneider → ATV320U75N4B)
50Hz/60Hz
50Hz/60Hz
Nissens (WEG)/Fluitecnik (Siemens)
a) Connect control wiring and select control configuration
b) Drive configuration
[Access level]:
LAC
[ACCES S LEVEL]
L A C Access to all menus on the Std Epr Epr
integrated display terminal
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
FD-2018-357131-00.
pdf
Motordatasheet_1L
E1001-1CB23-4FB4-Z_N11_de_en.pdf
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
[Acceleration]:
A C C
Acceleration time (s) 3.0 20 20
[Deceleration]:
d E C
Deceleration time (s) 3.0
[Low speed]:
SEt
L S P Motor frequency at minimum 0.0
reference (Hz)
[SETTINGS]
[High speed]:
H S P Motor frequency at maximum 50.0 80 65
reference (Hz)
[Mot. therm. current]:
Drive
i t H Nominal current on motor nameplate 41 15
(A) rating
e) Set control choice
C t L [Ref.1 channel]:
[COMMAND]
F r I
Reference control AI1 AI3 AI3
DRI > CONF > FULL > I_O
Factory UF380 UF480
Menu Code Description
settings 50Hz/60Hz
Nissens/Fluitecnik
50Hz/60Hz
I _ O
[AI3 CONFIGURATION]
A I 3 / C r L 3 [AI3 min value] 0 4mA 4mA
A t r - / A t r [Automatic restart] nO
F L t - A t r - / t A r [Max restart time] (min) 5
[FAULT MANAGEMENT] r S t - / r S F [Fault reset] nO LI2 LI2
I P L - [Input phase loss] Yes No No
F L t > U S b - U s b / U S b [UnderV Prevention] 0 2 2
F L t > U S b - U s b / S t P [UnderV Prevention] nO MMS MMS
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
ESC ENTER
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
NOTE: The speed drive configuration is always configured as if it is connected at 50Hz grid independently the real
grid frequency.
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
Configuration 50Hz/60Hz
UF380 UF480
(Siemens → 6SL3210-1KE23-2AB1) (Siemens → 6SL3210-1KE22-6AB1)
50Hz/60Hz
50Hz/60Hz
Nissens (WEG)/Fluitecnik (Siemens)
a) Connect control wiring and select control configuration
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
c) Drive configuration
[DRIVE COMMISSIONING]:
PARAMS/EXPERT FILTER
[DRIVE COMMISSIONING]
P 1 0 Sets the parameter filter to 0 1 1
commission a drive
Motordatasheet_1L
E1001-1CB23-4FB4-Z_N11_de_en.pdf
FD-2018-357131-00.
pdf
[Maximum speed]:
PARAMS/EXPERT FILTER
[DRIVE COMMISSIONING]
P 1 0 8 2 Sets the highest possible speed 1500 2870 1860
(rpm).
[Reference speed reference
P 2 0 0 0
frequency]: 1500 2870/2344 1860
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
P 7 5 6 [ 0 0 ]
[CU analog inputs type]: 4 3 3
Sets the type of analog inputs. [-10V…+10V] [4…20mA] [4…20mA]
[Acknowledge faults]:
PARAMS/EXPERT FILTER P 2 1 0 3 [ 0 0 ] Sets the first signal source to 722.2 722.1 722.1
[DRIVE COMMISSIONING] acknowledge faults [DI2] [DI1] [DI1]
P 1 1 1 3 [ 0 ]
[Setpoint inversion]: 722.1 0 0
Setpoint remains unchanged. [DI1] [No invert] [No invert]
g) Fault management
[DRIVE COMMISSIONING]:
PARAMS/EXPERT FILTER
[DRIVE COMMISSIONING]
P 1 0 Sets the parameter filter to 1 0 0
commission a drive
[SAVE PARAMETERS]:
PARAMS/EXPERT FILTER
[DRIVE COMMISSIONING]
P 9 7 1 Setting to save parameters in 0 1 1
nonvolatile memory.
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
Other settings:
G1 G2 G3 DEVICE SETTING
X BT030 0ºC
X BT031 5ºC
X BT032 5ºC
X BT032 15ºC
KR330H
- RELECO
(only off-delay)
- ROCKWELL
- FINDER
Units:
Time: 3
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
- FINDER 83.02
1m
10
1b
CE
1. Connection to fan is done via cable interface (USB connection to PC and RSA-RSB connection pinned to
fan connection box).
i. This cable interface can be requested from EBMPAPST_Ibérica as: cable interface
21490-1-0174.
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
Software necessary: EC Control 3.0 or newer; can be downloaded from EBM web site:
http://info.ebmpapst.us/ec-control-version-3.12-download .
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
3. This configuration could be re-loaded into the fan, instead of configured, just using EC CLONE software
(included file in CD-ROM) from a computer connected to the fan and loading configuration included in
files:
Supposing a fan received from supplier without configuration, steps to follow are:
i. Communicate with the fan, connection a laptop with it, viea USB interface described on top
of this document. Laptop must have ECclone already installed.
ii. Write the file gamesa 110319.modbus
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
IBE-TEC-001_1-R01- Edition 2
Confidentiality: 2 / SUPPLIER INFORMATION
IBE-TEC-001_1-R01- Edition 2