1) All performance values are subject to IS/IEC 60034-1 tolerances, unless otherwise specified.
2) Performance values are at rated voltage and rated frequency condition and for DOL starting condition.
3) Motor GD2 = Load GD2 assumed wherever not mentioned.
4) Where starting time is more than 10 seconds, provision of heavy duty relays is mandatory.
Notes for VFD Motors
1) Motors suitable to run on VFD supply are designed with an insulation system suitable for withstanding voltage of 1.56 kV (peak phase
to phase) and rise time > = 0.1 micro sec.
2) The customer / his system integrator have to ensure that the voltage at motor terminals shall not exceed above limit by properly
selecting cable length and using suitable filters / choke.
3) Switching frequency should not exceed 5.0 kHz
4) For constant torque application, voltage boost is necessary for frequencies <= 17Hz
5) Temperature rise of motor by resistance measurement with VFD supply will be limited to class F limit.
0.750K4P3HLAXXAAX / 3H0804EBATSSX
1 MCG MCG 1/18/2022
0 MCG MCG 7/9/2021
Rev No. Prepared By Checked By Date
2 X 660 MW, UDANGUDI STPP (STAGE-1) BAP-RANIPET
SPECIFICATION FOR LT MOTOR No: ROS:4261, REV: 01
d. Test running of the motors, checking the temperature rise and identifying the hot
spot.
DRAWINGS TO BE SUBMITTED AFTER AWARD OF CONTRACT
1) OGA drawing showing the position of terminal boxes, earthing connections etc.
2) Arrangement drawing of terminal boxes.
3) Characteristic curves:
i. Current vs. time at rated voltage.
ii. Speed vs. time at rated voltage.
iii. Torque vs. speed at rated voltage and minimum voltage.
For the motors with solid coupling the above curves i), ii), iii) to be furnished for the
motors coupled with driven equipment. In case motor is coupled with mechanical
equipment by fluid coupling, the above curves shall be furnished with and without
coupling.
iv. Thermal withstand curve under hot and cold conditions at rated voltage and max.
permissible voltage.
v. Load performance curves.
DATA SHEET
LT MOTORS (A.C.)
1. Application :
2. Type : Energy Efficient (IE3)
3. Frame size : 80
4. Manufacturer : Bharat Bijlee
5. Rated output in KW : 0.75 Kw
6. Duty cycle : Continuous, S1
7. Rated voltage, no. of phases
and frequency : 415 V, 3 Ph, 50 Hz
8. Allowed voltage variation : 10%.
9. Allowed frequency variation : (+) 3% and (-) 5%
10. Combined voltage and Frequency
Variation : 10 % (Absolute sum)
11. At rated Voltage and frequency
a. Full load current (Amps) : 1.71 Amps
b. Rated speed : 1420 rpm
c. Full load efficiency : 82.5 %
d. Full load power factor : 0.74
e. Starting torque in % of FLT : 0.51
12. Method of starting : DOL
13. Degree of protection : IP55
14. Method of ventilation : TEFC
15. Class of insulation : "F" (temp. rise limited to class B)
16. Stator winding connection : Star
(For continuous run) (Delta / Star)
17. Full load torque : 1.53 Kgm
18. Breakdown torque in % of FLT : 1.68 Kgm
19. Pull up torque in % of FLT : 1.22 Kgm
20. Locked rotor current in Amps : 9.4 Amps
(600% with tolerance of 20%)
21. Motor efficiency and P.F.AT :
a. 100 % load 82.5 %
b. 75% load 82.5 %
c. 50% load 80.0 %
d. 25% load NA
22. Locked rotor withstand time under
hot/cold condition at 110 % Voltage : 24.7 Hot / 49.5 Cold (Sec)
2 X 660 MW, UDANGUDI STPP (STAGE-1) BAP-RANIPET
SPECIFICATION FOR LT MOTOR No: ROS:4261, REV: 01
a. Bidder shall provide all cable glands required for glanding the above mentioned cables
both at field instrument and local control panel side, junction boxes side and at control
room side.
b. Cable glands
i. Cable glands shall conform to BS: 6121 and be of robust construction capable of
clamping cable and cable armour (for armoured cables) firmly without injury to
insulation.
ii. Cable glands shall be made of heavy duty brass machine finished and nickel chrome
plated. Thickness of plating shall not be less than 10 micron. All washers and
hardware shall also be made of brass with nickel chrome plating Rubber components
shall be of neoprene and of tested quality. Necessary cable dimensions shall be
furnished to the successful contractor.
iii. Cable glands shall be single compression for indoor use, double compression type for
outdoor use. Glands for classified hazardous areas shall be double compression type
flameproof and weather proof duly certified by CMRS and approved by CCE.
Cable lugs/ferrules
The cables lugs shall be conforming to IS: 8309. Machine ferruling shall be adopted.
PERFORMANCE CURVES
3 Phase Squirrel Cage Induction Motor
Customer : TAMIL NADU GENERATION AND DISTRIBUTION CORPORATION LIMITED BBL Ref No.: - Quantity : 4 Nos
Consultant : TATA CONSULTING ENGINEERS LIMITED BANGALORE Tag Nos. : 90GCN09 AE001/AE002 & 90GCN10 AE001/AE002
600%
500%
400%
300%
200%
100%
0%
0% 20% 40% 60% 80% 100%
% Synchronous speed
0.750K4P3HLAXXAAX/3H0804EBATSSX
Customer : TAMIL NADU GENERATION AND DISTRIBUTION CORPORATION LIMITED BBL Ref No.: - Quantity : 4 Nos
Consultant : TATA CONSULTING ENGINEERS LIMITED BANGALORE Tag Nos. : 90GCN09 AE001/AE002 & 90GCN10 AE001/AE002
85 1.00
80
0.90
75
70 0.80
Efficiency in %
Power Factor
65
0.70
60
55 0.60
50
0.50
45
40 0.40
0% 25% 50% 75% 100%
Output in % of FL
0.750K4P3HLAXXAAX/3H0804EBATSSX
Customer : TAMIL NADU GENERATION AND DISTRIBUTION CORPORATION LIMITED BBL Ref No.: - Quantity : 4 Nos
Consultant : TATA CONSULTING ENGINEERS LIMITED BANGALORE Tag Nos. : 90GCN09 AE001/AE002 & 90GCN10 AE001/AE002
1000
Time in seconds
100 94
60
50
47
30 25
10
1.3
1
0.5
0.4
0
0 100 200 300 400 500 600 700
0.750K4P3HLAXXAAX/3H0804EBATSSX