Sas Io List

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 6

SL.No.

TAG DESCRIPTION DI DO
220kV SWITCHYARD
A 220KV TRAFO CIRCUIT BREAKER-1 Signal Description
1 SY-220-CB-PTR SY-220-CB-PTR -OPEN INDICATION
2 SY-220-CB-PTR SY-220-CB-PTR -CLOSE INDICATION
3 SY-220-CB-PTR SY-220-CB-PTR- LOCAL/REMOTE
4 SY-220-CB-PTR SY-220-CB-PTR DC-FAIL
5 SY-220-CB-PTR SY-220-CB-PTR -O/C PROTE. OPERATED
6 SY-220-CB-PTR SY-220-CB-PTR -O/C PROTE. FAULTY
7 SY-220-CB-PTR SY-220-CB-PTR -TR. DIFF. PROT. OPERATED
8 SY-220-CB-PTR SY-220-CB-PTR - TR. DIFF. RELAY FAIL
9 SY-220-CB-PTR SY-220-CB-PTR - TCS -1 FAULTY
10 SY-220-CB-PTR SY-220-CB-PTR -TCS-2 FAULTY
11 SY-220-CB-PTR SY-220-CB-PTR -LOSS OF SF6 LOCKOUT
12 SY-220-CB-PTR SY-220-CB-PTR - LOSS OF SF6 ALARM
13 SY-220-CB-PTR SY-220-CB-PTR -DC SUPPLY FAIL
14 SY-220-CB-PTR SY-220-CB-PTR -AC SUPPLY FAIL
15 SY-220-CB-PTR SY-220-CB-PTR -MAIN DC SUPPLY HELTHY
SY-220-CB-PTR -86 -1 /2 MASTER RELAY
16 SY-220-CB-PTR OPERATED
17 SY-220-CB-PTR SY-220-CB-PTR MANUL CLOSED
18 SY-220-CB-PTR SY-220-CB-PTR MANUAL TRIP
19 SY-220-CB-PTR SY-220-CB-PTR CLOSED FROM SCADA
20 SY-220-CB-PTR SY-220-CB-PTR TRIP FROM SCADA
21 SY-220-CB-PTR SY-220-CB-PTR -SPRINGE CHARGE

B ISOLATORS OF 220KV TRAFO PENAL-1


1 SY-220 LINE -ISO SY-220 LINE -ISO-1 OPEN/CLOSE
2 SY-220 LINE -ISO SY-220 LINE -ISO-1 REMOTE OPEN
3 SY-220 LINE -ISO SY-220 LINE -ISO-1 REMOTE CLOSED
4 SY-220 LINE -ISO SY-220 BUS -ISO OPEN/CLOSE
5 SY-220 LINE -ISO SY-220 BUS -ISO-1 REMOTE OPEN
6 SY-220 LINE -ISO SY-220 BUS -ISO-1 REMOTE CLOSED
7 SY-220 LINE -ISO SY-220 TRNS -ISO-1 OPEN/CLOSE

C EARTH SWITCH -1
1 SY-220 LINE -E/SW SY-220 LINE -EARTH SWITCH OPEN/CLOSE
1 SY-220 TRAS-E/SW SY-220 LINE -EARTH SWITCH OPEN/CLOSE

220KV LINE DIFF FEEDER CIRCUIT


D BREAKER-1 Signal Description
SY-220-CB-LINE SY-220-CB-LINE -OPEN INDICATION
SY-220-CB-LINE SY-220-CB-LINE -CLOSE INDICATION
SY-220-CB-LINE SY-220-CB-LINE- LOCAL/REMOTE
SY-220-CB-LINE SY-220-CB-LINE DC-FAIL
SY-220-CB-LINE SY-220-CB-LINE -O/C PROTE. OPERATED
SY-220-CB-LINE SY-220-CB-LINE -O/C PROTE. FAULTY
SY-220-CB-LINE SY-220-CB-LINE -LINE DIFF. PROT. OPERATED
SY-220-CB-LINE SY-220-CB-LINE -LBB PROT. OPERATED
SY-220-CB-LINE SY-220-CB-LINE -LINE DIFF. RELAY FAULTY
SY-220-CB-LINE SY-220-CB-LINE - TCS -1 FAULTY
SY-220-CB-LINE SY-220-CB-LINE -TCS-2 FAULTY
SY-220-CB-LINE SY-220-CB-LINE -LOW GAS PRE LOCKOUT SF6
SY-220-CB-LINE SY-220-CB-LINE - LOW GAS OF SF6 ALARM
SY-220-CB-LINE SY-220-CB-LINE -DC SUPPLY FAIL
SY-220-CB-LINE SY-220-CB-LINE -AC SUPPLY FAIL
SY-220-CB-LINE SY-220-CB-LINE -MAIN DC SUPPLY HELTHY
SY-220-CB-LINE SY-220-CB-LINE -86 -1 /2 MASTER RELAY
OPERATED
SY-220-CB-LINE SY-220-CB-LINE MANUL CLOSED
SY-220-CB-LINE SY-220-CB-LINE MANUAL TRIP
SY-220-CB-LINE SY-220-CB-LINE CLOSED FROM SCADA
SY-220-CB-LINE SY-220-CB-LINE TRIP FROM SCADA
SY-220-CB-LINE SY-220-CB-LINE -SPRINGE CHARGE
E ISOLATORS OF 220KV LINE DIFF FEEDER
SY-220 LINE -ISO-89A SY-220 LINE -ISO-1 OPEN/CLOSE
SY-220 LINE -ISO-89A SY-220 LINE -ISO-1 REMOTE OPEN
SY-220 LINE -ISO-89A SY-220 LINE -ISO-1 REMOTE CLOSED
SY-220 BUS -ISO-89A SY-220 BUS -ISO OPEN/CLOSE
SY-220 BUS -ISO-89A SY-220 BUS -ISO-1 REMOTE OPEN
SY-220 BUS -ISO-89A SY-220 BUS -ISO-1 REMOTE CLOSED

F 220KV LINE DIFF FEEDER EARTH SWITCH


SY-220 LINE -E/SW SY-220 LINE -EARTH SWITCH OPEN
SY-220 TRAS-E/SW SY-220 LINE -EARTH SWITCH CLOSE

G ANNUNCIATORS -LINE & TRANS PENAL


SY-220 LINE -ANN ANNUNCIATOR
SY-220 TRAS-ANN ANNUNCIATOR
H TVM
1 SY-220-TVM SY-220-TVM

I MFM
1 SY-220-MFM SY-220-MFM

J PQM
1 SY-220-PQM SY-220-PQM

K LINE/TRFO BCPU
1 SY-220-LINE-PTR-BCPU SY-220-LINE-PTR BCPU

L TRAFO DIFF PROT RELAY


1 SY-220-PTR-DIFF SY-220-PTR DIFF PROTECTION RELAY
SY-220-PTR-DIFF SY-220-PTR Bucholz Alarm
SY-220-PTR-DIFF SY-220-PTR Bucholz Trip
SY-220-PTR-DIFF SY-220-PTR MOG Alarm
SY-220-PTR-DIFF SY-220-PTR OSR Trip
SY-220-PTR-DIFF SY-220-PTR OTI Alarm
SY-220-PTR-DIFF SY-220-PTR OTI Trip
SY-220-PTR-DIFF SY-220-PTR PRV Trip
SY-220-PTR-DIFF SY-220-PTR WTI Alarm
SY-220-PTR-DIFF SY-220-PTR WTI Trip
SY-220-PTR-DIFF SY-220-PTR Differential Highset Trip
SY-220-PTR-DIFF SY-220-PTR Differential Trip
SY-220-PTR-DIFF SY-220-PTR REF Trip
MV SWITCHGEAR PANEL
M
INCOMER-1 to INCOMER-N
1 MC-MV-INC1 MCR-33KV-INC1-F1-VCB-ON/OFF 1
2 MC-MV-INC1 MCR-33KV-INC1-F1-LR SW LOCAL/REMOTE 1
3 MC-MV-INC1 MCR-33KV-INC1-F1-VCB-SPRING CHARGED 1
4 MC-MV-INC1 MCR-33KV-INC1-F1-VCB-E.STOP 1
5 MC-MV-INC1 MCR-33KV-INC-F1-VCB.IN SERVICE POS. 1
6 MC-MV-INC1 MCR-33KV-INC-F1-VCB.IN TEST POS. 1
7 MC-MV-INC1 MCR-33KV-INC1-F1-ISO-ON 1
8 MC-MV-INC1 MCR-33KV-INC1-F1-ISO-OFF 1
9 MC-MV-INC1 MCR-33KV-INC1-F1-VCB-TCH 1
10 MC-MV-INC1 MCR-33KV-INC1-F1-VCB-0C/EF 1
11 MC-MV-INC1 MCR-33KV-INC1-F1-ES-ON/OFF 1
12 MC-MV-INC1 MCR-33KV-INC1-F1-MASTER TRIP 1
13 MC-MV-INC1 MCR-33KV-INC1-F1-VCB-REMOTE ON 1
14 MC-MV-INC1 MCR-33KV-INC1-F1-VCB-REMOTE OFF 1
15 MC-MV-INC1 MCR-33KV-INC1-F1-VCB-86-RESET 1
16 MC-MV-INC1 MCR-33KV-INC1-F1-AC FAIL 1
17 MC-MV-INC1 MCR-33KV-INC1-F1-DC FAIL 1
18 MC-MV-INC1 ALL PROTECTION RELAY SIGNALS (SOFT)
19 MC-MV-INC1 ANNUNCIATOR
20 MC-MV-INC1 TVM
RS-485 AI IEC61850 REMARK

DI DO TCP/IP
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1

2
1
1
1
1
1

2
1
1
2
1
1
2

2
2

DI DO TCP/IP

1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
2

1
1
1
1
1

2
1
1
2
1
1

1
1

1
1

1
1
1
1
1
1
1
1
1
1
1
1
1

1
1
1