The continuity test report summarizes the results of testing the electrical cable from the MDP to the Coal Yard panel. Testing of phases R, S, and T and the neutral and grounding conductors all showed acceptable continuity. Insulation resistance testing also found resistance above 2000 MΩ. The report was submitted by PT Wasamitra and witnessed/approved by PT BJP.
The continuity test report summarizes the results of testing the electrical cable from the MDP to the Coal Yard panel. Testing of phases R, S, and T and the neutral and grounding conductors all showed acceptable continuity. Insulation resistance testing also found resistance above 2000 MΩ. The report was submitted by PT Wasamitra and witnessed/approved by PT BJP.
The continuity test report summarizes the results of testing the electrical cable from the MDP to the Coal Yard panel. Testing of phases R, S, and T and the neutral and grounding conductors all showed acceptable continuity. Insulation resistance testing also found resistance above 2000 MΩ. The report was submitted by PT Wasamitra and witnessed/approved by PT BJP.
The continuity test report summarizes the results of testing the electrical cable from the MDP to the Coal Yard panel. Testing of phases R, S, and T and the neutral and grounding conductors all showed acceptable continuity. Insulation resistance testing also found resistance above 2000 MΩ. The report was submitted by PT Wasamitra and witnessed/approved by PT BJP.
Panel Name : MDP TO COAL YARD Feeding : 00BGJ04 (COAL YARD SUS BOARD C) Bld. 815 Cable Type : NYY 5Cx35mm Location : NEAR TT 452 Date : 04 MAY 2023
No Item Test From TO Result
1 Phase R MDP 00BGJ04 (COAL YARD SUS BOARD C) Accepted 2 Phase S MDP 00BGJ04 (COAL YARD SUS BOARD C) Accepted 3 Phase T MDP 00BGJ04 (COAL YARD SUS BOARD C) Accepted 4 Neutral (N) MDP 00BGJ04 (COAL YARD SUS BOARD C) Accepted 5 Grounding (G) MDP 00BGJ04 (COAL YARD SUS BOARD C) Accepted
NOTE Insulation Resistance Tester
R,S,T : Phase Brand : HIOKI N : Neutral Model : IR4056-20 G : Ground SN : 220110693 N : Neutral Calibration Date : Jan 2022 OL : > 2000 MΩ Calibrated By : PT Delta instruments