Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

27th Iranian Conference on Electrical Engineering (ICEE2019)

Voltage sag Assessment Considering Low Voltage


Ride-Through Requirement for Wind Turbines
Based on SARFI Index
Sina Shakeri Saeid Esmaeili Mohammad Hossein Rezaeian Koochi
Department of Electrical Engineering Department of Electrical Engineering Department of Electrical Engineering
Shahid Bahonar University of Kerman Shahid Bahonar University of Kerman Shahid Bahonar University of Kerman
Kerman, Iran Kerman, Iran Kerman, Iran
s.shakeri@eng.uk.ac.ir s_esmaeili@uk.ac.ir mh_rezaeian@eng.uk.ac.ir

Abstract—This paper defines a system average root mean for wind turbines. Among the large number of methods
square variation frequency (SARFI) index based on the area of proposed in literature the most well-known ones are critical
vulnerability (AOV) and proposes a systematic method for distance and fault position methods. The critical distance
determining accurate AOVs for fault induced voltage sags. The cannot be applied on meshed networks [6], [7]. The fault
SARFI index specifies the number of voltage sags experiencing position method, which has been widely used in many
at a given area or in a given system per year more severe than studies, can be applied to both meshed and radial networks
the curve limits. The SARFI index is helpful in establishing [8]–[10]. However, this method heavily depends on the
efficient planning for mitigation of voltage sags. This paper also choice of fault positions and the number of simulated faults
assesses voltage sags considering low voltage ride-through
and is inefficient for large power systems [11], [12]. Another
(LVRT) requirements for wind turbines. The determination of
method for assessing voltage sags performance is an
AOVs is very important for assessing voltage sags
performance, since voltage sags can be caused by faults
analytical method, which is based on an analytical
occurring in different parts of a power system. In this paper, formulation of system faults [13], [14]. The shortcoming of
the procedure of determining AOVs for balanced faults are this method is that in some cases it can’t determine the area
considered. The proposed methodology is applied on the IEEE of vulnerability (AOV) accurately.
30-bus test system integrated with eight wind turbines. In this paper, the voltage sag assessment is performed
considering the low voltage ride-through requirement for
Keywords— Area of vulnerability (AOV), Low voltage ride-
wind turbines based on system average root mean square
through (LVRT) requirement, System average root mean square
variation frequency (SARFI) index, Voltage sag variation frequency (SARFI) index. To obtain the AOVs
without applying any fault to the system, the method
I. INTRODUCTION presented in [15] has been adopted in which the quadratic
interpolation and secant method are used for finding accurate
Power quality disturbances such as over voltages, voltage
roots of equations. However, in case where the maximum
sags, etc. can affect the quality of electrical power delivered
magnitude of voltage sag is far from a maximum magnitude
to consumers. Nowadays, the equipment, especially in
of interpolation, the method fails to find the accurate root.
industrial sector, are so sensitive that power delivery with
Therefore, the golden section search method is used in this
poor quality can lead to malfunction of the equipment or
paper. After finding the AOVs, the expected sag frequencies
even cause them to trip. Therefore, in addition to
(ESFs) are calculated and then the proposed SARFI index is
continuously monitoring of power quality [1], it is also
utilized to assess the voltage sags.
necessary to analyze the system performance against
disturbances in an offline or online manner [2], [3]. II. VOLTAGE SAG ASSESSMENT
Voltage sag is defined as the decrease in RMS voltage to A. Determining the area of vulnerability
values between 0.9 p.u and 0.1 p.u for durations ranging from
0.5 cycles of power system frequency to 1 minute [4]. The The area of vulnerability is the region of the system
main cause of voltage sag is faults occurring in a power which includes buses and lines that experience post-fault
system. In some cases, voltage sags can cause tripping of voltages lower than a voltage threshold in the case of fault
wind turbines and in turn overloading the generators in the occurrence [13]. To calculate AOV, fault voltage equations
rest of system. This situation may lead to cascading generator are required. Then, AOV for a given voltage threshold is
failures and instability of the whole system. Therefore, the determined using the voltage equations solved by numerical
connection of wind turbines to power grids has been methods. An effective method for calculating accurate AOV
becoming an important challenge to ensure stable power is proposed in [15]. This method can determine AOV for
system operation. three-phase faults without requiring short-circuit calculation
Many countries have established grid codes to ensure at different fault positions. To do that, first, pre-fault voltages
stable power system operation. The low voltage ride-through are calculated using load flow analysis. Furthermore, the
(LVRT) requirement is also included in grid codes. The main positive system impedance matrix is also obtained by
LVRT requirement for wind turbines is to stay connected to inversing the positive system admittance matrix. Then, the
the grid over specified range of voltage sags [5]. Therefore, residual voltage equation corresponding to the three-phase
there is strong need for an effective method to assess voltage fault is formulated.
sag performance considering different LVRT requirements
978-1-7281-1508-5/19/$31.00 ©2019 IEEE

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on May 25,2023 at 05:39:54 UTC from IEEE Xplore. Restrictions apply.
470
27th Iranian Conference on Electrical Engineering (ICEE2019)

B. Expected sag frequency calculation B. Voltage sag assessment based on SARFI index
After obtaining the AOV, the ESF can be calculated A widely used approach for computing the number of
considering the fault rates which are determined from the voltage sags is the system average rms frequency index
historical performance of the system. The ESF for the (SARFI), which was originally proposed in [20]. There are
balanced fault is calculated as follows [13]. two types of SARFI indices:   and   . The
m n
  index is the number of voltage sags at a given area or
ESF = ¦ BFR + ¦ I L × LFR (1) in a given system per year with a magnitude less than X
B =1 L =1 percent. The   index gives annual number of
where m and n are the number of buses and lines inside events below the predefined curve [21]. For example,
the AOV, respectively. BFR and LFR are bus and line fault   gives the number of events more severe than the
rates and  is the length of the line inside the AOV. After SEMI curve [22].
calculating ESF, the cumulative ESF for magnitude range ˆ Ǧ
– is obtained as follows [14].
Voltage

ESFV f −V t = ESFV t − ESFV f (2)


V2
In (2),  – and  ˜ˆ are the cumulative ESFs for DNAZ2
voltage thresholds – and ˆ , respectively. Then, the DNAZ1
cumulative probability  for duration range šˆ Ǧš– at voltage
V1
level L is calculated as follows [16], [17].
xt
1 x1 x2
³σ
2
/ 2σ L2 ) Time
PL = e − (( x − m L ) dx (3)
xf L 2π Fig. 1. LVRT requirement curve with diagonal (DNAZ1) and rectangular
where ݉௅ , ³ and ³ʹ are average duration, standard (DNAZ2) zones
deviation and variance at voltage level L, respectively.
III. ESTIMATION OF ESF CONSIDERING LVRT REQUIREMENT V2
DNAZ2
BASED ON SARFI INDEX
A B
A. Calculation of ESF reflecting LVRT requirement
The LVRT curve involves various ranges of sag Vm
magnitude and duration. Also LVRT curve consists of
diagonal and rectangular parts as shown as Fig. 1. Therefore,
C D
an effective method for estimation of ESF reflecting LVRT
requirement is required [14], [18], [19]. To estimate
cumulative ESFs for rectangular and diagonal zones, the V1
method proposed in [14] is adopted here. ESF for the X1 Xm X2
rectangular zone can be estimated as follows [14]. Fig. 2. Sub-zones for DNAZ2
ESFDNAZ 1 = ESFV 1 −V 2 × PL ,0 − X 1 (4) The SARFI index is recommended by standard-setting
organizations in [21] and [23]. It is a power quality index that
where  ͳǦʹ and ǤͲǦͳ are cumulative ESF for provides a measure for rate of voltage sags. The   is
voltage range ͳ Ǧʹ and cumulative probability for duration useful for assessing voltage sags at wind turbine connection
range ͲǦͳ , respectively. In this paper, to calculate the ESF points and can identify more severe voltage sags causing
for the diagonal zone, first, the rectangular zone is divided wind turbine disconnections. The   can be
into four sub-zones as shown in Fig. 2. Therefore, the ESF calculated as in (9).
for the diagonal zone can be calculated as follows [14].
SARFI LVRT = ¦ ª¬ ESF L ,V 2 − ESFL , DNAZ 2 º¼ (9)
ESFDNAZ 2 = ESFDNAZ 2' + ESFDNAZ 2" (5) L ∈SL

ESFDNAZ 2 ' = ESFV m −V 2 × PL , X 1 − X m (6) In (9), SL is the set of all voltage levels in a power
system, while  Ǥʹ and  Ǥʹ are the cumulative ESF
1 for voltage threshold ʹ at voltage level L and cumulative
ESFDNAZ 2" = (ESFV1 −V m × PL , X 1 −X m + ESFV m −V 2 × PL , X m − X 2 ) (7)
2 ESF for DNAZ2 zone at voltage level L, respectively.
(V +V 2 ) (X 1 + X 2 ) The overall flowchart of voltage sag assessment using
Vm = 1 ,X m = (8)
2 2 proposed index for considering low voltage ride-through
requirement of wind turbines is shown in Fig. 3. In the first
where  and  are median values of the voltage step, load flow analysis is performed to obtain the pre-fault
magnitude and duration ranges.  ʹ̵ is the cumulative voltage values needed for calculating AOV for a wind
ESF of zone A, while  ʹ̵̵ is the cumulative ESF for turbine connection point. Then, AOV for the three phase
combination of zones B and C. faults is calculated without any need to apply faults using the

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on May 25,2023 at 05:39:54 UTC from IEEE Xplore. Restrictions apply.
471
27th Iranian Conference on Electrical Engineering (ICEE2019)

method presented in [15]. The expected sag frequencies at TABLE I. HISTORICAL DATA OF PROTECTION SYSTEMS AND FAULT
RATES
voltage levels defined by the LVRT curve and the cumulative
ESFs associated with the LVRT curve are calculated in the Voltage
Mean Standard Line fault rate
Bus fault rate
next step. Finally, the SARFI index is calculated for the wind duration deviation (event/100
level (kV) (event/year)
turbine connection point using (9). (ms) (ms) km/year)
33 100 200 0.225 0.005
IV. CASE STUDIES

The IEEE 30-bus test system shown in Fig. 4 and two


LVRT curves for three-phase faults shown in Fig. 5 [24] are 30 29 26
used in this paper. Furthermore, eight wind turbines are 132 kV 25
assumed to be installed at buses 3, 6, 7, 14, 18, 21, 26 and 29. 33 kV 18 19 27
23
24
28
15 16
Start G 14 20 21 22
1 13
G 17
12 9
Perform load flow analysis 10
G
4 6 11
G 3
2
Determine AOV for a wind 8
turbine connection point G
7
5
G

Calculate ESFs
Fig. 4. Single-line diagram of IEEE 30-bus test system

Calculate cumulative ESFs for a


predefined LVRT curve V [p.u]
LVRT I
LVRT II
Compute the SARFI index for each wind
turbine connection point
0.80
0.75

End
0.20
Fig. 3. Procedure for calculating SARFI index 0.15

The historical data related to the operation of protection 0 120 150 750 900 Time [ms]
systems, as well as line and bus fault rates are listed in Tables
I [14].
Fig. 5. LVRT requirement curves
To illustrate the proposed method, the calculation of
SARFILVRT at bus 21 is explained here. The SARFI In the next step, the cumulative ESFs for DNAZ1 and
calculations for other selected buses follows the same   corresponding to LVRT curves I and II at voltage
procedure. For calculating SARFILVRT at bus 21, first AOVs level 33 kV are calculated as follows.
for voltage threshold values 0.2 and 0.75 for LVRT curve I,
and 0.15 and 0.8 for LVRT curve II are calculated. Figs. 6-9 ESFDANZ 1 = ESF0.75 − 0.2 × P33,0 −120 = 6.5890 × 0.006848=0.0451
show the AOVs obtained for LVRT curves and different
voltage thresholds. After determining AOVs for bus 21, the ESFDANZ 1 = ESF0.8 − 0.15 × P33,0 −150 = 7.6678 × 0.01087 = 0.0833
ESFs for three-phase faults is calculated. Then the
cumulative ESFs for LVRT curves I and II are obtained as ESFDA NZ 2 ' = ESF0.75− 0.475 × P33,120 − 510 = 5.1457 × 0.3182=1.6374
follows.
ESF0.75− 0.2 = ESF0.75 − ESF0.2 = 7.6478 − 1.0588 = 6.5890 ESFDANZ 2 ' = ESF0.8− 0.475 × P33,150 − 450 = 6.1730 × 0.2144 = 1.3235
ESF0.8 − 0.15 = ESF0.8 − ESF0.15 = 8.6751 − 1.0073 = 7.6678
1
ESFDA NZ 2 '' = ( ESF0.475 − 0.2 × P33,120 − 510 + ESF0.75 − 0.475 × P33,510 −900 )
2
1
= (1.4433 × 0.3182 + 5.1457 × 0.6068) = 1.6995
2

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on May 25,2023 at 05:39:54 UTC from IEEE Xplore. Restrictions apply.
472
27th Iranian Conference on Electrical Engineering (ICEE2019)

1
ESFDA NZ 2 '' = ( ESF0.475 − 0.15 × P33,150 − 450 + ES F0.475 − 0.8 × P33,450 − 750 )
2 30 29 26
1
= (1.4948 × 0.2144 + 6.1730 × 0.5467) = 1.7750 AOV 25
2 18 19 27
23
24
28
15 16
G 14 20 21 22
30 29 26 1 13
G 17
AOV 25
18 19 27 12 9
10
23
24 G
4 6 11
28 G 3
15 16
G 14 20 21 2
22 8
1 13 G
7
G 17 5
12 9 G
10
G
4 6 11 Fig. 8. AOV obtained for voltage threshold 0.2 p.u
G 3
2
8
G
7 30 29 26
5
G AOV 25
18 19 27
23
Fig. 6. AOV obtained for voltage threshold 0.8 p.u 24
28
15 16
G 14 20 21 22
30 29 26 1 13
G 17
AOV 25
18 27 12 9
19 10
23 G
24
4 6 11
28 G 3
15 16
G 14 20 21 2
22 8
1 13 G
7
G 17 5
12 9 G
10
G
G 4 6 11 Fig. 9. AOV obtained for voltage threshold 0.15 p.u
3
2
8
G
7
5
G

Fig. 7. AOV obtained for voltage threshold 0.75 p.u

ESFDNAZ 2,curve I = ESF + ESF = 3.3369


DNAZ 2' DNAZ 2"

ESFDNAZ 2,curve II = ESF + ESF = 3.0985


DNAZ 2' DNAZ 2"

SARFI curve I = ESF0.75 − ESFDNAZ = 4.2658

SARFI curve II = ESF0.8 − ESFDNAZ = 5.4933


Fig. 10. The results of SARFIcurve for LVRT curve I
The results of proposed SARFI index are compared with
the method presented in [14] and are shown in Figs. 10 and
11. Fig. 10 shows the SARFI values for LVRT curve I. It can
be seen that the lowest value relates to bus 7 in both methods,
while bus 26 and bus 29 have the highest voltage sag index
values for proposed method and the method in [14],
respectively. Fig. 11 shows the SARFI values obtained for
LVRT curve II. From Fig. 11 it can be seen that, bus 3 is the
bus with lowest voltage sag index value for the proposed
method, while for the method [14] the lowest value
corresponds to bus 7. Furthermore, bus 26 is the bus with the
highest SARFI value for both methods.

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on May 25,2023 at 05:39:54 UTC from IEEE Xplore. Restrictions apply.
473
27th Iranian Conference on Electrical Engineering (ICEE2019)

[7] A. K. Goswami, C. P. Gupta and G. K. Singh, “Voltage Sag


Assessment in a Large Chemical Industry,” IEEE Trans. Ind. Appl.,
vol. 48, no. 5, pp. 1739–1746, Sep. 2012.
[8] L. Conrad, K. Little and C. Grigg, “Predicting and preventing
problems associated with remote fault-clearing voltage dips,” IEEE
Trans. Ind. Appl., vol. 27, no. 1, pp. 167–172, 1991.
[9] G. Carpinelli, P. Caramia, C. Di Perna, P. Varilone and P. Verde,
“Complete matrix formulation of fault-position method for voltage-
dip characterisation,” IET Gener. Transm. Distrib., vol. 1, no. 1, p. 56,
2007.
[10] I. B. N. C. Cruz, A. P. Lavega and J. R. C. Orillaza, “Overview of
voltage sag profile estimation,” in TENCON 2015 - 2015 IEEE
Region 10 Conference, 2015, vol. 2016–Janua, pp. 1–6.
[11] C. Ceja-Espinosa, A. Ramos-Paz, and E. Espinosa-Juarez,
“Parallelization of the Fault Positions Method for stocastic assessment
of voltage sags,” in 2013 IEEE International Autumn Meeting on
Power Electronics and Computing (ROPEC), 2013, pp. 1–5.
Fig. 11. The results of SARFIcurve for LVRT curve II [12] C. H. Park, G. Jang and R. J. Thomas, “The Influence of Generator
Scheduling and Time-Varying Fault Rates on Voltage Sag
Prediction,” IEEE Trans. Power Deliv., vol. 23, no. 2, pp. 1243–1250,
I. CONCLUSION Apr. 2008.
This paper proposed a systematic method to determine [13] C.-H. Park and G. Jang, “Stochastic Estimation of Voltage Sags in a
AOVs for three-phase faults and assessed voltage sag Large Meshed Network,” IEEE Trans. Power Deliv., vol. 22, no. 3,
pp. 1655–1664, Jul. 2007.
performance considering low voltage ride-through
[14] C.-H. Park and G. Jang, “Voltage quality assessment considering low
requirement for wind turbines based on SARFI index. voltage ride-through requirement for wind turbines,” IET Gener.
Voltage sag assessment heavily depends on determining Transm. Distrib., vol. 10, no. 16, pp. 4205–4212, Dec. 2016.
accurate AOVs. To exactly identify AOVs the golden section [15] C.-H. Park and G. Jang, “Systematic Method to Identify an Area of
search was used for finding maximum sag magnitude and its Vulnerability to Voltage Sags,” IEEE Trans. Power Deliv., vol. 32,
point. The SARFI index is effective to assess the annual no. 3, pp. 1583–1591, Jun. 2017.
number of voltage sags considering allowable zones of wind [16] Wenyuan Li and P. Choudhury, “Probabilistic planning of
turbine disconnection on a LVRT curve. The proposed transmission systems: Why, how and an actual example,” in 2008
IEEE Power and Energy Society General Meeting - Conversion and
method could determine the buses which have the high and Delivery of Electrical Energy in the 21st Century, 2008, pp. 1–8.
the low voltage sag values.
[17] J. Momoh, Adaptive Stochastic Optimization Techniques with
Applications. CRC Press, 2015.
REFERENCES
[18] S. R. Naidu, G. V. de Andrade and E. G. da Costa, “Voltage Sag
[1] L. Kamyabi, S. Esmaeili and M. H. Rezaeian Koochi, “Power quality Performance of a Distribution System and Its Improvement,” IEEE
monitor placement in power systems considering channel limits and Trans. Ind. Appl., vol. 48, no. 1, pp. 218–224, Jan. 2012.
estimation error at unobservable buses using a bi-level approach,” Int.
[19] J. W. Sagre, J. E. Candelo and J. H. Montaña Chaparro, “Voltage sag
J. Electr. Power Energy Syst., vol. 102, pp. 302–311, Nov. 2018.
assessment using an extended fault positions method and Monte Carlo
[2] M. H. R. Koochi, S. Esmaeili, and P. Dehghanian, “Coherency simulation,” DYNA, vol. 83, no. 195, pp. 180–188, Feb. 2016.
detection and network partitioning supported by wide area
[20] D. L. Brooks, R. C. Dugan, M. Waclawiak, and A. Sundaram,
measurement system,” in 2018 IEEE Texas Power and Energy
“Indices for assessing utility distribution system RMS variation
Conference (TPEC), 2018, pp. 1–6.
performance,” IEEE Trans. Power Deliv., vol. 13, no. 1, pp. 254–259,
[3] M. H. Rezaeian, S. Esmaeili and R. Fadaeinedjad, “Generator 1998.
coherency and network partitioning for dynamic equivalencing using
[21] D. D. Sabin and M. H. J. Bollen, “Overview of IEEE Std 1564-2014
subtractive clustering algorithm,” IEEE Syst. J., no. 99, pp. 1–11,
Guide for Voltage Sag Indices,” in 2014 16th International
2017.
Conference on Harmonics and Quality of Power (ICHQP), 2014, pp.
[4] IEEE and Institute of Electrical and Electronic Engineers, “IEEE Std 497–501.
1159 - IEEE Recommended Practice for Monitoring Electric Power
[22] “Materials International (SEMI), Specification for semiconductor
Quality.,” 2009.
processing equipment voltage sag immunity,” 2006.
[5] M. Mohseni and S. M. Islam, “Comparing technical connection
[23] G. Beaulieu and G. Borloo, “Power quality indices and objectives,” in
requirements for large wind power plants,” in 2011 IEEE Power and
18th International Conference and Exhibition on Electricity
Energy Society General Meeting, 2011, pp. 1–8.
Distribution (CIRED 2005), 2005, vol. 2005, pp. v2-79-v2-79.
[6] M. H. J. Bollen, “Method of critical distances for stochastic
[24] Https://labs.ece.uw.edu/pstca/pf30/pg_tca30bus.htm, “ieee30cdf.” .
assessment of voltage sags,” IEE Proc. - Gener. Transm. Distrib., vol.
145, no. 1, p. 70, 1998.

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on May 25,2023 at 05:39:54 UTC from IEEE Xplore. Restrictions apply.
474

You might also like