Table Cause & effet

Project No: Q6521


Client: OCP
Project Name: Laayoune Washing Plant
Sub-Project Name: General
Jacobs Document No:JEC-Q6521-00-IV/D.03a/00002
Client Document No:
Revision: A

Prepared Checked Discipline Project


Rev. Issue date Revision description
by by Approval Approval
A 23-Oct-17 For Inquiry

673120873.xls Page : 1/15


ZONES TABLE FACP

LOCATION ALARM AREA DEVICES CODE

CR_SP-DF-N°1
CR-SC-DF-N°2
CR-SC-DF-N°3
CR-SC-DF-N°4
CR_SP-ALR-N°1 CR-SC-DF-N°5
CR_ING-DF-N°1
CR_PR-DF-N°1
CR_CL-DF-N°1
CR_REF-DTHRM-R-N°1
CR_CLEA-DF-N°1
CR_TGBT-DF-N°1
Heat/Smoke detectors
CR_OS-DF-N°1
CR_OS-DF-N°2
CONTROL ROOM Zone 1 CR_CL-ALR-N°1 CR_CL-DF-N°2
CR_REU-DF-N°1
CR_CL-DF-N°3
CR_RES-DF-N°1
CR_CL-DF-N°4
CR_ADMIN-DF-N°1
CR_CL-DF-N°5
CR_CL-DF-N°6
CR_VIP-DF-N°1
CR_CL-ALR-N°2 CR_SP-MAC-N°1
CR_SP-MAC-N°2
Manual fire alarm call point CR_SP-MAC-N°3
CR_CL-MAC-N°1
CR_CL-MAC-N°2
PEBT1_VT-DF-N°1
PEBT1_VT-DF-N°2
PEBT1_VT-DF-N°3
PEBT1_VT-DF-N°4
PEBT1_VT-DF-N°5
PEBT1_VT-DF-N°6
PEBT1_VT-DF-N°7
PEBT1_VT-DF-N°8
PEBT1_VT-DF-N°9
Smoke detectors
PEBT1_VT-DF-N°10
PEBT1_VT-DF-N°11
Zone 2 PEBT1_VT-ALR-N°1
PEBT1_VT-DF-N°12
PEBT1_VT-DF-N°13
PEBT1_VT-DF-N°14
PEBT1_VT-DF-N°15
PEBT1_VT-DF-N°16
PEBT1_VT-DF-N°17
PEBT1_VT-DF-N°18
PEBT1_VT-MAC-N°1
Manual fire alarm call point PEBT1_VT-MAC-N°2
PEBT1_VT-MAC-N°3
Poste électrique basse tension SPK CONTROL VALVE SPRINKLER CONTROL VALVE-VT
sous-station 1 PEBT1_TR-DMC-N°1
PEBT1_TR-DMC-N°2
PEBT1_TR-DMC-N°3
PEBT1_TR-DMC-N°4
PEBT1_TR-DMC-N°5
PEBT1_TR-DMC-N°6
PEBT1_TR-ALR-N°1
PEBT1_TR-DMC-N°7
Heat / Smoke detectors
PEBT1_TR-DMC-N°8
PEBT1_TR-DMC-N°9
PEBT1_TR-DMC-N°10
PEBT1_TR-DMC-N°11
Zone 3
PEBT1_TR-DMC-N°12
PEBT1_TR-DMC-N°13

PEBT1_TR-ALR-N°2
Heat / Smoke detectors

Zone 3

PEBT1_LB-DF-SI-N°1
PEBT1_LB-DET-G--N°1
Hydrogen Gas detector
PEBT1_LB-DET-G--N°2
PEBT1_TR-MAC-N°1
PEBT1_TR-ALR-N°2
PEBT1_TR-MAC-N°2
PEBT1_TR-MAC-N°3
Manual fire alarm call point
PEBT1_TR-MAC-N°4
PEBT1_TR-MAC-N°5
PEBT1_TR-MAC-N°6
PEMT1_VT-DF-N°1
PEMT1_VT-DF-N°2
PEMT1_VT-DF-N°3
PEMT1_VT-DF-N°4
PEMT1_VT-DF-N°5
PEMT1_VT-DF-N°6
PEMT1_VT-DF-N°7
PEMT1_VT-DF-N°8
Heat / Smoke detectors PEMT1_VT-DF-N°9
Zone 4 PEMT1_VT-ALR-N°1 PEMT1_VT-DF-N°10
PEMT1_VT-DF-N°11
PEMT1_VT-DF-N°12
PEMT1_VT-DF-N°13
PEMT1_VT-DF-N°14
Poste électrique moyenne tension
PEMT1_VT-DF-N°15
sous-station 1
PEMT1_VT-DF-N°16
PEMT1_VT-DF-N°17
Manual fire alarm call point PEMT1_VT-MAC-N°1
SPK CONTROL VALVE SPRINKLER CONTROL VALVE-VT
PEMT1_TR-DMC-N°1
PEMT1_TR-DMC-N°2
PEMT1_TR-DMC-N°3
PEMT1_TR-DMC-N°4
Heat / Smoke detectors
PEMT1_TR-DMC-N°5
Zone 5 PEMT1_TR-ALR-N°1
PEMT1_TR-DMC-N°6
PEMT1_TR-DMC-N°7
PEMT1_TR-DMC-N°8
Manual fire alarm call point PEMT1_TR-MAC-N°1
AREA01_LV1-ALR-N°1 AREA01_LV1-MAC-N°1
SCRUBBING & SCREENING AREA01_LV1-ALR-N°2 AREA01_LV1-MAC-N°2
Zone 6 Manual fire alarm call point
AREA01 AREA01_LV1-ALR-N°3 AREA01_LV1-MAC-N°3
AREA01_LV1-ALR-N°4 AREA01_LV1-MAC-N°4
AREA0204_LV1-ALR-N°1 AREA0204_LV1-MAC-N°1
AREA0204_LV1-ALR-N°2 AREA0204_LV1-MAC-N°2
AREA0204_LV2-ALR-N°3 AREA0204_LV2-MAC-N°3
DESLIMING AREA0204 Zone 7 Manual fire alarm call point
AREA0204_LV2-ALR-N°4 AREA0204_LV2-MAC-N°4
AREA0204_LV3-ALR-N°5 AREA0204_LV3-MAC-N°5
AREA0204_LV3-ALR-N°6 AREA0204_LV3-MAC-N°6
AREA06-ALR-N°1 AREA06-MAC-N°1
AREA06-ALR-N°2 AREA06-MAC-N°2
FILTRATION PLANT Area06 Zone 8 Manual fire alarm call point
AREA06-ALR-N°3 AREA06-MAC-N°3
AREA06-ALR-N°4 AREA06-MAC-N°4
PEBT2_VT-DF-N°1
PEBT2_VT-DF-N°2
PEBT2_VT-DF-N°3
PEBT2_VT-DF-N°4
PEBT2_VT-DF-N°5
Heat / Smoke detectors
PEBT2_VT-DF-N°6
Zone 9 PEBT2_VT-ALR-N°1 PEBT2_VT-DF-N°7
PEBT2_VT-DF-N°8
PEBT2_VT-DF-N°9
PEBT2_VT-DF-N°10
PEBT2_VT-MAC-N°1
Manual fire alarm call point
PEBT2_VT-MAC-N°2
SPK CONTROL VALVE SPRINKLER CONTROL VALVE-VT
Poste électrique basse et moyenne
PEBT2_TR-DMC-N°1
tension
sous-station 2 PEBT2_TR-DMC-N°2
PEBT2_TR-DMC-N°3
PEBT2_TR-ALR-N°1 PEBT2_TR-DMC-N°4
Heat / Smoke detectors PEBT2_TR-DMC-N°5

Zone 10
Poste électrique basse et moyenne
tension
sous-station 2

PEBT2_TR-ALR-N°1
Heat / Smoke detectors
PEBT2_TR-DMC-N°6
PEBT2_TR-DMC-N°7
Zone 10 PEBT2_TR-DMC-N°8
PEBT2_LB-DF-SI-N°1
PEBT2_LB-DET-G--N°1
Hydrogen Gas detector
PEBT2_LB-DET-G--N°2
PEBT2_TR-ALR-N°2
PEBT2_LB-MAC-N°1
PEBT2_TR-MAC-N°1
Manual fire alarm call point
PEBT2_TR-MAC-N°2
PEBT2_TR-MAC-N°3
AREA07-ALR-N°1 AREA07-MAC-N°1
REAGENT Area 07 Zone 11 Manual fire alarm call point
AREA07-ALR-N°2 AREA07-MAC-N°2
AREA05-ALR-N°1 AREA05-MAC-N°1
AREA05-ALR-N°2 AREA05-MAC-N°2
AREA05-ALR-N°3 AREA05-MAC-N°3
FLOTATIONS Area05 Zone 12 Manual fire alarm call point
AREA05-ALR-N°4 AREA05-MAC-N°4
AREA05-ALR-N°5 AREA05-MAC-N°5
AREA05-ALR-N°6 AREA05-MAC-N°6
TD1-DMC-N°1
TD1-DMC-N°2
TD1-DMC-N°3
TD1-ALR-N°1
TD1-DMC-N°4
Heat / Smoke detectors
TD1-DMC-N°5
TD1-DMC-N°6
TUNNEL 21-TK-01 Zone 13 TD1-DMC-N°7
TD1-DMC-N°8
TD1-DET-G--N°1
Oxygen detectors
TD1-ALR-N°2 TD1-DET-G--N°2
TD1-MAC-N°1
Manual fire alarm call point
TD1-MAC-N°2
SPK CONTROL VALVE SPRINKLER CONTROL VALVE-VT
TD2-DMC-N°1
TD2-DMC-N°2
TD2-DMC-N°3
TD2-ALR-N°1
TD2-DMC-N°4
Heat / Smoke detectors
TD2-DMC-N°5
TD2-DMC-N°6
TUNNEL 21-TK-02 Zone 14 TD2-DMC-N°7
TD2-DMC-N°8
TD2-DET-G--N°1
Oxygen detector
TD2-ALR-N°2 TD2-DET-G--N°2
TD2-MAC-N°1
Manual fire alarm call point
TD2-MAC-N°2
SPK CONTROL VALVE SPRINKLER CONTROL VALVE-VT
LC-DTHRM-R-N°1
LC-DTHRM-R-N°2
LC-DTHRM-R-N°3
LC-DTHRM-R-N°4
LC-ALR-N°1 LC-DTHRM-R-N°5
LC-DTHRM-R-N°6
LC-DTHRM-R-N°7
LC-DTHRM-R-N°8
LC-DTHRM-R-N°9
LC-DTHRM-R-N°10
LC-DTHRM-R-N°11
LC-DTHRM-R-N°12
LOCAL DES COMPRESSEUR Heat / Smoke detectors LC-DTHRM-R-N°13
& Zone 15
VENTILATEUERS LC-ALR-N°2 LC-DTHRM-R-N°14
LC-DTHRM-R-N°15
LC-DTHRM-R-N°16
LC-DTHRM-R-N°17
LC-DTHRM-R-N°18
LC-DTHRM-R-N°19
LC-DTHRM-R-N°20
LC-DTHRM-R-N°21
LC-DTHRM-R-N°22
LC-ALR-N°3
LC-DTHRM-R-N°23
LC-DTHRM-R-N°24
LC-DTHRM-R-N°25
Manual fire alarm call point LC-MAC-N°1
SYSTEM OUTPUTS

Control unit Annunciation Notification Fire Safety Controls Supplementary

Actuate common supervisory signal/indicator


Overall Input / Output Matrix

Close smoke / fire dampers in rated walls


Actuate common trouble signal/indicator

Release magnetically held smoke doors


Actuate audible common trouble signal
Actuate common alarm signal/indicator

Actuate Zone 10 evacuation signals


Actuate Zone 11 evacuation signals
Actuate Zone 12 evacuation signals
Actuate Zone 13 evacuation signals
Actuate Zone 14 evacuation signals
Actuate Zone 15 evacuation signals

Activate Zone 10bis smoke exhaust


Actuate Zone 8 evacuation signals
Actuate Zone 1 evacuation signals
Actuate Zone 2 evacuation signals
Actuate Zone 3 evacuation signals
Actuate Zone 4 evacuation signals
Actuate Zone 5 evacuation signals
Actuate Zone 6 evacuation signals
Actuate Zone 7 evacuation signals

Actuate Zone 9 evacuation signals


Actuate audible supervisory signal

Transmit fire alarm signal to DCS

Activate Zone 10 smoke exhaust

Activate Zone 13 smoke exhaust


Activate Zone 14 smoke exhaust
Transmit fire alarm signal to DCI
Actuate Zone 10 alarm indicator
Actuate Zone 11 alarm indicator
Actuate Zone 12 alarm indicator
Actuate Zone 13 alarm indicator
Actuate Zone 14 alarm indicator
Actuate Zone 15 alarm indicator

Activate Zone 2 smoke exhaust


Activate Zone 3 smoke exhaust
Activate Zone 4 smoke exhaust
Activate Zone 5 smoke exhaust
Activate Zone 9 smoke exhaust
Display / print change of status
Actuate Zone 1 alarm indicator
Actuate Zone 2 alarm indicator
Actuate Zone 3 alarm indicator
Actuate Zone 4 alarm indicator
Actuate Zone 5 alarm indicator
Actuate Zone 6 alarm indicator
Actuate Zone 7 alarm indicator
Actuate Zone 8 alarm indicator
Actuate Zone 9 alarm indicator

Transmit trouble signal to DCS

Transmit trouble signal to DCI


Actuate audible alarm signal

Actuate forced ventilation (3)


Important note: Contractor is responsible of estimating quantities of each
device listed in this matrix.

Stop air-conditioning

Shutdown process(2)
Unlock exits
SYSTEM INPUTS A B C D E F G H I J K L M N O P Q R S T U V W X Y Z AA AB AC AD AE AF AG AH AI AJ AK AL AM AN AO AP AQ AR AS AT AU AV AW AX AY AZ BC BD BE BF BG BH BI BJ
1 Manual fire alarm call point Zone 1 ● ● ● ● ● ● ● ●
2 Manual fire alarm call point Zone 2 ● ● ● ● ● ● ●
3 Manual fire alarm call point Zone 3 ● ● ● ● ● ● ● ●
4 Manual fire alarm call point Zone 4 ● ● ● ● ● ● ●
5 Manual fire alarm call point Zone 5 ● ● ● ● ● ● ●
6 Manual fire alarm call point Zone 6 ● ● ● ● ● ● ●
PULL STATIONS

7 Manual fire alarm call point Zone 7 ● ● ● ● ● ● ●


8 Manual fire alarm call point Zone 8 ● ● ● ● ● ● ●
9 Manual fire alarm call point Zone 9 ● ● ● ● ● ● ● ●
10 Manual fire alarm call point Zone 10 ● ● ● ● ● ● ● ●
11 Manual fire alarm call point Zone 11 ● ● ● ● ● ● ●
12 Manual fire alarm call point Zone 12 ● ● ● ● ● ● ●
13 Manual fire alarm call point Zone 13 ● ● ● ● ● ● ● ●
14 Manual fire alarm call point Zone 14 ● ● ● ● ● ● ● ●
15 Manual fire alarm call point Zone 15 ● ● ● ● ● ● ●
16 Heat / smoke detectors Zone 1 ● ● ● ● ● ● ● ● ● ● ●
17 ● ● ● ● ● ● ● ● ● ●
HEAT & SMOKE DETECTORS

Heat / smoke detectors Zone 2


18 Heat / smoke detectors Zone 3 ● ● ● ● ● ● ● ● ● ● ●
19 Heat / smoke detectors Zone 4 ● ● ● ● ● ● ● ● ● ●
20 Heat / smoke detectors Zone 5 ● ● ● ● ● ● ● ● ● ●
21 Heat / smoke detectors Zone 9 ● ● ● ● ● ● ●
22 Heat / smoke detectors Zone 10 ● ● ● ● ● ● ● ● ● ● ●
23 Heat / smoke detectors Zone 13 ● ● ● ● ● ● ● ● ● ● ●
24 Heat / smoke detectors Zone 14 ● ● ● ● ● ● ● ● ● ●
25 Heat / smoke detectors Zone 15 ● ● ● ● ● ● ●
26 Hydrogen detector Zone 3 ● ● ● ● ● ● ● ● ●
DETECTORS

27 Hydrogen detector Zone 10 ● ● ● ● ● ● ● ● ●


GAS

28 Oxygen Gas detector Zone 13 ● ● ● ● ● ● ● ●


29 Oxygen Gas detector Zone 14 ● ● ● ● ● ● ● ●
30 Sprinkler control valve Zone 2 ● ● ● ● ● ● ●
KLER CONTROL

31 Sprinkler control valve Zone 4 ● ● ● ● ● ● ●


VALVE
SPRIN

32 Sprinkler control valve Zone 9 ● ● ● ● ● ● ●


33 Sprinkler control valve Zone 13 ● ● ● ● ● ● ●
34 Sprinkler control valve Zone 14 ● ● ● ● ● ● ●
35 FECP1/Alarm ● ● ● ● ● ●(1)
36 FECP1/Fault ● ● ● ●
37 FECP2/Alarm ● ● ● ● ● ●(1)
38 FECP2/Fault ● ● ● ●
39 FECP3/Alarm ● ● ● ● ● ● ● ● ●
40 FECP3/Fault ● ● ● ●
P
FECP/FACP

41 FECP5/Alarm ● ● ● ● ● ●(1)
42 FECP5/Fault ● ● ● ●
43 FECP6/Alarm ● ● ● ● ● ●(1)
44 FECP6/Fault ● ● ● ●
45 FECP7/Alarm ● ● ● ● ●
46 FECP7/Fault ● ● ● ●
47 FACP2/Alarm ● ● ● ● ●
48 FACP2/Fault ● ● ● ●
49 FACP3/Alarm ● ● ● ● ●
50 FACP3/Fault ● ● ● ●
51 Fire alarm AC power failure ● ● ● ●
52 Fire alarm system low battery ● ● ● ●
CONTROL

CIRCUITS
PANEL &

53 Open circuit ● ● ● ●
54 Ground fault ● ● ● ●
55 Notification appliance circuit short ● ● ● ●

(1) Action with temporization , after activation of gas extinguishing system


(2) Action controlled by DCS
(3) if this solution exist
SYSTEM OUTPUTS

Control unit Annunciation Notification Fire Safety Controls Supplementary

Actuate common supervisory signal/indicator

Close smoke / fire dampers in rated walls


Actuate common trouble signal/indicator

Release magnetically held smoke doors


Actuate common alarm signal/indicator

Actuate audible common trouble signal


Overall Input / Output Matrix

Transmit fire alarm signal to FACP


Actuate audible supervisory signal

Transmit trouble signal to FACP

Activate the gas solenoid valve


Display / print change of status
Actuate Zone 1 alarm indicator
Actuate Zone 2 alarm indicator
Actuate audible alarm signal

Actuate Emergency Lighting


Actuate evacuation signals
Important note: Contractor is responsible of estimating quantities of each

Shutdown systems (*)


device listed in this matrix.

Stop air-conditioning

Unlock exits
SYSTEM INPUTS A B C D E F G H I J K L M N O P Q R S T U V W X
STATIONS
PULL

1 Manual fire alarm call point ● ● ● ● ● ●


RELEASE
MANUAL

Manual release gas extinguishing


2
system
● ● ● ● ● ● ● ● ● ●
EMERGENCY
STOP

Emergency stop gas extinguishing


3 A
system
DETECTOR

4 smoke detectors Zone 1 ● ● ● ● ● ● C C C C C


HEAT &
SMOKE

5 Heat / smoke detectors Zone 2 ● ● ● ● ● ● C C C C C

6 Charge controller ● ● ●
PANEL & CIRCUITS

Gas flow controller ● ●


AC power failure ● ● ●
CONTROL

7 low battery ● ● ●
8 Open circuit ● ● ●
9 Ground fault ● ● ●
10 Notification appliance circuit short ● ● ●

A: Momentaneous stop and resume of temporisation once the emergency stop button is released

C : With confirmation mode

(*) Action controlled by DCS


ZONES TABLE FACP3

LOCATION ALARM AREA DEVICES CODE


PEBT3_LB-DET-G--N°1
Poste électrique PEBT1_LB-DF-SI-N°1
PEBT3- Heat/Smoke
basse tension Zone 1 PEBT3_LB-DET-G--N°2
ALR-N°1 detectors
sous-station 3 PEBT3_TR-DMC-N°13
PEBT3_LB-MAC-N°1
ZONES TABLE FECP1

Extinguishing zones
LOCATION Manual fire alarm call point Alarms
Extinguishing Zone 1 Extinguishing Zone 2
: Détection : Confirmation

PEBT1_MCC-DF-N°1 PEBT1_MCC-DMC-N°1
PEBT1_MCC-DF-N°2 PEBT1_MCC-DMC-N°2
PEBT1_MCC-DF-N°3 PEBT1_MCC-DMC-N°3 PEBT1_MCC-MAC-N°1
PEBT1_MCC-DF-N°4 PEBT1_MCC-DMC-N°4
PEBT1_MCC-DF-N°5 PEBT1_MCC-DMC-N°5 PEBT1_MCC-ALR-N°1
PEBT1_MCC-DF-N°6 PEBT1_MCC-DMC-N°6
PEBT1_MCC-DF-N°7 PEBT1_MCC-DMC-N°7
PEBT1_MCC-DF-N°8 PEBT1_MCC-DMC-N°8 PEBT1_MCC-MAC-N°2
MCC "LV " ROOM Smoke PEBT1_MCC-DF-N°9 Heat /Smoke PEBT1_MCC-DMC-N°9
SUBSTATION 1 detectors PEBT1_MCC-DF-N°10 detectors PEBT1_MCC-DMC-N°10
PEBT1_MCC-DF-N°11 PEBT1_MCC-DMC-N°11
PEBT1_MCC-DF-N°12 PEBT1_MCC-DMC-N°12
PEBT1_MCC-DF-N°13 PEBT1_MCC-DMC-N°13 PEBT1_MCC-MAC-N°3
PEBT1_MCC-DF-N°14 PEBT1_MCC-DMC-N°14 PEBT1_MCC-ALR-N°2
PEBT1_MCC-DF-N°15 PEBT1_MCC-DMC-N°15
PEBT1_MCC-DF-N°16 PEBT1_MCC-DMC-N°16
PEBT1_MCC-DF-N°17 PEBT1_MCC-DMC-N°17 PEBT1_MCC-MAC-N°4
PEBT1_MCC-DF-N°18 PEBT1_MCC-DMC-N°18
ZONES TABLE FECP2

Extinguishing zones
Manual fire alarm
LOCATION Extinguishing Zone 1 Extinguishing Zone 2 Alarms
call point
: Détection : Confirmation

PEMT1_MCC-DF-N°1 PEMT1_MCC-DMC-N°1
PEMT1_MCC-DF-N°2 PEMT1_MCC-DMC-N°2
PEMT1_MCC-DF-N°3 PEMT1_MCC-DMC-N°3
PEMT1_MCC-DF-N°4 PEMT1_MCC-DMC-N°4 PEMT1_MCC-MAC-N°1
PEMT1_MCC-DF-N°5 PEMT1_MCC-DMC-N°5
PEMT1_MCC-DF-N°6 PEMT1_MCC-DMC-N°6
PEMT1_MCC-DF-N°7 PEMT1_MCC-DMC-N°7
PEMT1_MCC-DF-N°8 PEMT1_MCC-DMC-N°8
PEMT1_MCC-DF-N°9 PEMT1_MCC-DMC-N°9
MCC "MV " ROOM Smoke PEMT1_MCC-DF-N°10 Heat /Smoke PEMT1_MCC-DMC-N°10
PEMT1_MCC-ALR-N°1
SUBSTATION 1 detectors PEMT1_MCC-DF-N°11 detectors PEMT1_MCC-DMC-N°11 PEMT1_MCC-MAC-N°2
PEMT1_MCC-DF-N°12 PEMT1_MCC-DMC-N°12
PEMT1_MCC-DF-N°13 PEMT1_MCC-DMC-N°13
PEMT1_MCC-DF-N°14 PEMT1_MCC-DMC-N°14
PEMT1_MCC-DF-N°15 PEMT1_MCC-DMC-N°15
PEMT1_MCC-DF-N°16 PEMT1_MCC-DMC-N°16
PEMT1_MCC-DF-N°17 PEMT1_MCC-DMC-N°17
PEMT1_MCC-MAC-N°3
PEMT1_MCC-DF-N°18 PEMT1_MCC-DMC-N°18
PEMT1_MCC-DF-N°19 PEMT1_MCC-DMC-N°19
PEMT1_MCC-DF-N°20 PEMT1_MCC-DMC-N°20
ZONES TABLE FECP3

Extinguishing zones
Manual fire alarm call
LOCATION Alarms
Extinguishing Zone 1 Extinguishing Zone 2 point
: Détection : Confirmation
CR_SA-DF-N°1 CR_SA-DMC-N°1
CR_SA-DF-N°2 CR_SA-DMC-N°2 CR_SA-MAC-N°1
SALLE DES CR_SA-DF-N°3 CR_SA-DMC-N°3
Smoke Heat /Smoke
ARMOIRES CR_SA-ALR-N°1
detectors CR_SA-DF-N°4 detectors CR_SA-DMC-N°4
CONTROL ROOM
CR_SA-DF-N°5 CR_SA-DMC-N°5 CR_SA-MAC-N°2
CR_SA-DF-N°6 CR_SA-DMC-N°6
ZONES TABLE FECP5

Extinguishing zones
Manual fire alarm call
LOCATION Alarms
Extinguishing Zone 1 Extinguishing Zone 2 point
: Détection : Confirmation

PEMT2_MCC-DF-N°1 PEMT2_MCC-DMC-N°1
PEMT2_MCC-DF-N°2 PEMT2_MCC-DMC-N°2
PEMT2_MCC-DF-N°3 PEMT2_MCC-DMC-N°3
PEMT2_MCC-DF-N°4 PEMT2_MCC-DMC-N°4
PEMT2_MCC-DF-N°5 PEMT2_MCC-DMC-N°5
PEMT2_MCC-DF-N°6 PEMT2_MCC-DMC-N°6
PEMT2_MCC-DF-N°7 PEMT2_MCC-DMC-N°7
PEMT2_MCC-DF-N°8 PEMT2_MCC-DMC-N°8
PEMT2_MCC-DF-N°9 PEMT2_MCC-DMC-N°9 PEMT2_MCC-MAC-N°1
PEMT2_MCC-DF-N°10 PEMT2_MCC-DMC-N°10
PEMT2_MCC-DF-N°11 PEMT2_MCC-DMC-N°11
PEMT2_MCC-DF-N°12 PEMT2_MCC-DMC-N°12
PEMT2_MCC-DF-N°13 PEMT2_MCC-DMC-N°13
PEMT2_MCC-DF-N°14 PEMT2_MCC-DMC-N°14
PEMT2_MCC-DF-N°15 PEMT2_MCC-DMC-N°15
MCC "MV " PEMT2_MCC-DF-N°16 PEMT2_MCC-DMC-N°16
ROOM Smoke PEMT2_MCC-DF-N°17 Heat /Smoke PEMT2_MCC-DMC-N°17
PEMT2_MCC-ALR-N°1
SUBSTATI detectors PEMT2_MCC-DF-N°18 detectors PEMT2_MCC-DMC-N°18
ON 2 PEMT2_MCC-DF-N°19 PEMT2_MCC-DMC-N°19
PEMT2_MCC-DF-N°20 PEMT2_MCC-DMC-N°20
PEMT2_MCC-DF-N°21 PEMT2_MCC-DMC-N°21
PEMT2_MCC-DF-N°22 PEMT2_MCC-DMC-N°22
PEMT2_MCC-DF-N°23 PEMT2_MCC-DMC-N°23
PEMT2_MCC-DF-N°24 PEMT2_MCC-DMC-N°24
PEMT2_MCC-DF-N°25 PEMT2_MCC-DMC-N°25
PEMT2_MCC-DF-N°26 PEMT2_MCC-DMC-N°26 PEMT2_MCC-MAC-N°2
PEMT2_MCC-DF-N°27 PEMT2_MCC-DMC-N°27
PEMT2_MCC-DF-N°28 PEMT2_MCC-DMC-N°28
PEMT2_MCC-DF-N°29 PEMT2_MCC-DMC-N°29
PEMT2_MCC-DF-N°30 PEMT2_MCC-DMC-N°30
PEMT2_MCC-DF-N°31 PEMT2_MCC-DMC-N°31
PEMT2_MCC-DF-N°32 PEMT2_MCC-DMC-N°32
PEMT2_MCC-DF-N°33 PEMT2_MCC-DMC-N°33
PEMT2_MCC-DF-N°34 PEMT2_MCC-DMC-N°34
ZONES TABLE FECP6

Extinguishing zones
Manual fire alarm call
LOCATION Extinguishing Zone 1 Extinguishing Zone 2 Alarms
point
: Détection : Confirmation
PEBT2_MCC-DF-N°1 PEBT2_MCC-DMC-N°1
PEBT2_MCC-DF-N°2 PEBT2_MCC-DMC-N°2
PEBT2_MCC-DF-N°3 PEBT2_MCC-DMC-N°3
PEBT2_MCC-MAC-N°1
PEBT2_MCC-DF-N°4 PEBT2_MCC-DMC-N°4
PEBT2_MCC-DF-N°5 PEBT2_MCC-DMC-N°5
MCC "LV " ROOM Smoke Heat /Smoke
PEBT2_MCC-DF-N°6 PEBT2_MCC-DMC-N°6 PEBT2_MCC-ALR-N°1
SUBSTATION 2 detectors detectors
PEBT2_MCC-DF-N°7 PEBT2_MCC-DMC-N°7
PEBT2_MCC-DF-N°8 PEBT2_MCC-DMC-N°8
PEBT2_MCC-DF-N°9 PEBT2_MCC-DMC-N°9 PEBT2_MCC-MAC-N°2
PEBT2_MCC-DF-N°10 PEBT2_MCC-DMC-N°10
PEBT2_MCC-DF-N°11 PEBT2_MCC-DMC-N°11
ZONES TABLE FECP7

Extinguishing zones
Manual fire alarm call
LOCATION Extinguishing Zone 1 Extinguishing Zone 2 Alarms
point
: Détection : Confirmation

PEBT2_DCS-MAC-N°1
DCS "LV " Smoke Heat /Smoke
PEBT2_DCS-DF-N°1 PEBT2_DCS-DMC-N°1 PEBT2_DCS-ALR-N°1
SUBSTATION 2 detectors detectors
PEBT2_DCS-MAC-N°2
ZONES TABLE FECP8

Extinguishing zones
Manual fire alarm call
LOCATION Extinguishing Zone 1 Extinguishing Zone 2 Alarms
point
: Détection : Confirmation

PEBT3_MCC-MAC-N°1

PEBT3_MCC-DF-N°1 PEBT3_MCC-DMC-N°1
"LV "
Smoke Heat /Smoke PEBT3_MCC-MAC-N°2PEBT3_MCC-ALR-N°1
SUBSTATIO
detectors detectors
N3

PEBT3_MCC-DF-N°2 PEBT3_MCC-DMC-N°2PEBT3_MCC-MAC-N°3