Wind loading analysis Open structures, without

roof

qz=0.613 Kz Kzt Kd Ke V² KN/m²

Kz 0.95 See Section 26.10.1


Kzt 1 See Section 26.8.2
Kd 0.85 See Section 26.6
Ke 1
V 50 m/s
qz 1237.49375 N/m²

As per SBC301-page 7/21, the reduction factor for area greater than 100 Sqm= 0.8

P=q G Cn KN/m²
q G= 989.995 N/m²

Windward Leeward Case


Cn -1.10 0.30
Case 1
P -1.09 0.30
Cn -0.20 1.20
Case 2
P -0.20 1.19
Cn -1.60 -0.50
Case 3
P -1.58 -0.49
Cn -0.90 -0.80
Case 4
P -0.89 -0.79
NB:Windward downd (compression) and Leeward up (tension), in case if the convention
changed, the direction of the load shall be changed.

Cn P Case Distance
-0.80 -0.79 Case 1 h
-0.60 -0.59 2h
-0.30 -0.30 More than 2h
0.80 0.79 Case 2 h
0.60 0.59 2h
0.30 0.30 More than 2h