The following table lists recommendations for each suction line based on the minimum and maximum cooling capacity.
GAS LINE EVAPORATOR SUCTION COMPRESSOR GAS LINE EVAPORATOR SUCTION COMPRESSOR
R-449A / R-452A / R-404A R-134a
Evap.
Diameter Minimum Cooling capacity max. (kW) for a temperature drop of saturation 1 K, Minimum Cooling capacity max. (kW) for a temperature drop of saturation 1 K,
temp.
line Cooling as equivalent to length of line Cooling as equivalent to length of line
ºC
capacity capacity
(kW) 10 m 15 m 20 m 25 m 30 m 40 m 50 m (kW) 10 m 15 m 20 m 25 m 30 m 40 m 50 m
3/8" 0.2 1.3 1.0 0.9 0.8 0.7 0.6 0.5 0.2 0.8 0.7 0.6 0.5 0.4 0.4 0.3
1/2" 0.5 3.2 2.6 2.2 1.9 1.7 1.5 1.3 0.5 2.0 1.6 1.4 1.2 1.1 0.9 0.8
5/8" 0.9 6.1 4.9 4.2 3.7 3.3 2.8 2.5 0.9 3.8 3.1 2.6 2.3 2.1 1.8 1.6
Evaporation temperature: 0 ºC
3/4" 1.4 10.1 8.1 6.9 6.1 5.5 4.7 4.2 1.5 6.4 5.1 4.4 3.9 3.5 3.0 2.6
7/8" 2.0 15.8 13 11 9.6 8.7 7.4 6.5 2.2 10 8.0 6.9 6.1 5.5 4.7 4.1
High temperature
3/4" 1.2 7.0 5.6 4.8 4.3 3.9 3.3 2.9 1.2 4.3 3.4 2.9 2.6 2.3 2.0 1.8
7/8" 1.7 11 8.8 7.5 6.7 6.0 5.1 4.5 1.8 6.7 5.4 4.6 4.1 3.7 3.1 2.8
Positive temperature
1" 2.5 15 13 11 9.7 8.8 7.5 6.7 2.6 9.9 7.9 6.7 6.0 5.4 4.6 4.1
1 1/8 " 3.5 19 18 15 13 12 10 9.1 3.0 11 10.8 9.2 8.1 7.4 6.3 5.5
1 3/8 " 5.5 28 28 25 22 20 17 15 5.0 16 17 16 14 12 11 9.4
1 5/8 " 9.0 40 40 40 36 33 28 25 7.5 23 24 25 22 20 17 15
2 1/8 " 18 70 70 70 70 69 59 52 15 41 42 43 44 42 36 32
2 5/8 " 30 105 105 105 105 105 101 90 25 62 63 64 65 66 62 55
3 1/8 " 50 155 155 155 155 155 155 146 40 90 91 92 93 94 95 89.7
3 5/8 " 65 200 200 200 200 200 200 200 60 120 121 122 123 124 125 126
4 1/8 " 90 265 265 265 265 265 265 265 75 150 151 152 153 154 155 156
3/8" 0.2 0.4 0.3 0.3 0.2 0.2 0.2 0.2
1/2" 0.3 1.0 0.8 0.7 0.6 0.5 0.4 0.4
Suction pipe selection
5/8" 0.5 1.8 1.5 1.3 1.1 1.0 0.9 0.8 Given a cooling capacity at a determined evaporating temperature, it is
Evaporation temperature: -30 ºC
3/4" 0.9 3.1 2.5 2.1 1.9 1.7 1.4 1.3 necessary to select the pipe that includes this capacity value between
the minimum recommended value for the pipe and the maximum
Negative temperature
5/8" 0.8 3.1 2.5 2.1 1.9 1.7 1.4 1.3 � High and positive temperature: 10 mm
Evaporation temperature: -30 ºC
3/4" 1.3 5.1 4.1 3.5 3.1 2.8 2.4 2.1 � Negative temperature (Evap. temp.: -30 ºC): 20 mm
7/8" 1.8 8.0 6.4 5.5 4.9 4.4 3.7 3.3
Calculation basis
1" 2.5 11 9.4 8.0 7.1 6.4 5.5 4.9
This calculation method developed by INTARCON is provided for
1 1/8 " 4.0 14 13 11 9.7 8.8 7.5 6.6 guidance only and it is the responsibility of the designer to carry
1 3/8 " 6.0 20 20 19 16 15 13 11 out the appropriate checks. The calculation is only valid for the pre-
1 5/8 " 10 30 30 30 26 24 20 18 dimensioning of refrigerant lines in copper piping for refrigeration use.
2 1/8 " 18 50 50 50 50 50 43 38 The maximum cooling capacities indicated for each case correspond
to a pressure drop of 1 K at saturation temperature, with a gas
2 5/8 " 30.0 75 75 75 75 75 75 66
velocity limit of 15 m/s (data in blue).
3 1/8 " 50.0 110 110 110 110 110 110 110 The minimum recommended cooling capacities for the suction lines
3 5/8 " 70.0 150 150 150 150 150 150 150 correspond to a minimum velocity of 4 m/s at medium and high
4 1/8 " 100.0 200 200 200 200 200 200 200 temperature, 5 m/s at low temperature.
All data ratings have been calculated based on a condensing
temperature of 45 °C, evaporator superheat of 10 K and expansion
valve subcooling of 0 K or 40 K for liquid subcooled at low
temperature.
www.intarcon.com
calculation method
Recommendations
In designing the layout of the refrigerant lines the following practices are recommended:
• Design the layout as straight as possible, with the minimum number of elbows, diversions
and valves.
• Install a trap in vertical runs of suction line every 3 meters.
• Install the horizontal sections of the suction line in a downward slope towards the
compressor.
• Evaporators refrigeration connections to the intake manifold must always be conducted
through the top of the units.
5 m x 7/8"
1/4"
3 m x 7/8"
3 m x 3/4 "
1/4"
3 m x 7/8"
3 m x 7/8"
1/4"