Professional Documents
Culture Documents
NPT-1200 V7.0 Imm
NPT-1200 V7.0 Imm
Version 7.0
ECI's qualification lab is accredited by A2LA for competence in electrical testing according to
the International Standard ISO IEC 17025-2005 General Requirements for the Competence of
Testing and Calibration Laboratories.
Related documents
Neptune Product Line General Description
Neptune Product Line System Specifications
Neptune Product Line Reference Manual
EMS-NPT User Manual
LCT-NPT User Manual
LightSoft® Network Management System User Manual
IEC Publication 825 - Laser Safety Requirements
Contact information
Telephone Email
ECI Documentation Group +972-3-9268145 techdoc.feedback@ecitele.com
ECI Customer Support +972-3-9266000 on.support@ecitele.com
Revision history
Revision Section Description
1 N/A
2 Install the air filter in the New section added
NPT-1200
1 Prepare the installation site and check the physical location, Before you start
environmental compliance, and availability of power sources.
2 Prepare power, alarm, management, and transmission cables Preparation of cables and fibers
at the installation site.
3 Route the required power, alarm, management, and Routing and connection of
transmission cables to the intended NPT-1200 equipment electrical interface cables to the
location. NPT-1200
5 Mark the location of each NPT-1200 shelf, relevant Mark rack floor
accessories (Fiber Storage Tray [FST], Optical Distribution
Frame [ODF], Digital Distribution Frame [DDF], and MCP30
Interconnection Panel [ICP_MCP30]) on each rack, in
accordance with the site installation plan.
Notes:
Only for NPT-1200 installation, it is recommended that
you leave at least 4 U of space above the NPT-1200 shelf
to enable future installation of the EXT-2U shelf.
The NPT-1200 can only support balanced E1 interfaces
directly. For unbalanced E1s, the xDDF-21 patch panel
must be configured, which provides conversion between
balanced and unbalanced E1s for 21 x E1s.
When auxiliary interfaces like RS-232, orderwire, or V.11
are used in your application, the ICP_MCP30 must be
installed in order to distribute the concentrated Auxiliary
connector into dedicated connectors for each function.
6 When applicable, install the EMS-APT management station. EMS-APT Installation Guide
8 Install the NPT-1200 shelves in the appropriate rack. Install the NPT-1200 shelf in the
rack
9 For each NPT-1200 shelf where optical modules are used, Installing the FST
install an FST under the NPT-1200 shelf and route the optical
fibers to the FST.
Note: Even if you are not currently installing an FST, it is
recommended that you leave enough space beneath the
NPT-1200 shelf to enable future installation.
11 Install the SFP modules for CPTS100 modules. Install SFP/XFP/SFP+ modules
12 Depending on the modules or cards in your NPT-1200 shelf: Route and connect E1 cables for
Route the PDH electrical cables from the DDF to the E1 balanced E1 interfaces
interfaces on the front panel of PME1_21 modules, the Route and connect electrical
E3/DS-3 interfaces on the front panel of PM345_3 cables between the MCP1200 and
modules, and STM-1e interfaces on the STM-1 electrical the ICP_MCP30
SFPs.
Route the data cables to the Fast Ethernet interfaces on
the front panel of DMFE_4_L1 modules.
If the ICP_MCP30 is installed, route the special cables to
connect the ICP_MCP30 and the MCP1200, and route
cables for interfaces on the ICP_MCP30 panel. If the
ICP_MCP30 is not installed and external alarms
interfaces are used, route the special Alarms cable from
the MCP1200 Auxiliary connector to the RAP.
Note: The DDF can be installed on the same rack as the
NPT-1200 shelf, or on a different rack.
WARNING: NPT-1200 shelves are intended for installation in restricted-access areas only.
Choose the physical location of the NPT-1200 shelves, taking the following aspects into consideration:
1. Equipment dimensions (see the following table).
2. Required floor loading capability: 100 kg for a typical eight-shelf installation.
3. Routing requirements for grounding, power, alarm monitoring, management cables, and optical
fibers. To ensure convenient access to cables and fibers, it is recommended, whenever possible, to
use overhead cable ladders to bring the cables/fibers to the top of each rack.
4. When a network management station, for example, the EMS-APT, is installed on the site, consider the
method of connection to the local network management station and the maximum allowed distance.
IMPORTANT: In any outdoor installation environment, where the Ethernet cables are
extended to other vendors’ equipment, you must:
Use only shielded cabling/wiring
Ensure that the equipment on the opposite end is adequately grounded
Equipment type Height (mm) Width (mm) Depth (mm) Max. weight (kg)
NPT-1200 88.9 442.4 243 11
EXT-2U 88.9 443.4 243 8
RAP-BG 88 440 150 4
RAP-4B 88 447 155 2.4
FST 44.5 440 240 5
ODF 44.5 440 240 8
xDDF-21 44.5 440 150 1.5
ICP_MCP30 44 440 140 1.5
NOTE: If the planned power consumption of the equipment installed in the shelf is 80% or
more of the maximum listed value, it is recommended to consult ECI Customer Support for
information about optimizing your network configuration.
NOTE: The NPT-1200 is suitable for installation in Central Office Facility and other indoor
applications.
In addition to the NPT-1200 shelf, the equipment installed in the rack can include:
One RAP installed at the top of the rack. The RAP is used to connect external power and alarm
monitoring lines (RAP-4B only) to the NPT-1200 shelves installed in the rack. The RAP fully supports up
to four shelves with dual power feeding. In addition to the space needed for RAP installation, you must
leave at least 50 mm of free space under the RAP for cable routing.
Fiber Storage Tray. A separate FST can be installed for each NPT-1200 with optical modules. Each FST
contains two storage reels, enabling the fiber to be stored on the right or left side of the tray. Leave at
least 50 mm of free space between the NPT-1200 shelf and its FST, and another 50 mm free between
the FST and the next NPT-1200 shelf.
xDDF-21. When unbalanced E1 interfaces are needed, the xDDF-21 must be installed with the
NPT-1200. Each xDDF-21 can support 21 channels of E1. The xDDF-21 can be installed anywhere on
the same rack as the NPT-1200 shelf or on another rack.
ICP_MCP30. When an RS-232 or V.11 interface from the MCP1200 is used, the ICP_MCP30 must be
installed to distribute the concentrated Auxiliary connector into dedicated connectors for each
function. The ICP_MCP30 can be installed anywhere on the same rack as the NPT-1200 shelf.
The following main types of cables are required for installing the NPT-1200:
Grounding cables
DC power cables (RAP input power cables and Shelf power cables)
Alarm cables
Management cables
Timing (clock) cables
Optical fibers
Electric traffic cables
Some of these cables are supplied as part of the NPT-1200 equipment, while others must be prepared on
site or ordered separately from ECI.
In the following sections, you will find information about the cables, and how to prepare them on site,
where relevant. For details about the equipment connector types and cable wiring, see Connection data.
WARNING: When preparing cables, in particular power and grounding cables, use only
UL-listed components of the specified types. Components must also comply with any
applicable national and local safety codes and regulations.
Only qualified trained personnel may be involved in the preparation of the various cable
types. Personnel must use only approved procedures, in accordance with the applicable
workmanship practice.
If the site timing reference distribution subsystem has unbalanced (75 ) G.703 interfaces, configure an
adapter with coaxial cables that provides balanced-to-unbalanced conversion (supplied by ECI).
Module or card Interface type Cable type Mating connector Connector at other Qty./module
end
DHGE_16 10/100/1000BaseT Cat.6a RJ-45 RJ-45
8
DHGE_24 10/100/1000BaseT Cat.6a RJ-45 RJ-45
12
NOTE:
For PME1_21 cable is used to connect the PME1_21 E1 interface connector to the
xDDF-21
Cables are required when electrical SFPs are used in the SMQ1, SMQ1&4, DMGE_4_L1,
DMGE_4_L2, DMGE_8_L2, DMXG_48_L2 and DMXE_22_L2 modules.
CAUTION: Intra-building Ethernet ports of the equipment or subassembly must use shielded
intra-building cabling/wiring that is grounded on both ends.
Table 2-5: Optical fibers and mating connector data for NPT-1200
I/O module Interface type Fiber type Mating connector Qty./module
SMQ1 STM-1 optical One pair of fiber patch cords per interface LC male 8 fibers
SMQ1&4 STM-1&4 optical One pair of fiber patch cords per interface LC male 8 fibers
SMS16 STM-16 optical One pair of fiber patch cords LC male 2 fibers
CPTS100 STM-64 optical One pair of fiber patch cords per interface LC male 2 fibers
STM-16 One pair of fiber patch cords per interface LC male 4 fibers
10 GbE One pair of fiber patch cords per interface LC male 4 fibers
MCIPS320 STM-16 optical One pair of fiber patch cords per interface LC male
STM-64 optical One pair of fiber patch cords per interface LC male
10 GbE One pair of fiber patch cords per interface LC male
MCIPS560 STM-16 optical One pair of fiber patch cords per interface LC male
STM-64 optical One pair of fiber patch cords per interface LC male
10 GbE One pair of fiber patch cords per interface LC male 8 fibers
DMFX_4_L1 100BaseFX One pair of fiber patch cords per interface LC male 8 fibers
DMGE_4_L1 1000BaseX One pair of fiber patch cords per interface LC male 8 fibers
DMFX_4_L2 100BaseFX One pair of fiber patch cords per interface LC male 8 fibers
DMGE_4_L2 1000BaseX One pair of fiber patch cords per interface LC male 8 fibers
DMGE_8_L2 1000BaseX One pair of fiber patch cords per interface LC male 16 fibers
DMXE_48_L2 1000BaseX One pair of fiber patch cords per interface LC male 8 fibers
DMXE_22_L2 1000BaseX One pair of fiber patch cords per interface LC male 2 fibers
MSC_2_8 STM-1 optical One pair of fiber patch cords per interface LC male 4 fibers
MS1_4 STM-1 optical One pair of fiber patch cords per interface LC male 8 fibers
DHGE_4E 10/100/1000 BaseT One pair of fiber patch cords per interface LC male 8 fibers
DHGE_8 1000BaseX One pair of fiber patch cords per interface LC male 8 fibers
DHGE_10 1000BaseX One pair of fiber patch cords per interface LC male 10 fibers
DHGE_16 1000BaseX/100BaseFX One pair of fiber patch cords per interface LC male 16 fibers
DHGE_24 1000BaseX/100BaseFX One pair of fiber patch cords per interface LC male 24 fibers
DHCE_1Q 100 GbE One pair of fiber patch cords per interface LC male 2 fibers
DHXE_2 10 GbE One pair of fiber patch cords per interface LC male 4 fibers
DHXE_4 10 GbE One pair of fiber patch cords per interface LC male 8 fibers
DHXE_4O 10 GbE One pair of fiber patch cords per interface LC male 8 fibers
NFVG_4 1000BaseX One pair of fiber patch cords per interface LC male 8 fibers
NOTE: Fibers are required when DMGE_4_L1 interface is working in 1000BaseFX mode. The
fiber type must be multimode.
Table 2-6: Optical fibers and mating connector data for EXT-2U
I/O module Interface type Fiber type Mating connector Qty./module
S1_4 STM-1 optical One pair of fiber patch cords per interface LC male 8 fibers
MPS_2G-8F 1000BaseX Two pairs of fiber patch cords per interface LC male 4 fibers
MPoE_12G 1000BaseX Four pairs of fiber patch cords per interface LC male 16 fibers
OM_BA 10 GbE Two pairs of fiber patch cords per interface LC male 2 fibers
OM_PA 10 GbE Two pairs of fiber patch cords per interface LC male 2 fibers
OM_ILA Two pairs of fiber patch cords per interface LC male 2 fibers
OM_LVM Two pairs of fiber patch cords per interface LC male 4 fibers
OM_DCM_80 Two pairs of fiber patch cords per interface LC male 2 fibers
OM_DCM_100 Two pairs of fiber patch cords per interface LC male 2 fibers
NPT-1200 platforms contain power sources of varying voltages. Note the following guidelines when
installing the platforms:
NOTE: If necessary, the gauge of the grounding lead can also be reduced to the gauge of the
RAP power leads.
The rack mounting rails must be free of paint and provide electrical continuity to the main grounding bolt.
The resistance between any rail and the rack main grounding bolt must be less than 0.1 .
Pay particular attention to the area in which the RAP is attached. Remove paint from the rack in this area to
ensure efficient electrical contact.
CAUTION: Connect the RAP grounding bolt to the rack grounding bolt with a grounding cable
complying with UL/ETSI recommendations. The cable must include bolt terminals on both
ends and be securely fastened with a nut and a star washer.
WARNINGS:
Hazardous voltages are present in the equipment when a source of electrical power is
applied.
Risk of electrical shock from the main power supply.
When working on the equipment with power applied, supervision of an additional
person is required. Provision of an emergency switch or disconnection strap is not
sufficient protection.
The supervisor must be capable of providing first aid in the event of electrical shock.
There is increased risk of accidents and electrical hazards when working on compact
equipment due the close proximity of components. Pay extra attention to safety rules.
All AC connections must be made according to the National Electrical Codes and must
conform to all local codes.
To avoid electrical hazards don't remove covers of the system or any component.
Protective shields and other safety devices provided with the equipment must be in
place when the equipment is operated.
Hazardous voltages may be present at the main power connector and in the equipment
for up to 10 seconds after disconnecting the power supply.
The operator is responsible to secure the proper precautions for maintenance or service
purposes.
During installation and maintenance, protective covers may be temporarily removed.
Use insulated tools and protective clothing. Handle fuses only with tools provided for
this purpose.
To avoid electrical shock, the system requires a single ground point permanently
connected to the earth ground.
WARNING: There must be a connection between the grounded conductor of the DC power
supply circuit and the equipment grounding conductor. See installation instructions for more
details.
When this connection is made, all the following conditions must be met:
The equipment is connected directly to the supply system grounding electrode conductor
or to a bonding jumper from a grounding terminal bar/bus to which the DC supply system
grounding electrode is connected.
The equipment is located in the same immediate area (such as adjacent cabinets) as any
other equipment that has a connection between the grounded conductor of the same DC
supply circuit and the grounding conductor, as well as the point of grounding of the DC
system. The DC system must not be grounded elsewhere.
The DC supply source is located within the same premises as this equipment.
There is no switching or disconnecting devices in the grounded circuit conductor between
the DC source and the point of connection of the grounding electrode conductor.
NOTES:
The Neptune equipment is suitable for installation as part of a Common Bonding Network
or an Isolated Bonding Network, or both.
The DC battery return input terminals can be connected to an Isolated dc return (DC-I),
Common dc return (DC-C), or both.
WARNING:
Ethernet ports must be cabled with shielded cables and the shield grounded at both ends.
Intra-building ports of the equipment or subassembly are suitable for connection to
intra-building or unexposed wiring or cabling only. Intra-building ports of the equipment
or subassembly MUST NOT be connected metallically to interfaces that connect to the
OSP or its wiring. These interfaces are designed for use as intra-building interfaces only
(Type 2 or Type 4 ports as described in GR-1089-CORE, Issue 4) and require isolation from
the exposed OSP cabling. The addition of Primary Protectors is not sufficient protection in
order to connect these interfaces metallically to OSP wiring.
LASER WARNING: When the NPT-1200 operates in conjunction with OM_BA or OM_ILA
optical amplifiers (installed in the EXT-2U) the NPT-1200's Laser classifications changes to
Hazard Class 1M Laser Product.
WARNING: To reduce the risk of exposure to hazardous radiation, note the following:
When performing maintenance and other activities on equipment using lasers, it is
recommended that you use protection goggles for the wavelength range of 1300 nm to
1600 nm.
Only authorized personnel must carry out hot insertion or swapping of an optical
module or optical interface module.
To prevent irremediable damage to your eyes, avoid looking into the fiber when
hot-removing and/or inserting a fiber termination.
Place plastic covers on module fiber ports and fiber terminations that are not currently
in use.
Do not operate controls, make adjustments, or perform procedures associated with the
laser device other than those specified herein.
It is strictly forbidden to interfere with any protective devices and interlocks that are used to
prevent direct exposure to the laser beam.
WARNING:
The connection from EDFA (OA_XXX) must be made using a single fiber (not using an MTP
connector) with EDFA (OA_XXX)
The total output power from the MTP connector (optical power) must not exceed 20 dbm.
In a configuration including several MTP connectors, the minimum distance between the
connectors must be based on IEC60825 requirements.
Note:
BD-3 refers to a single-fiber bidirectional transceivers with a transmit wavelength of 1310
nm,
BD-5 refers to a single-fiber bidirectional transceivers with a transmit wavelength of 1550
nm.
NOTE: For more Laser information refer to the Neptune Product Line System Specifications.
The information provided in this section is in line with CENELEC Electronic Components Committee (CECC)
specification CECC 00 015, which deals with protection of devices sensitive to ESD.
Most types of electronic equipment, assemblies, and components can be damaged by electrostatic
discharges. An ESD between two objects occurs when an object carrying static electrical charges touches or
is brought near another object.
Static electrical charges appear as a result of friction between surfaces of insulating materials or separation
of two such surfaces, and may also be induced by electrical fields. Routine activities such as walking across
an insulating floor, friction between garment parts, friction between objects, and so on, can easily build up
charges to levels that may cause damage, especially when humidity is low.
In many cases, the build-up of charge can be avoided by using special materials, for example, garments and
packaging of antistatic materials or materials that have high resistance, but yet are not insulators.
The best way to avoid damage by ESD is a combination of means and procedures that achieves the
following goals:
Avoids build-up of electrostatic charges
Creates a protected work environment that helps prevent ESD
Provides means for controlled discharge of any accumulated electrostatic charges when entering the
protected work environment
NOTE: An area in which ESDS can be handled with minimum risk of damage as a result of ESD
or fields, and in which the operator is not exposed to additional risks, is called an ESD
Protected Area (EPA).
CAUTION: The temporary EPA must be constructed in a way that ensures electrical bonding of
all the materials used, and prevents the occurrence of any sudden changes in potential within
the EPA that could cause unacceptable voltages or discharges to be applied to ESDS.
The operator and any work surface and flooring must be bonded to ground equipotentially. For this
purpose, the work surface and wrist straps must be bonded either to a designated ground bonding point or
to the equipment being serviced.
Whenever available, the mains’ ground serves as the ESD grounding facility.
WARNING: While the operator is within the temporary EPA, the minimum value of resistance
used for bonding to ground must limit the current to ground, produced by voltages accessible
to the operator, to limits specified as safe by the applicable regulations (see, for example,
CECC 00 015). The same approach is applicable to the surface resistance and resistance to
ground of materials used for temporary work surfaces and flooring.
To enable ESD bonding to ground of equipment racks and any other nonmoveable equipment containing
ESD, an ESD ground-bonding facility must be located near such equipment, or the equipment must be fitted
with a designated ground-bonding point presenting a resistance to ground not greater than 1 M.
NOTE: If you are not installing an FST for a particular NPT-1200 shelf, it is recommended that
you leave empty space in the rack in case optical modules are added in the future. If you are
not installing an EXT-2U for a particular NPT-1200 shelf, it is highly recommended that you
leave enough empty space (about 5U) above the NPT-1200 shelf in case one is added in the
future.
CAUTION:
If additional equipment is used in the rack, a heat buffer or a buffer plate must be
installed between such equipment and the NPT-1200 shelf to minimize the transfer of
heat from shelf to shelf. This heat buffer must be purchased from ECI.
During the installation of equipment in the rack, make sure all the optical connectors are
closed by protective caps. Do not remove the cap until an optical fiber is connected to
the corresponding connector.
NOTE: The FST must be installed below the NPT-1200. If the 9600E is not installed, space
above the NPT-1200 must be reserved for it.
Depending on the specific equipment being installed as listed in the site installation plan, the installation of
a NPT-1200 system comprises the following stages, listed in the required order of execution.
Step Procedure
5 Install the NPT-1200 modules in the NPT-1200 shelf. NPT-1200 modules include:
2 x INF_1800, 1 x FCU_1800, 1 x MCP1800, 2 x CIPS1T cards, and several Tslot modules.
Before unpacking, make a preliminary inspection of the shipping boxes. Immediately report evidence of
damage to the carrier, the project manager, and your local representative of the vendor.
NOTE: Do not remove plastic covers from optical connectors until optical cables are
connected to them.
3. Search the shipping boxes for any additional small items that may be present.
4. Open each of the module and card packages for inspection, but do not remove the modules/cards
from their individual protective packages until they can be inserted in the platform.
5. Check the contents of the shipping boxes against the packing list attached to each box. If damaged
parts are detected or if any parts are missing, notify the project manager and your vendor's local
representative immediately.
NOTE: NPT-1200 shelves can also be installed in standard street cabinets. Consult the vendor
for more details.
By default, the NPT-1200 is shipped with 19” mounting brackets. If you are installing in an ETSI
rack, ETSI brackets must be ordered separately and replaced in the field.
You can install up to six NPT-1200 shelves in a rack. A typical installation of four NPT-1200 shelves in an ETSI
2200 rack is displayed in the following figure.
Figure 3-2: Typical installation of four NPT-1200 shelves in a ETSI rack
NOTE: If necessary, contact your local customer support team or your vendor's sales
representative for help in meeting your specific installation requirements.
CAUTION: Caution: If additional equipment other than NPT-1200 shelves is used in the rack, a
heat buffer must be installed between such equipment and the NPT-1200 shelf to minimize
the transfer of heat from shelf to shelf. Consult your ECI representative regarding the exact
heat buffer required.
NOTE: According to accepted industry standards for connecting DC power, the positive lead
(+48 V) must be connected with a red cable and the negative lead (-48 V) with a black cable.
However, according to the BS7671 (GB) and HD 308 S2:2001 (EU) standards, the positive lead
must be connected with a blue cable and the negative lead with a gray cable. In the following
sections that describe DC power cable connections, use cables of appropriate colors to comply
with the standards in your area of residence.
The DC input power cables connect the two DC power sources and the RAP-BG source A and source B
inputs. Two cables are required, one for each source. Each cable consists of two stranded copper leads with
a cross section of 50 mm2 (.078 in.2), one red and the other black. Each lead is terminated with a
compression lug from the installation parts kit supplied with the equipment.
NOTE: When the RAP-BG provides power to a single Neptune platform, lower gauge cables
can be used. See DC power cables for DC power cable requirements.
CAUTION: If appropriate leads have already been prepared at the prescribed rack location,
make sure that the leads are not connected to any live voltage source before attaching the
lugs.
2. If necessary, prepare a grounding lead in accordance with the requirements described in Grounding
requirements.
3. Connect the lug at one end of the grounding lead to the RAP-BG grounding stud, using a spring
washer and nut.
4. Connect the lug at the other end of the grounding lead to the rack grounding stud.
2. Open the two captive screws fastening the RAP-BG front cover and remove the cover.
3. Identify the various terminals located on the power source terminal board by referring to the
following figure (showing the terminals at source A side; a similar board is used at source B side).
CAUTION: Before connecting the power leads, make sure to identify the terminal polarity on
the RAP-BG power terminal board.
4. Bring the two leads of DC source A input power cable to the appropriate RAP-BG opening.
5. Attach the lug of the red lead to the positive stud terminal marked (+) on the power terminal board
(see the previous figure).
6. Secure the lug using a flat washer, spring washer, and nut. Tighten the nut with a torque of 1450 N cm
to 1600 N cm.
7. Attach the lug of the black lead to the negative stud terminal marked (-) on the power terminal board
(see the previous figure).
8. Repeat Step 6 for the black lead lug.
9. If an additional power source (source B) is used, repeat Steps 3 to 8 for source B.
10. Securely attach the DC input power cables to the rack inner wall using cable ties.
8. Attach the grounding (shield) lead lug of the platform power cable to the ground stud terminal
located on the RAP-BG side panel.
9. Repeat Step 4 for the grounding lead lug.
10. If additional NPT-1200 platforms are installed in the rack, repeat Steps 2 to 9 for each platform power
cable.
11. If an additional power source is used, repeat Steps 2 to 10 to connect the platforms to source B.
12. Route each platform power cable along the rack side rails down to the corresponding platform
position, and then securely attach the power cable to the rack inner wall using cable ties. Attach a tag
to each power connector in accordance with its function.
2. Identify the circuit breaker corresponding to the power circuit A of Shelf 1 (the circuit breaker is
included in the installation parts kit supplied with the equipment; its rating is in accordance with the
ordered platform configuration).
3. Insert the circuit breaker into the circuit breaker sockets located on the RAP-BG source A power
terminal board, as shown in the previous figure.
4. If more platforms are powered from source A, repeat Steps 2 and 3 to insert the circuit breakers into
the corresponding platform positions of the power terminal board.
5. If an additional power source is used, repeat Steps 2 to 4 for source B circuit breakers.
9. Make sure the voltage is within the allowed range (-40 VDC to -72 VDC), and that it has the correct
polarity.
10. Return all the RAP-BG circuit breakers to OFF.
11. Disconnect the RAP-BG input power sources.
12. Reinstall the RAP-BG front cover and fasten it using the two captive screws.
NOTE: According to accepted industry standards for connecting DC power, the positive lead
(+48 V) must be connected with a red cable, and the negative lead (-48 V) with a black cable.
However, according to the BS7671 (GB) and HD 308 S2:2001 (EU) standards, the positive lead
must be connected with a blue cable and the negative lead with a gray cable. In the following
sections use cables of the colors to comply with the standards in your area of residence.
The DC input power cables connect the two DC power sources and the RAP-4B source A and source B
inputs. Two cables are required, one for each source. Each cable consists of two stranded copper leads with
a cross section of 50 mm2 (0.078 in.2), one red and the other black. Each lead is terminated with a
compression lug from the installation parts kit supplied with the equipment.
NOTE: When the RAP-4B provides power to a single platform, lower gauge cables may be
used. See DC power cables for DC power cable requirements.
CAUTION: If appropriate leads have already been prepared at the prescribed rack location,
make sure that the leads are not connected to any live voltage source before attaching the
lugs.
NOTE: The RAP-4B is supplied, by default, with a grounding cable connected to the rear of the
unit. Use this cable to connect ground to the RAP-4B.
1. The RAP-4B grounding studs are located on its rear cover as shown in the following figure.
4. Connect the two-hole lug at the other end of the grounding lead to the rack's grounding bar.
2. Open the two captive screws fastening the RAP-4B front cover and remove it.
3. Identify the various terminals located on the power source terminal board, as shown in the following
figure (showing source A side; a similar board is used at source B side).
CAUTION: Before connecting the power leads, make sure to identify the terminal polarity on
the RAP-4B power terminal board.
4. Bring the two leads of one DC source A input power cable to the appropriate RAP-4B opening.
5. Attach the lug of the red lead to the positive stud terminal marked (+) on the power terminal board
(see the previous figure).
6. Secure the lug using a flat washer, spring washer, and nut. Tighten the nut with a torque of 940 N cm
to 1060 N cm.
7. Attach the lug of the black lead to the negative stud terminal marked (-) on the power terminal board
(see the previous figure).
8. Repeat Step 6 for the black lead lug.
8. Attach the grounding (shield) lead lug of the platform power cable to the ground stud terminal
located on the RAP-4B side panel.
9. Repeat Step 4 for the grounding lead lug.
10. If more NPT-1200 platforms are installed in the rack, repeat Steps 2 to 9 for each platform power
cable.
11. If an additional power source is used, repeat Steps 2 to 10 to connect the platforms to source B.
12. Route each platform power cable along the rack side rails down to its corresponding platform, and
then securely attach the power cable to the rack inner wall using cable ties. Attach a tag to each
power connector in accordance with its function.
2. Identify the circuit breaker corresponding to power circuit A of Platform 1 (the circuit breaker is
included in the installation parts kit supplied with the equipment platform; its rating is in accordance
with the ordered platform configuration).
3. Insert the circuit breaker into the circuit breaker sockets located on the RAP-4B source A power
terminal board, as shown in the previous figure.
4. If more platforms are powered from source A, repeat Steps 2 and 3 to insert the circuit breakers into
the corresponding platform positions of the power terminal board.
5. If an additional power source is used, repeat Steps 2 to 4 above for source B circuit breakers.
5. Make sure the voltage is within the allowed range (-40 VDC to -72 VDC), and that it has the correct
polarity.
6. Return all the RAP-4B circuit breakers to OFF.
7. Disconnect the RAP-4B input power sources.
8. Reinstall the RAP-4B front cover and fasten it with the two captive screws.
NOTE: The FST has two opening positions. The tray latches with a click at the halfway position.
Pull it again to open it fully so that you can thread the fibers.
5. Thread the fibers into the FST, as shown in the following figure.
NOTE: All optical fibers should be arranged in groups inside the FST and fastened with Velcro
strips.
CAUTION: Make sure that all the optical connectors are closed at all times with the
appropriate protective caps or with the mating cable connector. Do not remove the protective
cap until an optical fiber is connected to the corresponding connector, and immediately install
a protective cap after a cable is disconnected.
The minimum bending radius of optical fibers is 35 mm. Sharp bending of fibers may degrade
the optical transmission characteristics.
2. Hold the end of the swing-out tray and pull it out to gain access to the ODF components.
3. Open the two cover thumb nuts and remove the protective cover from the ODF splice support.
4. Insert the external fibers cable through the protective tube.
5. Route the fiber ends through the cable guides to the splice support area.
6. Identify the adapter panel pigtail to be spliced to each user fiber.
7. Insert splicing sleeves over the pigtail, splice the user fiber to the pigtail, and slide the splicing sleeve
over the splice.
8. Place the splicing sleeve in one of the slots in the splice support.
NOTE: When more than 12 fibers are connected to the ODF, start by first filling the slots of
the lower splice support. After those slots are occupied, reinstall the top splice support and
continue filling the support slots.
9. After splicing all the fibers, reinstall the protective cover removed in Step 3.
10. Push the swing-out tray back into the unit.
11. Close the ODF front cover by pushing it up until it clicks to the unit.
12. See the “To attach the rack mounting brackets to the ODF” procedure, above, and secure the user
fibers with cable ties to the fiber fastening bracket at the rear of the ODF.
To install an ICP_MCP30:
1. Identify the prescribed position of the ICP_MCP30 in the rack in accordance with the rack installation
plan.
2. Place the ICP_MCP30 in the prescribed position using the two stabilizing pins to hold it temporarily in
place, and then fasten the platform to the rack side rails with four M6 screws, washers, and nuts.
NOTES:
Contact customer support or your local sales representative to order the following:
Air filter kit X35702.
For ETSI installation, order kit X44968.
For NEBS installation, order kit X44740.
The kit includes a frame, filter cover and mounting assembly for attaching the platform to the rack. The
following figure shows a general view of the air filter:
Air filter for NPT-1200 general view
The following two procedures describe the installation of the air filter with NEBS and ETSI mounting
brackets.
2. Attach the NEBS mounting bracket on the left side of the platform according to the drawing above.
3. Secure the bracket in place by tightening the four M4X8 screws with a screwdriver.
4. Attach the filter frame to the right side of the platform according to the drawing above.
5. Secure the frame in place by tightening the four M4X5 screws and two M2.5X6 screws with a
screwdriver.
6. Attach the NEBS mounting bracket on filter frame:
7. Secure the bracket in place by tightening the four M4X5 screws with a screwdriver.
8. Orient the air filter with bracket on the filter facing out and slide the filter in the frame along the guide
rails.
9. Attach the filter cover to the bracket and tighten the two captive screws on the cover:
2. Attach the ESD mounting bracket on the left side of the platform according to the drawing above.
3. Secure the bracket in place by tightening the three M4X8 screws with a screwdriver.
4. Attach the filter frame to the right side of the platform according to the drawing above.
5. Secure the frame in place by tightening the four M4X5 screws and two M2.5X6 screws with a
screwdriver.
6. Attach the ETSI mounting bracket on filter frame:
7. Secure the bracket in place by tightening the four M4X5 screws with a screwdriver.
8. Orient the air filter with bracket on the filter facing out and slide the filter in the frame along the guide
rails.
9. Attach the filter cover to the bracket and tighten the two captive screws on the cover:
WARNING: Before starting, make sure that the DC power is not connected to the rack and
that the circuit breakers in the RAP, if used, are set to OFF.
Review the grounding requirements specified in Before you start. Obtain the required materials and make
sure to perform the grounding connections in accordance with these requirements.
Review the grounding requirements specified in Preparation of cables and fibers. Obtain the required
materials and make sure to perform the grounding connections in accordance with these requirements.
NOTE: For more information about the FCM and FCU_1200B modules refer to Neptune
Reference Manual
1. Check that the module has not been physically damaged during shipment, and that the antistatic
protection bag of the original packaging is sealed.
2. Remove the module from its antistatic protection packaging and perform a visual inspection to detect
damage during shipping. Report any problems.
3. Hold the MCP1200 module extractor and insert the rear end of the module into the card guides of the
MS slot.
4. Push the module in until the panel at the front of the module is flush with the front of the NPT-1200
shelf. If resistance is felt before the connectors are flush, pull the module out and repeat the
procedure.
5. Secure the module in place by tightening the two screws with a screwdriver.
NOTE:
The DMXE_22_L2 is not supported in slot TS5 of the NPT-1200.
Up to 4 DMXE_22_L2 cards only can be supported.
Always install the DMXE_22_L2 on the right-hand-side slots (as close as possible to the
fan units).
For a list of available Tslot modules and their technical descriptions, refer to the Neptune Product Line
Reference Manual.
Figure 3-12: Installing Tslot module in the NPT-1200
3. Hold the module extractor and insert its rear end into the module guides.
4. Push the module in until the front of the module is flush with the front of the NPT-1200 shelf. If
resistance is felt, pull the module out and repeat the procedure.
5. Secure the module in place by tightening its two captive screws.
NOTE: Only SFP/XFP/SFP+ modules supplied by ECI can be used in the NPT-1200.
WARNING: Before starting to install the EXT-2U, make sure the DC power cable is not
connected to the EXT-2U, and that the circuit breakers in the RAP, if used, are set to OFF.
CAUTION: Before adding the EXT-2U to the NPT-1200, ensure that the rail stiffeners have
been installed. (It is very difficult to install the EXT-2U without them.) If not, it is highly
recommended that you first remove the NPT-1200 from the rack and install the rail stiffeners
before proceeding with the EXT-2U installation. See Install the rail stiffeners.
WARNING: Take great care when installing the EXT-2U in order to avoid damage to the
NPT-1200 or EXT-2U. Be sure to follow the drawing provided in the EXT-2U installation kit.
5. Verify that the caps of the rivets are flat on the bottom of the EXT-2U.
6. Fasten the four fastener screws (SST PH M6 x 16) to the mounting flange of the EXT-2U.
NOTE: The following figure shows the disassembling of the BG-30E from the BG-30B, the
removal of the EXT-2U from the NPT-1200 is similar.
2.
3. Raise the rivet cap by the screwdriver.
The figures show two possible arrangements for the EXT-2U slots layout. The upper figure shows the
regular layout of the EXT-2U. The lower figure is very similar to the first, with an extension arrangement for
the uppermost slot (ES 3#).
The EXT-2U platform consists of the following slots:
Two slots (PS A and PS B) for installing two DC power supply modules only (AC power supply is not
supported)
One slot (FS) for installing a fan module
Three slots (ES 1#, ES 2#, ES 3#) for accommodating expansion traffic card (Eslots)
Slot ES 3# (can be extended) for housing a long card (TP63_1 and TPEH1_1)
The following table lists the modules supported in V7.0 that can be configured in each slot in the EXT-2U.
This procedure is also applicable for replacing an operating FCU_E2U. To perform the replacement in the
shortest time, prepare the replacement FCU_E2U in advance by taking it out of its package and placing it
near the operating unit.
CAUTION: To avoid traffic hit in an operating system, don't turn it off while replacing an
FCU_E2U. The system can operate without a fan unit for up to 4 minutes. Perform the
replacement in this time.
4. Push the module in until the panel at the front of the module is flush with the front of the EXT-2U
platform. If resistance is felt before the connectors are flush, pull the module out and repeat the
procedure.
5. Secure the module in place by tightening the two screws with a screwdriver.
CAUTION: When installing a MPoE_12G card the total PoE power budget is up to 90 W.
NOTE: Extension cards support live insertion. They can be installed at any time without
affecting the existing traffic running on the NPT-1200 or EXT-2U.
Before installing a long card, remove the blank panel, covering the additional expansion space to the left of
slot ES 3# and the card guide at the left side of the slot.
2. Open the FH M1.6 screw fastening the card guide in the left side of ES 3#, and remove it.
CAUTION: Prevent the card guide touching other cards, while the system is operating.
NOTE: Long cards support live insertion. They can be installed at any time without affecting
the existing traffic running on the EXT-2U.
NOTE: For further details about the RAP installation procedure, see Install the RAP-BG or
Install the RAP-4B.
2. Connect the end of the DC power cable from one source, terminating with a 3-pin D-type female
connector in accordance with the rack installation plan and the cable tags, to the DC power connector
on one INF_1200.
3. Connect the end of the DC power cable from the second source, terminating with a 3-pin D-type
female connector in accordance with the rack installation plan and the cable tags, to the DC power
connector on the second INF_1200.
NOTE: When an expanded platform (EXT-2U above the NPT-1200) is installed, use a dual feed
high power cable (Y-cable) to connect the DC power. This cable enables to connect power to
both units from one output on the RAP, saving one circuit breaker and the need to use two
separate power cables.
4. Route the alarm cable leading from the RAP along the side of the rack to the appropriate NPT-1200
shelf (if an ICP_MCP30 is not installed) or to the appropriate ICP_MCP30 (if an ICP_MCP30 is
installed).
5. Connect the free ends of the alarm cable, in accordance with the rack installation plan and the cable
tags, to the Auxiliary connector on the MCP1200 (if an ICP_MCP30 is not installed) or Alarms
connector on the front panel of the ICP_MCP30 (if installed).
6. Secure the cable connector to the MCP1200 or ICP_MCP30 connector with the cable connector
screws. Tighten the screws manually. If you cannot reach the screws with your hands, use an
adjustable-torque flatblade screwdriver (maximum blade size 0.6). Set the tightening torque to 40 N
cm to 44 N cm.
CAUTION: Make sure that all the optical connectors are closed at all times with the
appropriate protective caps or with the mating cable connector. Do not remove the protective
cap until an optical fiber is connected to the corresponding connector, and immediately install
a protective cap after a cable is disconnected.
The minimum bending radius of optical fibers is 35 mm. Sharp bending of fibers may degrade
the optical transmission characteristics.
NOTE: The FST has two opening positions. The tray latches with a click at the halfway position.
If you cannot release the fiber in the halfway position, pull the tray again to open it fully.
3. Thread the end of the fiber through the rack slots to the optical transceiver LC connector on the
designated module. Leave some slack to prevent stress.
4. Thoroughly clean the connectors of the optical fibers using an approved cleaning kit.
5. Remove the cover from the optical transceiver. Connect the fiber connector to the LC connector on
the optical transceiver.
6. Repeat Steps 2 through 5 for all optical modules in the NPT-1200 shelf.
7. When you have completed the connection of all optical modules, gently push the FST back into the
rack until it clicks into place.
CAUTION: Do not exert excessive tightening torque to secure the cable connector as this may
damage the PME1_21.
The three 30 AWG cable pairs connect on one side to the double 136-pin VHDCI connector and on the other
side to the conversion box. The conversion box connects the three 30 AWG cable pairs and three pairs of 26
AWG cables, making the wire-size conversion. The 26AWG cables are connected at the other end to the
customer's DDF. Each cable in a pair is bonded to the other, shaping a figure-eight pattern.
Each pair of the 26 AWG cables carries 21 E1s, totaling 63 E1s. To facilitate identification of the E1 groups,
each cable pair is marked with color strips along its jacket according to the following key:
First pair, E1s Nos. 1 to 21 - red strips
Second pair, E1s Nos. 22 to 42 - blue strips
Third pair, E1s Nos. 43 to 63 - yellow strips
4. Route the 26AWG cables coming from the conversion box to the rack side rails and tighten them to
the rails with cable ties.
5. Use a cabling diagram of the site to associate the PME1_63 with the appropriate DDF connections.
CAUTION: Do not exert excessive tightening torque to secure the cable connector, as this may
damage the PME1_21.
CAUTION: Do not exert excessive tightening torque to secure the cable connector, as this may
damage the MCP1200 module.
6. Pull the other end of the cable to the level of the ICP_MCP30.
7. Bend the cable and thread it through the side cable guides of the rack and through the appropriate
opening near the ICP_MCP30 until the cable connector is positioned against the appropriate place.
Use cable ties as required to fasten the cable to the rack side rails.
8. Connect the cable connector to the SCSI-36 connector on the ICP_MCP30 front panel.
9. Secure the cable connector to the connector marked as J1 on the ICP_MCP30 front panel with the
cable connector screws. Tighten the screws manually. If you cannot reach the screws with your hands,
use an adjustable-torque flatblade screwdriver (maximum blade size 0.6). Set the tightening torque to
40 N cm to 44 N cm.
CAUTION: Do not exert excessive tightening torque to secure the cable connector, as this may
damage the ICP_MCP30.
Note: Personnel involved in the execution and supervision of commissioning tests must be
familiar with the applicable safety precautions and requirements.
Suitable equipment is available from a wide range of manufacturers and therefore no specific models are
listed. You can use any equipment that meets applicable international standards and has satisfactory
measurement accuracy over the range of operating parameters and environmental conditions that apply to
the specific network. If necessary, contact Field Engineering Department of the vendor for specific
recommendations.
NOTE: The average startup time varies depending on the configuration of the platform. The
NPT-1200 platform, equipped with CPTS100, CPTS320 or MCIPS560 dual matrix card, 3 DH
cards, 1 CES card and configured with 10 services, takes approximately 11 to 18 minutes to
start up.
The following table provides a typical list for recording the results of a visual inspection and mechanical
check.
2 Check the NPT-1200 installation; make sure that the NPT-1200 is properly
installed.
3 Check the ODF and FST installation and fiber connection (if applicable).
4 Check the DDF installation and relevant cable connections (if applicable).
6 Check the DC power cable connections (main fuse to RAP, RAP fuse to
NPT-1200 shelf).
9 Check the connection of relevant cables or fibers for all cards installed.
10 Provide DC supply voltage via the INF_1200 on slot PSA to the RAP (-40 V to
-75 V).
11 Provide DC supply voltage via the INF_1200 on slot PSB to the RAP (-40 V to
-75 V).
13 Check the proper operation of both RAP power sources by disconnecting one
source at a time.
14 Check the communication between the NPT-1200 shelf and the LCT-NPT via
the MNG Ethernet interface on the MCP1200.
16 Check LED operation using the LED TEST option in the LCT-NPT.
Parameter Value
Framing Unframed
Coding HDB3
Pattern 2 * 10-15 PRBS
Signal rate 2 Mbps
Timing Internal clock
Inject error Code error
Parameter Value
Framing Unframed
Coding HDB3
Pattern 2 * 10-15 PRBS
Signal rate 34 Mbps
Timing Internal clock
Inject error Code error
Parameter Value
Framing Unframed
Coding B3ZS
Pattern 2 * 10-15 PRBS
Signal rate 45 Mbps
Timing Internal clock
Inject error Code error
NOTE: For SDH tests configure the test equipment according to the interface type being
tested.
Parameter Value
Signal rate STM-1, STM-4, STM-16, STM-64
Mapping Any mapping (preferably bulk)
Pattern 2 * 10-15 PRBS
Signal rate 155.520 Mbps, 622.080 Mbps
Timing Received clock
Inject error BIP error
NOTE:
Measured latency is for both the forward and return paths. For a single path, the latency
is 50% of the measured value.
The latency test is dependent on the throughput results. For example, if 10 Mbps is
tested and the throughput is 4%, the latency test should be for 4 Mbps.
Inject traffic according to the assigned bandwidth.
Latency
1 Visually inspect the condition of cables and fibers. Check for correct X
routing (no sharp bends) and proper support to avoid stress. Avoid
touching fibers during the inspection, except as required to correct
problems.
3 Check the condition of rack front doors and RFI fingers. Clean as X
necessary with approved cleaning agents.
6 Check that cards and modules are securely attached. All module X
fastening screws must be tight (tighten only manually).
7 Check for proper operation of the fans (no abnormal noise and X
vibrations) in all NEs.
8 Clean all areas around the platform in the rack and the rack’s front door X
(if applicable), using a vacuum cleaner.
9 Check that the cables connecting the DC power sources (main and X
backup) to the RAP are properly connected.
10 X
Check that the external alarm cables are properly connected to the RAP.
12 Check that all RAP LEDs turn on and that the buzzer sounds while the X
POWER ON pushbutton on the RAP panel is pressed.
13 X
Check that all card and module LEDs turn on when performing the LED
TEST operation using the LCT-APT.
Note: LEDs for FE interfaces and LEDs for Laser On indications are not
checked by the LED test operation.
15 Check the proper operation of the OW system (if applicable to the NE).
NOTE: For a description of indicator functions, see the NPT-1200 Product Line Reference
Manual.
Table 5-3: General troubleshooting procedures for NPT-1200 power-on based on LEDs on MCP1200 panel
On On Off On Invalid NE
communication
parameters in install
file
NOTE: After NPT-1200 starts up, the ACT LED on the MCP1200 panel blinks periodically and
the FAIL LED on MCP1200 panel is permanently off.
NOTE: During the NE startup stage, the FAIL LED on Tslot or XIO cards must be Off, and the
ACT LED on Tslot or XIO cards On.
NOTE: Every FE port has two LEDs that reside on the RJ-45 connector. One is a link indicator
(green), the other is a speed indicator (orange).
Table 5-8: Special troubleshooting procedures for DMGE_4_L1, DMGE_4_L2 and DMGE_8_L2
NOTE: An optical port with ALS capability turns off its transmitter when the corresponding
receive signal is lost. Turning the transmitter off may cause a chain reaction, which turns the
optical signals off in a whole section of the network and generates a large number of alarms.
As a result, it may be difficult to identify the real cause of the problem and you may need to
use the management station log records to identify the port.
When inserting cards and modules, be sure to carefully align the card/module with the platform guide rails.
If you feel resistance during insertion, immediately retract the card/module and repeat the process.
Hold the card/module straight during insertion and removal, and pull or push it slowly and carefully to
avoid touching components located on adjacent cards/modules.
Do not use excessive torque when tightening the fastening screws of cards and modules.
Visually inspect the card and the mating backplane connectors and make sure that there are no signs of
physical damage. In particular, check for bent connector pins.
CAUTION: Replacing the MCP1200 card does not affect traffic on other Tslot cards. However,
T3/T4 synchronization signals, the E1-based DCC clear channel, and OW traffic are unavailable
for the duration of the replacement.
CAUTION: Because of XIO64 or XIO16_4 card redundancy, all the traffic on the main XIO64 or
XIO16_4 can be protected by the standby XIO64 or XIO16_4 when replacing the main XIO64 or
XIO16_4. To avoid breaks in traffic, the XIO64 or XIO16_4 cards must be replaced one by one.
It is important that the standby XIO64 or XIO16_4 card be running before replacing the main
XIO64 or XIO16_4 card.
CAUTION:
If using a DC power supply, each NPT-1200 shelf has two power modules; therefore,
replacing the power module does not cause the NE to power off.
Replace INF_1200 modules one at a time so that the system is not powered off.
CAUTION: The NPT-1200 is fed from two power sources, disconnect all power cables from the
platform before servicing.
CAUTION:
Each NPT-1200 shelf has one FCU module.
Replace the FCU_1200 or FCU_1200B module as soon as possible, as the temperature
inside the NPT-1200 continues to rise without the fan unit. The high temperature can
cause hardware damage.
IMPORTANT: The wiring of the SCSI-100 connector in both the PME1_21 and MSE1_16 is
identical. The different is that in the MSE1_16 only the first 16 E1s are used.
The following figure identifies the connector pins as seen when looking into the connector. The table lists
the pin assignment for a typical connector. It also lists the color of the wire connected to the corresponding
pin in the cables offered by ECI for connecting between the tributary connector and a distribution frame.
Figure 6-12: E1 connectors for PME1_21, pin identification
1 -- N/C -- --
1 -- N/C -- --
The following sections contain tables that describe the pin assignment of the connector for each type of
traffic module. These tables include the color of the wire connected to the corresponding pin in the cables
offered by ECI for connecting the SM_10E/EM_10E traffic module connector and a distribution frame.
The SM_EOP has two RJ-45 connectors for connecting to its interfaces and the SM_C37.94 has two pairs of
ST fiber optic connectors for connecting to its interfaces.
NOTE: Only 8 of 18 pairs of wires are used for the SM_FXO_8E or SM_FXS_8E interfaces.
NOTE: The number of wires used depends on the mode of each channel. All 18 pairs of wires
are used for the SM_EM_24W6E module if all channels are in four-wire E&M mode.
Table 6-23: SM_10E/EM_10E SM_V24E connector, pin assignment for 8 x V.24 transparent without
controls mode
In mode 4 x V.24 asynchronous with controls, the SM_V24E supports four channels, each with eight wires.
The following table lists the pin assignment for a typical connector when the SM_V24E is in 4 x V.24
asynchronous with controls mode. This table also lists the color of the wire connected to the corresponding
pin in the cables offered by ECI for connecting the tributary connector and a distribution frame.
In mode 2 x V.24 synchronous with controls, the SM_V24E supports two channels, each with eleven wires.
The following table lists the pin assignment for a typical connector when the SM_V24E is in 2 x V.24
synchronous with controls mode. This table also lists the color of the wire connected to the corresponding
pin in the cables offered by ECI for connecting the tributary connector and a distribution frame.
Table 6-25: SM_10E/EM_10E SM_V24E connector, pin assignment for 2 x V.24 synchronous with controls
mode
Mode
Port Pin Signal Sync V.24 V.35/V.36 V.11/X.24 RS422 RS449
20 TD (a) (T)
19 TD (b) (T)
2 RD (a) (R)
1 RD (b) (R)
22 ST (a) (S)
21 ST (b) (S)
4 RT (a)
3 RT (b)
6 TT (a)
#1 5 TT (b)
29 RTS (a) (C)
30 RTS (b) (C)
23 CTS (a) (I)
32 CTS (b) (I)
24 DSR
15 DCD
33 DTR
17 Ground
26 TD (a) (T)
25 TD (b) (T)
8 RD (a) (R)
7 RD (b) (R)
28 ST (a) (S)
27 ST (b) (S)
10 RT (a)
9 RT (b)
12 TT (a)
#2 11 TT (b)
31 RTS (a) (C)
34 RTS (b) (C)
13 CTS (a) (I)
36 CTS (b) (I)
Mode
14 DSR
16 DCD
35 DTR
18 Ground
There are eight RJ-45 connectors for external interfaces on the front panel of the ICP_VF. The figure
Ethernet connector, pin identification identifies the RJ-45 connector pins as seen when looking into the
connector. The following tables list the pin assignment for a typical connector, when serving each type of
traffic module. These tables also list the color of the wire connected to the corresponding pin in the cables
for connecting the tributary connector and a distribution frame.
ICP_VF RJ-45 connector, pin assignment for serving SM_FXS_8E or SM_FXO_8E
The following figure identifies the 9-pin D-type male connector pins as seen when looking into the
connector. The tables list the pin assignment for a typical connector in modes asynchronous with controls
and transparent without controls. These tables also list the color of the wire connected to the
corresponding pin in the offered cables for connecting the tributary connector and a distribution frame.
9-pin D-type male connector, pin identification
The following figure identifies the 25-pin D-type male connector pins as seen when looking into the
connector. The table lists the connector pin assignment for a typical connector and the color of the wire
connected to the corresponding pin in the cables offered by ECI for connecting the tributary connector and
a distribution frame.
Figure 6-20: 25-pin D-type male connector, pin identification
All platforms 25 CRIT_NC Critical alarm relay, normally closed contact Output Pink/Black
26 CRIT_NO Critical alarm relay, normally open contact Output Pink/Green
29 MAJ_NO Major alarm relay, normally open contact Output Light Blue
31 MIN_NC Minor alarm relay, normally closed contact Output Light Blue/Red
32 MIN_NO Minor alarm relay, normally open contact Output Light Blue/Violet
All platforms 67 WARN_NC Warning alarm relay, normally closed contact Output Blue/Black
68 WARN_NO Warning alarm relay, normally open contact Output Gray/White dots
NOTE: The instructions in this Appendix are relevant to the installation of all rack types.
However, it is recommended that NPT-1200 platforms be installed in ETSI A racks.