NOTES:

D44-S-0602 D44-U-0602
FOR STANDARD SYMBOLS / LEGEND AND TYPICAL DETAILS SEE DRAWINGS FROM
BACKWASH PROCESS COOLING WATER SIDE D47-A-0A-PR0001-001 THROUGH 023.
FILTER PIT HOLD 1 STREAM FILTER PACKAGE
SIZE : 26.7 ft x 15.4 ft x 5.9 ft CAPACITY : 1130.6 USGPM HOLD 1 ALL INSTRUMENT TAG NUMBERS SHALL BE PREFIXED BY UNIT NUMBER 403.
CAPACITY: 1730.0 ft^3 DP: 130.00 PSIG / 1. PACKAGE CONTENT IS INDICATIVE. PACKAGE TO BE FULLY AUTOMATED AND HAVE
TRIM: DT: / 180.00 °F THE ABILITY TO BE CONTROLLED FROM THE CONTROL ROOM. SUITABLE ALLOWANCES
TRIM : FOR CONNECTIONS TO DCS AND SAFEGUARDING SYSTEM ARE INCLUDED TO FACILITATE THIS .
2. BYPASS VALVE CV TO BE LIMITED IN BETWEEN 391 TO 1200.
3. REFER VENDOR P&ID NO. HOLD FOR FILTER PACKAGE VESSELS
SET @ 2261.0 USGPM NOTE 4
ARRANGEMENT AND OTHER DETAILS.
FC FLL 4. VALVE CLOSED STATUS TO BE ALARMED IN DCS BASED ON POSITIONER FEEDBACK.
L SET @ 2035.0 USGPM 3010 3010 C

0.0 - 3200.0 USGPM


FF
FT
3010 HOLD 4 D44-U-0602
TP NOTE 1,3
IAS 0001 HOLDS:
10"x8" 10"x8" 10"x8" 10"x8" 44538
CIRCULATION WATER 1. EQUIPMENT DESIGN INFORMATION IS ON HOLD.
10"-RW- 87091-1CS2W01
44539 1A-PR0150002 M 2. TAG NUMBERS ARE ON HOLD.
FROM D-44-G-0602A/B/C 8" HOLD 4 3. THIS DRAWING TO BE UPDATED FOR TECHNOLOGY PROVIDER'S PDP, LESSONS
D 1" D 1" D 1"
AO/AFC LEARNT AND VENDOR UPDATES AS ADVISED BY TECHNOLOGY PROVIDER / VENDOR.
FF FV 4. CONTROL VALVE AND BYPASS SIZE TO BE CONFIRMED DURING THE NEXT STAGE OF THE
FE + PROJECT.
+

3010 3010 5. UTILITY DISTRIBUTION AND PIPERACK INTERCONNECTING P&IDs TO BE DEVELOPED DURING
DETAIL DESIGN STAGE OF THE PROJECT.
NOTE 2 8"
HOLD 4 SGV

0010

LEGEND
PIPING MATERIAL INSTRUMENT DEFINITION & SYMBOLS SAES-J-004
SPECIFICATION SAES-L-105
AC/AFO -AIR TO CLOSE/ VE -VIBRATION ELEMENT
AIR FAILURE OPEN VS -VIBRATION SWITCH
AC/AFS -AIR TO CLOSE/AIR
INSTRUMENT AIR 53 mm
SLOPE PROCESS LINE
FAILURE STEADY
VT -VIBRATION TRANSMITTER
XL -PILOT LIGHT
1"-IA- 87219-1CG0U01 30480 mm
INSTRUMENT AO/AFC -AIR TO OPEN/ (NOT FOR MOTOR)
HOLD 5
AIR LINE AIR FAILURE CLOSE XS -LIMIT SWITCH
FROM DISTRIBUTION
D 1" TP INSTRUMENT
AO/AFS -AIR TO OPEN/AIR
FAILURE STEADY
ZV -SAFETY SHUTDOWN VALVE
ELECTRICAL LINE
0004 AOV -AIR OPERATED VALVE DATA LOGGER POINT
F-FLOW P-PRESS.

INPUTS
AT -ANALYZER TRANSMITTER
L-LEVEL T-TEMP.
DT -DENSITY TRANSMITTER

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL, OR IN PART, SHALL BE OBTAINED FROM THIS DRAWING WITHOUT THE WRITTEN CONSENT OF SAUDI ARAMCO.
X-MISC. A-ALARM
REDUCER ESD -EMER. SHUTDOWN SYSTEM
LOCAL PANEL
FC - FLOW CONTROLLER
SPECTACLE MOUNTED INSTR.
FV -FLOW CONTROL VALVE
PLATE-OPEN FCV -FLOW CONTROL VALVE
BOARD MOUNTED
(SELF-ACTUATED) INSTRUMENT
SPECTACLE FE -FLOW ELEMENT
PLATE-CLOSED FG -FLOW SIGHT GLASS
R/G
STATUS LIGHTS
GATE VALVE FHV -FLOW MANUAL CONT. VALVE XL R=RED, G=GREEN
FHTD -FLOW MANUAL TRANSDUCER PILOT LIGHT (DO NOT
GLOBE VALVE FIC -FLOW INDICATOR CONTROLLER USE FOR MOTOR STATUS)

CHECK VALVE FM -FLOW METER


FO -RESTRICTION ORIFICE MOTOR STATUS
PILOT LIGHT
PLUG VALVE FQI -FLOW TOTALIZER INDICATOR
FF FF BALL VALVE
FR -FLOW RECORDER
LOCAL MOUNTED
H H FT -FLOW TRANSMITTER ML
PDT PDI PDT PDI DOUBLE DISC FY -FLOW RELAY
INSTRUMENT

GATE VALVE HIC -HAND INDICATOR CONTROLLER


MOUNTED BEHIND
ANGLE VALVE HS -HAND SWITCH LOCAL PANEL
LA -LEVEL ALARM
LV -LEVEL CONTROL VALVE RACK MOUNTED
PRESS. RELIEF VALVE LCV -LEVEL CONTROL VALVE (OR BACK OF PANEL)
(SELF-ACTUATED)
LG -LEVEL GAUGE GLASS ELECTRICAL
LIC -LEVEL INDICATOR CONTROLLER SUPPLY REQUIRED
VACUUM.RELIEF VALVE LI -LEVEL INDICATOR
LR -LEVEL RECORDER INSTRUMENT
LS -LEVEL SWITCH AIR SUPPLY REQUIRED
M MOTOR OPERATED
LT -LEVEL TRANSMITTER
VALVE H
LTD -LEVEL TRANSDUCER HIGH LOW
ML -MOTOR STATUS LIGHT L
P MOV -MOTOR OPERATED VALVE
PISTON OPERATED NA -ANNUNCIATOR TWO PEN RECORDER
VALVE PB -PUSHBUTTON
PC -PRESSURE CONTROLLER FF
CONTROL VALVE PV -PRESS. CONTROL VALVE FOUNDATION
PCV -PRESS. CONTROL VALVE FIELDBUS INSTRUMENT
(SELF ACTUATED)
P
BALL TYPE PDC -PRESS. DIFF. CONTROLLER DISTRIBUTED CONTROL/SHARED
CONTROL VALVE PDI -PRESS. DIFF. INDICATOR DISPLAY SYMBOLS
WITH POSITIONER PDIC -PRESSURE DIFFERENTIAL
FO INDICATOR CONTROLLER
(DCS) DISTRIBUTED CONTROL
S SYSTEM, OPERATOR ACCESSIBLE
SOLENOID VALVE PDIS -PRESSURE DIFFERENTIAL IN CONTROL ROOM
INDICATOR SWITCH (DCS) DISTRIBUTED CONTROL
PDT -PRESS. DIFF. TRANSMITTER
VALVE NORMALLY SYSTEM, OPERATOR INACCESSIBLE
PDTD -PRESS. DIFF. TRANSDUCER IN CONTROL ROOM
CLOSED
PG -PRESSURE GAGE
PI (DCS) DISTRIBUTED CONTROL
-PRESSURE INDICATOR
SYSTEM, OPERATOR INACCESSIBLE
PIC -PRESS. INDICATOR CONTROLLER
IN FIELD
PR -PRESSURE RECORDER
PS -PRESSURE SWITCH
PT -PRESSURE TRANSMITTER DISTRIBUTED CONTROL
PX -PRESSURE POINT INTERCONNECTING LOGIC
PY -PRESS. COMPUTATION MOD. CONTROLLER WITH BINARY
PZV -PRESSURE RELIEF VALVE OR SEQUENTIAL FUNCTIONS
RTD -RESIST. TEMP. DETECTOR
(PLC) PROGRAMMABLE LOGIC
SI -SPEED INDICATOR
CONTROLLER, NORMALLY
SS -SPEED SWITCH INACCESSIBLE OR BEHIND THE
TC -TEMP. CONTROLLER PANEL DEVICE OR FUNCTIONS
TV -TEMP. CONTROL VALVE (PLC) PROGRAMMABLE LOGIC
TCV -TEMP. CONTROL VALVE CONTROLLER FUNCTION,
(SELF-ACTUATED) CAN BE NORMALLY
TE -TEMP. ELEMENT DISPLAYED ON CRT
TSO -TIGHT SHUT OFF TG -THERMOMETER LOCAL DCS OR AUXILIARY
S.C. - SAMPLE CONN. THS -TEMP. HAND SWITCH DCS LOCATION NORMALLY
TI -TEMP. INDICATOR ACCESSIBLE TO OPERATOR
S -DRAIN TO
TR -TEMP. RECORDER
PRESSURE SEWER (PLC) PROGRAMMABLE LOGIC
TS -TEMP. SWITCH
-OILY WATER SEWER CONTROLLER I/O POINT
OWS TT -TEMP. TRANSMITTER NORMALLY INACCESSIBLE
CIRCULATION WATER D -DRAIN TTD -TEMP. TRANSDUCER BY OPERATOR
10"-RW- 87079-1CS2W01 V -VENT TW
44542 1A-PR0150001 -THERMOWELL

TO D44-S-0601
D 1"
TP
0002

D44-A-1A-PR0094-017

3"-RW- 87310-1CS2W01

TP
0005
TO AMT TP
AT SAFE LOCATION 0003

TP
0006 B 24-FEB-23 IFD ISSUED FOR DESIGN BB GTS SV RV SD
3"-RW- 87311-1CS2W01 A 04-NOV-22 ICR ISSUED FOR CLIENT REVIEW BB GTS SV RP SD
REV DATE STATUS DESCRIPTION BY CHK APP APP APP
4"-VG- 87373-80CG0D01

16"-RW- 87087-1CS2W01
FREE DRAINING

REVISION VALIDATION
THIS REVISION NO. B IS COVERED, FOR ALL APPROVAL AND CERTIFICATION
REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:
10-20857-0001

DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER


(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)
ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

REV.NO. DATE REVISION DESCRIPTION


4"-OWS- 87323-1FE0U01 AS-BUILT
SLOPE
12"-OWS- 87893-1FE0U01 1 mm 180 mm JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
OWS 10-20857-0001 CONSTRUCTION UNTIL CERTIFIED AND DATED
D44-S- 0602 HOLD 5

DRAWING TYPE
PIPING & INSTRUMENTATION DIAGRAM PID
OWS
HOLD 5 GIP SIDE STREAM FILTER PACKAGE-COMMON
SULFUR RECOVERY UNIT
FADHILI SAUDI ARABIA
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.
THIS DOCUMENT IS DEVELOPED BASED ON
DOCUMENT NO. D44-A-RB-355630.001 D44 A 1A-PR0150 007 B
Saudi Aramco 5994 ENG. (09/03)