Professional Documents
Culture Documents
Standard For Elec Room
Standard For Elec Room
Standard For Elec Room
4.5
Electrical Rooms
Standards for Electrical Rooms -
Building Services
Grounds and Building Maintenance
Electrical Rooms must be considered in the early stages of the Design Phase, and consideration
must be given to location, size and number of Electrical Rooms. Service Entrance to Building
usually determines location for Transformer Vault. All Transformer Vaults must remain free of
other systems not associated with electrical distribution systems.
Main distribution with switchgear shall be designed in a separate room if the building
program allows the space and location.
1. Design Review – Facilities Engineering Department and Maintenance Department shall review
electrical systems at the following phases.
• Switchgear
• Transformers
• Distribution Panels
• Generator
• Branch Panels
• Feeder Distribution
• Panel Schedules
2. Room Construction
5. Housekeeping Pads
6. Equipment Mounting
a. Recessed/Surface:
– Surface mount in Mechanical Rooms
− Recessed in finished areas. (Spare conduits run to above
ceiling. Enough conduits to fill-out spare circuits. Box or
trough at end of conduit stubs. Must be accessible)
a. HVAC
• Equipment
• Piping
c. Elevator Equipment Rooms and Shaft – No other equipment not associated with Room or
Shaft.
d. OIT – Provide standard OIT station outlet at any new Switchgear Room near transfer switch
for SCADA requirements.
a. All lighting shall be 4’-0” fluorescent with T8 lamps, 3500ºK. Lighting shall be switched at
each door into Room.
b. At least one light shall be circuited to the emergency panel. Light shall be switched and
handle shall be lighted in the “Off” position. Locate switch closest to door frame.
c. One 20 Amp. convenience receptacle per 150 sq. ft. floor space or not more than 25 feet
apart. One receptacle (red) on emergency circuit in Main Mechanical Rooms, Switchgear
Rooms. Each space shall have a minimum of one receptacle or more.
d. At least one OIT outlet required for connecting selected equipment to the campus electric
SCADA system.
10. Scaled vertical section cut(s) at major horizontal distribution pathways (such as horizontal pipe
chases and above congested hallway ceilings), showing a coordinated depiction of all MEP
systems at multiple locations;
11. Refer to Section 3.12 (Electrical Systems Design) for allowable electrical pathway and conduit
equipment.
• Electrical power and lighting floor layout plans with conduit and circuits shown as-built.