M135C

NUMERICAL UNDER / OVER VOLTAGE


PROTECTION
TYPICAL CONNECTION DIAGRAM FOR M135C:

TERMINALS VIEWED FROM REAR SIDE:


M135C NUMERICAL UNDER / OVER VOLTAGE PROTECTION

FEATURES: • Secondary voltage values display.

Three phase under / over voltage protection • Reset time feature for inverse
and one residual (over) voltage protection characteristics.

• Over / under / residual protection have • Two group of protection settings.


two stages of protection - Stage 1 and
• External blocking feature.
Stage 2.
• Fuse failure protection.
• Inverse as well as definite time
• Configurable Digital inputs.
Characteristics for over, under and
residual voltage. • Configurable Digital outputs.

• User Friendly settings with Password • Configurable dual color LED


Protection. indications.

• 16 Characters 2 Line LCD display with • Feeder identification.

backlight - alphanumeric display • Relay test facility.

• Same input will accept wide secondary • 100 Fault records with time stampings.
voltage - voltage ratings selectable by
• 100 Event records with time stampings.
software.
• RS485 and USB port Communication
• Same relay for 24V, 30V, 48V or
with MODBUS or IEC 60870 - 5 - 103
110Vdc auxiliary supply.
protocol.
• Same relay for 110V or 220 Vdc
INTRODUCTION:
auxiliary supply.
Megawin’s M135C is a numerical four
• Residual voltage input is tuned for pole voltage protection relay with
fundamental. communication can be used to protect
substation, high voltage distribution and
• Self Monitoring.
transmission network. Relay with suitable
• Primary (voltage) Metering. rating is also available for low voltage system.

Page 3 of 16
Megawin Switchgear Private Limited M135C Numerical Under / Over voltage protection
As M135C contains neutral displacement The relay has pluggable screw type
protection also, which can be very well used terminals in the rear side. This facility makes
for capacitor bank protection and unearthed maintenances and the wiring easy with simple
system protection. The relay has user friendly tools and the relay can be taken out by
Human machine interface with five push unplugging the terminals without removal of
buttons and LCD display. wires.

DESCRIPTION: Self monitoring:

The relay continuously measures the The relay has continuous self
three phase voltages and the residual voltage monitoring facility by means of watchdog
of the protected system by sampling the input timer inside the controller. An output contact
by means of analog to digital converter. are configurable as well as a LED in the front
panel top of the LCD is provided for self
The micro-controller accepts the
monitoring. The settings are stored in non
setting by means of the push switches
volatile memory and the same are password
provided on the front and find out multiples of
protected.
set voltage signal and elapse the required time
as per the set characteristics before operating Ranges of input:
final trip miniature relays. Each input voltage
The input terminal remains same for
is also displayed on 16 x 2 LCD display for
phase to phase or phase to neutral connection
metering.
with the phase to phase ratings starting from
The relay has two stages of protection 100 to 125V AC. And this rating is settable in
settings for each under / over / residual voltage the front with password protection.
protection. Stage 1 protection operates with
Password protected:
inverse characteristics or definite time delay.
The stage 2 protection operates with definite The relay is password protected with
time delay. four alpha numeric characters. This will
prevent unauthorized access to setting
The relay has easy man made interface
changes, as well as testing the output relays.
with 16 × 2 alpha numeric LCD display with 5
push buttons with LED for navigating various
displays for settings / readings.

Page 4 of 16
Megawin Switchgear Private Limited M135C Numerical Under / Over voltage protection
Group of protection settings: Trip information:

Different settings for protection may be The relay will display all phase
required for different time or in different voltage values, group, the stage, characteristic
operational situation in a substation. This responsible for trip along with date and time at
relay has got two different settings group G1 the time of fault. In addition to this trip
or G2, but any one will be active at a time. information and TRIP LED’s also will glow
Any of the configurable digital input may be along with configured LED’s for the particular
used to change active group to G2. Active function.
Group can be set by manually also. Fault records with time stampings:

It is possible to edit one group when Which protection elements are


the relay protection algorithms operate with responsible for trip, all phase and residual
another active group. voltages at the time of trip, along with date

Blocking Feature: and time (with resolution of five milliseconds)


at the time of trip are stored in nonvolatile
M135C is having blocking function
memory. Last hundred such fault records are
Any of the elements such as under voltage
always available in the relay itself. This will
stage 1 & 2, over voltage stage 1 & 2, residual
help for analysis purpose.
voltage stage 1 & 2 or peer digital input
functions can be blocked through (configured) Event records with time stampings:

digital input.. The relay events along with date and

Fuse failure protection: time, with resolution of five milliseconds at


the time of event present are stored in
M135C is provided with three phase
nonvolatile memory. Last hundred such event
secondary PT fuse failure protection by using
records are always available in the relay itself.
three digital inputs .In this mode fuse failure is
detected by connecting digital input across the Configurable Digital inputs:

fuses. Configuring same for AC operation, for Three digital inputs are available with
fuse failure any of the output relay / LED can optical isolation. This can be set for accepting
be configured. AC or DC input. While on DC, this will accept
the input to the same range as auxiliary supply.
These inputs can be configured for,

Page 5 of 16
Megawin Switchgear Private Limited M135C Numerical Under / Over voltage protection
• Fuse failure Protection. Any one or all the output relays can be
programmed for Latch (hand reset contact).For
• Trip circuit supervision.
same function multiple relays (contacts) can be
• Group change. programmed.

• Blocking. Configurable LED indications:

• Reset the latched Relay / LED's. There are eight LEDs which can be
configured as per requirement. These LEDs
• These inputs can also be configured to
are twin color LEDs (red or yellow). Any
just initiate a timer either on energising
color can be configured for any protection
(pickup) or on releasing (drop-off). The
functions or for digital inputs.
time range is from zero milliseconds,
up to 24 hours. There is separate non configurable
LED indication for protection healthy and for
Example: 5minutes timer to re energise the
protection start / trip function. These two
capacitor bank feeder is easily possible with
LEDs along with one for setting purpose are
this feature.
fixed indications available in the relay which
Configurable Digital outputs:
are additions to eight configurable LEDs.
Totally six digital outputs in the form
Metering:
of miniature relay contacts are available. See
M135C will show all three phase and
the diagram for number of normally open or
residual of primary as well as secondary
closed or changeover contacts in each relay
voltage values.
output. These can be configured for,
Feeder identification:
• Any protection functions for trip or
alarm. Sixteen alpha numerical type values
can be set by push buttons in the front. This
• Protection Faulty alarm.
may be used to identify the feeder.
• Trip circuit supervision alarm.
Relay / LED test facility:
• Fuse failure protection.
Each output relay can be tested to
• Digital input repeat relay with / without check whether it is configured and operates its
time delay. contact output. Dual colour LEDs also can be
tested for its healthiness and configuration.
Page 6 of 16
Megawin Switchgear Private Limited M135C Numerical Under / Over voltage protection
COMMUNICATION: • Password security.

This relay is suitable for • Print / file facility for settings / fault
communication with external SCADA or records.
remote HMI the voltage values and fault /
From Computer to the relay:
event details and set the setting or reset /relay
operation command from remote. Front USB • Password.

port and rear connected RS485 port with • Settings


MODBUS or IEC 60870 - 5 - 103 protocol is
• Command to operate any output relay.
used for communication. Megawin make
(Ex: Remote close / remote trip).
software M135C PC STUDIO is available on
request to communicate with the relay. • Time synchronization.

From relay side to computer: • Reset command to reset the relay.

• Settings. Protocol:

• Fault data - Primary voltage values of • MODBUS - RTU or IEC 60870 - 5 - 103
all the phases and residual at the time of
Physical Layer:
trip with at which relay tripped, group,
with time stampings. • RS485 Rear port and USB front port.

Application software:
• Primary voltage values.
• Megawin‘s M135C PC STUDIO
• Event records.

At Computer (with supplied software


M135C PC studio)

• Fault record display.

• Primary / Secondary values of meter


display.

• Settings can be copied and send back to


other similar Relays.

• New settings can be entered and sent to


relay.
Page 7 of 16
Megawin Switchgear Private Limited M135C Numerical Under / Over voltage protection
TECHNICAL SPECIFICATIONS:
S. Parameters Values S. Parameters Values
NO. NO.
1. Type: M135C Inverse
2. Energizing input: characteristics
For Phase: (IEC standard)
Primary 0.1 to 600 kV AC in Where,
(Ph - Ph) step of 0.1 kV
( Formula V = Fault voltage,
Common for both Vs = Voltage setting,
Rated Voltage 100 to 125V AC in over & residual
Tm = Time
(Secondary) step of 1V. voltage protection)
multiplier.
(Ph - Ph) (Vn) (375-465 Vac is also
Under voltage
available on request)
Stage 1 OFF, 10.0 % to 120.0
For Residual:
% of Vn in step of 0.1
Primary 0.1 to 600 kV AC in
%
(Ph - Ph) step of 0.1 kV
Inverse
Rated Voltage 57.0 to 75.0 V AC characteristics
(Secondary) in step of 0.1 V (IEC standard)
(Each Ph) Where,
(Vgn) V = Fault voltage,
( Formula for
Frequency 50 Hz Vs = Voltage setting,
both under voltage
AC burden 110V AC = ≤ 1 VA Tm = Time
protection)
per phase multiplier.
Voltage withstand Time multiplier 0.50 to 100.0 in step
Continuous 275V setting* of 0.01
For 1 minutes 450V Definite time DTL
3. Auxiliary supply: characteristics*
Rated auxiliary 18V to 135V DC or Operating time 0.00s to 600.0s,
for DTL for 0.00 to 99.99s in step
supply 88V to 280VDC
stage 1* of 0.01s and
Power 6 watts (Quiescent)
remaining values are
Consumption and 10 watts (Max)
in step of 0.1s
4. Protection Setting :
Over voltage
Over voltage Stage 2 OFF, 80.0 % to
Stage 1 OFF, 80.0 % to 180.0 % 180.0 % of Vn in
of Vn in step of 0.1 % step of 0.1 %
Residual Voltage Residual Voltage
Stage 1 OFF, 5.0 % to 40.0% Stage 2 OFF, 5.0 % to 40.0%
of Vgn in step of 0.1% of Vgn in step of 0.1%

Page 8 of 16
Megawin Switchgear Private Limited M135C Numerical Under / Over voltage protection
S. Parameters Values S. Parameters Values
NO. NO.
Under voltage Operating Time for Definite time
Stage 2 OFF, 10.0 % to 120.0% At 1.5 × Vs ± 1% or ± 35ms
of Vn in step of 0.1% Metering
Operating time 0.00s to 600.0s, At 2V to 250V ± 1% or ± 200mV
for DTL for 0.00 to 99.99s in step 6. Fault record
stage 2* of 0.01s and Number of 100
remaining values are records
in step of 0.1s Record time Five millisecond
Reset time resolution with time and
Range* 0.50 to 100.0 in step calendar information
of 0.01 7. Digital Input:
* Independently settable for Over & Residual Number of 3
voltages Digital Inputs
5. Accuracy (at reference condition) : Rated Digital 18V to 135V DC or
General: IEC 60255 - 127 Input supply 88V to 280VDC
Pickup value Digital input Hours: 00 to 23hr in
Over & Residual 104 % of setting pick up delay step of 1hr.
voltage stage 1 ± 4% or ± 200mV Minutes: 00 to 59min
Over & Residual 100 % of setting in step of 1min.
voltage stage 2 ± 5% or ± 200mV Seconds: 00 to 59sec in
Under voltage 96 % of setting step of 1sec.
stage 1 ± 4% or ± 200mV Milliseconds: 000 to
Under voltage 100 % of setting 990ms in step of 10ms.
stage 2 ± 5% or ± 200mV Digital input Hours: 00 to 23hr. in
drop off delay step of 1hr
Repeatability ±1%
Minutes: 00 to 59min
Drop off
in step of 1min.
Over & Residual ≥ 95 % of
Seconds: 00 to 59sec in
voltage stage 1 & 2 operating voltage
step of 1sec.
Under voltage ≤ 105 % of Milliseconds: 000 to
stage 1 & 2 operating voltage 990ms in step of 10ms.
Repeatability ±1% 8. Event Record:
Operating Time for Inverse Number of 100
characteristics records
Timing ± 1% or ± 200mV Input Record time Five millisecond
Voltage variations resolution with time and
Repeatability ± 1 % calendar information

Page 9 of 16
Megawin Switchgear Private Limited M135C Numerical Under / Over voltage protection
S. Parameters Values S. Parameters Values
NO. NO.
9. Communication: Common start / trip 1
RS485 / USB (Independently settable) (Yellow / Red)
Communication 1200, 2400, 4800, Setting LED (Red) 1
Baud Rate 9600 , 19200 Configurable LEDs 8
Communication NONE, EVEN, (Yellow / Red)
Parity ODD 12. Environmental withstand :
Communication 1 or 2 Temperature IEC60068-2-1/2
Stop Bits Operating range -10°C to +55°C
Device ID 1 to 247 Storage range -25°C to +70°C
(common for both Variation over range ≤ 5 %
RS485 & USB) Humidity IEC60068-2-3
10. Output contacts : Operating test 40°C and 95 % RH
Total number of 6 Transient over voltage IEC60255-5
configurable output 5kV 1.2/50µs 0.5J
relay Insulation IEC60255-5
2 NO contact relay 1 2kV rms for 1 min
Change over contact 4 High frequency disturbance IEC60255-
relay 22-1 Class III
1 NC contact relay 1 Electrostatic discharge IEC60225-22-2
Contact ratings Class III
Carry 5A ac or dc Radio frequency interference
continuously IEC60255-22-3 Class III
Make and carry (Limit V ≤ 300V) Fast transient IEC60255-22-4 Class III
For 0.2 sec 30A dc Vibration IEC60255-21-1 Class I
Break (Limit ≤ 5A or ≤ 300volts) Shock & bump IEC60255-21-2 Class II
DC resistive 75W
DC inductive 30W at L/R ≤
40ms
11. Indication (dual color LEDs)
Total number of 11
LED
Protection healthy 1
(Red / Green)

Page 10 of 16
Megawin Switchgear Private Limited M135C Numerical Under / Over voltage protection
TYPICAL APPLICATIONS

Page 11 of 16
Megawin Switchgear Private Limited M135C Numerical Under / Over voltage protection
Page 12 of 16
Megawin Switchgear Private Limited M135C Numerical Under / Over voltage protection
Page 13 of 16
Megawin Switchgear Private Limited M135C Numerical Under / Over voltage protection
Page 14 of 16
Megawin Switchgear Private Limited M135C Numerical Under / Over voltage protection
Page 15 of 16
Megawin Switchgear Private Limited M135C Numerical Under / Over voltage protection
CASE: Flush mounting

CUTOUT FOR MOUNTING:

• Bezel dimension 178 mm × 178 mm

• Maximum depth inside the panel 190 mm

• All dimensions are equidistant from centre


line

ORDERING INFORMATION:

- Type : M135C

- Rated Voltage (AC)

- Auxiliary supply range


- Protocol
- Communication software if required.

QUALIFICATION:

ISO 9001 – 2000

Information provided in this catalog is subject to change due to continuous


improvements in the design

Page 16 of 16
Megawin Switchgear Private Limited M135C Numerical Under / Over voltage protection