1(2) DATA SHEET

Conventional Dual Infrared


Flame Detector
EVC-IR
Part no. 001133 (STOCK No. 60044)

System: All Salwico Fire Alarm Systems

General description Ingress protection Depending on base


EVC-IR is an Evolution conventional flame Relative humidity ≤ 95% RH
detector with dual infrared wavelength sensors. non-condensing
Traditional UV and IR flame detectors, in their Temperature range -10°C to +55°C
singular form, are susceptible to unwanted alarms. Certified according to
These false alarm sources differ for each type of 0832-CPD-1081
flame detector, however with dual infrared Cover material ABS/PC alloy
detector both elements must receive an alarm Colour White
signal prior to initiating a fire alarm signal to the Weight ~130 g
fire control panel.
The low profile combined with the Omniview™ For information about suitable base plates, see
alarm indication makes the detector suitable for separate document “Base Matrix”.
sites with high architectural requirements.
Dimensions (mm)
Testing
For functional test, use Salwico IR Test lamp, part
no. 001156.

Data
Function Conventional
Nominal voltage 24 VDC
Working voltage 10–32 VDC
Working current < 130 µA
Alarm current Max 65 mA
Sensor viewing angle 100° Max (±50°)
Current for remote Max 2 mA
indication

The specifications described herein are subject to change without notice. Data sheet no. 001133 EVC-IR.11 4.I0E

www.cnsystem.se
DATA SHEET 2(2)

Connection

Figure 1. Connection for EVC-IR

Installation

Preventive measures
CAUTION!
The flame detector is sensitive to and may
have false alarms or no response when
exposed to the following false stimuli;
electric heater, incandescent light, halogen
light and direct sunlight.
Avoid the detector to be exposed for
these false stimuli sources.

The specifications described herein are subject to change without notice. Data sheet no. 001133 EVC-IR.11 4.I0E

www.cnsystem.se