Professional Documents
Culture Documents
Ag 200005
Ag 200005
INTRODUCTION
Loss-of-Potential (LOP) logic must operate faster than distance or directional elements for true
LOP conditions while not operating for system fault conditions. New ELOP setting options of
the SEL-321 Relay enable new LOP logic which meets both of these operational criterion while
simplifying the relay setting task. The purpose of this guide is to describe the new LOP logic and
to identify applications where you should consider changing from the traditional LOP logic to the
new LOP logic.
Because this new LOP function operates in less than one-half cycle, distance element security is
much less dependent on the supervisory overcurrent elements. These overcurrent elements may
be set to their minimum pickup if desired. (Always check that the minimum overcurrent
thresholds are set below minimum fault levels to ensure correct distance relay operation.) If the
intended application has high load with a low power factor (e.g., pf ≤ 0.9), use the
load-encroachment feature of the relay for additional LOP security during high-load conditions.
Many protective relays and control devices include LOP logic to detect the loss of one or more
incoming ac potential circuits. Fuses or molded case breakers protect the power system voltage
transformers (vts) against short circuits in the secondary wiring (external to the vts). In those
applications using fuses to protect the vt secondary circuits, one, two, or all three fuses can blow
and remove the ac potential from the relay. In the case of molded case circuit breakers, all three
potentials are removed from the relay at once regardless of the type of load-side short circuit. For
this reason, protective relays should include LOP logic which detects the loss of all three potential
inputs.
Molded case breaker (MCB) protection without LOP detection logic is commonplace in many
existing applications where older technology relays use negative-sequence voltage. The
reasoning for this MCB preference was twofold: 1) someone could not accidentally leave one
fuse out of service, and 2) if a short circuit did develop on the vt secondary, the MCB removed all
three potentials. In both cases the magnitude of negative-sequence voltage (V2) is zero. Since
these older relays require a minimum amount of V2 to operate, the loss of all three phase
potentials effectively blocks their operation. This same minimum V2 threshold also limited their
fault resistance coverage [1].
The logic in Figure 1 discriminates between faults (which may reduce voltage magnitudes to
nearly zero) and loss-of-potential. Note that the voltage and current thresholds are user settable
and require some degree of setting coordination. The following equation shows the LOP
detection logic in Boolean form:
SET LOP1 = [NOT(50QF + 50QR) * 59QL] Detects the presence of negative-sequence
voltage in the absence of negative-sequence
current.
+ [NOT(59PL) * NOT(50M)] Detects the absence of positive-sequence
voltage in the absence of current above the
50M setting.
Where:
50QF Low-set, negative-sequence overcurrent detector2
50QR Low-set, negative-sequence overcurrent detector2
50M Medium-set, phase overcurrent element
59QL Low-set, negative-sequence overvoltage detector
59PL Low-set, positive-sequence overvoltage detector
* Logical AND
+ Logical OR
Note 1: If ELOP = Y, ILOP (Internal Loss-of-Potential) follows the state of LOP.
Note 2: The relay uses these fault detectors for the negative-sequence directional element
supervision.
The new logic is based upon measuring a decrease in the magnitude of positive-sequence voltage
without a simultaneous change (magnitude or angle) in either the positive-sequence or the
zero-sequence currents. Figure 2 gives an overview of the improved LOP logic.
No
No
∠ I1
Yes
changing?
No
|I0|
Yes
changing?
No
Yes
∠ I0 Declare
END Yes No
changing? LOP
5
Measure positive-sequence current angle (∠I1k) and compare it to ∠I1(k - 1 cycle) from one
cycle earlier. If this difference is greater than 5°, then the condition measured is not an
LOP even if Steps 1 and 2 and the conditions in the next steps are met. This input is
labeled as ∆∠I1 > 5° in Figure 8. If |I1| < 0.05 • INOM, this angle check does not block
LOP.
4. Zero-sequence current magnitude is not changing.
Measure zero-sequence current magnitude (|I0k|) and compare it to |I0(k - 1 cycle)| from one
cycle earlier. If this difference is greater than 10% of nominal, the condition measured
is not an LOP even if all other conditions are met. This input is labeled as ∆|I0| > 10%
in Figure 8.
5. Zero-sequence current angle is not changing.
Measure zero-sequence current angle (∠I0k) and compare it to ∠I0(k - 1 cycle). If this
difference is greater than 5°, the condition measured is not an LOP even if all other
conditions are met. This input is labeled as ∆∠I0 > 5° in Figure 8. For security this
declaration requires that |I0| be greater than 1.6% of INOM to override an LOP
declaration.
If the criteria identified in all five steps listed above is met, the improved LOP logic declares an
LOP condition. This LOP condition is reset when balanced voltages at near “nominal” levels are
restored to the relay. The factory default setting for nominal secondary voltage is 57 VL-N
(100 VL-L). To change the nominal voltage, set the LPVNOM setting in the calibration access
level to match your application. The setting range for LPVNOM is 30–100 VL-N secondary.
The most onerous system condition to discriminate between faults and LOP conditions is one
where the end-of-line fault duty is below load. The traditional LOP logic work-around for this
has been to adjust the positive-sequence voltage threshold such that the phase overcurrent
element (50M in Figure 1) picks up for a fault where the 59PL element is dropped out. However,
you may not be able to achieve a suitable positive-sequence voltage threshold when transmission
lines are electrically short, heavily loaded, and the positive-sequence source impedance behind
the relay location is weak. Figure 3 shows a system single line diagram of an application that
illustrates this problem.
Relay 1 Relay 2
m=0 m=1
Table 1 lists the positive-sequence voltage and current values seen by Relay 1 for the three
system conditions in Figure 3:
1. Maximum load with no fault,
2. Three-phase fault at m = 0,
3. Three-phase fault at m = 1.
From Table 1, we see that the maximum load condition requires you to set the 50M element
pickup greater than 3.92 A secondary (in the traditional LOP scheme). Given a typical setting
margin of 10%, this dictates setting 50M > 4.31 A secondary. For the three-phase fault values
shown in Table 1, the 50M element never picks up for forward faults. Referring back to Figure 1,
the three-phase LOP sets when the 59PL and 50M elements are both dropped out. Because 50M
is never picked up in this application, and a three-phase fault at m = 0 gives us V1 = 0 V, we see
that you cannot set 59PL low enough to avoid setting ILOP for a three-phase fault immediately in
front of the relay. In this situation the traditional LOP blocks the phase distance and directionally
controlled phase overcurrent elements. Another tripping solution for the fault at m = 0 would be
to use non-directional phase overcurrent elements since these elements do not rely on voltage
quantities. However, this solution is spoiled by the fact that the phase-current magnitude for
faults behind the relay location (reverse faults) is greater than that for faults in front of the relay
location (forward faults). Non-directional elements do not give fault direction discrimination for
this application and therefore cannot be used for tripping without further qualification such as a
time delay.
The traditional loss-of-potential logic must be disabled for applications such as the one just
described.
For the fault shown in the Figure 4, no fault current flows through the healthy line due to the
equal sources (equal voltages at both line ends) and the fault placement. With the traditional LOP
logic, the healthy line relays measure negative-sequence voltage and no negative-sequence
current for unbalanced faults. These measurements undesirably set the traditional LOP logic
during a midline fault. This traditional LOP logic then prevents the relays on Line 1 from
tripping if the fault evolves from Line 2 to Line 1. If the fault evolves before the LOPD timer
expires, the traditional LOP logic does not set and the undesirable LOP latching does not occur.
If the fault does not evolve to Line 1, the traditional LOP logic resets when the relay is presented
with balanced phase voltages.
The new LOP logic does not latch for any of these scenarios. During the fault on Line 2, the
relays on the healthy line measure a decrease in positive-sequence voltage while neither the
positive-sequence or zero-sequence current magnitudes or angles change (no load case). For this
situation, LOP asserts but is not latched for 60 cycles. This 60-cycle delay is adequate time for
the relaying on the faulted line to detect the fault and trip the associated breakers. Please note
that this is a special case where both lines have the same impedance and the source strengths on
either line end are exactly equal. In a traditional LOP scheme, LOP latches (based on
negative-sequence voltage with no negative-sequence current) for the relays on the unfaulted
line with no opportunity to reset if the fault evolves to Line 1.
BUS S BUS R
LINE 2
52-3 52-4
SOURCE S SOURCE R
Relay 3 Relay 4
Fault
m = 0.5
LINE 1
52-1 52-2
Relay 1 Relay 2
For the fault shown in Figure 5, very little or no current flows in three of the four breakers shown.
Let us assume the protection scheme is using a communications-assisted tripping scheme.
The traditional LOP logic sets at Relays 2–4. Setting the traditional LOP forces the relay
directional declarations to forward. This declaration makes all forward reaching negative-
and zero-sequence directional elements non-directional–67Q2 and 67N2, respectively. After
Breaker 1 opens, the fault current redistributes and flows through both lines. The desired
breaker for tripping in this case is Breaker 2. However, since Relays 2–4 measure fault current
magnitudes above their 67N2/Q2 element thresholds, and these elements are non-directional, the
communication tripping scheme trips the healthy line breakers. If the line relaying is not using
communications-assisted tripping, Line 2 does not trip if the scheme is properly time coordinated.
BUS S BUS R
LINE 2
52-3 52-4
SOURCE S
Relay 3 Relay 4
LINE 1
52-1 52-2
Relay 1 Relay 2
Fault
Figure 5: Single-Line Diagram for One Source Systems (or Weak Source at Bus R)
One onerous event, which causes vt secondary fuses to blow, is when someone drops a metal tool
across two fuses (see Figure 6). If only one fuse blows, the relay is still presented with full phase
voltage on all three fuses. However, two of these phase voltages presented to the relay are the
same. LOP logic which only checks the magnitude of each phase voltage presented to the relay
cannot detect this condition. Both the traditional and the improved LOP logic detect this
condition and assert LOP. The new LOP logic detects a drop in positive-sequence voltage
without a corresponding change in positive- or zero-sequence current thereby causing ILOP to
set.
To Relay
blown
vt
Recall that it is very desirable for the LOP logic not to set for system fault conditions. Figure 7
shows an application example where a tower bypass jumper fails and drops the B-Phase
conductor onto the lower A-Phase conductor. The protection scheme tripped Breakers 1 and 2 for
the initial fault. Reclosing Breaker 1 does not create a fault condition, as Breaker 2 must close to
complete the short circuit of phases A and B.
If the relaying scheme at Breaker 2 uses line side vts, closing Breaker 1 does not set ILOP as this
action causes an increase in positive-sequence voltage. For this scenario, the traditional LOP
scheme sets when Breaker 2 is open due to the presence of negative-sequence voltage without
negative sequence current. Setting LOP for this event is undesirable as it prevents the distance
and directional protective elements from tripping high-speed upon closing Breaker 2. With bus
side vts, closing Breaker 2 does cause a drop in positive-sequence voltage but the increase in
current prevents ILOP from setting.
Crossed Conductors
A
Open Phase
Breaker 1 Breaker 2
11
Improved LOP Logic Diagram
Refer to Figure 8 for the location of the Logic Points described below.
Logic Point ! This point is a logical one when |V1| is less than 90% of |V1| one cycle earlier.
This comparator threshold of 0.9 is appropriate for speed and security. The
LOP logic must be fast enough to detect blown fuses and issue an LOP block
before any protective elements which use voltages in their trip decision can
operate. The higher the threshold compare, the quicker that Logic Point 1
asserts for blown potential fuse conditions. However, a higher threshold risks
false LOP declarations. The magnitude of V1 must be greater than 5 V to
enable -∆|V1| detection.
The plots shown in Figure 9 and Figure 10 illustrate the need for rapid LOP declarations when the
protected line is carrying full load. Figure 9 shows the positive-sequence voltage and current
magnitudes (secondary quantities), respectively. For our example, we presented the relay with
69.4 V secondary, and the nominal secondary current of 5 A ∠-33.8° before removing all phase
voltages. In this application, we set the Zone 1 reach to 80% of a 15.6 Ω secondary line: Z1P =
12.48 Ω.
Notice from the upper plot of Figure 9 that the positive-sequence voltage drops to 90% of 69.4 V
(62.82 V) in approximately one quarter cycle or two relay processing intervals. The -∆|V1|
criterion is satisfied before Cycle 0.25.
Positive-Sequence Voltage Magnitude
80
69.4 V
Secondary Volts
70
62.82 V
60
50
-.5 0 .5 1 1.5 2 2.5
4
Secondary Amps
0
-2 -1 0 1 2 3 4 5 6 7 8 9
Cycles
20
Reach Required to Detect Fault
15 Zone 1
Threshold
10 AB BC
CA
0
-.5 0 .5 1 1.5 2 2.5
Cycles
Figure 10: Distance Element Operating Speed Slower Than LOP Logic Speed
For LOP conditions which occur during heavy load and high-load angles, the distance elements
operate faster than for heavy load conditions with unity power factor. In these instances, the LOP
logic is still faster than the distance elements. As an additional measure of security, we
recommend that you enable and set the Load-Encroachment (LE) logic. The LE logic uses the
magnitude and angle of the measured positive-sequence impedance (Z1). The LE logic drops out
when one of the following two conditions are satisfied:
Criterion 1. |Z1| is less than the LE magnitude (ZLF for load-out, ZLR for load-in).
Criterion 2. NLAF < ∠Z1° < PLAF, where PLAF defines the upper load angle boundary
for forward load and NLAF defines the negative load angle boundary for
reverse load.
Figure 11 plots positive-sequence impedance magnitude vs. time for a three-phase LOP condition
and load of 5 A ∠30°. In this example, Criterion 1 was the condition met to dropout the LE
element. Notice from Figure 11 that the LE element drops out at 0.375 cycles. The new LOP
logic pickup time is unaffected and asserts before Cycle 0.25. Thus, enabling the LE logic
ensures a secure margin between asserting the improved LOP logic output and the pickup of the
distance elements.
14
13
Z1 Magnitude (Ohms)
Load-Encroachment
12
Magnitude Threshold
11
10
8
-.5 0 .5 1 1.5 2 2.5
Cycles
The instantaneous output of Logic Point 2 is routed to the LOP and ILOP logic points via the OR
gate of Logic Point 3. Please note that the instantaneous output does not latch LOP or ILOP to
account for the case of no-load breaker opening operations where line-side vts are used. In this
situation, the ∆I logic (Logic Point 5) always gives a logical zero output. To address the concern
of giving a false sealed-in ILOP, we use the output of the 3PO and SPO logic in the seal-in
circuit. If we do get a false ILOP (due to slow SPO and 3PO conditions related to breaker
auxiliary contact speed), it is not sealed-in and is squelched by 3PO or SPO becoming a logical
one. Relay Word bit 3PO is the output of a time-delayed pickup (TDPU), instantaneous dropout
timer. The 60-cycle time delay of Logic Point 2 ensures that any false LOP condition is
squelched by either the assertion of 3PO or SPO for the situation described, or the output of Logic
Point 5 for the cases described below. The LOP output is also a bit in the Relay Word for you to
use for control and monitoring purposes. In the relay setting procedure, you may disable the loss-
of-potential logic by setting ELOP (Enable Loss-of-Potential) = N1. The ELOP = N1 setting
option permits easy testing and commissioning of the relay in cases where this LOP logic may
block protection element operation.
Logic Point # This logic point is the output of a two input OR gate. One input is from the
undelayed Logic Point 2, and the other is from the output of the S/R flip-flop.
The output of the S/R flip-flop, Q, is a logical one when the S and not the R
input asserts. If both the S and R inputs assert simultaneously, then the R
input has priority and Q is not true.
Logic Point & The purpose of this logic is to reset the ILOP and LOP logic once valid
three-phase voltages are restored to the relay. A valid voltage condition is
one where |V1| > 88% of the LPVNOM setting, the magnitude of the
zero-sequence voltage (V0) is less than 9% of LPVNOM, the magnitude of
positive-sequence voltage is not decreasing, and that the magnitude of each
phase voltage is greater than 90% of LPVNOM. To ensure that this condition
is not transient, the logic requires balanced voltage conditions be present for
one cycle.
Logic Point ' This logic resets the LOP logic when the breaker is judged open by the single-
pole or three-pole open logic and there was not an LOP condition during the
last processing interval. If the relay detects a LOP condition, you must restore
balanced three phase voltages to the relay to reset LOP. This new LOP logic
does not give a nuisance alarm when the breaker is open and the application
uses line-side vts.
Logic Point ( This logic point is the output of a two-input logical OR gate. One input is a
one cycle delayed Logic Point 6. The others are the single-pole and three-pole
open logic. The status of this logic point is routed to the RESET input of the
LOP S/R flip-flop. When Logic Point 8 is true, ILOP and LOP are both reset.
1.a. Line-side vts: For the situation of a bolted fault with zero volts on all three phases, both V1
now and V1 from one cycle earlier are zero. Since this delta voltage is <10%
of VNOM secondary, the ILOP cannot set.
There are multiple security guards for this situation. However, the ultimate
security guard is the fact that the current magnitude is changing by more than
10% when the breaker is first closed. Note that Logic Point 5 has a 60-cycle
dropout time such that the relay blocks LOP for one second after the breaker
is closed into a fault.
To avoid setting ILOP for this situation, the logic relies upon the ∆I
magnitude and angle checks. The only situation where the ∆I check is not
sufficient is when there is no current. This scenario is found in weak-source
applications and also replicates the case where an operator transfers the
potential source to a deenergized bus from a live bus.
Again, the ultimate security guard is the fact that the current magnitude is
changing by more than 10% when the breaker is first closed.
2.a. Line-side vts: For the situation of normal load interruption, where the voltage is decreasing
to zero volts on all three phases, V1(k) is zero while V1(k - 1 cycle) is non-zero for
one cycle after the breaker opens. This V1 ratio check matches that of a true
three-phase loss-of-potential.
Again, the ∆I magnitude and angle checks avoid setting ILOP for this
situation. Here we know the current magnitude is decreasing, so the ∆I1
logic asserts to block setting ILOP. The 60-cycle time-delayed-dropout timer
blocks ILOP to ensure that there is not a race condition between the |V1| ratio
check logic and the ∆I detection logic (Logic Point 5). In the case of no-load
breaker opening operations, the ∆I logic gives a logical zero output. To
address the concern of giving a false ILOP, the relay uses the output of the
3PO logic in the four input AND gate labeled as 6. If the 3PO logic point
does not assert before 1 asserts (due to slow 52a contacts), the ILOP
declaration is only transient because it is not sealed-in for 60 cycles.
2.b. Bus-side vts: This situation is simple because |V1| increases or remains the same. In
addition, the ∆I logic gives additional security except in the case where there
is no load. Again, in the case of no-load, the ∆I logic gives a logical zero
output. To address any concern of giving a false ILOP, we again use the
output of the 3PO logic as discussed above.
3.a. Line-side vts: See 2.a. The logic does not give a false ILOP as fault conditions which cause
a drop in |V1| are associated with ∆I conditions.
3.b. Bus-side vts: See 2.a. The logic does not give a false ILOP as fault conditions which cause
a drop in |V1| are associated with ∆I conditions.
REFERENCES
[1.] Jeff Roberts, Edmund O. Schweitzer, III, Renu Arora, and Ernie Poggi, “Limits to the
Sensitivity of Ground Directional and Distance Protection,” 50th Annual Georgia Tech
Protective Relaying Conference, Atlanta, GA, May 1–3, 1996.
FACTORY ASSISTANCE
The employee-owners of Schweitzer Engineering Laboratories are dedicated to making electric
power safer, more reliable, and more economical.
We appreciate your interest in SEL products, and we are committed to making sure you are
satisfied. If you have any questions, please contact us at:
Schweitzer Engineering Laboratories
2350 NE Hopkins Court
Pullman, WA USA 99163-5603
Tel: (509) 332-1890
Fax: (509) 332-7990
We guarantee prompt, courteous, and professional service.
We appreciate receiving any comments and suggestions about new products or product
improvements that would help us make your job easier.
All brand or product names appearing in this document are the trademark or registered trademark of their respective holders.
Schweitzer Engineering Laboratories, SELOGIC, Connectorized, Job Done, and are registered trademarks of Schweitzer Engineering Laboratories.