Professional Documents
Culture Documents
Entrance Hall
Entrance Hall
07.06.2023
Operator
Telephone
Fax
e-Mail
Height of Room: 2.800 m, Mounting Height: 2.900 m, Maintenance factor: Values in Lux, Scale 1:120
0.80
Workplane:
Height: 0.000 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.321, Ceiling / Working Plane: 0.231.
No. Pieces Designation (Correction Factor) F (Luminaire) [lm] F (Lamps) [lm] P [W]
1 8 N N/A Photometry_One_NL_30_Wide (1.000) 658 658 11.9
Total: 5267 Total: 5264 95.4
Specific connected load: 1.88 W/m² = 2.16 W/m²/100 lx (Ground area: 50.64 m²)
Page 1