Main page 1 Connecting to Daikin VRV System
2 Setting Indoor Group Address
Products
3 Reading Thermostat ambient temperature instead of return air
CoolMasterNet
4 KRP928A2S Auto Mode Control
CooLinkNet
5 KRP928xxx Limitations
CoolPlug + Hub
ThermoPad
6 Daikin Self-diagnostic Malfunction (Error) Codes
Tools
Scroll down to Group No. setting function and press Menu/Enter button
Remember if Indoor unit can not see a CoolMasterNet you won't have the Group Address menu option. So make sure the
CoolMasterNet is wired to F1 F2 HVAC line and powered.
KRP928xxx Limitations
This is taken from original Daikin document "Interface Adaptor for DIII-NET" :
The range of temperatures that can be set from the central controller is 18°C to 32°C in cooling and 14°C to 28°C in heating.
Fan operation cannot be selected from the central controller or wired remote controller.
Group control (i.e., control of multiple indoor units with a single remote controller) is not available.
Monitoring is not available of the thermo status, compressor operating status, indoor fan operating status, electric heater, or humidifier
operating status.
Forced thermo off, filter sign display and reset, fan direction and speed settings, air conditioning fee management, energy savings
instructions, low-noise instructions, and demand instructions cannot be made.
Defective compressor
STD compressor motor
E6 Defective control PCB V V V V 0x36
overcurrent/lock
The stop valve is not opened
Defective electronic expansion
System No.1 Compressor valve
E6 V 0x36
overcurrent Shortage of refrigerant amount
Defective compressor
Fan motor failure
Neglect to connect or defective
Malfunction of outdoor unit connection of harness/
E7 fan connector between the fan motor V V V V V 0x37
motor system and the PCB
Fan does not rotate due to foreign
matters caught in it
Defective compressor
Defective inverter main circuit
Overcurrent of inverter
E8 capacitor V V 0x38
compressor
Defect of outdoor unit PCB
Defect of power transistor
Disconnection of connectors from
Malfunction of electronic electronic expansion valves
E9 expansion Defective electronic expansion V V V V 0x39
valve coil valve coil
Defective outdoor unit control PCB
Defective four way valve
Malfunction of four way
Shortage of gas
EA valve or V 0x3A
Defective outdoor unit PCB
cool/heat switchin
Defective thermistor
Cooling water temperature
Malfunction of entering
abnormality
EC water V 0x3C
Defective outdoor unit PCB
temperature
Defective thermistor
Defective discharge pipe thermistor
Malfunction of discharge Abnormal discharge pipe
F3 pipe temperature V V V V V 0x53
temperature Defective outdoor unit control PCB
Defective connector contact
Refrigerant overcharged
Disconnection of heat exchanger
deicer thermistor
Abnormal high pressure or Disconnection of outdoor air
F6 V V V V 0x56
refrigerant overcharged thermistor
Disconnection of liquid pipe
temperature thermistor
Defective outdoor unit PCB
Malfunction of sensor Harness is disconnected, or
H0 system of defective connection V V 0x40
compressor Defective PCB
Malfunction of room
temperature Defective limit switch
H1 V V 0x41
sensor or humidifi er unit Defective damper
damper
Malfunction of leaving
water Defective connector contact
81 temperature thermistor or Defective leaving water V
drain temperature thermistor
pipe heater
System No. 1
Defective connector contact
O 82 Malfunction of refrigerant V
Defective refrigerant thermistor
t thermisto
h System No. 2
Defective connector contact
e 83 Malfunction of refrigerant V
thermistor Defective refrigerant thermistor
r
s
System No. 1
Defective connector contact
Malfunction of heat
84 Defective heat exchanger V
exchanger
thermistor
thermistor
System No. 2
Defective connector contact
Malfunction of heat
85 Defective heat exchanger V
exchanger
thermistor
thermistor
System No. 1
Malfunction of discharge Defective connecting connector
86 V
pipe Defective discharge pipe thermistor
thermistor
System No. 2 Shortage of gas
Malfunction of discharge Defective discharge pipe thermistor
88 V
pipe Defective connector contact
temperature Clogged refrigerant piping
Malfunction of brazed-plate Dirty heat exchanger
89 heat Shortage of refrigerant amount V
exchanger freezing Defective thermistor
System No. 2
Defective connector contact
Malfunction of leaving
8A Defective leaving water V
water
temperature thermistor
temperature thermistor
System No. 1
Defective connector contact
8E Malfunction of suction pipe V
Defective suction pipe thermistor
thermistor 1 for heating
System No. 1
Defective connector contact
8F Malfunction of suction pipe V
Defective suction pipe thermistor
thermistor 2 for heating
Three way valve malfunction
Abnormal hot water high
8H Defective thermistor V
temperature
Defect of water temperature setting
Abnormal chilled water
Shortage of water volume
90 quantity or V
Disconnection of AXP
abnormal AXP
Defective connector contact
91 Defective electronic V
expansion valve coil
System No. 2
Defective connector contact
92 Malfunction of suction pipe V
Defective suction pipe thermistor
thermistor
Malfunction of transmission
Defective fan unit PCB
(between heat reclaim
94 Defective connecting wire between V
ventilator
(1) and (2)
and fan unit)
System No. 1
95 Malfunction of inverter Defective fan inverter unit V
system
System No. 2
96 Malfunction of inverter Defective fan inverter unit V
system
Malfunction of thermal
97 Defective thermal storage unit V
storage unit
Malfunction of thermal
Actuation of thermal storage brine
98 storage V
pump overcurrent (OC)
brine pump
Malfunction of thermal
Low water level of thermal storage
99 storage
brine tank
brine tank