Daikin
Contents [hide]
Main page 1 Connecting to Daikin VRV System
2 Setting Indoor Group Address
Products
3 Reading Thermostat ambient temperature instead of return air
CoolMasterNet
4 KRP928A2S Auto Mode Control
CooLinkNet
5 KRP928xxx Limitations
CoolPlug + Hub
ThermoPad
6 Daikin Self-diagnostic Malfunction (Error) Codes

Tools

What links here Connecting to Daikin VRV System


Related changes System with single Outdoor Unit
Special pages
Printable version
Permanent link
Page information

System with multiple Outdoor Units

Setting Indoor Group Address


Indoor Group Address (centralized address) is required for proper CoolMasterNet operation. Without Group Address Indoor unit is not visible
and can not be controlled by CoolMasterNet or any other Daikin equipment. Group Address is set with wired remote controller. Here is a
simple sequence of operations for Daikin BRCE61 wired remote controller to set Group Address.

Press and hold Cancel button for a few seconds

Scroll down to Group No. setting function and press Menu/Enter button

Program Group Address and then press Menu/Enter to save address

Remember if Indoor unit can not see a CoolMasterNet you won't have the Group Address menu option. So make sure the
CoolMasterNet is wired to F1 F2 HVAC line and powered.

Reading Thermostat ambient temperature instead of return air


CoolMasterNet will read ambient temperature measured by Thermostat - local wired controller (like BRC1E72) if following field settings had
being done on Thermostat:
Setting 10-2 = 03 - Only the thermostat thermistor will be utilized by Indoor unit.
Setting 10-5 = 02 - Room temperature value reported to CoolMasterNet by Indoor is taken from Thermostat

KRP928A2S Auto Mode Control


To enable proper Auto Mode control from CoolMasterNet of the Indoor Unit connected via KRP928A2S adapter, make sure to configure SW3
switch to GLO position:

KRP928xxx Limitations
This is taken from original Daikin document "Interface Adaptor for DIII-NET" :

The range of temperatures that can be set from the central controller is 18°C to 32°C in cooling and 14°C to 28°C in heating.
Fan operation cannot be selected from the central controller or wired remote controller.
Group control (i.e., control of multiple indoor units with a single remote controller) is not available.
Monitoring is not available of the thermo status, compressor operating status, indoor fan operating status, electric heater, or humidifier
operating status.
Forced thermo off, filter sign display and reset, fan direction and speed settings, air conditioning fee management, energy savings
instructions, low-noise instructions, and demand instructions cannot be made.

Daikin Self-diagnostic Malfunction (Error) Codes


Cool
Models Automation
Encoding
Malfunction Problem Supposed Sky Pac Chil Fan
Code Description Causes RA VRV HRV HEX DEC
Air kage ler Coil
External protection device
A0 External protection device connected to the terminal strip T1- V V V 0x10
activated T2 of indoor unit is activated

Malfunction of indoor unit Defective indoor unit PCB


A1 V V V V V V 0x11
PCB External factor (Noise etc.)
Drain clogging, upward slope, etc
Drain Level Control System Defective drain pump
A3 V V V V V 0x13
Abnormality Defective float switch or short
circuit connector
Shortage of water volume
Malfunction of freezing Low water temperature setting
A4 V V V V V V 0x14
protection Defective water temperature
thermistor
Clogged air filter of indoor unit and
High pressure control in
short circuit
A5 heating, freeze-up V V V V 0x15
Defect of indoor unit heat
protection control in cooling
exchanger thermistor
Broken wires in, short circuit of, or
disconnection of connectors from
A6 Malfunction of fan motor the fan motor harness V V V V V 0x16
Defective fan motor
Defective indoor unit PCB
Defective swing fl ap motor
Defective indoor unit PCB
I Malfunction of swing flap
A7 Defective connection cable V V 0x17
motor
Defective airflow direction adjusting
n
fl ap-cam
Malfunction of power Defective power supply voltage
d
A8 supply or AC input Defective connection on signal line V V V 0x18
overcurrent Defective wiring
o
Defective electronic expansion
o Malfunction of electronic valve coil
A9 V V V V V 0x19
expansion valve Defective indoor unit PCB
r Defective relay cables
AA Heater overheat 26WH is activated V V 0x1A
Humidifi er unit (optional
accessory) leaking
Malfunction of a humidifi er
AF Defective drain piping (upward V V V 0x1F
system
slope, etc.)
Defective indoor unit PCB
U
Defect of dust collecting element
Stained insulator part
n Malfunction of dust
AH Defect of high voltage power V V V V 0x1B
collector of air cleaner
supply unit
i
Defect of indoor unit PCB

t The capacity setting adaptor was


Malfunction of capacity
AJ not installed when replacing PCB. V V V 0x1D
setting(Indoor unit PCB)
Defective indoor unit PCB
Failure of transmission
Defective connection of the
С1 (between indoor unit PCB V V 0x21
connector between indoor unit PCB
and sub PCB)
Malfunction of liquid pipe Defective thermistor for liquid pipe
С4 thermistor for heat Defective indoor unit PCB V V V V V V V 0x24
exchanger Defective connector contact
Malfunction of gas pipe Defective thermistor for gas pipe
C5 thermistor for heat Defective indoor unit PCB V V V V V 0x25
exchanger Defective connector contact
Defective fan PCB
Malfunction of fan motor Defective connection of capacity
C6 V V 0x26
sensor or fan control driver setting adaptor
Field setting error
Front panel driving motor Defective front panel driving motor
C7 V 0x27
fault Defective limit switch
Defective thermistor for suction air
Malfunction of suction air
C9 Defective indoor unit PCB V V V V V V 0x29
thermistor
Defective connector contact
Defective thermistor for discharge
Malfunction of discharge air air
CA V V V V 0x2A
thermistor Defective indoor unit PCB
Defective connector contact
Malfunction of humidity Defective humidity sensor
CC V V V 0x2C
sensor system Defective connector contact
Defective room temperature
Room temperature
thermistor in remote controller
CJ thermistor in remote V V V V V 0x2D
Defective remote controller PCB
controller abnormality
External factor (Noise etc.)
Protection device connected to
Protection devices
outdoor unit PCB actuated
E0 activated V V V 0x30
Defective protection device
(unifi ed)
connector contact
Defective outdoor unit PCB
E1 Defective outdoor unit PCB Defective connection of inside/ V V V V V 0x31
outside relay wires
Dirty outdoor unit heat exchanger
Actuation of high pressure
Defective high pressure switch
E2 switch V V V V 0x33
Clogged refrigerant piping
(HPS)
Defective connector contact
Dirty outdoor unit heat exchanger
System No.1
Shortage of water volume
Actuation of high pressure
E3 Clogged refrigerant piping V 0xE33
switch
Defective connector contact
(HPS)
Defective HPS
Abnormally drop in low pressure
Actuation of low pressure
Defective low pressure sensor
E4 switch V V V V 0x34
Defective outdoor unit PCB
(LPS)
Defective connector contact
Inverter compressor lock
High differential pressure
Inverter compressor motor
E5 or Defective inverter PCB V V V V V 0x35
overheat UVW connection error

Defective connector contact

Defective compressor
STD compressor motor
E6 Defective control PCB V V V V 0x36
overcurrent/lock
The stop valve is not opened
Defective electronic expansion
System No.1 Compressor valve
E6 V 0x36
overcurrent Shortage of refrigerant amount
Defective compressor
Fan motor failure
Neglect to connect or defective
Malfunction of outdoor unit connection of harness/
E7 fan connector between the fan motor V V V V V 0x37
motor system and the PCB
Fan does not rotate due to foreign
matters caught in it
Defective compressor
Defective inverter main circuit
Overcurrent of inverter
E8 capacitor V V 0x38
compressor
Defect of outdoor unit PCB
Defect of power transistor
Disconnection of connectors from
Malfunction of electronic electronic expansion valves
E9 expansion Defective electronic expansion V V V V 0x39
valve coil valve coil
Defective outdoor unit control PCB
Defective four way valve
Malfunction of four way
Shortage of gas
EA valve or V 0x3A
Defective outdoor unit PCB
cool/heat switchin
Defective thermistor
Cooling water temperature
Malfunction of entering
abnormality
EC water V 0x3C
Defective outdoor unit PCB
temperature
Defective thermistor
Defective discharge pipe thermistor
Malfunction of discharge Abnormal discharge pipe
F3 pipe temperature V V V V V 0x53
temperature Defective outdoor unit control PCB
Defective connector contact
Refrigerant overcharged
Disconnection of heat exchanger
deicer thermistor
Abnormal high pressure or Disconnection of outdoor air
F6 V V V V 0x56
refrigerant overcharged thermistor
Disconnection of liquid pipe
temperature thermistor
Defective outdoor unit PCB
Malfunction of sensor Harness is disconnected, or
H0 system of defective connection V V 0x40
compressor Defective PCB
Malfunction of room
temperature Defective limit switch
H1 V V 0x41
sensor or humidifi er unit Defective damper
damper

Defective high pressure switch


Malfunction of high
Broken wire
H3 pressure switch V V V V V 0x43
Defective outdoor unit PCB
(HPS)
Defective connector contact
Defective low pressure switch
Malfunction of low pressure
Broken wire
H4 switch V V V 0x44
Defective outdoor unit PCB
(LPS)
Defective connector contact
Malfunction of compressor Defect of compressor motor
H5 motor overload thermistor V V 0x45
overload thermistor Defective connector contact
Faulty contact of compress or
Malfunction of position
cable
H6 detection V V V 0x46
Defective compressor
sensor
Defective outdoor unit PCB
Abnormal signal from fan motor
(Circuit failure)
Malfunction of outdoor unit
Disconnection/Short circuit in fan
H7 fan V V V V 0x47
motor leads or
motor signal
disconnection of connector
Defective inverter PCB
Defective power transistor
Malfunction of compressor
Defective reactor
H8 input V V 0x48
Faulty wiring of inverter system
(CT) system
Defective outdoor unit PCB
Defective connection of thermistor
Malfunction of outdoor air
H9 Defective outdoor unit PCB V V V V V 0x49
thermistor
Defective outdoor air thermistor
Defective connection of thermistor
Malfunction of (hot) water Defective outdoor unit PCB
HC V V V 0x4C
temperature thermistor Defective water temperature
thermistor
Thermal storage group defective
Alarm in thermal storage wiring
HF unit or Defective setting V 0x4F
storage controller Excess of thermal storage tank
numbers
Low water level
Low water level
Defective switch setting
Defective switch setting
HJ Water level detecting V V V V 0x4D
Water level detecting sensor failure
sensor failure
Defective connector contact
Defective connector contact
Defective pressure sensor
Malfunction of pressure connector contact
J1 V V V 0x61
sensor Defective pressure sensor
Defective outdoor unit PCB
Malfunction of current Defective current sensor
J2 sensor of Defective compressor V V V V V 0x62
compressor Defective outdoor unit PCB
Malfunction of discharge Defective connection of thermistor
J3 pipe Defective discharge pipe thermistor V V V V V 0x63
thermistor Defective outdoor unit PCB
Malfunction of low pressure
Defective connection of thermistor
equivalent saturated
J4 Defective thermistor V V 0x64
temperature
Defective outdoor unit PCB
sensor system
Defective connection of thermistor
O Malfunction of suction pipe
J5 Defective suction pipe thermistor V V V V 0x65
thermistor
Defective outdoor unit PCB
u
Defective connection of thermistor
Malfunction of heat
Defective heat exchanger
t J6 exchanger V V V V V 0x66
thermistor
thermistor
Defective outdoor unit PCB
d
Defective connection of thermistor
Malfunction of thermistor
o J7 Defective liquid pipe thermistor V V V V 0x67
(Refrigerant circuit
Defective outdoor unit PCB
o Defective connection of thermistor
Malfunction of thermistor
J8 Defective liquid pipe thermistor V V V V V 0X68
(Refrigerant circuit)
r Defective outdoor unit PCB
Defective connection of thermistor
Malfunction of thermistor
J9 Defective gas pipe thermistor V V V V V 0x69
(Refrigerant circuit)
Defective outdoor unit PCB
U
Defective connector contact
Connection of low pressure sensor
n Malfunction of high
in mistake for high
JA pressure V V V V 0x6A
pressure sensor
i sensor
Defective high pressure sensor
Defective outdoor unit PCB
t
Defective connector contact
Connection of high pressure
Malfunction of low pressure sensor in mistake for low
JC V V V V 0x6C
sensor pressure sensor
Defective low pressure sensor
Defective outdoor unit PCB
Malfunction of oil pressure Defective connector contact
JE sensor Defective sub-tank thermistor V 0x6E
or sub-tank thermistor Defective outdoor unit PCB
Malfunction of oil level Defective connector contact
sensor or Defective heat exchanger
JF V 0x6F
heating heat exchanger thermistor
thermistor Defective outdoor unit PCB
Shortage of power supply capacity
Malfunction of inverter
L0 Defective power transistor V V V V V 0x70
system
Defective outdoor unit PCB
Defective compressor wiring
Defective outdoor unit fan motor
L1 Malfunction of inverter PCB V V V V 0x71
Blown fuse
Defective inverter PCB
Fin temperature rise due to short
circuit
El.compo. box temperature
L3 Defective outdoor unit fan motor V V V V 0x73
rise
Defective power transistor
Defective outdoor unit PCB

Malfunction of inverter Fin temperature rise due to short


L4 radiation fi n circuit V V V V V 0x74
temperature rise Defective fi n thermistor

Defective compressor coil (such as


wiring disconnection or
nverter instantaneous
insulation failure)
L5 overcurrent V V V V V 0x75
Compressor startup failure
(DC output)
(mechanical lock)
Defective inverter PCB
Overcharge of refrigerant amount
Inverter instantaneous
Shortage of power supply capacity
L6 overcurrent V V V V V 0x76
Defective compressor
(AC output)
Defective inverter unit
Compressor overloaded
Wiring disconnection in
Malfunction of overcurrent
compressor coil
L8 inverter V V V V V 0x78
Disconnection of compressor
compressor
wiring
Defective inverter PCB
The stop valve is not opened
Defective compressor
Malfunction of inverter
Error in wire connections to
compressor
L9 compressor V V V V V 0x79
startup error (Stall
Large differential pressure before
prevention)
compressor startup
Defective inverter PCB
Defective power transistor
Malfunction of power
LA Defective compressor V V 0x7A
transistor
Defective inverter PCB
Defective connection between the
inverter PCB and the
Malfunction of transmission control PCB
LC between control and External factors (e.g. noise) V V V V V 0x7C
inverter PCB Defective inverter compressor
Defective control PCB
(transmission block)
Malfunction of central
Defective central remote controller
M1 remote V V V V V 0xA1
PCB
controller PCB
Other centralized control power
Malfunction of transmission disconnection
between optional Centralized control reset switch ON
M8 V V V V V 0xA8
controllers for Defective transmission wiring
centralized control Central remote controller address
change
Improper combination of optional
controllers for centralized
Improper combination of
control
optional
MA More than one master controller is V V V V V 0xAA
controllers for centralized
connected
control
Faulty setting of centralized control
Defect of centralized control
Address duplication,
Address duplication of central
MC improper V V V V V 0xAC
remote controller
setting
Shortage of refrigerant
Shortage of refrigerant
PO amount V V 0x80
Clogged refrigerant piping
(thermal storage unit)
Open phase
Interphase voltage imbalance
Power voltage imbalance
Defective capacitor in the main
P1 or 0x81
circuit
inverter PCB
Defective wiring in the main circuit
Defective inverter PCB
Automatic refrigerant The stop valve is not opened
P2 V V V V 0x82
charge operation stop Closed valve of refrigerant tank
Malfunction of thermistor in Defective connection of thermistor
P3 switch Defective reactor thermistor V V V V V 0x83
box Defective inverter PCB
Defective radiation fi n temperature
thermistor
Malfunction of radiation fi n
P4 Defective inverter PCB V V V V V 0x84
temperature sensor
Defective INV. compressor
Defective fan motor
Heat exchanger freezing
protection (Close the refrigerant cylinder. Start
P8 V V V 0x88
during automatic refrigerant again from step 1.)
charging
Defective fan motor
Malfunction of fan motor Defective outdoor unit PCB
P9 V 0x89
(humidifi er unit) Broken relay harness
Defective connector contact
Automatic refrigerant
P9 charge — V V V V 0x89
operation completed
Refrigerant cylinder during
Refrigerant cylinder of master unit
PA automatic refrigerant V V V 0x8A
is empty
charging
Defective heater unit
Broken wire of heater
PA Defective thermistor V 0x8A
(humidifi er unit)
Defective outdoor unit PCB
Refrigerant cylinder during
Refrigerant cylinder of slave unit 2
PC automatic refrigerant V V 0x8C
is empty
charging
Automatic refrigerant
PE charge — V V V 0X8E
operation nearly completed
Defective heater unit
Refrigerant cylinder during
Defective connector contact
PH automatic refrigerant V V V 0x8B
Defective thermistor
charging
Defective outdoor unit PCB
Capacity setting adaptor is not
Malfunction of capacity
installed
PJ setting V 0x8D
Improper capacity setting adaptor
(Outdoor unit PCB)
Defective outdoor unit PCB
Mis-matching of type of PCB
Improper combination
Improper (or no) fi eld setting after
PJ between V V V V 0x8D
replacing outdoor unit
inverter and fan driver
main PCB
Refrigerant shortage and
refrigerant clogging
(wrong piping)
U0 Shortage of refrigeran V V V V V 0x90
Defective thermistor
Defective low pressure sensor
Defective outdoor unit main PCB
Power supply reverse phase
Reverse phase, open
U1 T phase open phase V V V V V V V 0x91
phase
Defective outdoor unit PCB (A1P)
Malfunction of power Abnormal power supply voltage
U2 supply or Instantaneous power failure V V V V V V 0x92
instantaneous power failure Defective main circuit wiring
Check operation not
U3 executed or Check operation is not executed. V V V V V V V 0x93
transmission error
Short circuit in indoor-outdoor or
outdoor-outdoor
transmission wiring (F1 / F2), or
Malfunction of transmission wrong wiring
U4 between indoor and Outdoor unit power supply is OFF V V V V V V V 0x94
outdoor unit
System address does not match
Defective indoor unit PCB
Defective outdoor unit PCB

Transmission error between indoor


unit and remote
controller
Connection of 2 main remote
Malfunction of transmission
controllers (when using 2
between indoor unit and
U5 remote controllers) V V V V V V 0x95
remote
Defective indoor unit PCB
controller
Defective remote
controller PCB
Transmission error caused by
noise
Faulty wiring
Malfunction of transmission
U6 External factor (Noise etc.) V V V V 0x96
between indoor units
Defective indoor unit PCB
Connection error of transmission
wirings between outdoor
unit and external control adaptor
Malfunction of transmission
for outdoor unit
between outdoor units or
U7 Connection error of transmission V V V V V 0x97
outdoor
wirings between outdoor
storage unit
units
Defective outdoor
unit PCB
Transmission error between main
and sub remote
S Malfunction of transmission controller
U8 V V V V V V 0x98
y between remote controllers Connection between sub remote
s controllers
t Defective remote controller PCB
e Transmission error between other
m
indoor and outdoor units
Defective electronic expansion
Malfunction of transmission valve of other indoor unit
U9 (other Defective indoor unit PCB of other V V V V V 0x99
system) indoor unit
Improper connection of
transmission wiring between
indoor and outdoor unit
Wrong model connections
Defect of indoor/outdoor
Improper power supply
UA power V 0x9A
Wrong PCB connected
supply
Defective PCB
Excess of connected indoor units
Defective outdoor unit PCB
Mismatch of the refrigerant type of
Improper combination of
indoor and outdoor unit
UA indoor V V V V 0x9A
Setting of outdoor unit PCB was
and outdoor units
not carried out after
replacing to
spare PCB
Remote temperature Remote temperature setting wire
UA setting wire disconnection V 0x9A
disconnection Defective connector contact
Malfunction of setting of Address duplication of centralized
UC centralized control equipment V V V V V V 0x9C
control equipment address Defective indoor unit PCB
Transmission error between
optional controllers for
centralized control equipment and
indoor unit
Malfunction of transmission Connector for setting main
between indoor unit and controller is disconnected.(or
UE V V V V V V 0x9E
centralized control disconnection of connector for
equipment independent / combined
use changeover switch.)
Defective PCB for central remote
controller
Defective indoor unit PCB
Improper connection of
transmission wiring between
indoor-outdoor units and outdoor-
UF System is not set yet outdoor units V V V V 0x9F
Failure to execute check operation
Defective indoor unit PCB
Stop valve is not opened
Improper connection of
transmission wiring between
indoor-outdoor units and outdoor-
UH Malfunction of system V V V 0x9B
outdoor units
Defective indoor unit PCB
Defective outdoor unit PCB
Malfunction of transmission Defect of accessory devices
UJ V V V V V 0x9D
(accessory device) Faulty wiring
Actuation of external protection
External protection device
device
60 activated (Heat reclaim V
Defective output signal wiring
ventilator)
Defective control PCB
Malfunction of indoor air Defective connector contact
64 thermistor Defective indoor air thermistor V
(Heat reclaim ventilator Defective control PCB
Malfunction of outdoor air Defective connector contact
65 thermistor (Heat reclaim Defective outdoor air thermistor V
ventilator) Defective control PCB
Defective connector contact
Malfunction of damper
Defective limit switch
6A system V
Defective damper motor
(Heat reclaim ventilator)
Defective control PCB
Shortage of refrigerant amount
System No. 2
70 Defective connector contact V
Compressor overheat
Leakage of four way valve
Shortage of refrigerant amount
System No. 2
71 Short circuit V
Compressor overcurrent
Defective compressor

Defective fan motor connector


System No. 2 contact
72 V
Fan motor overcurrent Defective fan motor
Defective PCB
Dirty heat exchanger
System No. 2
Shortage of water volume
Actuation of high pressure
73 Clogged refrigerant piping V
switch
Defective connector contact
(HPS)
Defective HPS
System No. 2 Clogged refrigerant piping
Actuation of low pressure Defective connector contact
74 V
switch Shortage of gas
(LPS) Defective LPS
System No. 2 Defective connector contact
75 Malfunction of low pressure Defective low pressure sensor V
sensor Defective PCB
System No. 2
Defective connector contact
Malfunction of high
76 Defective high pressure sensor V
pressure
Defective PCB
sensor
System No. 1 Defective relay contact
77 V
Malfunction of fan inter lock Broken wire
System No. 2 Defective relay contact
78 V
Malfunction of fan inter lock Broken wire
System No. 2
Defective current sensor
Malfunction of compressor
7A Defective compressor V
current
Defective outdoor unit PCB
sensor
System No. 2
Cooling water pump interlock
7C Malfunction of pump inter V
actuated
lock
Defective connector contact
Malfunction of entering
80 water Defective entering water V
temperature thermistor temperature thermistor

Malfunction of leaving
water Defective connector contact
81 temperature thermistor or Defective leaving water V
drain temperature thermistor
pipe heater
System No. 1
Defective connector contact
O 82 Malfunction of refrigerant V
Defective refrigerant thermistor
t thermisto

h System No. 2
Defective connector contact
e 83 Malfunction of refrigerant V
thermistor Defective refrigerant thermistor
r
s
System No. 1
Defective connector contact
Malfunction of heat
84 Defective heat exchanger V
exchanger
thermistor
thermistor
System No. 2
Defective connector contact
Malfunction of heat
85 Defective heat exchanger V
exchanger
thermistor
thermistor
System No. 1
Malfunction of discharge Defective connecting connector
86 V
pipe Defective discharge pipe thermistor
thermistor
System No. 2 Shortage of gas
Malfunction of discharge Defective discharge pipe thermistor
88 V
pipe Defective connector contact
temperature Clogged refrigerant piping
Malfunction of brazed-plate Dirty heat exchanger
89 heat Shortage of refrigerant amount V
exchanger freezing Defective thermistor
System No. 2
Defective connector contact
Malfunction of leaving
8A Defective leaving water V
water
temperature thermistor
temperature thermistor
System No. 1
Defective connector contact
8E Malfunction of suction pipe V
Defective suction pipe thermistor
thermistor 1 for heating
System No. 1
Defective connector contact
8F Malfunction of suction pipe V
Defective suction pipe thermistor
thermistor 2 for heating
Three way valve malfunction
Abnormal hot water high
8H Defective thermistor V
temperature
Defect of water temperature setting
Abnormal chilled water
Shortage of water volume
90 quantity or V
Disconnection of AXP
abnormal AXP
Defective connector contact
91 Defective electronic V
expansion valve coil
System No. 2
Defective connector contact
92 Malfunction of suction pipe V
Defective suction pipe thermistor
thermistor

Malfunction of transmission
Defective fan unit PCB
(between heat reclaim
94 Defective connecting wire between V
ventilator
(1) and (2)
and fan unit)
System No. 1
95 Malfunction of inverter Defective fan inverter unit V
system
System No. 2
96 Malfunction of inverter Defective fan inverter unit V
system
Malfunction of thermal
97 Defective thermal storage unit V
storage unit
Malfunction of thermal
Actuation of thermal storage brine
98 storage V
pump overcurrent (OC)
brine pump
Malfunction of thermal
Low water level of thermal storage
99 storage
brine tank
brine tank

This page was last edited on 17 December 2020, at 10:05.