SOM6916952
Catégorie Doc.
Echelle
/ SUPPLIER CONTROLLER COMMUNICATION LIST
Format
A4
Projet Numéro MR Numéro PO Progressif Feuille Rév.
20096 52110 4580091611 022 1/27 F
Document de propriété Arkad SpA: défense de le reproduire, circuler et utiliser sans autorisation
-Electronically Approved Drawing-Checked:Baviera, F.,Approved:Visintin, F.- Internal DT-'N'
COMMUNICATION LIST
CUSTOMER : ARKAD FOR SONATRACH
PLANT LOCATION : OUARGLA ALGERIA
PLANT : 4th TURBO COMPRESSOR IN OUARGLA SC3 COMPRESSION
JOB. NO : 1607464/1106660
ITEM NO : C-0904
DATA TYPE 32 BIT FORMAT FLOATING FOR ANALOG DATA, 16 BIT REGISTER FOR BOOLEAN DATA
REGISTERS FOR ANALOG SIGNALS 40001 ÷ 40239, 40241÷40281, 40387÷40401, 40291÷40335, 40337÷40385 <4>
REGISTERS FOR DIGITAL SIGNALS (BIG ENDIAN) <1> 41423.00 ÷ 41442.15, 41540.00÷41547.15, 41555.00÷41559.15, 41565.00÷41568.15
FOR DIGITAL SIGNALS, DESCRIPTION IS REFERING TO THE ACTIVE STATUS (STATUS ACTIVE = TRUE)
NOTES:
1) RANGES SHOWN FOR ANALOG SIGNALS ARE ONLY FOR THEIR REPRESENTATION. ANALOG SIGNALS ARE REPRESENTED IN REAL VALUE (32bit) IN ENGINEERING UNITS. NO CONVERSION OPERATIONS ARE REQUIRED BY
CUSTOMER DCS
2) THERE ARE GAPS IN THE DATA ADDRESSES TO ACCOMMODATE ANY ADDITIONS LATER IN THE INDIVIDUAL CATEGORIES. THE MODBUS MASTER SHOULD NOT QUERY ANY REGISTER THAT FALLS IN THE GAP AS IT WILL
RETURN AN ERROR.
3) RANGES WHICH ARE SHOWN IN BLANK WILL BE UPDATED ONCE THE DATA IS AVAILABLE.
4) <4>
5) CALIBRATION RANGE ARE PROVIDED ONLY FOR INSTRUMENT THAT ACTUALLY REQUIRES CALIBRATION ON FIELD: RANGE WITH (*) ARE OPERATIVE RANGE AS PER P&ID <2>