Professional Documents
Culture Documents
s2.0 S1359431119335434 Main
s2.0 S1359431119335434 Main
a
Department of HVAC, College of Urban Construction, Nanjing Tech University, P.O. Box 76, 210009 Nanjing, China
b
Department of Mechanical Engineering, School of Engineering, Aalto University, P.O. Box 14400, FI-00076 Aalto, Finland
HIGHLIGHTS
Keywords: An innovative airflow optimisation method applying tilted servers was introduced to improve the airflow dis-
Data centers tribution and cooling efficiency in data centers. The numerical data center model was established and simulated
Airflow management by Airpak 3.0 packages and validated with on-site measurements in Nanjing, China. In the analysis, different
Tilted servers server inclination angles and different heat load levels were simulated. The simulation model is validated well
Temperature distribution
with the on-site experimental results. The results show that the performance of airflow distribution and cooling
Rack hotspot
Local hotspot
efficiency can be improved with the application of 15° and 30° tilted servers, while the optimum thermal en-
vironment is achieved when the angle of servers is set to 30°. When the heat load of rack is 32 kW, the maximum
temperature reduces by 3.3 °C when the 30° tilted servers are used instead of 0° tilted servers. That decreases
significantly the temperature of rack hotspots and thus prevents local hotspots. Moreover, the heat transfer from
the rack is at least 5.7% more efficient with the rack applying 30° tilted servers compared with the 0° tilted
servers in all cases with different heat load. The heat transfer even improved 10% when the heat load is 32 kW in
each rack.
1. Introduction 12% [5,6]. In China, the power consumed by DCs in 2014 reached more
than 83 billion kWh, while the estimated DCs electricity consumption
Data centers (DCs) are centralized repositories housing computer will increase to approximately 140 billion kWh by 2020 [7,8]. Thus,
servers and associated data storage and telecommunications system for under the existing technology conditions, the increase of energy con-
data storage as well as data processing and transmitting. DCs have the sumption of DCs will be no doubt explosive in the near future.
characteristics of large scale and working 24/24, 365 days/year causing DCs are building synthesis equipped with many different instru-
potentially very high energy consumption [1]. During the past several ments mainly divided into four parts: IT equipment, cooling system,
decades, in order to satisfy the increasing demand of cloud computing, power supply equipment and safety & control systems. Fig. 1 illustrates
data storage and Internet use, the Information and Communications the composition of typical DCs [9,10]. Among them, IT equipment and
Technologies (ICTs) experienced a rapid development bringing ex- cooling system are two main parts occupying more than 80% of the
plosive energy consumption in DCs [2–4]. In fact, approximately 1.5% energy consumption within DCs [8]. Huge amount of data processing
of power generation of the whole world is consumed by DCs in 2010 and circulation results in tremendous electricity consumption, and a
and the annual growth rate of energy consumption in DCs is around large number of heats converted from the electricity, which needs to be
⁎
Corresponding author.
E-mail address: jxliu@njut.edu.cn (J. Liu).
https://doi.org/10.1016/j.applthermaleng.2019.114444
Received 22 May 2019; Received in revised form 20 August 2019; Accepted 24 September 2019
Available online 25 September 2019
1359-4311/ © 2019 Elsevier Ltd. All rights reserved.
X. Yuan, et al. Applied Thermal Engineering 164 (2020) 114444
Nomenclature servers, °C
t1 temperature difference between mean exhaust and supply
P static pressure air temperature with horizontal servers, K
T stress tensor tex mean exhaust air temperature with horizontal servers, °C
keff thermal conductivity ts mean supply air temperature with horizontal servers, °C
g gravitational acceleration vector r ratio of the heat removal ration between with 0° and 30°
S volumetric heat generation tilted servers, %
veff effective fluid viscosity. Q0 heat removal with 30° tilted servers in each case, kJ/h
U0 inlet airflow velocity, m/s Q1 heat difference taken away in the rack with horizontal
Qt tile flow rate, m3/s servers (0°), kJ/h
T0 inlet air temperature, °C
Qs server flow rate, m3/s Abbreviation
Ps server heat generation, W
σt perforated tiles porosity, % DC data center
σr rack porosity, % ICT Information and Communications Technology
Q generated heat, kJ/h CRACs computer room air conditioning units
cp specific heat capacity of air, kJ/(kg K) FB flexible baffle
m mass of air, kg CFD Computational Fluid Dynamics
t temperature difference, K CAC closed aisle containment
air density, kg/m3 SAT supply air temperature
v volume of air, m3 SST Shear Stress Transport
t0 exhaust mean temperature reduction with 0° and 30° tilted RSM Reynolds Stress Model
servers, K DES Detached Eddy Simulations
t 30° exhaust mean temperature of rack A8 with 30° tilted ser- RANS Reynolds-averaged Naiver-Stokes
vers, °C ER experimental result
t 0° exhaust mean temperature of rack A8 with horizontal SR simulation result
dissipated immediately. Otherwise, the temperature of computer ser- Investigation on airflow management methods are an upsurge in the
vers may rise dramatically threatening the operation safety of computer field of energy conservation in DCs. According to Tao et al. [18], air-
servers and malfunction [11,12]. Fig. 2 shows the breakdown of the flow management is defined as the way to maintain operating para-
energy consumption within typical DCs, and the IT equipment and the meters (IT equipment) within the recommended ranges with minimum
cooling requirements account for 44% and 40% of the total energy use, energy consumption. In recent years, researchers still have efforts on
respectively [13,14]. Thus, energy conservation in DCs can be achieved the airflow distribution optimisation methods to improve the thermal
by addressing IT load inefficiencies and improving cooling efficiency environment and achieve considerable energy saving within DCs. Yuan
[13]. It is reported that enhanced semiconductor technologies and et al. [16] proposed an innovative airflow organisation optimisation
server virtualisation can efficiently decrease the energy use of IT method applying flexible baffles (FBs) set in the front door of racks to
equipment [15], while the cooling efficiency in DCs can be improved in improve cooling efficiency and achieve energy conservation in DCs. The
many ways, such as airflow management, liquid cooling method, free results demonstrated that the use of FBs is an effective method to im-
cooling technologies, etc. [16]. At the moment, airflow management is prove airflow distribution and cooling efficiency within DCs, while the
considered as the most adopted method of improving energy efficiency optimal thermal environment appeared when the front doors of racks
in DCs. According to Cho et al. [17], airflow management is an operable were equipped with 20-cm FBs with 75° angle in the vertical direction.
and convenient way to reduce energy consumption and enhance Tatchell-Evans et al. [19] performed an experimental and theoretical
cooling efficiency and the thermal environment in DCs by changing investigation of bypass air in DCs employing cold aisle containments
computer room air conditioning units’ (CRACs) air supply conditions
and configuration of DCs.
Fig. 1. Main equipment in a typical data center. Fig. 2. The breakdown of energy consumption in typical DCs.
2
X. Yuan, et al. Applied Thermal Engineering 164 (2020) 114444
and its impact on energy consumption. The results demonstrated that 2.2. Experimental setup
the airflow bypass rate at typical cold aisle plenum pressures is about
20% increasing the flow rate demand of CRACs. If bypass airflow is In this study, experiments were carried out in July 2017 in the li-
minimized, the total energy consumption can be reduced about 8.8%. brary DC of Nanjing Tech University, Nanjing, China. The objectives of
In addition, excessive plenum pressure is not conductive to energy the experiments were to obtain the exhaust air temperature distribution
conservation, which increases energy consumption up to 16%. Ni et al. of the racks in an operating DC. According to the server running in-
[20] used CFD modelling to simulate the thermal distribution and air- formation over the whole year operation condition from the FM de-
flow conditions in a small DC and investigate the optimum airflow partment, rack A was selected for the study. Fig. 5 shows the heat load
distribution conditions. The results of CFD simulation showed that in of each rack in the rack A, and rack A1, A4 and A9 are not in operating
the optimal conditions high performing airflow distribution is reached. condition. In the experiments, rack A2 – A8 were selected to be the
Wibron et al. [21] used CFD software to compare the performance measured objectives. The location of temperature sensors is shown in
metrics of partial aisle containments and raised floor data center. They Fig. 6, describing the measurement arrangement and the locations pf
found that combining the performance metrics could improve the air- sensors. For each rack, there are installed 6 temperature sensors in the
flow distribution in the raised floor configurations. Huang et al. [22] rear door of the racks. The first temperature sensor is set 200 cm above
also established numerical model to compare and analyse the airflow the plenum, while the distance between the adjacent sensors is the
distribution in DCs with three different airflow patterns in 2017. The same, which is set as 300 cm. The supply air temperatures (SATs) of
results showed that compared to under-floor and row-level air supply rack A2-A8 through the plenum were measured with a hand-held air
pattern, rack level airflow pattern performed the best with highest flow anemometer. According to the measurement results, the SATs
cooling efficiency. As a result, the existing researches on the optimi- varied from 22 °C to 22.2 °C, while the supply air temperature of CRACs
sation of airflow organisation focused more on room-level and row- was set as 22 °C. Under this condition, the SATs of rack A2-8 were as-
level parameters optimisation instead of rack-level airflow optimisa- sumed to be the same, which was equal to the CRACs’ SAT of 22 °C.
tion. However, the cause of non-uniform airflow distribution in the DC
is from the servers within racks, thus more researches should focus on
the improvement of cooling efficiency and new method of airflow dis- 2.3. Experimental condition and measuring instruments
tribution within the rack.
The novelty of this paper is to tilt the servers and change 4 different To improve the reliability and obtain more accurate experimental
tilting angles (15°, 30°, 45° and 60°) to change the direction of cold results, there were carried out together 9 experiments between 15th
airflow so that the cooling efficiency and thermal environment can be July and 17th July, while each day was divided into three groups of the
improved and the temperature of rack hotspots and the possibility of morning, afternoon and evening experiments. Each measurement case
potential local hotspots can be reduced in DCs. The objectives of this was lasted 2 h. Thus, 9 groups of experimental results were obtained
paper are to: (i) develop a CFD DC model to Airpak 3.0 packages, (ii) during three days. The results were the average value of all measured
validate the CFD model based on the real DC in Nanjing, China, (iii) values (average of three days data, except of experimental data with
apply the CFD model to the DC scenarios where the servers are placed large deviation).
evenly and with different tilted angles, and (iv) with different tilt angles, Type-K thermocouples of nickel-chromium-silicon were used as the
optimize power of servers. The organization of this paper is as follows. In temperature sensor, which were connected to the Agilent 34972A data
Section 1, the recent development status of DCs and the investigations of acquisition logger. This Agilent data acquisition logger recorded the
airflow management strategy are summarized, and the innovation of our exhaust air temperature of each sensors and transferred the data to a
airflow optimisation method is carried out. Then, Section 2 introduces personal computer. The specific parameters of the thermocouples and
the studied DC and the experimental setup. In Section 3, the simulation handheld air flow anemometer were shown in Table 2. The temperature
information is described in detail mainly including CFD model, para- data was received by Agilent data acquisition logger every 10 s, which
meter settings, grid independent test, simulation conditions, boundary meant there were approximately 720 temperature data for each test
conditions, etc. In Section 4, the CFD model is validated by the experi- point after 2-h measurement time. Thus, the temperatures of each test
mental data, and then new CFD models with evenly placed servers with point during the 2-h measurement time were the arithmetic mean of
different inclination angles are established. The simulation results with 720 data avoiding the interference of transient temperature fluctuation
different server placement and different racks’ heat load are discussed on the actual exhaust air temperature distribution.
and compared, while Section 5 draws the conclusions.
2. Methodology
3
X. Yuan, et al. Applied Thermal Engineering 164 (2020) 114444
The main research object was the exhaust air temperature of racks;
thus both the steady-state and unsteady-state flow fields were needed
be calculated in the simulation process. According to Ni et al [20] and
Alkharabsheh et al. [24], compared to k-ω turbulent model, Shear
Stress Transport (SST) and Reynolds Stress Model (RSM), the k-ε tur-
bulence model performed better in terms of overall operation perfor-
mance, accuracy, simulation time and coincidence degree with ex-
periments. The simulation model is selected as described in our
previous paper [16]. Wibron et al. [25] recently examined the perfor-
mance of k-ε turbulence model, the Reynolds Stress Model (RSM) and
Detached Eddy Simulations (DES) in CFD modelling of data centers.
They concluded that RSM turbulent model has higher precision than k-ε
turbulence model and spent fewer solution times than DES turbulent
model. However, up to now, the standard k-ε turbulence model has
been adopted widely and performed well [13,24,26–29]. Standard k-ε
turbulence model is adopted with an enhanced wall function, followed
by a finite-volume approximation of the Reynolds-averaged Naiver-
Stokes (RANS) [26–27,30].
Fig. 5. Heat load of each rack in rack A9. Some assumptions were set as described in our previous works
4
X. Yuan, et al. Applied Thermal Engineering 164 (2020) 114444
Table 2 Ì¿
(u ) + u · u = p+ ·(T ) + g
Specific parameters of thermocouples and air flow anemometer. t (2)
Items Type Measuring range Uncertainty
(h ) + ·(h u ) = ·[keff T ] + S
Thermocouple Type-K 0–400 °C ± 0.4% t (3)
Handheld air flow KIMO Temperature: ± 0.4%
Anemometer VT200/ −20 °C to 80 °C The Stress tensor T is given by
FC300 Velocity: 0.15–30 m/s ± 2.0% Ì¿
T = veff · u (4)
·u = 0 (1)
The boundary conditions are the same as our previous paper [16].
5
X. Yuan, et al. Applied Thermal Engineering 164 (2020) 114444
Table 4
Parameter settings for boundary conditions [16].
Boundary conditions Symbol Equation Value
Table 3
Simulation model’s specifications and boundary conditions [23].
Objects Type Dimension/cm × cm (×cm) Quantity Remark
6
X. Yuan, et al. Applied Thermal Engineering 164 (2020) 114444
Table 5 respectively. Thus, 574,938 and 1,098,659 are selected as the mesh
Parameters setting of each scenario. number in the simulations for the scenario 1 and the scenario 2 and 3,
Scenario Heat load per rack (kW) Tilted angle (°) respectively. It should be emphasised that Fig. 9 is quoted from our
previous research [16,23]. According to CFD Airpak3.0, the mesh
Scenario 1 8 0 quality can be checked after grid generation, while the quality of 99%
Scenario 2 8 Case I 0
meshes can meet the software requirement.
Case II 15
Case III 30
Case IV 45
Case V 60 4. Results and discussions
Scenario 3 Case1 8 0 X
Case2 12
The simulation is divided into 3 scenarios. In scenario 1, the si-
Case3 16
Case4 20 mulation model is validated with the experimental data. In scenario 2,
Case5 24 some changes are made in the servers’ heat load and tilting angles. Rack
Case6 28 A7 and A8 were selected as the studied racks, where each equipped
Case7 32
with 8 one-kW servers placed evenly. Then, the optimum angle and
exhaust temperature distribution can be obtained by adjusting the
horizontal angle (0°, 15°, 30°, 45°, 60°) of servers. Under this circum-
maximum temperatures with grid number in the scenario 1 and the
stance, the optimal angle is record as X°. Based on scenario 2, scenario 3
scenario 2 and 3, respectively. The object maximum temperature
studied the exhaust air distribution optimisation and energy saving
reaches the minimum and is stable when the mesh numbers are no less
potential between the model with 0° servers and X° servers under 7
than 574,938 and 1,098,659 for the scenario 1 and the scenario 2 and 3,
different heat load levels of server.
Fig. 8. Side view of servers’ position in one rack with different angles.
7
X. Yuan, et al. Applied Thermal Engineering 164 (2020) 114444
Table 6
The different mesh numbers for the scenario 1 and the scenario 2 and 3 applied in the simulation.
Category Mesh numbers
In the scenario 2, the total heat load for each rack is 8 kW. The
simulation results in the scenario 2 are shown in Fig. 14. It could be
noted that there are obvious heat accumulations at the bottom of both
rack A7 and A8 in Case I. The highest temperature of rack A7 and A8 is
Fig. 10. Mesh sensitivity analysis of object maximum temperatures variations 28.0 °C and 28.4 °C, respectively. According to our previous work [16],
with grid number in scenario 2 and 3. rack hotspots were defined as the highest exhaust air temperature
points in each rack, which were the most possible locations that could
4.1. Statistical analysis and validation study damage the servers once the temperature of rack hotspot is higher than
45 °C and become local hotspot [34]. According to ASHRAE Technical
In the experiment part, after data sorting of 9 exhaust temperature Committee (TC) 9.9 [34], the existence of local hotspots leads to non-
data sets, 7 groups of them were saved for the arithmetic values of each uniform air distribution, which would shorten operational life span of
test point. The measurement data from the morning of 16th July and servers and increase the energy use in DCs. Thus, although the highest
the evening of 17th July where neglected because of a big difference
from other sets of data. For the rest 7 groups of experimental data, Table 7
standard deviation of them in each measuring points of Racks A2-8 was Sensitivity analysis of 7 groups of temperature data in each measuring points of
done. As shown in Table 7, the standard deviation of temperature Racks A2-8.
measuring point 1 in Rack A7 was the largest of 0.33, while those of the Standard deviation A2 A3 A4 A5 A6 A7 A8
rest measuring points were no more than 0.2. All the standard devia-
1 0.09 0.15 0.05 0.08 0.08 0.33 0.10
tions of 42 measuring points were small and acceptable. Thus, the ar-
2 0.05 0.12 0.05 0.12 0.16 0.20 0.10
ithmetic mean of these 7 groups of exhaust temperature data sets can be 3 0.00 0.00 0.05 0.05 0.14 0.10 0.08
used as the actual temperature values in each measuring points. The 4 0.14 0.05 0.05 0.05 0.13 0.15 0.08
arithmetic values of each test point are presented in Fig. 11 as the solid 5 0.13 0.09 0.05 0.04 0.14 0.08 0.05
lines. 6 0.05 0.04 0.10 0.05 0.08 0.08 0.06
8
X. Yuan, et al. Applied Thermal Engineering 164 (2020) 114444
Fig. 11. Comparison of temperature value of six outlet measuring points in rack Fig. 13. The relative error of 6 test points in rack A8 between experimental and
A2 - A8 between experimental (solid line) and simulation (dotted line) results. simulation results.
temperature of rack A7&A8 could not reach the level of the local hot- terminal of servers which is shown in Fig. 15. In addition, as shown in
spot, the risk of server damage should be prevented. Moreover, the Fig. 14 of Case I, a high percentage of bypassing air flows directly from
exhaust air distribution of rack A7 and A8 were still non-uniform. A the upper side of the rack where no server is placed. Thus, the cool air
more uniform air distribution can decrease the energy consumption supplied to the bottom of the rack is limited, causing the heat accu-
within DCs. mulated at the bottom of the rack.
As shown in Fig. 14, the maximum exhaust air temperature of rack However, the application of 30° tilted servers in Case III keep the
A7 and A8 are 28.0 °C and 28.4 °C in Case I. The exhaust air tempera- tilted angle of servers and the inlet cool air direction of the rack basi-
ture decreased to the lowest points of 26.7 °C and 26.8 °C in Case III, cally the same. Moreover, the occupied spaces of inclined servers inside
respectively. There is an increase of the maximum air temperature of the rack are larger than servers of Case I to reduce the bypassing effect.
29.4 °C and 29.6 °C, in Case Ⅴ. In addition, the heat accumulation of It can be seen in Fig. 15 of Case III that although a part of cool air is still
Case Ⅳ and Case Ⅴ are different to those in Case I-III. blocked by the servers, the cool air flows along the upper and lower
The reasons for the abnormal heat accumulation are can be depicted sides of the servers, and then the cool air inclines downward and dis-
in Fig. 15. Due to the similar server angle, the exhaust air distribution of sipates the heat at the terminal of the servers. The most direct effect of
Case II and Case III are similar, while the exhaust air distribution of the application of 30° tilted servers is shown in Fig. 14 of Case III, where
Case Ⅳ and Case Ⅴ are similar too. Fig. 15 just shows the velocity vector the temperature of rack hotspot of rack A8 decreases from 28.4 °C in
of rack A8 in Case I, Case III and Case Ⅴ. In Case I, the cool air from the Case I to 26.7 °C in Case III, and the heat accumulation of rack A8 is
vents inclines upward into rack A8 and a part of the cool air is blocked reduced and the highest temperature rises to the middle of the rack.
by the servers, while the rest of the cool air flows through the tunnel In Fig. 15 of Case Ⅴ, when the tilted angle of servers continues rising
between the servers in a horizontal direction. A small part of the cold to 60° in Case Ⅴ, the distance between neighbouring servers decreases
air flowing through the channel take away the heat from the terminal of greatly and almost stick together, which blocks the flow pattern of cool
the servers, while the rest become bypass cold air and flow out of the air extremely. Considering that the height of rack cannot be changed,
rack. Under this circumstance, the heat removal by the cool air is very the distance between adjacent tilt servers cannot be increased. The cool
limited in Case I. The heat accumulation zone always exists in the air rises up to the top and cross the top server, which can be regarded as
Fig. 12. The simulation results of exhaust air temperature distribution of rack A2-A8.
9
X. Yuan, et al. Applied Thermal Engineering 164 (2020) 114444
Fig. 14. The cloud map of exhaust air temperature of rack A7 and A8 in the scenario 2 with different server tilted angles.
Fig. 15. The air flow direction of Case I, Case III and Case.
1
For interpretation of color in Fig. 17, the reader is referred to the web
Fig. 16. The velocity magnitude sketch of Case Ⅴ in scenario 2. version of this article.
10
X. Yuan, et al. Applied Thermal Engineering 164 (2020) 114444
Fig. 17. Minimum-maximum range and mean temperature of rack A7 and A8.
Fig. 18. The mean and maximum temperature reduction of rack A8 with 0° and
30° tilted servers.
11
X. Yuan, et al. Applied Thermal Engineering 164 (2020) 114444
Table 8 liquid-cooled data centers: from chip to the cooling system, Appl. Energy 205
The temperature parameters between server inclination angle of 0° and 30° in (2017) 1165–1188.
scenario 3. [9] S.V. Patankar, Airflow and cooling in a data center, J. Heat Transfer 132 (7) (2010)
073001.
Case 1 2 3 4 5 6 7 [10] Y. Joshi, P. Kumar, Energy Efficient Thermal Management of Data Centers, Springer
Science & Business Media, 2012.
Heat load of each rack (kW) 8 12 160 20 24 28 32 [11] J. Siriwardana, S.K. Halgamuge, T. Scherer, W. Schott, Minimizing the thermal
Mean temperature drop (K) 0.21 0.35 0.48 0.64 0.82 1.11 1.44 impact of computing equipment upgrades in data centers, Energy Build. 50 (2012)
81–92.
Maximum temperature of rack A8 28.4 31.4 34.2 36.9 39.9 42 45.3
[12] T. Ding, Z.G. He, T. Hao, Z. Li, Application of separated heat pipe system in data
with 0° servers (°C)
center cooling, Appl. Therm. Eng. 109 (2016) 207–216.
Maximum temperature of rack A8 26.8 29.1 32.2 34.3 37.4 38.8 42.0
[13] A. Almoli, A. Thompson, N. Kapur, J. Summer, H. Thompson, G. Hannah,
with 30° servers (°C) Computational fluid dynamic investigation of liquid rack cooling in data centers,
Appl. Energy 89 (2012) 150–155.
[14] H. Zhang, S. Shao, H. Xu, H. Zou, C. Tian, Free cooling of data centers: a review,
Table 9 Renew. Sustain. Energy Rev. 35 (2014) 171–182.
[15] R. Cushing, L. Doherty, Next Generation Data Centers, MSC Business Development
The heat removal capacity with 0° and 30° tilted servers in case 1-7. LTD., 2009.
Case 1 2 3 4 5 6 7 [16] X. Yuan, Y. Wang, J. Liu, X. Xu, X. Yuan, Experimental and numerical study of
airflow distribution optimisation in high-density data center with flexible baffles,
Build. Environ. 14 (2018) 128–139.
Cp [kJ/(kg K)] 1
[17] J. Cho, J. Yang, W. Park, Evaluation of air distribution system's airflow performance
m (kg/h) 1.29 kg/m3·0.24 * 3600 m3/h = 1114.6 kg/h
for cooling energy savings in high-density data centers, Energy Build. 68 (2014)
Δt1 (K) 3.5 5.4 7.6 9.2 11 12.6 14.4
270–279.
Δt0 (K) 0.2 0.35 0.5 0.7 0.85 1.1 1.5 [18] T. Lu, X. Lü, M. Remes, M. Viljanen, Investigation of air management and energy
Q0 (kJ/h) 223 392 559 783 950 1118 1678 performance in a data center in Finland: case study, Energy Build. 43 (2011)
Q1 (kJ/h) 3900 6018 8470 10,253 12,260 14,043 16,049 3360–3372.
r (%) 5.7 6.5 6.6 7.6 7.7 8.0 10 [19] M. Tatchell-Evans, N. Kapur, J. Summers, H. Thompson, D. Oldham, An experi-
mental and theoretical investigation of the extent of bypass air within data centers
employing aisle containment, and its impact on power consumption, Appl. Energy
186 (2017) 457–469.
Acknowledgement [20] J. Ni, B. Jin, B. Zhang, X. Wang, Simulation of thermal distribution and airflow for
efficient energy consumption in a small data centers, Sustainability 9 (2017) 664,
This work is supported by the National Natural Science Foundation https://doi.org/10.3390/su9040664.
[21] E. Wibron, A. Ljung, T.S. Lundström, Comparing performance metrics of partial
of China (Grant No. 51806096) and Natural Science Foundation
aisle containments in hard floor and raised floor data centers using CFD, Energies
of the Jiangsu Higher Education Institutions of China (Grant No. 12 (2019) 1473, https://doi.org/10.3390/en12081473.
18KJB560007). We acknowledge the help from Information Center of [22] Z. Huang, K. Dong, Q. Sun, L. Su, T. Liu, Numerical simulation and comparative
analysis of different airflow distributions in data centers, Proc. Eng. 205 (2017)
Nanjing Tech University for providing on-site experimental sites.
2378–2385.
[23] X. Yuan, X. Zhou, J. Liu, Y. Wang, R. Kosonen, X. Xu, Experimental and numerical
Appendix A. Supplementary material investigation of an airflow management system in data center with lower-side
terminal baffles for servers, Build. Environ. 155 (2019) 308–319.
[24] S. Alkharabsheh, J. Fernandes, B. Gebrehiwot, D. Agonafer, K. Ghose, A. Ortega,
Supplementary data to this article can be found online at https:// Y. Joshi, B. Sammakia, A brief overview of recent developments in thermal man-
doi.org/10.1016/j.applthermaleng.2019.114444. agement in data center, J. Electron. Packag. 137 (2015) 1–19.
[25] E. Wibron, A.L. Ljung, T.S. Lundström, Computational fluid dynamics modelling
and validating experiments of airflow in a data center, Energies 11 (2018) 644,
References https://doi.org/10.3390/en11030644.
[26] Z. Song, Thermal performance of a contained data center with fan-assisted per-
[1] B. Durand-Estebe, C.L. Bot, J.N. Mancos, E. Arquis, Simulation of a temperature forations, Appl. Therm. Eng. 102 (2016) 1175–1184.
adaptive control strategy for an IWSE economizer in a data center, Appl. Energy [27] S.W. Ham, J.W. Jeong, Impact of aisle containment on energy performance of a data
134 (2014) 45–56. center when using an integrated water-side economiser, Appl. Therm. Eng. 105
[2] V. Depoorter, E. Oro, J. Salom, The location as an energy efficiency and renewable (2016) 372–384.
energy supply measure for data centers in Europe, Appl. Energy 140 (2015) [28] E. Cruz, Y. Joshi, Coupled inviscid-viscous solution method for bounded domains:
338–349. application to data-center thermal management, Int. J. Heat Mass Transf. 85 (2015)
[3] K. Ebrahimi, G.F. Jones, A.S. Fleischer, A review of data center cooling technology, 181–194.
operating conditions and the corresponding low-grade waste heat recovery op- [29] L. Phan, C. Lin, A multi-zone building energy simulation of a data center model with
portunities, Renew. Sustain. Energy Rev. 31 (2014) 622–638. hot and cold aisles, Energy Build. 77 (2014) 364–376.
[4] S. Sevencan, G. Lindbergh, C. Lagergren, P. Alvfors, Economic feasibility study of a [30] ANSYS, ANSYS Fluent User’s Guide, Release 15, ANSYS, Inc., Canonsburg, PA,
fuel cell-based combined cooling, heating and power system for a data center, 2013.
Energy Build. 111 (2016) 218–223. [31] Fluent Inc, Airpak 3.0 User’s Guide, Fluent Inc, Lebanon, 2007.
[5] J.G. Koomey, Growth in Data Center Electricity Use 2005 to 2010, Analytics Press, [32] K. Zhang, X. Zhang, S. Li, G. Wang, Numerical study on the thermal environment of
Oakland, CA, 2011. UFAD system with solar chimney for the data center, Energy Proc. 48 (2014)
[6] R. Brown, et al., Report to Congress on Server and Data Center Efficiency: Public 1047–1054.
Law 109-431, Lawrennce Berkeley National Laboratory, 2007, https://doi.org/10. [33] S. Nada, H. El-Batsh, H. Elattar, N. Ali, CFD investigation of airflow pattern, tem-
2172/929724. perature distribution and thermal comfort of UFAD system for theatre buildings
[7] J. Whitney, P. Delforge, Data Center Efficiency Assessment, Natural Resources applications, J. Build. Eng. 6 (2016) 274–300.
Defense Council, New York, 2014. [34] ASHRAE, Thermal guideline for liquid cooled data processing environments, White
[8] A.H. Khalaj, S.K. Halgamuge, A review of efficient thermal management of air-and paper prepared by ASHRAE Technical Committee (TC) 9.9, 2015.
12