Lowest allowed bending radius

in accordance with DIN VDE 0298 part 3


Nominal voltage up to 0,6 / 1kV

Outer diameter of cable / Thickness of flat cable in mm

Cables for fixed installation up to over/up to over


10 mm 10-25 mm 25 mm

for fixed installation 4xd 4xd 4xd

for internal wiring 1xd 2xd 3xd

Outer diameter of cable / Thickness of flat cable in mm

Flexible cables up to over/up to over/up to over


8 mm 8-12 mm 12-20 mm 20 mm

for fixed installation 3xd 3xd 4xd 4xd

at free movement 3xd 4xd 5xd 5xd

at introduction 3xd 4xd 5xd 5xd

Flexible cables Outer diameter of cable / Thickness of flat cable in mm

at restricted guidance up to over/up to over/up to over


8 mm 8-12 mm 12-20 mm 20 mm

Drum operation 5xd 5xd 5xd 6xd


www.halleycables.com

Cable trolley operation 3xd 4xd 5xd 5xd

Drag chain operation 4xd 4xd 5xd 5xd

Roller deviation 8xd 8xd 8xd 8xd

HALLEY CABLES, Str. Siderurgistilor, nr. 9, 800364, Galati, Romania HALLEY CABLES and HALLEY CABLES logo are registered trademarks of HALLEY CABLES SRL
The above values correspond to the manufacturer's specifications and are not guaranteed. Tel. +40 236 319 000 Fax. +40 236 319 085 Created by HALLEY CABLES SRL