Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

EVSS

Electronic fan speed controller with TK


The EVSS1 electronic speed controllers automatically control the speed of
single-phase voltage controllable electric motors (230 VAC - 50 / 60 Hz).
These units are equipped with Modbus RTU (RS485) communication, an
alarm relay output and thermal contacts to provide overheating protection
of motors with cut-out contacts. The EVSS1 controllers feature a wide range
of functionalities: remote control options, adjustable off level, min. and
max. output voltage settings, time-limited motor operation initiated by a
logic or switch signal .
Key features
• Invertible analogue input signal: 0—10 / 10—0 VDC or 0—20 / 20—0 mA

• Minimum and maximum output voltage setting by trimmers or via Modbus

• Off value setting by trimmer or via Modbus

• Modbus RTU (RS485) communication

• Kick start or soft start

• Remote control input with selectable functionality (normal or timer)

• Analogue input functionality (normal or logic - only for the timer start)

• 1 regulated output for the motor

• 1 unregulated output (230 VAC / max. 2 A) for 3-wire motor connection or


voltage supply

• 1 low voltage supply output (+12 VDC / 1 mA) for external 10 kΩ potentiometer

• Overheating protection

• Alarm output 230 VAC / 1 A

• Green LED operating indication

• Red LED overheating indication

• Illuminated power switch

Technical specifications Article codes


Power supply 230 VAC ± 10 % - 50 / 60 Hz Nominal current, [A] Fuse rating, (5*20 mm ) [A]

Regulated output 30—100 % Us (69—230 VAC) EVSS1-15-DM 1,5 F 3,15 A H 250 VAC

EVSS1-30-DM 3,0 F 5,0 A H 250 VAC


Unregulated output 230 VAC / max. 2 A
EVSS1-60-DM 6,0 F 10,0 A H 250 VAC
Maximum load depends on the version
EVSS1100-DM 10,0 (6,3*32 mm) F 16,0 A H 250 VAC
Analogue input 0—10 / 10—0 VDC or 0—20 / 20—0 mA

Logic input Timer start Area of use


Minimum output • Fan speed control in ventilation systems
30—70% Us (69—161 VAC)
voltage setting
• For indoor use only
Maximum output
75—100 % Us (175—230 VAC)
voltage setting

Off level
0—4 VDC /        0—8 mA  for ascending mode Standards
10—6 VDC / 20—12 mA for descending mode
• Low Voltage Directive 2006/95/EC
Supply output +12 VDC / 1 mA
• EMC  Directive 2004/108/EC: EN 61326
Alarm relay output 230 VAC (50 / 60 Hz) / 1 A • WEEE Directive 2012/19/EU
• RoHs Directive 2011/65/EU
Protections Overheating, overvoltage and overcurrent

Protection standard IP54 (according to EN 60529) Accessories


Logic controllers, switches, timers, • CNVT-PWM-010V converter
Temperature -20—40 °C potentiometers, converters & relay modules • PMW converter
Ambient conditions
Rel. humidity 0—80 % rH (non-condensing)
Combine with
• MTP-X10K potentiometer
Logic controllers, switches, • MTV series of potentiometers
Modbus registers timers, potentiometers, • DTA series
converters & relay modules • DTAP series
The  parameters of the  unit can be configured through • MCS series
the 3SModbus software platform. You can download it • EH2 series
from the following link: Electronic heater controllers • EH3 series
http://www.sentera.eu/english/hvac-software-downloads. • AH2 series
html
Sensors, sensor switches & Room sensors / switches
You can find register maps in the  mounting instructions. Download them from: Duct sensors / switches
sensor controllers Pressure transmitters
http:www.sentera.eu/products
For more detailed information about the product series features visit:
http://www.sentera.eu/english/download-catalogue.html

S.3.2.4 www.sentera.eu DS-EVSS-EN-000 - 15 / 02 / 16


EVSS
Electronic fan speed controller with TK

VR3 VR3
VR2 VR1
VR2 VR1
5 5 3 3 Settings
1 - DIP switch settings

Off Min.Off Max.


Min. Max.
level speed
level speed
speed speed
adj adj adj adj
adj adj ON – Descending mode:
ON
10—0 VDC / 20—0 mA
4 4 Ascending / descending
0 - 10v / 0 - 20 mA

0 - 10v / 0 - 20 mA
input mode selection
0 - 10v / 10 - 0v

0 - 10v / 10 - 0v
(DIP switch, position 1) OFF – Ascending mode:
1 2 3 4
0—10 VDC / 0—20 mA
Kickstart

Kickstart
Off level

Off level

ON ON - enabled
1 ON
1 ON
OFF level selection
(DIP switch, position 2)
1 2 3 4 1 2 3 4 OFF - disabled
1 2 3 4

7 7 8 8 ON ON – Kick start enabled


Front Front Front Front Kick start selection
cover cover cover cover (DIP switch, position 3)
1 2 3 4 OFF – Kick start disabled

ON – Current mode (0—20 mA /


ON
20—0 mA)
Input mode selection
(DIP switch, position 4)
1 2 3 4 OFF – Voltage mode (0—10 VDC /
10—0 VDC)

6 6
2 - Network bus resistor *
EVSS is the first or last unit
jumper (NBT)
NBT

NBT

VR1
2 2 Adjusts the maximum output voltage
3 - Max. speed trimmer from 175 VAC (left) to 230 VAC
(right)

VR2
Adjusts the minimum output voltage
4 - Min. speed trimmer from 69 VAC (left) to
161 VAC (right)

Wiring and connections


Ascending mode
L Supply voltage 230 VAC ± 10 % – 50 / 60 Hz

N Neutral Off value from 0 VDC (left) to 4 VDC


(right) in voltage mode
PE Earth terminal

L1 Unregulated output (230 VAC / max. 2 A) Off value from 0 mA (left) to 8 mA
VR3 (right) in current mode
U1, U2 Regulated output to the motor
5 - Off level value
TK, TK Thermal contacts trimmer Descending mode

N Neutral Off value from 10 VDC (left) to 6 VDC


(right) in descending and voltage
AL Alarm output (230 VAC / 1 A)
mode
SW Remote control switch

A Modbus RTU (RS485) signal A Off value from 20 mA (left) to 12 mA


(right) in descending and current
/B Modbus RTU (RS485) signal /B mode

+V Supply output +12 VDC / 1 mA


6 - Modbus communication
Ai Analogue input 0—10 VDC / 0—20 mA (10—0 VDC / 20—0 mA) Blinking green Transmitting / receiving
indication
GND Ground
7 - Overheating indication
Cable cross section  max. 2,5 mm2 Cont. red Motor overheating
(on the front cover)
Connections
Cable gland clamping range 3—6 mm / 5—10 mm
8 - Operating LED Cont. green Normal operation
Caution: If an AC power supply is used with any of the units in a Modbus network, the
indication
GND terminal should NOT BE CONNECTED to other units on the network or via the
(on the front cover) Blinking green Stand-by
CNVT-USB-RS485 converter. This may cause permanent damage to the communication
semiconductors and / or the computer!
* indicates open (OFF) position of the jumper.

S.3.2.4 www.sentera.eu DS-EVSS-EN-000 - 15 / 02 / 16


8
EVSS
Electronic fan speed controller with TK

Operational diagrams
Operating modes
Off level disabled Off level enabled

Uout,[%] Uout, [%]


100 100
Umax Off level
Umax
rangeUmax range Umax

75 75
70
70
Umin
Umin 2 range Umin
range Umin 2
30
30
0
10 VDC Ai,
0 20 mA [VDC] /
10 VDC Ai, Off level
Off level range
range [mA]
20 mA [VDC]/[mA]

Ai (
Descending mode calculation formula Uout = Umax - Aimax Umax - Umin) Descending calculation formula
Ai - Off level
Uout = Umax - Aimax (Umax - Umin)
- Off level
Ai (
Uout = Umin + Aimax Umax - Umin)
Ascending mode calculation formula Ai - Offlevel
Ascending calculation formula Uout = Umin + Aimax (Umax - Umin)
- Offlevel

Ascending / Descending input mode


Note: The operational diagrams for Descending mode are mirror images of the diagrams above for Ascending mode.

Kick start enabled Soft start enabled

Uout, [%] Uout, [%]

100 100
Ai, 10 VDC / 20 mA Ai, 10 VDC / 20 mA
Umax
range

Umax Umax Umax


Umax

0 VDC / 0 mA 0 VDC / 0 mA
range

range Umax range

75 75

70 70
2 1
range
range

Umin

Umin
Umin

Umin Umin
range Umin
Ai, 10 VDC / 20 mA range
1 OFF Level
0 VDC / 0 mA
30 30
Ai, 10 VDC / 20 mA
2 0 VDC / 0 mA
0 0
Kick starttime
Kickstart time t [s] Soft starttime
Softstart time t [s]

Kick start & off level Soft start & off level

Uout,[%]
Uout, [%]

100 100
Ai, 10 VDC / 20 mA Ai, 10 VDC / 20 mA
Umax
range

Umax
range

Umax 0 VDC / 0 mA Umax Umax 0 VDC / 0 mA


range Umax range

75 75

70 70
2 1
range
range

Umin
Umin

Umin Umin Umin


range Umin range
OFF Level OFF Level
30 30
Ai, 10 VDC / 20 mA
1 Ai, 10 VDC / 20 mA
2 0 VDC / 0 mA
0 VDC / 0 mA 0
0
Soft start time
Softstart time t [s]
Kick start time
Kickstart time t [s] Softstart time

1 - Descending mode Note: More details about EVS control functionalities you can find in our mounting instruction published on our site. Please follow the
link: http://www.sentera.eu
2 - Ascending mode

S.3.2.4 www.sentera.eu DS-EVSS-EN-000 - 15 / 02 / 16


9
EVSS
Electronic fan speed controller with TK

Operational diagrams
Timer mode Logic mode
Kick start enabled Switch control signal

Remote
Remote
Uout, [%] Switch,
Switch,
[VDC]
[VDC]
100
5 VDC
Umax
range Voltage
amplitude
75 range
range
2,5 VDC

0
0
Kick start time Operation timer Controller t [s] t, [s]
is off
Stand-by Operate
Operate

Soft start enabled

Switch control signal Ai control signal

Ai>2,4 VDC min. 30 ms min. 30 ms


SW

ON OFF ON OFF t ON OFF ON OFF t

Soft
start Soft
start

Holding Holding t
t Holding Holding
register register register register
18 18 18 18
Timer
Timer

t
Holding t Holding Holding
register register register
21 21 21
Output
Umax Output
Umax

Start Soft start Operation Stop Start Soft start Stop t Start Soft start Operation Stop Start Soft start Operation Stop t
duration timer duration duration timer duration timer

Fixing and dimensions Packaging


L W
4x

124 102
4,
50

Length Width Height Net Gross


140

Article Packaging
[mm] [mm] [mm] weight weight
205
EVSS1-15- Unit (1 pc.) 210 130 110 0,65 kg 0,81 kg
DM
Box (15 pcs.) 545 405 245 9,71 kg 13,05 kg
EVSS1-30- Unit (1 pc.) 210 130 110 0,69 kg 0,92 kg
DM
Box (15 pcs.) 545 405 245 10,33 kg 13,89 kg
EVSS1-60- Unit (1 pc.) 210 130 110 0,85 kg 1,02 kg
DM
Box (15 pcs.) 545 405 245 12,74 kg 15,39 kg
92
EVSS1100- Unit (1 pc.) 210 130 110 0,87 kg 1,04 kg
DM
Box (15 pcs.) 545 405 245 13,10 kg 16,44 kg