STATEMENT RECOMMENDATION

USE 15AT, 22KAIC MCCB


THE GIVEN DATA SHOWS THE CURRENT VALUES RECORDED USE 20AT, 22KAIC MCCB
DURING RMS SYMMETRICAL SHORT CIRCUIT CALCULATION ,
NAMELY FAULT 1, FAULT 2, AND FAULT 3. THE RECORDED CURRENT USE 30AT, 22KAIC MCCB
VALUES FOR THESE FAULTS ARE 12847.43 AMPERES, 11940 AMPERES, USE 50AT, 22KAIC MCCB
AND 10223.93 AMPERES, RESPECTIVELY. USE 60AT, 22KAIC MCCB
FROM THE GIVEN DATA, IT CAN BE OBSERVED THAT FAULT 1 USE 75AT, 22KAIC MCCB
RESULTED IN THE HIGHEST CURRENT VALUE OF 12847.43 AMPERES, USE 40AT, 22KAIC MCCB
WHILE FAULT 3 RESULTED IN THE LOWEST CURRENT VALUE OF
10223.93 AMPERES. FAULT 2 RESULTED IN A CURRENT VALUE OF USE 100AT, 22KAIC MCCB
11940 AMPERES, WHICH IS IN BETWEEN THE CURRENT VALUES OF USE 125AT, 25KAIC MCCB
FAULT 1 AND FAULT 3.
USE 150AT, 25KAIC MCCB
IT IS IMPORTANT TO ANALYZE SUCH DATA IN ORDER TO IDENTIFY USE 175AT, 25KAIC MCCB
AND PREVENT FAULTS IN ELECTRICAL SYSTEMS. BASED ON THE FOR MAIN CIRCUIT BREAKER USE 600AT,
GIVEN DATA, IT IS RECOMMENDED TO FOCUS ON FAULT 1, WHICH
85KAIC MCCB (FUJI OR JAPAN BRAND)
RESULTED IN THE HIGHEST CURRENT VALUE. FURTHER INVESTIGATION
SHOULD BE CARRIED OUT TO IDENTIFY THE ROOT CAUSE OF THIS FAULT
AND TO TAKE APPROPRIATE MEASURES TO PREVENT SUCH FAULTS FROM
OCCURRING IN THE FUTURE. IT IS ALSO RECOMMENDED TO CONDUCT
SIZE OF THE TRANSFORMER
REGULAR INSPECTIONS AND MAINTENANCE OF THE ELECTRICAL SYSTEM
TO PREVENT FAULTS FROM OCCURRING. THIS CAN HELP TO ENSURE THE
TOTAL DEMAND LOAD = DEMAND LOAD /DIVERSITY FACTOR
SAFETY AND RELIABILITY OF THE ELECTRICAL SYSTEM. (AS PER IEC 61439)
PROVIDE 225 KVA 3ɸ TRANSFORMER
OR 3-75KVA TRANSFORMER
TOTAL DEMAND LOAD = 557.23 / 1.429 BASED ON IEEE/ANSI C57.12.00
TOTAL DEMAND LOAD = 389.94 AMPS

LEGEND, SYMBOLS, & ABBREVIATIONS APPLY 125% TO TOTAL DEMAND LOAD CHECK TRANSFORMER 80% LOADING

IT = 389.94 X 125% 389.94 X 1.73 X 230


CIRCUIT BREAKER MAIN FEEDER (EXISTING) / SERVICE ENTRANCE
= 115.15 KVA
M SERVICE METER TRANSFORMER
IT = 487.43 AMPS 1000
GROUND FUSE CUT OUT

DPST DOUBLE POLE SINGLE THROW FAULT LOCATION


STRANSFORMER = 3 (487.43)(230) 115.15 KVA
X 100 = 68.96%
1000 225 KVA

STRANSFORMER = 194.18 KVA

SCHOOL: PROJECT TITLE: PREPARED BY: PRC REGISTRATION: APPROVED BY: SEAL: SHEET CONTENT: SHEET NO.

PROPOSED 6 STOREY 58 ROOMS HOTEL P.T.R.#: STATEMENT


REPUBLIC OF THE PHILIPPINES
ELECTRICAL PLAN ALBERT P. ROJAS RECOMMENDATION
EASTERN VISAYAS STATE UNIVERSITY
ORMOC CAMPUS
CRISTITUTO L. ERAS JR DATE ISSUED:
PLACE ISSUED: ORMOC CITY
SIZE OF THE TRANSFORMER E-3
BSEE STUDENT REGISTERED ELECTRICAL ENGINEER LEGEND, SYMBOL, & ABBREVIATION
ORMOC CITY LOCATION: BARANGAY LUNA, ORMOC CITY
ENGINEERING DEPARTMENT, EVSU-OC T.I.N: FACULTY, ENGINEERING DEPARTMENT, EVSU-OC