Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Ground Floor

07.06.2023

Operator
Telephone
Fax
e-Mail

Entarnace Hall / Single Sheet Output

Height of Room: 2.800 m, Mounting Height: 2.900 m, Maintenance factor: Values in Lux, Scale 1:120
0.80

Surface r [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 87 13 182 0.152
Floor 30 87 13 183 0.154
Ceiling 80 20 13 24 0.667
Walls (4) 60 28 13 71 /

Workplane:
Height: 0.000 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.321, Ceiling / Working Plane: 0.231.

Luminaire Parts List

No. Pieces Designation (Correction Factor) F (Luminaire) [lm] F (Lamps) [lm] P [W]
1 8 N N/A Photometry_One_NL_30_Wide (1.000) 658 658 11.9
Total: 5267 Total: 5264 95.4

Specific connected load: 1.88 W/m² = 2.16 W/m²/100 lx (Ground area: 50.64 m²)

Page 1

You might also like