Professional Documents
Culture Documents
Fill Fluid Slytherm Technical Datasheet
Fill Fluid Slytherm Technical Datasheet
SYLTHERM 800
Heat Transfer Fluid
800
In The United States And Canada: 1-800-447-4369 • FAX: 1-517-832-1465
In Europe: +31 20691 6268 • FAX: +31 20691 6418
In The Pacific: +886 2 715 3388 • FAX: +886 2 717 4115
In Other Global Areas: 1-517-832-1556 • FAX: 1-517-832-1465
http://www.dow.com/heattrans
NOTICE: No freedom from any patent owned by Seller or others is to be inferred. Because use conditions and applicable laws may differ from one location
to another and may change with time, Customer is responsible for determining whether products and the information in this document are appropriate for
Customer’s use and for ensuring that Customer’s workplace and disposal practices are in compliance with applicable laws and other governmental
Product Technical Data
enactments. Seller assumes no obligation or liability for the information in this document. NO WARRANTIES ARE GIVEN; ALL IMPLIED WARRANTIES OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE EXPRESSLY EXCLUDED.
NOTE: SYLTHERM heat transfer fluids are manufactured by Dow Corning Corporation and distributed by The Dow Chemical Company.
28 1
*
Printed in U.S.A. *Trademark of The Dow Chemical Company NA/LA/Pacific: Form No. 176-01435-1097 AMS
Europe: CH 153-046-E-1097
LC
Condensate
CONTENTS SYLTHERM 800 Heat Transfer Fluid␣ Figure 21 — Typical Liquid Phase Heating Scheme
Steam
▼
Introduction ................................................................................ 3 Using SYLTHERM Fluid
Performance................................................................................. 3
Steam Condensate
Cooling Process
(450˚F) (232˚C) Process Fluid
Fluid Selection Criteria␣ .......................................................................... 4
Pump
Heating or
▼
▼
TIC
Equilibrium and Operating Pressures .......................................... 5 ▼
▼
▼
▼
Simplified Schematic for Loop Design ....................................... 7
TRC
FI
PI
Circulating Pump
Steam
Flammability and Fire Hazards................................................ 8, 9 ▼
PRV
Steam Generator
Cooling Loop
Stm. Hdr.
▼
Heat Exchanger
▼
▼
New System Start-up␣ ........................................................................... 10
(380˚F) (193˚C)
PIC
PRV
#2
▼
▼
Process Fluid
Health and Safety Considerations␣ ...................................................... 11
▼
▼
▼
Vent
(375˚F) (191˚C)
LC
Customer Service␣ ................................................................................. 11
▼
▼
▼
▼
Vent
Instrument Air Lines
Fluid Analysis ............................................................................ 11 ▼
▼
Retrofill ..................................................................................... 12
Process Tank
Electrical Lines
Shipping Limitations ................................................................ 12
▼
Storage and Shelf-life ................................................................ 12
▼
Packaging................................................................................... 12
Circulating Pump
Properties and Engineering Characteristics␣
Jacket Loop
FI
▼
▼
TIC
Physical Properties .................................................................... 12
▼
English Units ................................................................ 13
Vent Header
TIC
SI Units ........................................................................ 13
Liquid Saturation Properties ▼ ▼ ▼
▼
English Units ................................................................ 14
▼ ▼
▼
LI
Figure 2
PRV
Thermal Conductivity .............................................................. 16
Process Fluid
Pressure Indicating Controller
SeeExpansion
PCV
Tank
Vent
▼
Calculated Heat of Vaporization .............................................. 17
▼
▼
N2
▼
▼
Vapor Pressure ........................................................................... 18
LAH/L
LSL
#1
Specific Heat ............................................................................. 19 ▼ ▼
▼
▼
Heat Exchanger
▼
Pressure Switch High
Pressure Relief Valve
PRV
Pressure Switch Low
Circulating Pump
Density ...................................................................................... 20
▼
▼
Heating Loop
Pressure Indicator
TRC
▼
Viscosity .................................................................................... 21
FRC
▼ ▼
▼
▼
▼
▼
Vent
Engineering Data␣
▼
TIC
Spare Pump
7
FSL
▼ ▼ ▼
Liquid Film Coefficient
SYLTHERM Fluid
English Units ................................................................ 22
Heater for
SI Units ........................................................................ 23
TSH
Pressure Drop ▼
▼ ▼
BA
BC
BE
English Units ................................................................ 24
1
–
–
–
–
–
–
–
–
▼
To Pilot Light
SI Units ........................................................................ 25
PRV
PSH
TRC
TSH
PSL
PSH
PIC
TIC
PI
Thermal Expansion ................................................................... 26
Typical Liquid Phase Heating Scheme ..................................... 27
PI
Flow Indicator (Orifice)
PI
Pressure Control Valve
▼
PSL
For Information About Our Full Line of Fluids... ▼ ▼
PCV
Snuffing Stm.
Flow Switch Low
To learn more about the full line of heat transfer fluids manufactured
Level Controller
Fuel Gas
Burner Control
or distributed by Dow — including DOWTHERM* synthetic
Burner Alarm
Instrument Legend
organic, SYLTHERM† silicone and DOWTHERM, DOWFROST*,
TIC
Media
▼
Call the number for your area listed on the back of this brochure.
LI
Atm.
Vent
Cond.
*Trademark of The Dow Chemical Company
▼
BA –
BC –
BE –
FI –
FRC –
FSL –
LC –
PVC –
▼
†Trademark of Dow Corning Corporation
▼
▼
▼
27
▼
2 ▼
Loading
Pump
▼
Figure 19 — Thermal Expansion of Liquid SYLTHERM 800 Fluid (English Units) SYLTHERM 800 A Virtually Odorless, SYLTHERM 800 heat transfer fluid
Basis: 1 gallon at 75°F Heat Transfer Fluid Long-lasting provides excellent high-temperature
stability. It is capable of operating
2.0 Heat Transfer Fluid more than 10 years at 750°F (400°C)
without the fouling or periodic
SYLTHERM† 800 fluid is a highly reprocessing problems associated
1.8 stable, long-lasting, silicone fluid with other heat transfer media.
designed for high-temperature liquid-
phase operation. It has a recommended Performance
operating temperature range of
1.6 -40°F (-40°C) to 750°F (400°C).
Expanded Volume, gallon
■ Long life
ented formulation. Systems using
SYLTHERM 800 fluid require no
■ Noncorrosive
periodic venting; therefore, the low-
Figure 20 — Thermal Expansion of Liquid SYLTHERM 800 Fluid (SI Units) ■ Low acute oral toxicity molecular-weight linear and cyclic
Basis: 1 cubic meter at 25°C ■ Low odor siloxanes that result from the
■ Non-reportable under SARA
rearrangement remain part of the
2.0
Title III, Section 3131 heat transfer media and do not cause
system fouling. The rearrangement
that occurs with SYLTHERM 800 heat
1.8 transfer fluid is not a degradation
reaction and does not affect fluid life.
1.6
Expanded Volume, m3
1.4
1.2
1.0
26 3
FLUID SELECTION CRITERIA fer properties. Because it exhibits 1000°F (538°C) with low or no Figure 18 — Pressure Drop vs. Flow Rate of SYLTHERM 800 Fluid in Schedule 40 Nominal Pipe and
low potential for fouling, large flow, polymer cross-linking may BWG Tube (SI Units)
Stability correction factors for fouling in occur. This will eventually cause
heat transfer coefficient calcula- the fluid viscosity to increase,
SYLTHERM 800 fluid offers good tions are not needed (a fouling requiring fluid replacement. Some
thermal stability at temperatures up factor of 0.0001 (hr)(ft2)(°F)/Btu problem areas to be avoided 1,000
to 750°F (400°C). The maximum [1.45 x 10 -5 m2 K/W] is commonly include:
recommended film temperature is used). Additionally, the unique
800°F (427°C). 1. Flame impingement.
rearrangement chemistry of
m
Freeze Point SYLTHERM 800 heat transfer fluid 2. Operating the heater above its
25m
can offset the viscosity increases rated capacity.
SYLTHERM 800 fluid has a minimum characteristic of heat transfer fluids SC
m
3. Modifying the fuel-to-air mixing HE
pumpability temperature less than
38m
as they age. The result is that, DU
procedure to change the flame LE
m
-40°F (-40°C). throughout its life, the film heat 40
50m
height and pattern. This can PI
PE
Low Odor, Non-reportable transfer coefficient of SYLTHERM 800
yield higher flame and gas
heat transfer fluid can remain as
m
75m
The chemical composition of temperatures together with 100
good as, or can improve above, the
mm
SYLTHERM 800 fluid makes it a higher heat flux.
original fluid values.
100
preferred choice for users with the 4. Low fluid velocity/high heat flux
Three key areas of focus for heat
mm
need for low odor. Additionally, areas resulting in excessive heat
transfer operations are designing
150
SYLTHERM 800 has no components transfer fluid film temperatures.
12 m
and operating the heater and/or 3.0
currently listed as reportable under
mm
G, 2m
SARA Title III, Section 313.1 energy recovery unit, preventing The manufacturer of the fired
BW , 1
2.5
18 BWG
SYLTHERM 800 is not a hazardous chemical contamination, and heater should be the primary
19 m
eliminating fluid contact with air contact in supplying you with the
mm
G, 19m
product as defined in the OSHA
16
2.0
Hazard Communication Standard. and water. proper equipment for your heat
BW G,
25 m
16 4 BW
transfer system needs.
mm
G, 5m
ec)
When units are operated at high TU
BW G, 2
10 1.5
Thermal Stability
m/s
BE
1
temperatures, fluid velocities in Contamination and SI
Y(
16 W
ZE
heaters should be a minimum of Oxidation Effects
CIT
14
The thermal stability of a heat 6 feet per second (2 m/s); a range
LO
At elevated temperatures, SYLTHERM
of 6 to 12 feet per second (2 – 4 m/s) 1.0
VE
transfer fluid is dependent on 800 heat transfer fluid is sensitive to
many factors. Properly maintained should cover most cases. The actual
contamination. Contamination by
SYLTHERM 800 heat transfer fluid velocity selected will depend on an
acids or bases can result in accelerated
can be aged continuously at 750°F economic balance between the
rates of volatile by-product formation.
(400°C) for more than 10 years cost of circulation and heat transfer
Contamination by water, oxygen,
before it needs replacement. Longer surface.
or other oxidants can result in cross- 0.5
fluid life can be expected in systems Operating limitations are usually linking of polymer molecules, and,
operating at lower temperatures. 1.0
placed on heat flux by the equip- if not corrected, can cause a gradual 0.00001 0.0001 0.001 0.01 0.1
Heat Transfer Capability ment manufacturer. This heat flux increase in viscosity. Flow Rate, m3/sec
is determined for a maximum film
The exceptional thermal stability of It is important that contamination
temperature by the operating
SYLTHERM 800 heat transfer fluid be minimized. Potential sources of Temperature Correction
conditions of the particular unit.
results in uniquely stable heat trans- contaminants such as water, steam, Multiplier Factor
3.5
Heater Design and Operation process material, atmospheric air,
and humidity should be appraised
Poor design and/or operation of the 3.0
and modifications made where
fired heater can cause overheating
necessary.
Multiplication Factor
2.5
and will eventually cause the fluid’s
viscosity to increase to a point 2.0
1
where replacement of the fluid
You may need to comply with similar or
additional legislation in other countries.
is necessary to restore system 1.5
0.5
-1 0 1 2 3 4 5
Temperature, °C x 100
4 25
Figure 17 — Pressure Drop vs. Flow Rate of SYLTHERM 800 Fluid in Schedule 40 Nominal Pipe and Equilibrium and fluid to meet your process require- lower than the equilibrium vapor
BWG Tube (English Units) Operating Pressures ments. (For a copy of this brochure, pressure of the fluid for a given
please contact your nearest Dow temperature, periodic venting of the
G, 1 /2 "
SYLTHERM 800 heat transfer fluid
/2 "
representative or call the number for volatile materials will take place.
BW , 1
TU
BE does not have a distinct boiling point.
18 BWG
SIZ your area listed on the back of this The fluid will suffer no deleterious
E Its molecular weight distribution
brochure.) effect; however, periodic additions
G, 3 /4 "
50 10
16
/4 "
shifts with time at high temperatures,
B W G, 3
of new fluid will be needed to
affecting vapor pressure, viscosity, In some system designs, lower
16 BW
c)
8 maintain system volume.
/se
G, 1"
flash point, and freeze point. Once expansion-tank pressures than those
1"
14
(ft
B W G,
the fluid composition reaches equi- derived from the curves in Figures 7 An inert gas (such as nitrogen)
TY
16 BW
CI
6 librium at a temperature (usually a and 8 (page 18) are required because blanket on the expansion tank is
14
LO
matter of months), an “equilibrium of equipment design constraints. required to prevent the fluid from
VE
vapor pressure” can be measured. This method of operation results in coming into contact with the outside
10 4 venting of low-molecular-weight air. Without this inert gas blanket,
As supplied, SYLTHERM 800 heat
volatile materials from the system, humid, outside air is likely to be
transfer fluid exhibits a low vapor
3 which requires periodic make-up drawn into the tank whenever the
pressure. With time at high temper-
with new fluid. Contact your nearest system cools below its normal
atures, the previously described
Dow representative or call the number operating temperature. This
rearrangement reaction results in
Pressure Drop, psi/100 foot of pipe
for your area listed on the back of moisture contamination can result
a gradually rising vapor pressure.
this brochure for assistance if you in increased pressure in the system
Ultimately, the silicone components
plan to design your system with due to steam formation on the next
reach an equilibrium composition
pressures below the curves in Figures heat-up cycle. To avoid this, the
2 and exhibit an equilibrium vapor
7 and 8. inert gas supply regulator should be
pressure.
adjusted and maintained at a low
1.0 Expansion Tank
The curves on page 18 represent setting of 3 to 5 psi (0.2 to 0.3 bar).
typical equilibrium pressures for Figure 2 (page 7) is a simplified This will minimize both the inert
1"
SYLTHERM 800 heat transfer fluid. schematic of a recommended system gas consumption and the additive
In practice, operating pressures in loop design for SYLTHERM 800 heat effects of the blanket gas on total
the expansion tank are often higher transfer fluid. The expansion tank system pressure.
/2 "
11
SC due to the additive effect of other point in the system and has the
HE equilibrium silicone vapor pressure
DU gases such as the nitrogen blanket capability for full flow of the heat
LE that SYLTHERM 800 heat transfer
3"
1.0
0.5
-1 0 1 2 3 4 5 6 7 8
Temperature, °F x 100
24 5
If the expansion tank is designed as tank, some of these materials will Second, the inert gas blanket on Figure 16 — Liquid Film Coefficient of SYLTHERM 800 Fluid Inside Pipes and Tubes (Turbulent Flow Only)
shown in Figure 2, the back pressure be vented out of the system. Since the expansion tank should allow (SI Units)
regulator setting on the expansion these materials are largely respon- for a continuous flow of inert gas to
tank will control the pressure at the sible for the vapor pressure exerted be purged through the vapor space 3,000
entrance to the pump. The regula- by SYLTHERM 800 heat transfer fluid, during the initial start-up. Separate
tor set point should be a minimum of their removal will enable system inert gas supply and discharge
10 to 15 psi (0.7 to 1.0 bar) above the operating pressures below those nozzles, spaced as far apart as
vapor pressure corresponding to the shown by the curves in Figs. 7 and 8. possible, will help ensure that any
SCH
m
fluid temperature in the expansion volatile contaminants (such as water EDU
25m
The rate of venting will be deter- LE 4
m
0 PIP
tank. or solvents) will be swept from the E
38m
m
mined primarily by the system
50m
system during initial start-up.
m
NPSH requirements are primarily temperature profile and the setting
mm
75m
satisfied by the elevation of the of the back pressure regulator. The vent lines from the safety relief
100
mm
expansion tank. The elevation is Several systems using SYLTHERM 800 valve and back pressure regulator
150
determined by calculating the total heat transfer fluid are operating should be discharged to a safe area 3.0
head necessary to overcome frictional at pressures below the pressure- away from open flame and other
line losses and specific NPSH require- temperature curves (Figs. 7 and 8) potential sources of ignition. An 2.5
Film Coefficient,W/m2 K
ments of the pump. In systems where providing process service tempera- appropriate outside container located 1,000
such tank elevation is not practical, tures that would not be possible well away from building air-intake 2.0
NPSH requirements can be met with competitive heat transfer fans is recommended. The vented
by increasing the amount of the fluids in the equipment as designed. volatile materials will be typically
1.5
ec)
blanket gas (usually nitrogen) in the For additional details on how to classified as flammable.
m/s
vapor space of the expansion tank, design a system with operating
The expansion tank should be sized
Y(
thereby increasing the overall pressures below this line, as well
so that it is approximately 1⁄4 full
CIT
pressure in the tank. However, the as comments on its expected
when the system is at ambient 1.0
LO
12m m
additional system pressure created operational fluid loss rates, contact
m
temperature, and 3⁄4 full when the
VE
BW , 12
by the nitrogen should be accounted your nearest Dow representative or
19m m
m
system is at its maximum operating
G, mm
18 BWG
G,
for during the system design. call the number for your area listed
m
BW , 19
25m
temperature. Expansion tank instru-
BW G, 25
on the back of this brochure.
G,
16 BWG
In some cases, design constraints, mentation and fittings must meet the
16
W
such as permissible process vessel Whether the loop is designed to design requirements of the anticipated
14
TU
B
BE
pressures, limit the maximum allow- operate as a closed system or at a operating temperatures and pressures
14
SIZ
16
E 0.5
able pressures for a system, thereby reduced pressure, the expansion of the system and should include
limiting the back pressures that can tank design must satisfy two (refer to Fig. 2):
be used in the expansion tank. In necessary requirements for proper
1. Electronic level gauge covering
these situations, the maximum back start-up and operation of the
the full fluid-level range.
pressure on the expansion tank is system. First, the system piping
200
determined by the constraining to the expansion tank should be 2. Fluid temperature indicator. 0.00001 0.0001 0.001 0.01 0.1
pressure on the system. When the designed to permit full flow of fluid Flow Rate, m3/sec
3. Level alarm (high/low) with low-
back pressure on the expansion through the tank. A double drop
level shutdown to protect pump.
tank at a given temperature is less leg design (see Fig. 2, page 7) is the
Temperature Correction
than the pressure exerted by the low most effective arrangement to 4. Pressure indicator with high- Multiplier Factor
molecular weight materials in the remove air, water vapors and other pressure alarm. 1.1
Sieder and Tate equation
noncondensibles during system start- Process Heat Transfer,
1.0
up. The tank and connecting D.Q. Kern (1950) p.103
piping should also be insulated to µ 0.14
()
0.9
Multiplication Factor
prevent the condensation of any Nu = 0.027Re PR 0.8 1/3 ——
vapors that may accumulate in this 0.8 µw
portion of the system.
µ
()
0.7 0.14
Chart based on —— = 1
0.6 µw
0.5
Note: The values in this graph are
based on the viscosity of fluid as
0.4
.5 1 1.5 2 2.5 3 3.5 4 4.5 supplied.
Temperature, °C x 100
6 23
Figure 15 — Liquid Film Coefficient of SYLTHERM 800 Fluid Inside Pipes and Tubes (Turbulent Flow Only) Figure 2 — Simplified System Schematic for SYLTHERM 800 Heat Transfer Fluid
(English Units)
TUB
G, 1 2 "
/2 "
500 E SI
/
18 WG, 1
ZE
G, 3 4 "
/4 "
BW , 3/
BW
B
16 BWG
BW , 1"
1"
16
10
16 WG
G,
14
B
14
8
ec)
ft/s
Y(
CIT
6
LO
VE
Film Coefficient, Btu/hr ft2 °F
2
100
1"
2"
1 1/
2"
SCH
3"
EDU
LE 40
4"
PIPE
6"
50
1.0 10 100 1,000
Flow Rate, gpm
Temperature Correction
Multiplier Factor
1.1
Sieder and Tate equation
1.0
Process Heat Transfer,
D.Q. Kern (1950) p.103
µ 0.14
()
0.9
Multiplication Factor
22 7
Figure 13 — Viscosity of SYLTHERM 800 Fluid (English Units)
Tracing For added safety, the tracing system Flammability
The low freezing point of SYLTHERM
can be extended to include the pip- and Fire Hazards 100
ing downstream of the safety relief
800 heat transfer fluid allows the
valve since these valves often develop
fluid to be pumped at any tempera- All organic heat transfer fluids may
small leaks while in service. Where
ture normally encountered in an operate at temperatures substantially
long runs of piping make tracing
industrial environment. Therefore, above their flash and fire points.
impractical, an alternative solution
freeze protection is not required on This is also the case with SYLTHERM
is to install a rupture disk device
any fluid transfer lines. However, a 800 heat transfer fluid. However,
between the safety relief valve and
portion of the low molecular weight when proper precautions are taken 10
the protected vessel. Application
volatile materials formed during in system designs and procedures,
of a rupture disk device should be
normal operation will crystallize at these materials can be used.
Viscosity, cP
carefully evaluated to ensure that it
142°F (61°C). These crystalline
meets the requirements of Section The following paragraphs describe
materials are readily soluble in
VIII of the ASME Boiler and the fire and explosion hazards of
SYLTHERM 800 heat transfer fluid
Pressure Vessel Code. SYLTHERM 800 heat transfer fluid.
and will not be formed at any place
in the system except where a cold This data sheet presents general
vapor space exists. Thus all vapor- Corrosivity guidelines for design. 1.0
Viscosity, mPa•s
reliable and economical. expansion tank will contain low-
following:
molecular-weight silicone polymers
that are potentially flammable at
Construction Material Contaminant
ambient temperatures, vapor vents
Austenitic Stainless Steel Chlorides and safety relief lines must be
vented to safe areas away from 1.0
Nickel Sulfur sparks or open flames.
Copper Alloys Ammonia
0.1
-50 0 50 100 150 200 250 300 350 400 450
Temperature, °C
8 21
Figure 11 — Density of SYLTHERM 800 Fluid (English Units)
SYLTHERM 800 heat transfer fluid Static Spark Hazard Heat Release
generates low-molecular-weight
65 Heat transfer fluids like SYLTHERM Under carefully controlled pool fire
hydrocarbon gases during operation
800 heat transfer fluid are generally conditions, SYLTHERM 800 heat
at high temperatures, although to a
poor electrical conductors, which transfer fluid was found to generate
much lesser extent than organic heat
60 means they can build up static charges less heat and was easier to extinguish
transfer fluids. For SYLTHERM 800
and discharge static electricity with- than organic heat transfer fluids.
heat transfer fluid, the hydrocarbon
in vessels or while being drained out An independent testing laboratory
gas is predominantly methane.
55 of vessels. Therefore, safe engineering performed a series of tests to charac-
Methane is flammable, and appro-
practice dictates that oxygen must terize the fire-hazard potential of
priate precautions must be taken.
be excluded from the head-space SYLTHERM 800 heat transfer fluid
The concentration of methane in a
of the expansion tank. Similar relative to conventional organic
Density, lb/ft3
800
Density, kg/m3
700
600
500
-50 50 150 250 350 450
Temperature, °C
20 9
NEW SYSTEM START-UP 2. Completely drain the flush fluid check for leaks and ensure that Figure 9 — Specific Heat of SYLTHERM 800 Fluid (English Units)
by pressurizing the system with all instrumentation is operating
The following information is a brief nitrogen or dry air, and opening properly. Maintain the 250°F 0.56
summary of general recommenda- all low-point drains. Alternately (120°C) temperature until the
tions and procedures for starting up open and close all drain valves amount of steam or solvent
a new system with SYLTHERM 800 to increase the velocity of the gas vapors exiting the vent line from
heat transfer fluid. flow. This will help to remove the expansion tank has subsided.
0.52
residual water/solvent and loose This may require several hours.
Prior to start-up, the system must foreign particles.
be cleaned of dirt, welding slag and 6. Raise the fluid temperature to
other miscellaneous debris. Extra 3. Fill the system with SYLTHERM 300°F (150°C) and repeat the
1.6
1.4
-50 50 150 250 350 450
Temperature, °C
10 19
Figure 7 — Vapor Pressure of SYLTHERM 800 Fluid (English Units) HEALTH AND SAFETY ventilated areas with high concen- Fluid Sampling Procedures
CONSIDERATIONS trations of mist and decomposition
When a sample is taken from a hot
300 by-products should be avoided.
system it should be cooled to below
A Material Safety Data Sheet Leaks should be repaired as soon as 100°F (40°C) before it is put into
(MSDS) for SYLTHERM 800 heat they occur to reduce the potential the shipping container. Cooling the
100 transfer fluid is available by calling for smoke inhalation and loss of fluid. sample below 100°F (40°C) will
the number for your area listed on the prevent the possibility of thermal
back of this brochure or by contacting The predominant vented by-products
burns to personnel; also, the fluid
your nearest Dow representative. of thermal decomposition are low-
is then below its flash point. In
The MSDS contains complete health molecular-weight dimethylsiloxanes.
addition, any low boilers will not
and safety information regarding the The low toxicity of these cyclic and
flash and be lost from the sample.
Vapor Pressure, psia
use of this product. Read and under- linear siloxanes is inferred by their
10 Cooling can be done by either a
stand the MSDS before handling or common use in such personal care
batch or continuous process. The
otherwise using this product. products as cosmetics and deodorants.
batch method consists of isolating
SYLTHERM 800 heat transfer fluid the hot sample of fluid from the
has been studied for acute toxico- system in a properly designed sample
CUSTOMER SERVICE FOR collector and then cooling it to
logical properties under the Federal USERS OF SYLTHERM 800
1.0 Hazardous Substance Act (FHSA) below 100°F (40°C). After it is
guidelines. As a result of the FHSA
HEAT TRANSFER FLUID cooled, it can be withdrawn from
study, SYLTHERM 800 heat transfer the sampling collector into a
fluid can be classified as: container for shipment.
Fluid Analysis
■ Nontoxic with regard to acute The continuous method consists
oral ingestion or dermal absorp- of controlling the fluid at a very low
0.1 The Dow Chemical Company, rate through a steel or stainless steel
100 200 300 400 500 600 700 800 tion and its affiliates, offer an analytical cooling coil so as to maintain it at
Temperature, °F service for SYLTHERM 800 heat
■ Neither an eye nor a skin 100°F (40°C) or lower as it comes
irritant transfer fluid. It is recommended out of the end of the cooler into
that users send a one-pint (0.5 liter) the sample collector. Before a
Additional studies indicate that
representative sample at least sample is taken, the sampler should
repeated, prolonged skin contact
annually to: be thoroughly flushed. This initial
Figure 8 — Vapor Pressure of SYLTHERM 800 Fluid (SI Units) should not result in irritation.
Normal industrial handling fluid should be returned to the
North America & Pacific
procedures are adequate to system or disposed of in a safe
100 The Dow Chemical Company
handle this product. manner in compliance with all
Larkin Lab/Thermal Fluids
laws and regulations.
When SYLTHERM 800 heat 1691 North Swede Road
transfer fluid leaks, an aerosol Midland, Michigan 48674 It is important that samples sent
comprised of a mist and white United States of America for analysis be representative of
smoke is evolved. The mist is the charge in the unit. Ordinarily,
mostly unchanged fluid, but Europe samples should be taken from the
10 oxidation of the hot vapor in air Dow Benelux NV main circulating line of a liquid
produces some toxic by-products, Testing Laboratory for SYLTHERM system. Occasionally, additional
Vapor Pressure, bar
including carbon monoxide. and DOWTHERM Fluids samples may have to be taken from
Exposure to the mist and decom- Oude Maasweg 4 other parts of the system where
position by-products may cause 3197 KJ Rotterdam – Botlek specific problems exist. A detailed
serious, transient irritation of the The Netherlands method for analyzing the fluid to
respiratory tract and watering of determine its quality is available
the eyes. Watering of the eyes or Latin America upon request.
1.0
throat irritation indicates exces- Dow Quimica S.A. Used heat transfer fluid which
sive levels of hot vapor leaks. In Fluid Analysis Service has been stored in drums or tanks
areas of adequate ventilation no 1671, Alexandre Dumas should be sampled in such a fashion
special breathing apparatus is Santo Amaro – Sao Paulo – as to ensure a representative sample.
required. However, prolonged Brazil 04717-903
exposure or exposure in poorly
This analysis gives a profile of fluid
0.1 changes to help identify trouble
100 150 200 250 300 350 400 450
from product contamination or
Temperature, °C
thermal decomposition.
18 11
Retrofill Shipping Limitations will meet sales-specification require-
ments for a period of 24 months Figure 5 — Calculated Heat of Vaporization of SYLTHERM 800 Fluid (English Units)
from date of shipment.
SYLTHERM 800 heat transfer fluid SYLTHERM 800 heat transfer fluid 100
has successfully replaced organic is classified by U.S. D.O.T. as non- Store fluid at ambient temperature.
fluids in existing heat transfer systems. hazardous. However, used fluid or
However, there are engineering con- volatiles will have different flamma- Packaging
siderations that should be addressed bility ratings, and appropriate
due to the unique characteristics of handling precautions should be
SYLTHERM 800 heat transfer fluid. SYLTHERM 800 heat transfer fluid is
taken. Regulations vary by country; 80
It is suggested that The Dow routinely supplied in 420-pound
check with your Dow representative.
(191 kg) containers (net weight)
40
Viscosity at 77°F (25°C) 9.1 cP 9.1 mPa•s ≥ 6.0 cP ≥ 6.0 mPa•s Figure 6 — Calculated Heat of Vaporization of SYLTHERM 800 Fluid (SI Units)
Flash Point3, Closed Cup, Typical 320°F 160°C ≥ 95°F ≥ 35°C
200
Flash Point4, Open Cup, Typical 350°F 177°C ≥ 135°F ≥ 57°C
Fire Point3 380°F 193°C ≥ 155°F ≥ 68°C
Autoignition Point, 175
ASTM D 2155 725°F 385°C 725°F 385°C
Acid Number, Typical 0.03 0.03
50
100 150 200 250 300 350 400
Temperature, °C
12 17
Table 2 — Saturated Vapor Properties of SYLTHERM 800 (English Units)
Figure 3 — Thermal Conductivity of SYLTHERM 800 Fluid (English Units) Values are based on an Equation of State
Temp. ∆Hlv Molecular Zvapor Cp/Cv
0.09
°F Btu/lb Weight
200 89.0 223.2 0.990 1.019
220 86.1 228.3 0.990 1.019
240 83.3 233.0 0.988 1.019
0.08 260 80.6 237.5 0.985 1.018
280 77.9 241.8 0.981 1.018
300 75.3 245.8 0.975 1.018
Thermal Conductivity, Btu/hr ft2 (°F/ft)
16 13
Table 4 — Saturated Liquid Properties of SYLTHERM 800 Fluid (English Units) Table 5 — Saturated Liquid Properties of SYLTHERM 800 Fluid (SI Units)
500 0.482 44.62 0.0519 0.63 41.13 240 1.984 734.35 0.0936 0.74 204.8
250 2.001 724.24 0.0918 0.69 242.1
520 0.487 43.90 0.0507 0.58 48.58
260 2.018 713.96 0.0899 0.63 283.6
540 0.491 43.15 0.0495 0.53 56.85
270 2.035 703.51 0.0880 0.59 329.6
560 0.496 42.40 0.0483 0.49 65.97
280 2.052 692.87 0.0861 0.54 380.2
580 0.500 41.63 0.0471 0.45 75.96
290 2.069 682.03 0.0842 0.50 435.4
600 0.505 40.84 0.0459 0.42 86.84
300 2.086 670.99 0.0824 0.47 495.5
620 0.510 40.03 0.0447 0.39 98.61 310 2.104 659.73 0.0805 0.44 560.5
640 0.514 39.20 0.0435 0.36 111.29
320 2.121 648.24 0.0786 0.41 630.5
660 0.519 38.36 0.0423 0.34 124.88
330 2.138 636.52 0.0767 0.38 705.6
680 0.523 37.49 0.0411 0.31 139.39 340 2.155 624.55 0.0748 0.36 785.7
700 0.528 36.60 0.0398 0.29 154.81 350 2.172 612.33 0.0729 0.33 870.9
720 0.532 35.69 0.0386 0.27 171.14 360 2.189 599.83 0.0711 0.31 961.2
740 0.537 34.76 0.0374 0.26 188.37 370 2.206 587.07 0.0692 0.29 1057
760 0.541 33.80 0.0362 0.24 206.50 380 2.223 574.01 0.0673 0.28 1157
780 0.546 32.82 0.0350 0.22 225.51 390 2.240 560.66 0.0654 0.26 1262
800 0.550 31.81 0.0338 0.21 245.39 400 2.257 547.00 0.0635 0.25 1373
14 15
Table 4 — Saturated Liquid Properties of SYLTHERM 800 Fluid (English Units) Table 5 — Saturated Liquid Properties of SYLTHERM 800 Fluid (SI Units)
500 0.482 44.62 0.0519 0.63 41.13 240 1.984 734.35 0.0936 0.74 204.8
250 2.001 724.24 0.0918 0.69 242.1
520 0.487 43.90 0.0507 0.58 48.58
260 2.018 713.96 0.0899 0.63 283.6
540 0.491 43.15 0.0495 0.53 56.85
270 2.035 703.51 0.0880 0.59 329.6
560 0.496 42.40 0.0483 0.49 65.97
280 2.052 692.87 0.0861 0.54 380.2
580 0.500 41.63 0.0471 0.45 75.96
290 2.069 682.03 0.0842 0.50 435.4
600 0.505 40.84 0.0459 0.42 86.84
300 2.086 670.99 0.0824 0.47 495.5
620 0.510 40.03 0.0447 0.39 98.61 310 2.104 659.73 0.0805 0.44 560.5
640 0.514 39.20 0.0435 0.36 111.29
320 2.121 648.24 0.0786 0.41 630.5
660 0.519 38.36 0.0423 0.34 124.88
330 2.138 636.52 0.0767 0.38 705.6
680 0.523 37.49 0.0411 0.31 139.39 340 2.155 624.55 0.0748 0.36 785.7
700 0.528 36.60 0.0398 0.29 154.81 350 2.172 612.33 0.0729 0.33 870.9
720 0.532 35.69 0.0386 0.27 171.14 360 2.189 599.83 0.0711 0.31 961.2
740 0.537 34.76 0.0374 0.26 188.37 370 2.206 587.07 0.0692 0.29 1057
760 0.541 33.80 0.0362 0.24 206.50 380 2.223 574.01 0.0673 0.28 1157
780 0.546 32.82 0.0350 0.22 225.51 390 2.240 560.66 0.0654 0.26 1262
800 0.550 31.81 0.0338 0.21 245.39 400 2.257 547.00 0.0635 0.25 1373
14 15
Table 2 — Saturated Vapor Properties of SYLTHERM 800 (English Units)
Figure 3 — Thermal Conductivity of SYLTHERM 800 Fluid (English Units) Values are based on an Equation of State
Temp. ∆Hlv Molecular Zvapor Cp/Cv
0.09
°F Btu/lb Weight
200 89.0 223.2 0.990 1.019
220 86.1 228.3 0.990 1.019
240 83.3 233.0 0.988 1.019
0.08 260 80.6 237.5 0.985 1.018
280 77.9 241.8 0.981 1.018
300 75.3 245.8 0.975 1.018
Thermal Conductivity, Btu/hr ft2 (°F/ft)
16 13
Retrofill Shipping Limitations will meet sales-specification require-
ments for a period of 24 months Figure 5 — Calculated Heat of Vaporization of SYLTHERM 800 Fluid (English Units)
from date of shipment.
SYLTHERM 800 heat transfer fluid SYLTHERM 800 heat transfer fluid 100
has successfully replaced organic is classified by U.S. D.O.T. as non- Store fluid at ambient temperature.
fluids in existing heat transfer systems. hazardous. However, used fluid or
However, there are engineering con- volatiles will have different flamma- Packaging
siderations that should be addressed bility ratings, and appropriate
due to the unique characteristics of handling precautions should be
SYLTHERM 800 heat transfer fluid. SYLTHERM 800 heat transfer fluid is
taken. Regulations vary by country; 80
It is suggested that The Dow routinely supplied in 420-pound
check with your Dow representative.
(191 kg) containers (net weight)
40
Viscosity at 77°F (25°C) 9.1 cP 9.1 mPa•s ≥ 6.0 cP ≥ 6.0 mPa•s Figure 6 — Calculated Heat of Vaporization of SYLTHERM 800 Fluid (SI Units)
Flash Point3, Closed Cup, Typical 320°F 160°C ≥ 95°F ≥ 35°C
200
Flash Point4, Open Cup, Typical 350°F 177°C ≥ 135°F ≥ 57°C
Fire Point3 380°F 193°C ≥ 155°F ≥ 68°C
Autoignition Point, 175
ASTM D 2155 725°F 385°C 725°F 385°C
Acid Number, Typical 0.03 0.03
50
100 150 200 250 300 350 400
Temperature, °C
12 17
Figure 7 — Vapor Pressure of SYLTHERM 800 Fluid (English Units) HEALTH AND SAFETY ventilated areas with high concen- Fluid Sampling Procedures
CONSIDERATIONS trations of mist and decomposition
When a sample is taken from a hot
300 by-products should be avoided.
system it should be cooled to below
A Material Safety Data Sheet Leaks should be repaired as soon as 100°F (40°C) before it is put into
(MSDS) for SYLTHERM 800 heat they occur to reduce the potential the shipping container. Cooling the
100 transfer fluid is available by calling for smoke inhalation and loss of fluid. sample below 100°F (40°C) will
the number for your area listed on the prevent the possibility of thermal
back of this brochure or by contacting The predominant vented by-products
burns to personnel; also, the fluid
your nearest Dow representative. of thermal decomposition are low-
is then below its flash point. In
The MSDS contains complete health molecular-weight dimethylsiloxanes.
addition, any low boilers will not
and safety information regarding the The low toxicity of these cyclic and
flash and be lost from the sample.
Vapor Pressure, psia
use of this product. Read and under- linear siloxanes is inferred by their
10 Cooling can be done by either a
stand the MSDS before handling or common use in such personal care
batch or continuous process. The
otherwise using this product. products as cosmetics and deodorants.
batch method consists of isolating
SYLTHERM 800 heat transfer fluid the hot sample of fluid from the
has been studied for acute toxico- system in a properly designed sample
CUSTOMER SERVICE FOR collector and then cooling it to
logical properties under the Federal USERS OF SYLTHERM 800
1.0 Hazardous Substance Act (FHSA) below 100°F (40°C). After it is
guidelines. As a result of the FHSA
HEAT TRANSFER FLUID cooled, it can be withdrawn from
study, SYLTHERM 800 heat transfer the sampling collector into a
fluid can be classified as: container for shipment.
Fluid Analysis
■ Nontoxic with regard to acute The continuous method consists
oral ingestion or dermal absorp- of controlling the fluid at a very low
0.1 The Dow Chemical Company, rate through a steel or stainless steel
100 200 300 400 500 600 700 800 tion and its affiliates, offer an analytical cooling coil so as to maintain it at
Temperature, °F service for SYLTHERM 800 heat
■ Neither an eye nor a skin 100°F (40°C) or lower as it comes
irritant transfer fluid. It is recommended out of the end of the cooler into
that users send a one-pint (0.5 liter) the sample collector. Before a
Additional studies indicate that
representative sample at least sample is taken, the sampler should
repeated, prolonged skin contact
annually to: be thoroughly flushed. This initial
Figure 8 — Vapor Pressure of SYLTHERM 800 Fluid (SI Units) should not result in irritation.
Normal industrial handling fluid should be returned to the
North America & Pacific
procedures are adequate to system or disposed of in a safe
100 The Dow Chemical Company
handle this product. manner in compliance with all
Larkin Lab/Thermal Fluids
laws and regulations.
When SYLTHERM 800 heat 1691 North Swede Road
transfer fluid leaks, an aerosol Midland, Michigan 48674 It is important that samples sent
comprised of a mist and white United States of America for analysis be representative of
smoke is evolved. The mist is the charge in the unit. Ordinarily,
mostly unchanged fluid, but Europe samples should be taken from the
10 oxidation of the hot vapor in air Dow Benelux NV main circulating line of a liquid
produces some toxic by-products, Testing Laboratory for SYLTHERM system. Occasionally, additional
Vapor Pressure, bar
including carbon monoxide. and DOWTHERM Fluids samples may have to be taken from
Exposure to the mist and decom- Oude Maasweg 4 other parts of the system where
position by-products may cause 3197 KJ Rotterdam – Botlek specific problems exist. A detailed
serious, transient irritation of the The Netherlands method for analyzing the fluid to
respiratory tract and watering of determine its quality is available
the eyes. Watering of the eyes or Latin America upon request.
1.0
throat irritation indicates exces- Dow Quimica S.A. Used heat transfer fluid which
sive levels of hot vapor leaks. In Fluid Analysis Service has been stored in drums or tanks
areas of adequate ventilation no 1671, Alexandre Dumas should be sampled in such a fashion
special breathing apparatus is Santo Amaro – Sao Paulo – as to ensure a representative sample.
required. However, prolonged Brazil 04717-903
exposure or exposure in poorly
This analysis gives a profile of fluid
0.1 changes to help identify trouble
100 150 200 250 300 350 400 450
from product contamination or
Temperature, °C
thermal decomposition.
18 11
NEW SYSTEM START-UP 2. Completely drain the flush fluid check for leaks and ensure that Figure 9 — Specific Heat of SYLTHERM 800 Fluid (English Units)
by pressurizing the system with all instrumentation is operating
The following information is a brief nitrogen or dry air, and opening properly. Maintain the 250°F 0.56
summary of general recommenda- all low-point drains. Alternately (120°C) temperature until the
tions and procedures for starting up open and close all drain valves amount of steam or solvent
a new system with SYLTHERM 800 to increase the velocity of the gas vapors exiting the vent line from
heat transfer fluid. flow. This will help to remove the expansion tank has subsided.
0.52
residual water/solvent and loose This may require several hours.
Prior to start-up, the system must foreign particles.
be cleaned of dirt, welding slag and 6. Raise the fluid temperature to
other miscellaneous debris. Extra 3. Fill the system with SYLTHERM 300°F (150°C) and repeat the
1.6
1.4
-50 50 150 250 350 450
Temperature, °C
10 19
Figure 11 — Density of SYLTHERM 800 Fluid (English Units)
SYLTHERM 800 heat transfer fluid Static Spark Hazard Heat Release
generates low-molecular-weight
65 Heat transfer fluids like SYLTHERM Under carefully controlled pool fire
hydrocarbon gases during operation
800 heat transfer fluid are generally conditions, SYLTHERM 800 heat
at high temperatures, although to a
poor electrical conductors, which transfer fluid was found to generate
much lesser extent than organic heat
60 means they can build up static charges less heat and was easier to extinguish
transfer fluids. For SYLTHERM 800
and discharge static electricity with- than organic heat transfer fluids.
heat transfer fluid, the hydrocarbon
in vessels or while being drained out An independent testing laboratory
gas is predominantly methane.
55 of vessels. Therefore, safe engineering performed a series of tests to charac-
Methane is flammable, and appro-
practice dictates that oxygen must terize the fire-hazard potential of
priate precautions must be taken.
be excluded from the head-space SYLTHERM 800 heat transfer fluid
The concentration of methane in a
of the expansion tank. Similar relative to conventional organic
Density, lb/ft3
800
Density, kg/m3
700
600
500
-50 50 150 250 350 450
Temperature, °C
20 9
Figure 13 — Viscosity of SYLTHERM 800 Fluid (English Units)
Tracing For added safety, the tracing system Flammability
The low freezing point of SYLTHERM
can be extended to include the pip- and Fire Hazards 100
ing downstream of the safety relief
800 heat transfer fluid allows the
valve since these valves often develop
fluid to be pumped at any tempera- All organic heat transfer fluids may
small leaks while in service. Where
ture normally encountered in an operate at temperatures substantially
long runs of piping make tracing
industrial environment. Therefore, above their flash and fire points.
impractical, an alternative solution
freeze protection is not required on This is also the case with SYLTHERM
is to install a rupture disk device
any fluid transfer lines. However, a 800 heat transfer fluid. However,
between the safety relief valve and
portion of the low molecular weight when proper precautions are taken 10
the protected vessel. Application
volatile materials formed during in system designs and procedures,
of a rupture disk device should be
normal operation will crystallize at these materials can be used.
Viscosity, cP
carefully evaluated to ensure that it
142°F (61°C). These crystalline
meets the requirements of Section The following paragraphs describe
materials are readily soluble in
VIII of the ASME Boiler and the fire and explosion hazards of
SYLTHERM 800 heat transfer fluid
Pressure Vessel Code. SYLTHERM 800 heat transfer fluid.
and will not be formed at any place
in the system except where a cold This data sheet presents general
vapor space exists. Thus all vapor- Corrosivity guidelines for design. 1.0
Viscosity, mPa•s
reliable and economical. expansion tank will contain low-
following:
molecular-weight silicone polymers
that are potentially flammable at
Construction Material Contaminant
ambient temperatures, vapor vents
Austenitic Stainless Steel Chlorides and safety relief lines must be
vented to safe areas away from 1.0
Nickel Sulfur sparks or open flames.
Copper Alloys Ammonia
0.1
-50 0 50 100 150 200 250 300 350 400 450
Temperature, °C
8 21
Figure 15 — Liquid Film Coefficient of SYLTHERM 800 Fluid Inside Pipes and Tubes (Turbulent Flow Only) Figure 2 — Simplified System Schematic for SYLTHERM 800 Heat Transfer Fluid
(English Units)
TUB
G, 1 2 "
/2 "
500 E SI
/
18 WG, 1
ZE
G, 3 4 "
/4 "
BW , 3/
BW
B
16 BWG
BW , 1"
1"
16
10
16 WG
G,
14
B
14
8
ec)
ft/s
Y(
CIT
6
LO
VE
Film Coefficient, Btu/hr ft2 °F
2
100
1"
2"
1 1/
2"
SCH
3"
EDU
LE 40
4"
PIPE
6"
50
1.0 10 100 1,000
Flow Rate, gpm
Temperature Correction
Multiplier Factor
1.1
Sieder and Tate equation
1.0
Process Heat Transfer,
D.Q. Kern (1950) p.103
µ 0.14
()
0.9
Multiplication Factor
22 7
If the expansion tank is designed as tank, some of these materials will Second, the inert gas blanket on Figure 16 — Liquid Film Coefficient of SYLTHERM 800 Fluid Inside Pipes and Tubes (Turbulent Flow Only)
shown in Figure 2, the back pressure be vented out of the system. Since the expansion tank should allow (SI Units)
regulator setting on the expansion these materials are largely respon- for a continuous flow of inert gas to
tank will control the pressure at the sible for the vapor pressure exerted be purged through the vapor space 3,000
entrance to the pump. The regula- by SYLTHERM 800 heat transfer fluid, during the initial start-up. Separate
tor set point should be a minimum of their removal will enable system inert gas supply and discharge
10 to 15 psi (0.7 to 1.0 bar) above the operating pressures below those nozzles, spaced as far apart as
vapor pressure corresponding to the shown by the curves in Figs. 7 and 8. possible, will help ensure that any
SCH
m
fluid temperature in the expansion volatile contaminants (such as water EDU
25m
The rate of venting will be deter- LE 4
m
0 PIP
tank. or solvents) will be swept from the E
38m
m
mined primarily by the system
50m
system during initial start-up.
m
NPSH requirements are primarily temperature profile and the setting
mm
75m
satisfied by the elevation of the of the back pressure regulator. The vent lines from the safety relief
100
mm
expansion tank. The elevation is Several systems using SYLTHERM 800 valve and back pressure regulator
150
determined by calculating the total heat transfer fluid are operating should be discharged to a safe area 3.0
head necessary to overcome frictional at pressures below the pressure- away from open flame and other
line losses and specific NPSH require- temperature curves (Figs. 7 and 8) potential sources of ignition. An 2.5
Film Coefficient,W/m2 K
ments of the pump. In systems where providing process service tempera- appropriate outside container located 1,000
such tank elevation is not practical, tures that would not be possible well away from building air-intake 2.0
NPSH requirements can be met with competitive heat transfer fans is recommended. The vented
by increasing the amount of the fluids in the equipment as designed. volatile materials will be typically
1.5
ec)
blanket gas (usually nitrogen) in the For additional details on how to classified as flammable.
m/s
vapor space of the expansion tank, design a system with operating
The expansion tank should be sized
Y(
thereby increasing the overall pressures below this line, as well
so that it is approximately 1⁄4 full
CIT
pressure in the tank. However, the as comments on its expected
when the system is at ambient 1.0
LO
12m m
additional system pressure created operational fluid loss rates, contact
m
temperature, and 3⁄4 full when the
VE
BW , 12
by the nitrogen should be accounted your nearest Dow representative or
19m m
m
system is at its maximum operating
G, mm
18 BWG
G,
for during the system design. call the number for your area listed
m
BW , 19
25m
temperature. Expansion tank instru-
BW G, 25
on the back of this brochure.
G,
16 BWG
In some cases, design constraints, mentation and fittings must meet the
16
W
such as permissible process vessel Whether the loop is designed to design requirements of the anticipated
14
TU
B
BE
pressures, limit the maximum allow- operate as a closed system or at a operating temperatures and pressures
14
SIZ
16
E 0.5
able pressures for a system, thereby reduced pressure, the expansion of the system and should include
limiting the back pressures that can tank design must satisfy two (refer to Fig. 2):
be used in the expansion tank. In necessary requirements for proper
1. Electronic level gauge covering
these situations, the maximum back start-up and operation of the
the full fluid-level range.
pressure on the expansion tank is system. First, the system piping
200
determined by the constraining to the expansion tank should be 2. Fluid temperature indicator. 0.00001 0.0001 0.001 0.01 0.1
pressure on the system. When the designed to permit full flow of fluid Flow Rate, m3/sec
3. Level alarm (high/low) with low-
back pressure on the expansion through the tank. A double drop
level shutdown to protect pump.
tank at a given temperature is less leg design (see Fig. 2, page 7) is the
Temperature Correction
than the pressure exerted by the low most effective arrangement to 4. Pressure indicator with high- Multiplier Factor
molecular weight materials in the remove air, water vapors and other pressure alarm. 1.1
Sieder and Tate equation
noncondensibles during system start- Process Heat Transfer,
1.0
up. The tank and connecting D.Q. Kern (1950) p.103
piping should also be insulated to µ 0.14
()
0.9
Multiplication Factor
prevent the condensation of any Nu = 0.027Re PR 0.8 1/3 ——
vapors that may accumulate in this 0.8 µw
portion of the system.
µ
()
0.7 0.14
Chart based on —— = 1
0.6 µw
0.5
Note: The values in this graph are
based on the viscosity of fluid as
0.4
.5 1 1.5 2 2.5 3 3.5 4 4.5 supplied.
Temperature, °C x 100
6 23
Figure 17 — Pressure Drop vs. Flow Rate of SYLTHERM 800 Fluid in Schedule 40 Nominal Pipe and Equilibrium and fluid to meet your process require- lower than the equilibrium vapor
BWG Tube (English Units) Operating Pressures ments. (For a copy of this brochure, pressure of the fluid for a given
please contact your nearest Dow temperature, periodic venting of the
G, 1 /2 "
SYLTHERM 800 heat transfer fluid
/2 "
representative or call the number for volatile materials will take place.
BW , 1
TU
BE does not have a distinct boiling point.
18 BWG
SIZ your area listed on the back of this The fluid will suffer no deleterious
E Its molecular weight distribution
brochure.) effect; however, periodic additions
G, 3 /4 "
50 10
16
/4 "
shifts with time at high temperatures,
B W G, 3
of new fluid will be needed to
affecting vapor pressure, viscosity, In some system designs, lower
16 BW
c)
8 maintain system volume.
/se
G, 1"
flash point, and freeze point. Once expansion-tank pressures than those
1"
14
(ft
B W G,
the fluid composition reaches equi- derived from the curves in Figures 7 An inert gas (such as nitrogen)
TY
16 BW
CI
6 librium at a temperature (usually a and 8 (page 18) are required because blanket on the expansion tank is
14
LO
matter of months), an “equilibrium of equipment design constraints. required to prevent the fluid from
VE
vapor pressure” can be measured. This method of operation results in coming into contact with the outside
10 4 venting of low-molecular-weight air. Without this inert gas blanket,
As supplied, SYLTHERM 800 heat
volatile materials from the system, humid, outside air is likely to be
transfer fluid exhibits a low vapor
3 which requires periodic make-up drawn into the tank whenever the
pressure. With time at high temper-
with new fluid. Contact your nearest system cools below its normal
atures, the previously described
Dow representative or call the number operating temperature. This
rearrangement reaction results in
Pressure Drop, psi/100 foot of pipe
for your area listed on the back of moisture contamination can result
a gradually rising vapor pressure.
this brochure for assistance if you in increased pressure in the system
Ultimately, the silicone components
plan to design your system with due to steam formation on the next
reach an equilibrium composition
pressures below the curves in Figures heat-up cycle. To avoid this, the
2 and exhibit an equilibrium vapor
7 and 8. inert gas supply regulator should be
pressure.
adjusted and maintained at a low
1.0 Expansion Tank
The curves on page 18 represent setting of 3 to 5 psi (0.2 to 0.3 bar).
typical equilibrium pressures for Figure 2 (page 7) is a simplified This will minimize both the inert
1"
SYLTHERM 800 heat transfer fluid. schematic of a recommended system gas consumption and the additive
In practice, operating pressures in loop design for SYLTHERM 800 heat effects of the blanket gas on total
the expansion tank are often higher transfer fluid. The expansion tank system pressure.
/2 "
11
SC due to the additive effect of other point in the system and has the
HE equilibrium silicone vapor pressure
DU gases such as the nitrogen blanket capability for full flow of the heat
LE that SYLTHERM 800 heat transfer
3"
1.0
0.5
-1 0 1 2 3 4 5 6 7 8
Temperature, °F x 100
24 5
FLUID SELECTION CRITERIA fer properties. Because it exhibits 1000°F (538°C) with low or no Figure 18 — Pressure Drop vs. Flow Rate of SYLTHERM 800 Fluid in Schedule 40 Nominal Pipe and
low potential for fouling, large flow, polymer cross-linking may BWG Tube (SI Units)
Stability correction factors for fouling in occur. This will eventually cause
heat transfer coefficient calcula- the fluid viscosity to increase,
SYLTHERM 800 fluid offers good tions are not needed (a fouling requiring fluid replacement. Some
thermal stability at temperatures up factor of 0.0001 (hr)(ft2)(°F)/Btu problem areas to be avoided 1,000
to 750°F (400°C). The maximum [1.45 x 10 -5 m2 K/W] is commonly include:
recommended film temperature is used). Additionally, the unique
800°F (427°C). 1. Flame impingement.
rearrangement chemistry of
m
Freeze Point SYLTHERM 800 heat transfer fluid 2. Operating the heater above its
25m
can offset the viscosity increases rated capacity.
SYLTHERM 800 fluid has a minimum characteristic of heat transfer fluids SC
m
3. Modifying the fuel-to-air mixing HE
pumpability temperature less than
38m
as they age. The result is that, DU
procedure to change the flame LE
m
-40°F (-40°C). throughout its life, the film heat 40
50m
height and pattern. This can PI
PE
Low Odor, Non-reportable transfer coefficient of SYLTHERM 800
yield higher flame and gas
heat transfer fluid can remain as
m
75m
The chemical composition of temperatures together with 100
good as, or can improve above, the
mm
SYLTHERM 800 fluid makes it a higher heat flux.
original fluid values.
100
preferred choice for users with the 4. Low fluid velocity/high heat flux
Three key areas of focus for heat
mm
need for low odor. Additionally, areas resulting in excessive heat
transfer operations are designing
150
SYLTHERM 800 has no components transfer fluid film temperatures.
12 m
and operating the heater and/or 3.0
currently listed as reportable under
mm
G, 2m
SARA Title III, Section 313.1 energy recovery unit, preventing The manufacturer of the fired
BW , 1
2.5
18 BWG
SYLTHERM 800 is not a hazardous chemical contamination, and heater should be the primary
19 m
eliminating fluid contact with air contact in supplying you with the
mm
G, 19m
product as defined in the OSHA
16
2.0
Hazard Communication Standard. and water. proper equipment for your heat
BW G,
25 m
16 4 BW
transfer system needs.
mm
G, 5m
ec)
When units are operated at high TU
BW G, 2
10 1.5
Thermal Stability
m/s
BE
1
temperatures, fluid velocities in Contamination and SI
Y(
16 W
ZE
heaters should be a minimum of Oxidation Effects
CIT
14
The thermal stability of a heat 6 feet per second (2 m/s); a range
LO
At elevated temperatures, SYLTHERM
of 6 to 12 feet per second (2 – 4 m/s) 1.0
VE
transfer fluid is dependent on 800 heat transfer fluid is sensitive to
many factors. Properly maintained should cover most cases. The actual
contamination. Contamination by
SYLTHERM 800 heat transfer fluid velocity selected will depend on an
acids or bases can result in accelerated
can be aged continuously at 750°F economic balance between the
rates of volatile by-product formation.
(400°C) for more than 10 years cost of circulation and heat transfer
Contamination by water, oxygen,
before it needs replacement. Longer surface.
or other oxidants can result in cross- 0.5
fluid life can be expected in systems Operating limitations are usually linking of polymer molecules, and,
operating at lower temperatures. 1.0
placed on heat flux by the equip- if not corrected, can cause a gradual 0.00001 0.0001 0.001 0.01 0.1
Heat Transfer Capability ment manufacturer. This heat flux increase in viscosity. Flow Rate, m3/sec
is determined for a maximum film
The exceptional thermal stability of It is important that contamination
temperature by the operating
SYLTHERM 800 heat transfer fluid be minimized. Potential sources of Temperature Correction
conditions of the particular unit.
results in uniquely stable heat trans- contaminants such as water, steam, Multiplier Factor
3.5
Heater Design and Operation process material, atmospheric air,
and humidity should be appraised
Poor design and/or operation of the 3.0
and modifications made where
fired heater can cause overheating
necessary.
Multiplication Factor
2.5
and will eventually cause the fluid’s
viscosity to increase to a point 2.0
1
where replacement of the fluid
You may need to comply with similar or
additional legislation in other countries.
is necessary to restore system 1.5
0.5
-1 0 1 2 3 4 5
Temperature, °C x 100
4 25
Figure 19 — Thermal Expansion of Liquid SYLTHERM 800 Fluid (English Units) SYLTHERM 800 A Virtually Odorless, SYLTHERM 800 heat transfer fluid
Basis: 1 gallon at 75°F Heat Transfer Fluid Long-lasting provides excellent high-temperature
stability. It is capable of operating
2.0 Heat Transfer Fluid more than 10 years at 750°F (400°C)
without the fouling or periodic
SYLTHERM† 800 fluid is a highly reprocessing problems associated
1.8 stable, long-lasting, silicone fluid with other heat transfer media.
designed for high-temperature liquid-
phase operation. It has a recommended Performance
operating temperature range of
1.6 -40°F (-40°C) to 750°F (400°C).
Expanded Volume, gallon
■ Long life
ented formulation. Systems using
SYLTHERM 800 fluid require no
■ Noncorrosive
periodic venting; therefore, the low-
Figure 20 — Thermal Expansion of Liquid SYLTHERM 800 Fluid (SI Units) ■ Low acute oral toxicity molecular-weight linear and cyclic
Basis: 1 cubic meter at 25°C ■ Low odor siloxanes that result from the
■ Non-reportable under SARA
rearrangement remain part of the
2.0
Title III, Section 3131 heat transfer media and do not cause
system fouling. The rearrangement
that occurs with SYLTHERM 800 heat
1.8 transfer fluid is not a degradation
reaction and does not affect fluid life.
1.6
Expanded Volume, m3
1.4
1.2
1.0
26 3
LC
Condensate
CONTENTS SYLTHERM 800 Heat Transfer Fluid␣ Figure 21 — Typical Liquid Phase Heating Scheme
Steam
▼
Introduction ................................................................................ 3 Using SYLTHERM Fluid
Performance................................................................................. 3
Steam Condensate
Cooling Process
(450˚F) (232˚C) Process Fluid
Fluid Selection Criteria␣ .......................................................................... 4
Pump
Heating or
▼
▼
TIC
Equilibrium and Operating Pressures .......................................... 5 ▼
▼
▼
▼
Simplified Schematic for Loop Design ....................................... 7
TRC
FI
PI
Circulating Pump
Steam
Flammability and Fire Hazards................................................ 8, 9 ▼
PRV
Steam Generator
Cooling Loop
Stm. Hdr.
▼
Heat Exchanger
▼
▼
New System Start-up␣ ........................................................................... 10
(380˚F) (193˚C)
PIC
PRV
#2
▼
▼
Process Fluid
Health and Safety Considerations␣ ...................................................... 11
▼
▼
▼
Vent
(375˚F) (191˚C)
LC
Customer Service␣ ................................................................................. 11
▼
▼
▼
▼
Vent
Instrument Air Lines
Fluid Analysis ............................................................................ 11 ▼
▼
Retrofill ..................................................................................... 12
Process Tank
Electrical Lines
Shipping Limitations ................................................................ 12
▼
Storage and Shelf-life ................................................................ 12
▼
Packaging................................................................................... 12
Circulating Pump
Properties and Engineering Characteristics␣
Jacket Loop
FI
▼
▼
TIC
Physical Properties .................................................................... 12
▼
English Units ................................................................ 13
Vent Header
TIC
SI Units ........................................................................ 13
Liquid Saturation Properties ▼ ▼ ▼
▼
English Units ................................................................ 14
▼ ▼
▼
LI
Figure 2
PRV
Thermal Conductivity .............................................................. 16
Process Fluid
Pressure Indicating Controller
SeeExpansion
PCV
Tank
Vent
▼
Calculated Heat of Vaporization .............................................. 17
▼
▼
N2
▼
▼
Vapor Pressure ........................................................................... 18
LAH/L
LSL
#1
Specific Heat ............................................................................. 19 ▼ ▼
▼
▼
Heat Exchanger
▼
Pressure Switch High
Pressure Relief Valve
PRV
Pressure Switch Low
Circulating Pump
Density ...................................................................................... 20
▼
▼
Heating Loop
Pressure Indicator
TRC
▼
Viscosity .................................................................................... 21
FRC
▼ ▼
▼
▼
▼
▼
Vent
Engineering Data␣
▼
TIC
Spare Pump
7
FSL
▼ ▼ ▼
Liquid Film Coefficient
SYLTHERM Fluid
English Units ................................................................ 22
Heater for
SI Units ........................................................................ 23
TSH
Pressure Drop ▼
▼ ▼
BA
BC
BE
English Units ................................................................ 24
1
–
–
–
–
–
–
–
–
▼
To Pilot Light
SI Units ........................................................................ 25
PRV
PSH
TRC
TSH
PSL
PSH
PIC
TIC
PI
Thermal Expansion ................................................................... 26
Typical Liquid Phase Heating Scheme ..................................... 27
PI
Flow Indicator (Orifice)
PI
Pressure Control Valve
▼
PSL
For Information About Our Full Line of Fluids... ▼ ▼
PCV
Snuffing Stm.
Flow Switch Low
To learn more about the full line of heat transfer fluids manufactured
Level Controller
Fuel Gas
Burner Control
or distributed by Dow — including DOWTHERM* synthetic
Burner Alarm
Instrument Legend
organic, SYLTHERM† silicone and DOWTHERM, DOWFROST*,
TIC
Media
▼
Call the number for your area listed on the back of this brochure.
LI
Atm.
Vent
Cond.
*Trademark of The Dow Chemical Company
▼
BA –
BC –
BE –
FI –
FRC –
FSL –
LC –
PVC –
▼
†Trademark of Dow Corning Corporation
▼
▼
▼
27
▼
2 ▼
Loading
Pump
▼
SYLTHERM 800
Heat Transfer Fluid
Product Technical Data
SYLTHERM 800
Heat Transfer Fluid
800
In The United States And Canada: 1-800-447-4369 • FAX: 1-517-832-1465
In Europe: +31 20691 6268 • FAX: +31 20691 6418
In The Pacific: +886 2 715 3388 • FAX: +886 2 717 4115
In Other Global Areas: 1-517-832-1556 • FAX: 1-517-832-1465
http://www.dow.com/heattrans
NOTICE: No freedom from any patent owned by Seller or others is to be inferred. Because use conditions and applicable laws may differ from one location
to another and may change with time, Customer is responsible for determining whether products and the information in this document are appropriate for
Customer’s use and for ensuring that Customer’s workplace and disposal practices are in compliance with applicable laws and other governmental
Product Technical Data
enactments. Seller assumes no obligation or liability for the information in this document. NO WARRANTIES ARE GIVEN; ALL IMPLIED WARRANTIES OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE EXPRESSLY EXCLUDED.
NOTE: SYLTHERM heat transfer fluids are manufactured by Dow Corning Corporation and distributed by The Dow Chemical Company.
28 1
*
Printed in U.S.A. *Trademark of The Dow Chemical Company NA/LA/Pacific: Form No. 176-01435-1097 AMS
Europe: CH 153-046-E-1097