Professional Documents
Culture Documents
Chapter 8 POWER FLOW THROUGHT INTERCONNECTORS
Chapter 8 POWER FLOW THROUGHT INTERCONNECTORS
Chapter 8 POWER FLOW THROUGHT INTERCONNECTORS
Contact:
Mr S. D. Lumina, B.Tech (Elec Eng), M.Eng (Elec Eng)
Email: luminas@cput.ac.za
Department of Electrical, Electronics and Computer Engineering.
CPUT, Bellville Campus
1
Complex Power
Power system engineers treat a capacitor as a source of reactive power rather
than as a load. Inductors are treated as loads absorbing reactive power.
By convention is has been decided that for inductors and capacitors their
complex power are:
𝑆 𝑉∠0°
+𝑗𝑄 −ɵ
ɵ
I∠ −ɵ
𝑃
2
Capacitive : 𝑆∠-𝞱=𝑃 − 𝐽𝑄 = 𝑉𝐼∗ 𝑉𝑜𝑙𝑡𝑎𝑚𝑝𝑒𝑟𝑠
𝑃
−ɵ
𝑆 −𝑗𝑄 I∠ɵ
ɵ
𝑉∠0°
𝑉 𝑉
Thus 𝐼ഥ∗ = ( 𝑆 ∠𝛿 − ᴪ)-( 𝑅∠−ᴪ)
𝑍 𝑍
Therefore
Receiving-end complex power: 𝑆𝑅 = 3𝑉𝑅 𝐼ഥ∗
𝑉𝑆 𝑉𝑅
= 3𝑉𝑅 ∠0 ∠𝛿 − ᴪ− ∠ − ᴪ
𝑍 𝑍
6
Example
Let 𝑉1 𝑎𝑛𝑑 𝑉2 on a power system be 100∠20° and 80∠0° volts respectively.
Let the interconnector impedance be 5∠90°
Calculate using the current conjugate method, the power flows and represent your
answers on a on-line diagram clearly indicating their directions, this to be
determined from where or not they are being supplied or absorbed.
100∠20° −80∠0° °
𝐼= = 7.38∠ −22.21 (6.84 − 𝐽2.79)
5∠90°
𝑆𝐼 =𝐸1 𝐼 ∗ =(100∠20° )(7.38∠22.2° )= 738∠ −42° = 548.4 + 𝐽493.81
𝑃1 (𝑠𝑒𝑛𝑑𝑖𝑛𝑔) 𝑄1 (𝑠𝑒𝑛𝑑𝑖𝑛𝑔)
8
In the above example 100∠20° 𝑉 was assumed the sending-end voltage. In
power system it is difficult to say which is the sending or receiving-end. It
however makes no difference. The 80∠0° 𝑉 could be assumed as the sending-
end. To prove that the same results are obtained the above example is repeated
but the 80∠0° 𝑉 is assumed as sending-end.
80∠0° −100∠20° °
𝐼= = 7.38∠ − 22.2
5∠90°
𝑆1 = 80∠0° X 7.38∠22.2° = 590∠20,2°
𝑆2 = 100∠0° X 7.39∠22.2° = −547 − j496
It can be seen that the same power flows are obtained after applying the table.
𝑆1 acting as the sending end (generator). As power are both negative it can be
seen from the table that these powers are being absorbed. Likewise, 𝑆2 at
receiving-end (motor) which are also negative are being absorbed. The same
results as previously have been obtained proving the above statement. 9
Power flow using the formula method
• Using the same one-line diagram as before, the following formular can be
provided.
𝑉𝑆 ∠𝛿− 𝑉𝑅 ∠0° 𝑉𝑆 ∠𝛿 𝑉𝑅 ∠0°
𝐼= = -
𝑍∠ᴪ 𝑍∠ᴪ 𝑍∠ᴪ
Sending end
𝑉𝑆 ∠ᴪ−𝛿 𝑉𝑅 ∠ᴪ |𝑉𝑆 |2 ∠ᴪ 𝑉𝑆 𝑉𝑅 cos(ᴪ+𝛿)
𝑆𝑆 = 𝑉𝑅 𝐼∗ = 𝑉𝑆 ∠𝛿 − = −
|𝑍| |𝑍| |𝑍| |𝑍|
|𝑉𝑆 |2 cos(ᴪ) 𝑉𝑅 |𝑉𝑆 |
𝑃𝑆 = - cos( ᴪ+ 𝛿)
|𝑍| |𝑍|
|𝑉𝑆 |2 Sin(ᴪ) 𝑉𝑅 |𝑉𝑆 |
𝑄𝑆 = - sin( ᴪ+ 𝛿)
|𝑍| |𝑍|
Please not if 𝑅 = 0, 𝑍 = 𝑋 ∠0 ∴ ᴪ=90° then :
𝑉𝑅 |𝑉𝑆 | cos(90° −𝛿) |𝑉𝑅 |2 𝑉 |𝑉 |
𝑃𝑅 =
𝑋
- cos 90° = 𝑅𝑋 𝑆 (cos 90° cos 𝛿 + sin 90° sin 𝛿
𝑋
𝑉𝑅 |𝑉𝑆 |
= 𝑋
sin 𝛿 11
• Since sin 90 − 𝛿 = sin 90° cos𝛿-cos 90° sin𝛿=cos 𝛿
𝑉𝑅 |𝑉𝑆 | |𝑉𝑅 |2
𝑄𝑅 = cos 𝛿 -
𝑋 𝑋
• If a 3 phase studied, then the voltages used in these formulars are phase
voltages and not line voltages. The answers obtained for 𝑃𝑅 ,𝑄𝑅 ,𝑃𝑆 and 𝑄𝑆
will be one phase values only. They will need to be multiplied by three for 3
phase power flows,
12
• The results obtained by using these formulars will be the same as obtained by
the current conjugate power flow method.
• The one-line diagram used previously did not include powers being absorbed
by the loads A and B. When the circuit breakers to these loads are closed,
machines A and B must supply the required powers to these loads. Some of
the power (real and/or reactive) may need to be supplied across the
interconnector.
13
Example: Power station A and B are connected by means of an interconnector
6∠80° Ω per conductor, the local 3-phase loads:
At A 10 MW at pf of 0.8 lagging , At B 80 MW at pf of 0.75 lagging
The system line voltage is 33Kv and 80MW is to be received at B from
the interconnector.
14
Power station A System parameters Power station B
𝑃1 = 10𝑀𝑊 𝑉𝐿 = 33𝑘𝑉 𝑃2 = 80𝑀𝑊
𝑃𝑓 = 0.8 𝑙𝑎𝑔 𝑃 = 80𝑀𝑊 𝑃𝑓 = 0.75 𝑙𝑎𝑔
∅1 = 36.87° ∅ = 80° ∅2 = 41.41°
33𝑥103
𝑉𝑝ℎ = ∠𝛿
3
=𝑉𝑠 = 19.053𝑥103 ∠𝛿
= 𝑉𝑅 = 19.053𝑥103 ∠0°
80𝑀𝑊
𝑃𝑝ℎ = =26,667𝑀𝑊
3
Find 𝛿
|𝑉𝑅 |2
𝑉𝑅 |𝑉𝑆 | cos(∅)
We know that 𝑃𝑅 = 𝑍
- cos ∅
𝑍
3 2 3 2
6 (19,053 𝑋 10 ) cos(80−𝛿) (19.053 𝑋 10 )
= 26.667𝑋10 = - cos 80°
6 6
15
26.667 𝑋 106 = 60.503 𝑋 106 cos 80° − 𝛿 − 10.506 𝑋 106
80° − 𝛿 = 52.092°
𝛿 = 80 − 52.092 = 27.91°
Now find 𝑄𝑅 and 𝑄𝑆
𝑉𝑅 |𝑉𝑆 | sin(∅−𝛿 ) |𝑉𝑅 |2
𝑄𝑅(𝑝ℎ) =
|𝑍|
- sin ∅
|𝑍|
(19,053 𝑋 103 )2 sin(80° −27.91° ) (19.053 𝑋 103 )2
- sin 80°
6 6
16
𝑄𝑅(𝑝ℎ) = −11.848𝑀𝑉𝐴𝑅𝑆
𝑄𝑅(3𝑝ℎ) = −35,545𝑀𝑉𝐴𝑅𝑆 (Supplies)
|𝑉𝑆 |2 𝑉𝑅 |𝑉𝑆 | sin(∅+𝛿)
𝑄𝑅(𝑝ℎ) = sin ∅-
|𝑍| |𝑍|
(19,053 𝑋 103 )2 sin(80° ) (19.053 𝑋 103 )2 sin(80° +27.91° )
- = 2.013𝑀𝑉𝐴𝑅𝑆
6 6
𝑄𝑆(3𝑝ℎ) = 6,038𝑀𝑉𝐴𝑅𝑆 (Supplies)
|𝑉𝑆 |2 𝑉𝑅 |𝑉𝑆 | cos(∅+𝛿)
𝑃𝑆 = cos ∅-
|𝑍| |𝑍|
(19,053 𝑋 103 )2 cos(80° ) (19.053 𝑋 103 )2 cos(80° +27.91° )
- = 29.112𝑀𝑊
6 6
𝑃𝑆(3𝑝ℎ) = 87.337𝑀𝑊
𝑄𝑙𝑜𝑎𝑑𝑠
𝑄1 = 𝑃1 tan 𝑄1 = 10𝑋106 tan 36.87° = 7.5𝑀𝑉𝐴𝑅𝑆 𝑙𝑜𝑎𝑑 𝐴 𝑎𝑏𝑠𝑜𝑟𝑏𝑠
𝑄2 = 𝑃2 tan 𝑄2 = 80𝑋106 tan 41.41° = 70.554𝑀𝑉𝐴𝑅𝑆 𝑙𝑜𝑎𝑑 𝐴 𝑎𝑏𝑠𝑜𝑟𝑏𝑠
17
𝑃𝐴 = 𝑃1 + 𝑃𝑆 = 10𝑀𝑊 + 87.336𝑀𝑊 = 97.336𝑀𝑊𝑠𝑢𝑝𝑝𝑙𝑖𝑒𝑠
𝑄𝐴 = 𝑄1 + 𝑄𝑆 = 7.5𝑀𝑉𝐴𝑅𝑆 + 6.039𝑀𝑉𝐴𝑅𝑆 = 13.539 𝑀𝑉𝐴𝑅𝑆 𝑠𝑢𝑝𝑝𝑙𝑖𝑒𝑠
𝑃𝐵 = 𝑂𝑀𝑊
𝑄𝐵 = 𝑄𝑅 + 𝑄2 = 35,545𝑀𝑉𝐴𝑅𝑆 + 70,554𝑀𝑉𝐴𝑅𝑆 = 106.099 𝑀𝑉𝐴𝑅𝑆
18
Thank you
19