Drain Pump

Safety First
• Cut off the power supply before installation and maintenance.
• Drain Pump Assy must be installed at safe area where it is far away from the user.
• Drain Pump Assy must be installed at appointed location.
• All wiring and connections are for installation only.

Screw Cap

Drain pump Assy

Quantity
Quantity Package contents
1 Drain Pump Assy(AC220~240V, 50/60Hz, 400cm3/min)
4 Screw
1 Cap
1 Installation manual

Service Parts List


No. Location No. P/No. Description Remark
1 158590 5858A10001L Pump Water
2 266012 6601A20001E Switch Assy, Float

P/No.:3828A20224A
1
How to install

1. Remove the filter. 2. Open the top cover.

3. Remove the knock-out from the side 4. Assemble the drain pump assy.
panel. - Drive 4 screws to the Side Panel.

5. Connect two lead wires to control box. 6. Close the drainage hole with the provided
(One is for float switch, the other is for cap.
power supply to drain pump.)

7. Assemble the top cover. 8. Insert the filter.

2
Attention

1. Possible drain-head height is up to


700mm. So, it must be installed
below 700mm. 1/50~1/100

Drain Pipe
2. Keep the drain hose downward up
to 1/50~1/100 inclination. MAX 700mm
Prevent any upward flow or
reverse flow in any part.

Drain Pump

Thermal insulator
(Local supply)
3. 5mm or thicker formed thermal Drain pipe
insulator is provided for the drain (Local supply)
pipe. Unit

Elbow

Drain pump

Wall
4. Upward routing is not allowed.
Drain hose

5. Be sure to check the drain pump


for normal operation and abnormal
noise when electrical wiring is
complete.

6. Be sure to be no water leakage


after closing the drainage hole with
a cap.
Cap

Drainage Hole

3
Wiring Diagram

INDOOR ELECTRIC CIRCUIT

THERMISTOR
YL

TEMP.
INDOOR DRAIN

GN/YL
MOTOR PUMP

OR
BR

BL
BL
BK
FUSE
250V 8A
1 (L ) 2 (N )

BR
TRIAC
BL
TO OUTDOOR UNIT

COMP

4 WAY PIPE

VENT
RD Drain Pump Assy THERMISTOR
3

BK
4

FLOAT S/W
BL BR
5

GN/YL REMOTE
CONTROL

TERMINAL
BLOCK T/B
A/CL TELECONTROL/ ZONE OPTION
UNIT CENTRAL CONTROL CONTROL
VENTILATOR

Test operation
• Before test operation, be sure all information is understood completely, and follow
the guideline of manual.
• Connect the power and turn on cooling mode.
• After compressor operating, it starts and compressor off, it stops 6 minutes later.

Troubleshowting

PROBLEM CAUSE REMEDY


Check electrical connection and voltage of
No power supply
the power supply.
Pump does not work.
Float switch doesn't
Check float switch.
operate.
Check pump connection for water
Pumping air
contamination.
Pump noisy
Vibrating against Check the assembly state of drain pump to
surfaces. the unit.