Cooling water thermostat (high-temperature water) (2-step temperature control)


Inspection and maintenance 1/2

PRODUCTION MANAGEMENT DATA


Intervals 1 years
4000 working hours
CONDITION The 2-step temperature control specification is to control the temperature at the following 2-steps: 85°C at
low load, and 60°C at high load.
PERSONNEL!
a Engine crew Intermediate 2.5 h
b Engine crew 2.5 h
EQUIPMENT !ffl~mslliliJB:tlll!ll[E!J

SPARES ---•
O-ring 24326-000750 1 pc
O-ring 24326-000700 1 pc
O-ring 24326-000550 1 pc
SAFETY

Obey the instructions that follow when you do maintenance of the cooling water thermostat (high-temperature
water).

1. Disassembly
1. Close all valves at the inlet and the outlet of the cooling water system.
2. Drain the cooling water from inside the cylinder jacket.
3. Remove the cooling water manifold pipe 2.
4. Remove the cooling water bypass pipe 6.
5. Remove the cooling water selecting valve assembly 1.
6. Remove the thermostat case 5.
7. Remove the thermostats 3 and 4.
8. Make sure that the temperature setting of the thermostat is correct.
Be careful that you do not let the thermostat fall.
Opening temperature and number of thermostats: 81 °C x 2 (on the high-temperature setting side).
: SS°C x 2 (on the low-temperature setting side).

1
·,,
,''i",.. ',"-.

LFj""
in~ Y...._
'
!'-ti.::'',,
." ...,__'

Fig. 1 Cooling water thermostat (high-temperature water) - Disassemble procedure