Professional Documents
Culture Documents
2020 Sinpac Installation Instructions
2020 Sinpac Installation Instructions
23
Installation Instructions for SINPAC Switches Continued
Caution: Application of 230 Vac to the mechanical switch – it is not If mounted external to motor,
line input terminals (1 and 2) of a 115 necessary to remove the always use gasket supplied with
Vac rated SINPAC Switch will result in existing centrifugal switch kit.
immediate switch failure. The switch actuating mechanism, but if 9. DO NOT USE a Variac to gradually
may rupture and emit smoke. feasible, it should be removed increase the voltage to the motor
as it is no longer needed, and starting circuit when SINPAC
Important can cause future mechanical Switch is installed.
Please read these instructions carefully problems in the motor should
before installing, operating, or servicing the mechanism fail. Follow the 10. Reassemble the motor with
your SINPAC Switch. Failure to comply manufacturers recommendation SINPAC Switch installed, so as to
with these instructions could cause when removing the shaft end not damage lead wires.
injury to personnel and/or damage to bearing, if necessary, to take off 11. If the motor fails to start or the start
property if the switch is installed or the centrifugal actuator. winding does not cut out properly,
operated incorrectly. For definition of see Troubleshooting Guide (Page
6. Remove the existing electronic
limited warranty/liability, contact 30).
switch. Determine the existing
Rexnord Industries, LLC, Stearns
wiring diagram. Mark the existing 12. Hipot test procedures:
Division, 5150 S International Drive,
wires and determine which wires
Cudahy, Wisconsin 53110, Motors 250 Volts or Less and
can be reused for installation of
(414) 272-1100. 1/2 Horsepower or Less
the SINPAC Switch. Select a
Initial Inspection and Handling location in the motor conduit box or The motor, equipped with SINPAC
Upon receipt, check for package endbell for mounting the SINPAC Switch, shall be tested for
damage. Note any signs of damage on Switch. dielectric withstand (hipot), by the
appropriate shipper forms. Upon If a metal enclosure version of application of a 1200 volt
opening package, if concealed damage SINPAC Switch is being used, the sinusoidal potential, in the range of
is found, immediately file a claim with switch with SINPAC Switch gasket 40-70 Hz, for 1 second. During the
carrier. may be mounted on an external test, each lead of the primary
mounting surface such as the motor wiring, accessible at the
Check the label to verify that data connection board or conduit box,
conforms to specifications of ordered exterior of the conduit box. Plastic
enclosure versions of the SINPAC are to be connected together and
switch and the connection diagram to one terminal of the test
agrees with labeling. Switch should be mounted
internally, within the conduit box, or equipment, and the second test
Caution externally, under a capacitor equipment terminal is to be
1. Installation and servicing must be housing. connected to the accessible dead
made in compliance with all local metal.
IMPORTANT: SINPAC Switch in
safety codes including a metal enclosure must have Motors 250 Volts or Less and
Occupational safety and Health Act the metal enclosure grounded. More Than 1/2 Horsepower
(OSHA). All wiring and electrical The motor, equipped with SINPAC
connections must comply with the The temperature at the
mounting location should not Switch, shall be tested for
National Electric Code (NEC) and dielectric withstand (hipot), by the
local electric codes in effect. exceed 65°C (149°F). (2CVR
application of an 1800 volt
2. To prevent an electrical hazard, temperature should not exceed sinusoidal potential, in the range of
disconnect power source before 55°C.) 40-70 Hz, for 1 second. During the
working on the motor. If power TEFC/TENV motors require test, each lead of the primary
disconnect point is out of sight, lock external mounting of SINPAC motor wiring, accessible at the
disconnect in the off position and Switch. connection board or conduit box,
tag to prevent accidental are to be connected together and
application of power. 7. Refer to motor manufacturer’s to one terminal of the test
wiring diagram to aid in identifying equipment, and the second test
3. Make certain power source terminal locations for the start
conforms to the requirements equipment terminal is to be
winding switch, start winding, start connected to the accessible dead
specified on the SINPAC Switch and run capacitors (if needed) and
nameplate. metal.
AC line.
4. Installation and servicing should be 13. CAUTION: The terminals of the
8 Connect the SINPAC circuit per the
performed only by qualified SINPAC Switch should not be used
connection diagram (on Pages
personnel familiar with the as the junction for this field wiring.
24-25 or 26-27) using insulated
operation of the SINPAC Switch. terminals. If the connections are
5. Determine what type of start switch made incorrectly, the result will be
the motor presently has: no starting torque and possible
damage to the circuit and/or motor.
a) Externally mounted electronic
switch – go to Step 6. CAUTION: Be sure that
appropriate insulation is used
b) Internally mounted electronic between the terminals of the
switch – go to Step 6. switch and the body of the motor
c) Externally or internally mounted or conduit box.
24