Indicate how the most remote area is determined in each case

We have 3 scenarios

1- FHC only, it depends on there is two cabinet stations open during fire emergency, each cabinet
need 250 gallons per mints at 100 psi residual pressure.
2- The most demand area (CSMA sprinklers) it depends on the fire occur at racks area about 1500
square feet.
The area of sprinkler operation 1500 FT2 (130 M2) at the density 0.2 GPM/FT2 ordinary hazard
from FIGURE 11.2.3. 1.1 Density/ Area Curves. NFPA 13
The number of sprinklers in this area are 10 spk with k=16.8 plus 100 GPM non spk flow.
3- The fire occur above ceiling (most remote area) at about 1500 square feet
The area of sprinkler operation 1500 FT2 (130 M2) at the density 0.15 GPM/FT2 light hazard from
FIGURE 11.2.3. 1.1 Density/ Area Curves. NFPA 13
The number of sprinklers in this area are 19 spk with k=5.6 plus 100 GPM non spk flow.