Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

Smart MCC

Innovate with
LS Smart Motor Control Solution!
LS smart MCC enhanced the function of motor operation,
protection and measurement by applying smart EMPR.
It is smarter control and management system that gives you the convenience
from energy management to maintenance.

PC manager

Local HMI

Smart EMPR

02
Smart MCC

CONTENTS

System configuration .................................................................... 04


S-EMPR ........................................................................................ 05
Local HMI . .................................................................................... 08
PC manager . ................................................................................. 11
MCC panel .................................................................................... 12
Application .................................................................................... 14

MCC panel

Safety for operation and management


•Minimize fault spread and repair cost by rapid detecting fault and accident
and real-time alarming

Customer convenience
•Minimize field check by remote monitoring through PC manager
•Setting and monitoring multiple EMPRs through local HMI and PC manager

Enhanced energy management and maintenance function


•Monitoring the quantity of electricity by motor
•Data of total operation time and continuous operation time by motor
•Daily and monthly report (current value, power, power factor, etc.)

03
Smart MCC

System configuration
Our system improves convenience and safety of your system operation and
management by enhancing local & remote monitoring function through local HMI and PC manager.

• Maximum 30 S-EMPRs can be connected to 1 HMI.

• Maximum 10 HMIs can be connected to 1 PC manager.


→ Maximum 300 S-EMRPs can be set, monitored and controlled with 1 PC manager.

PC manager
Maximum 10 HMIs can be
connected to 1 PC manager.

SCADA

Local HMI Ethernet (Modbus)

Maximum 30 S-EMPRs
can be connected to 1 HMI.

RS-485
(modbus)

04
Smart MCC

S-EMPR MMP
A variety of SCADA functions based on sequence structure.
One S-EMPR model is applicable to various motor starting types,
such as full voltage starting, Y-△ starting, reversible starting,
reactor starting, and inverter starting.

Easy to use Quick setup


Same setting for another devices in different panels can be done simply via the display
unit.

Date information display


When a failure occurs, the date and time of failure occurrence are saved in the system to
accurately identify the date of motor failure.

Total operating time and operating time setting


When the predefined operating time has elapsed, related information is displayed so
that operators may replace the motor bearing and check the refueling cycle.

Convenience
Wide setting range and dual protection
Providing ground fault protection by dual detections -zero-phase current and residual
current levels.

One-body type and separate body type


The display unit can be separated from the device to mount on the face of the panel,
which enables the access to the unit without opening the door. All the functions remain
unchanged after the separation.

Various motor starting modes


In a single device several starting modes of operation available : Full voltage start,
Y- △ start, reversible start, reactor start, inverter start.

Up to 100A the device can be used without external CT


to provide convenience and cost-effective solution.

A wide range of reset functions


Manual / Automatic / Electrical reset functions are provided for user convenience.

Communication function (RS485 modbus and 4~20mA output)


With universal RS485 / Modbus communication types, it is possible to establish various
system and communication networks. Analog current signal (4~20mA) output is
compatible with conventional TD (Transducer) based system.

05
Smart MCC

S-EMPR MMP

Reliability
Comprehensive dgital motor protection relay with the MCU (Microprocessor Control Unit)
Providing real-time processing and high precision

Metering of current, voltage and energy (with 1% accuracy for A & V)


Real-time energy metering with high accuracy to support energy-saving current /
voltage THD measurements (16 harmonic)

Carrying out complex relay functions related to current, voltage,


energy and power factor
Overpower alarm supported for energy monitoring

Applicable to invertor circuits


It can be installed in the downstream of a speed driver where harmonic noise exists.
The allowable frequency range is 10 to 400Hz.
A harmonic filter must be used if THD (Total Harmonic Distortion) is over 30%.
* Set the ground fault mode off to avoid the trip due to current unbalace.
* Voltage parameters are not available. Power measurement accuracy is not guaranteed.

Thermal heat build-up inverse time/inverse time/definite time selection function


It is possible to select one of two types of inverse time and definite time in order to
protect a motor perfectly.

Self-diagnosis and sequence monitoring


Providing a self-diagnosis function such as internal memory check in order to check
fault conditions quickly

Power loss and restarting


Device restarts after the momentary power loss for less than 30 seconds and returns
to the former state. Time-delay setting between 0 to 300 sec. is available to prevent
overload from all the motors' restarting at the same time.

Frequent-starting protection
The number of automatic resets for the set time (20 minutes) is settable to provide
frequent-starting protection.

Password setting
When changing the set values, a password must be inserted.

Function to store the cause(s) of failure / fault


Up to 5 motor failure events can be saved in the system, so that the failure history can
be easily identified.

06
Smart MCC

S-EMPR MMP specifications


Description MMP
Connection Tunnel type (passing through CT holes)
Operation characteristic Thermal-inverse / Inverse / Definite
Rated current 0.5~10A/5~100A (select rated on order)
Display screen 4 digit, 7-segment, LED
Control power 110Vac or 220Vac 50/60Hz
Auto 1-20 minutes
Reset
Manual On / Off selectable
Mounting Display unit : sepatately mountable

Current and voltage metering : ± 1% of rating or ± 2% of minimum rating


Accuracy
4~20mA output : ± 5%
Start 1-200 seconds
Time delay
Operation 1-60 seconds

Auxiliary 6 contacts (3A / 250VAC at resistive load, power type based)


contacts Contact minimum load 10mA / 5VDC

Basic installation of built-in ZCT


ZCT input
External ZCT (200mA/1.5mA, universal ZCT connectable)
Operation temp. -10~55℃
Environment Storage temp. -20~70℃
Humidity RH 80% or under (non-condensing)
Insulation resistance 100MΩ/500VDC
Lightning impulse voltage 1.2 × 50μs 5kV standard waveform applied
Fast transient 2kV/1Min
Power consumption 5W or under

07
Smart MCC

Local HMI MMP-HMI10


Wide type applied TFT LCD
LED backlight adopted
RTC (Real Time Clock) function (with a battery)

Features
10.2 inch wide display Convenience of MMP setting Enhanced field monitoring function
• Display size : 25.9cm (10.2”) • Check and change all • Monitoring max. 30 MMPs at a time
• Resolution : 800 x 480 (WVGA) the set value of MMP • Operation condition and load rate
• CPU : ARM9 core, 454MHz • Possible to change the • Fault / Alarm check
• Communication interfaces set value of multi MMP • Motor on / off control
: RS 485 ↔ Ethernet

Local HMI Main Screen General settings screen MMP communication connection screen
① ② • Automatically scan the modbus address (No.
1 ~ 30) and communicate with the MMP of the
corresponding address automatically.
③ ④ • Automatically recognize the type (current type
/ power type / ground type) of the MMP during
communication connection.

① General settings
MMP settings screen
HMI device setting / HMI communi-
cation setting / MMP communica- • Display the setting value according to each
MMP type
tion setting / MMP communication
• Possible to change each setting item through
connection pop-up window
② MMP settings • Possible to collectively change the set value of
a specific MMP to an MMP of the same type
Measurement value checking and
changing functions
③ Monitoring / Control
Monitoring / Control screen 10 MMP monitoring screens

Multiple MMP monitoring • Check the operation status of each MMP


(30/10 view modes) : On / Stop / Fault / Error / Alarm
• Possible to check load factor, motor initiation di-
detailed measurement value and
rection, and main measured value for each MMP
On / Rev / Stop / Reset control of • Measured value display: Peak current of
each MMP three-phase current, continuous operation
time, total operation time, active power
④ Fault log
amount* (total)
Confirmation of fault log
* MMP power model only

for each MMP


(5 confirmations per device) Fault log screen
• Confirmation of fault log list for each MMP
-5 devices can be checked
• Possible to check the details of faults through
fault log
• Fault log list of all MMPs can be saved to USB

08
Smart MCC

Local HMI MMP-HMI10 specifications


Description MMP-HMI10
Display type TFT color LCD
Display size 25.9cm (10.2 inch)
Resolution 800 x 480 (WVGA)
Color 65,536 colors
Left / Right: 55 deg.
Display angle
Up: 35 deg. Down: 55 deg.
Backlight LED mode, auto on/off
Backlight capacity 20,000 hr
Brightness (LCD) 350 cd/㎡
Touch panel 4-wire system, analogue
Processor ARM9 Core (32bit RISC), 454MHz
Flash 128MB (screen 64MB)
Memory Operation RAM 128MB
Backup RAM 128MB
Battery capacity Around 3 years (upon operation at 25℃)
RTC function available
Ethernet 1 channel, 10 / 100BASE-TX
1 channels, USB 2.0 host (for mouse, keyboard and USB driver)
USB port
1 channel, USB 2.0 slave (for debugging)
RS-485 1 channel
Language Korean, English, Chinese
Certification KC, CE
Degree of protection IP65
Size (mm) 276.0×218.0×44.2
Panel cut (mm) 260.0×202.0
Power DC24V
Power consumption (W) 23.1
Weight (kg) 1.0

09
Smart MCC

Local HMI MMP-HMI10 dimensions


(Unit : mm)

(259.5)
(107.6) (107.6)

276+0.3

(201.5)
(208.1)
218+0.3
44.4+0.3

(107.3) (127.3)

Item Standard Tolerance


Size(mm) 276.0 × 218.0 × 44.4 ±0.3

Panel cut(mm) 260.0 × 202.0 0 ~ +1.0

10
Smart MCC

PC manager S/W
All functions of HMI such as setting, monitoring, and control are
operated remotely. Trend check function enables smart operation
anytime, anywhere.

Features
All HMI functions can be used remotely Trend check function (data export possible)
(setting / monitoring / control, etc.) • Check the measured value trend: current, voltage*,
• Check and change the MMP setting load rate, distortion rate, etc.
• MMP monitoring and control • Energy management function support: Power by motor
• Check fault log • Maintenance function support: Continuous operation time,
total operation time for each motor * MMP power model only

MMP settings screen MMP fault log screen


• Confirmation of fault log list for each MMP
• Possible to check the details of faults by
fault log
• Fault log list of all MMPs list can be saved
to USB

• Displays setting values for each Report menu - Current / Voltage information check screen
MMP type
• Possible to collectively change the • Possible to check by bar/line/table type,
set value of a specific MMP to an 15 minutes data display, data storage
MMP of the same type • Check load factor, current, voltage*
and power factor * for each MMP
* MMP power model only

Monitoring / Control menu Report menu - Energy management check screen *


• Possible to check by bar/line/table type,
possible to compare with past amount,
data storage
• Possible to check total power usage and
individual MMP power levels
* MMP power model only
• Check the operation status of
each MMP
: On / Stop / Fault / Error / Alarm
Report menu - Operation time management check screen
• Measured value display: Peak current • Possible to check by bar/line/table type,
of three-phase current, continuous data storage
operation time, total operation • Possible to check total operation time
time, active power amount* (total) and continuous operation time for each
* MMP power model only MMP

11
Smart MCC

MCC panel Susol MCC


Susol MCC is designed and produced to construct high quality
power system. It secures high performance & high quality
complying with global standard and improves customer's
convenience and safety.

Features

Stability and reliability Customer-oriented structure


• Designed to meet the IEC61439-1&2 standard • Usability improvement through 3-way unit withdrawal type
• Degree of protection : IP43 (Up to 54) (ASTA certification)
• Form 4b structure • Easy to change the unit position
- Prevention fault spread by metal partitions • Independent modular structure for maintenance
• Structure and various options for user safety
• Segregation of the busbars by applying multi function wall

Unit Multi function wall


• Withdrawable unit's height is adjustable from 150 mm Multi function wall has modularized and standardized
up to 750 mm. structure and high level of safety
• Unit's height can be adjusted by 50 mm pitch.
• MCCB, magnetic contactors, protective relays, auxiliary relay, Features
timer, CT, ZCT and fuse are attached horizontally from the • Simple structure by integration of components and functions
front of the unit case. • Separation of phase to phase each busbar
• Primary and secondary plug of main circuit and control circuit • Rated short circuit current: up to 100kA/1s, 85kA/3s
plug are attached at the back of the unit case.
Busbar systems
Unit configuration • Separation of phase to phase each busbar( )
•½ Unit configuration • Support the middle of busbar( )
- ½ unit configuration provides expanded working • Support the end of busbar’s top and bottom( )
space and allows optimal space management

½ Unit
1단적 유니트
유니트 ½단적 유니트
1 Unit

• Safety embedded design for operators


- Padlock-equipped gear device indicator
- Unit withdrawal/insertion disabled when circuit
breaker is on
- Interior shaft prevents negligent accidents

12
MCC panel Susol MCC specifications
Description Susol MCC
Rated operating voltage Up to 500V
Main Up to 5000A
Rated current
Distribution Up to 1500A
Phases 3P4W
Rated frequency 50/60Hz
Rated short time withstand current Up to 100kA/1sec
Arc fault containment Up to 100kA/0.3sec
(IEC TR 61641) (85kA/0.5sec)
Rated insulated voltage 750V
Rated impulse withstand voltage 8kV
Degree of protection Up to IP54
Form of internal separation Form 4b

Size Double front type 1000 x 1000 x 2250


(W x D x H, mm) Single front type 1000 x 650 x 2250
Standard IEC 61439-1&2

13
Smart MCC

Application
Building (office, commercial, residential, hospital, etc.)
Building

Industry (oil & gas, electronics, steel, semiconductor, cement, glass, etc.)
Industrial

Public facility (gas, water & sewage, airport, railway, port, etc.)
Public

14
Smart MCC

MEMO

15
www.lselectric.co.kr

■Headquaters ■Overseas Branches


127, LS-ro(hogye-dong) Dongan-gu, Anyang-si, Gyeonggi-Do, 14119, Korea • LS ELECTRIC Tokyo Office (Japan)
Tel: 81-3-6268-8241 E-Mail: jschuna@lselectric.biz
■Seoul Office
LS Yongsan Tower, 92, Hangang-daero, Yongsan-gu, Seoul, 04386, Korea • LS ELECTRIC Beijing Office (China)
Tel: 86-10-5095-1631 E-Mail: chendm@lselectric.com.cn
Tel: 82-2-2034-4916, 4684, 4429
• LS ELECTRIC Shanghai Office (China)
■Overseas Subsidiaries Tel: 86-21-5237-9977 E-Mail: khpaek@lselectric.com.cn
• LS ELECTRIC Japan Co., Ltd. (Tokyo, Japan)
Tel: 81-3-6268-8241 E-Mail: jschuna@lselectric.biz • LS ELECTRIC Guangzhou Office (China)
Tel: 86-20-3818-2883 E-Mail: chenxs@lselectric.com.cn
• LS ELECTRIC (Dalian) Co., Ltd. (Dalian, China)
Tel: 86-411-8730-5872 E-Mail: jiheo@lselectric.com.cn • LS ELECTRIC Chengdu Office (China)
Tel: 86-28-8670-3201 E-Mail: yangcf@lselectric.com.cn
• LS ELECTRIC (Wuxi) Co., Ltd. (Wuxi, China)
Tel: 86-510-6851-6666 E-Mail: jdyim@lselectric.com.cn • LS ELECTRIC Qingdao Office (China)
• LS ELECTRIC Vietnam Co., Ltd. Tel: 86-532-8501-2065 E-Mail: wangzy@lselectric.com.cn
Tel: 84-93-631-4099 E-Mail: jhchoi4@lselectric.biz (Hanoi) • LS ELECTRIC Nanjing Office (China)
Tel: 84-28-3823-7890 E-Mail: sjbaik@lselectric.biz (Hochiminh) Tel:86-25-8467-0005 E-Mail: ylong@lselectric.com.cn
• LS ELECTRIC Middle East FZE (Dubai, U.A.E.)
Tel: 971-4-886-5360 E-Mail: hschoib@lselectric.biz • LS ELECTRIC Bangkok Office (Thailand)
Tel: 66-90-950-9683 E-Mail: sjleet@lselectric.biz
• LS ELECTRIC Europe B.V. (Hoofddorf, Netherlands)
Tel: 31-20-654-1424 E-Mail: europartner@lselectric.biz • LS ELECTRIC Jakarta Office (Indonesia)
Tel: 62-21-2933-7614 E-Mail: yjleee@lselectric.biz
• LS ELECTRIC America Inc. (Chicago, USA)
Tel: 1-800-891-2941 E-Mail: sales.us@lselectricamerica.com • LS ELECTRIC Moscow Office (Russia)
Tel: 7-499-682-6130 E-Mail: jdpark1@lselectric.biz

• LS ELECTRIC America Western Office (Irvine, USA)


Tel: 1-949-333-3140 E-Mail: jwyun@lselectricamerica.com

2020. 04 2018. 10. LS ELECTRIC Co.,Ltd. All rights reserved. / (01) 2020. 04. PACO STORY