Assessment on Human Comfort Criteria of Tall Building under Dynamic Wind Loading
Published By:
Retrieval Number: B6688129219/2019©BEIESP Blue Eyes Intelligence Engineering
DOI: 10.35940/ijitee.B6688.129219 2266 & Sciences Publication
International Journal of Innovative Technology and Exploring Engineering (IJITEE)
ISSN: 2278-3075, Volume-9, Issue-2, December 2019
500mm x 900mm
Inner
9 Beam Size (31-50 story)
Slab 200mm ( 1-30 story)
10 thickness 180mm(31-50 story) 160mm ( 1-30 story)
Shear Wall 500mm ( 1-30 story)
11 Thickness 400mm(31-50 story) 350mm ( 1-30 story)
Density of
12 concrete 25 KN/M3 25 KN/M3 Fig 4: G+ 50 maximum Story displacements
Density of
13 steel 78.50KN/M3 78.50KN/M3 Discussion: -
Density of 1) In G+50 Framed Tube Structure with Normal Slab,
brick wall
with
Secondary Beam, Waffle Slab and Ribbed Slab, the
14 plaster 20 KN/M3 20 KN/M3 Maximum Story displacement is obtained at framed tube with
Terrain secondary beam and minimum Displacement is obtained at
15 category 1,2,3 &4 1,2,3 &4
framed tube with Ribbed Slab.
Structural
16 class C C 2) Framed Tube Structure with secondary beam are dominant
secondary in Story Displacement due to the self weight (dead weight) of
17 beam size 500mm x 800 mm 300mm x 600 mm
the structure are increases due to secondary beam.
100 mm depth with 100 mm depth with 150
Waffle slab 150 mm stem width mm stem width at top 3) Terrain Category 1 (TC1) obtained the maximum
18 size at top and bottom and bottom Displacement and Terrain Category 4 (TC4) obtained the
100 mm depth with 100 mm depth with 150 minimum Displacement from the TC1, TC2, TC3 & TC4.
Ribbed 150 mm stem width mm stem width at top
19 slab size at top and bottom and bottom 4) As per above result the Framed Tube Structure with
Foundatio Fixed at Ground Fixed at Ground Level Ribbed Slab lies in TC4 will be safer side from the all the
20 n Level structural from models.
Table- III: Material Properties of Buildings A.2 G+40 Story:-
Material Properties of Buildings
Table- V: Maximum Story Displacement
S.No. Material Grade Maximum Story Displacement Results (mm)
1 Concrete M40 G+40 Story
(Beam
Column) S.No. Structure Type TC1 TC2 TC3 TC4
Framed Tube
2 Concrete M40 Structure with Normal
(Shear Wall) 1 Slab 24.385 23.118 20.535 18.531
3 Concrete M40 Framed Tube
(Slab) Structure with
2 Secondary Beam 24.452 23.185 20.602 18.597
4 Reinforcemen HYSD-500 Framed Tube
t (Rebar) Structure with Waffle
IV. RESULT AND DISCUSSIONS 3 Slab 24.405 23.139 20.556 18.551
Framed Tube
A. Maximum Story Displacement:- Structure with Ribbed
A.1 G+50 Story:- 4 Slab 24.385 23.118 20.535 18.531
Published By:
Retrieval Number: B6688129219/2019©BEIESP
2267 Blue Eyes Intelligence Engineering
DOI: 10.35940/ijitee.B6688.129219
& Sciences Publication
Assessment on Human Comfort Criteria of Tall Building under Dynamic Wind Loading
Published By:
Retrieval Number: B6688129219/2019©BEIESP Blue Eyes Intelligence Engineering
DOI: 10.35940/ijitee.B6688.129219 2268 & Sciences Publication
International Journal of Innovative Technology and Exploring Engineering (IJITEE)
ISSN: 2278-3075, Volume-9, Issue-2, December 2019
Table- VIII: Peak Acceleration Results Framed Tube Structure With 0.084 0.085 0.086 0.091
4 Ribbed Slab 6 9 4 9
2
Peak Acceleration Results (m/s )
G+50 Story
S.
No. Structure Type TC1 TC2 TC3 TC4
Framed Tube Structure
1 With Normal Slab 0.1143 0.1211 0.1336 0.1345
Framed Tube Structure
2 With Secondary Beam 0.1145 0.1213 0.1339 0.1354
Framed Tube Structure
3 With Waffle Slab 0.1143 0.1211 0.1336 0.1339
Framed Tube Structure
4 With Ribbed Slab 0.1144 0.1212 0.1338 0.1347
G+40 Story
S.
No. Structure Type TC1 TC2 TC3 TC4
Published By:
Retrieval Number: B6688129219/2019©BEIESP
2269 Blue Eyes Intelligence Engineering
DOI: 10.35940/ijitee.B6688.129219
& Sciences Publication
Assessment on Human Comfort Criteria of Tall Building under Dynamic Wind Loading
2) Terrain Category 1 (TC1) obtained the minimum Mode 3 0.639 0.00423 1.565 0.000020 0.000023 0.000028 0.000031
acceleration and Terrain Category 2 (TC2) obtained the Mode 4 1.185 0.003344 0.844 0.000055 0.000061 0.000076 0.000084
maximum acceleration from the TC1, TC2, TC3 & TC4. Mode 5 1.194 0.003406 0.837 0.000057 0.000063 0.000078 0.000087
3) As per above result the different models of Framed Tube Mode 6 1.765 0.004875 0.566 0.000178 0.000198 0.000245 0.000271
Structure are generated the peak acceleration value under the Mode 7 2.34 0.002695 0.427 0.000173 0.000193 0.000238 0.000263
range 0.072 to 0.076 m/s2. 2.385 0.419
Mode 8 0.002797 0.000187 0.000208 0.000256 0.000284
B.4 G+20 Story:-
Mode 9 3.181 0.003932 0.314 0.000466 0.000520 0.000641 0.000710
Table- XI: Peak Acceleration Results
Mode 10 3.579 0.003135 0.279 0.000471 0.000525 0.000647 0.000716
Peak Acceleration Results (m/s2)
Mode 11 3.681 0.003232 0.272 0.000513 0.000572 0.000705 0.000781
G+20 Story
S. Mode 12 4.629 0.003051 0.216 0.000766 0.000854 0.001053 0.001166
No. Structure Type TC1 TC2 TC3 TC4
Framed Tube Structure
1 With Normal Slab 0.042 0.0416 0.0394 0.035
Framed Tube Structure
2 With Secondary Beam 0.0424 0.0419 0.0399 0..0355
Framed Tube Structure
3 With Waffle Slab 0.0426 0.0421 0.0401 0.0357
Framed Tube Structure
4 With Ribbed Slab 0.0424 0.042 0.04 0.0356
Published By:
Retrieval Number: B6688129219/2019©BEIESP Blue Eyes Intelligence Engineering
DOI: 10.35940/ijitee.B6688.129219 2270 & Sciences Publication
International Journal of Innovative Technology and Exploring Engineering (IJITEE)
ISSN: 2278-3075, Volume-9, Issue-2, December 2019
Published By:
Retrieval Number: B6688129219/2019©BEIESP
2271 Blue Eyes Intelligence Engineering
DOI: 10.35940/ijitee.B6688.129219
& Sciences Publication
Assessment on Human Comfort Criteria of Tall Building under Dynamic Wind Loading
Modes result of Peak Acceleration (TC4) obtained the minimum Displacement due to buffeting
Story Minimum Maximum Reference Effect effect of building.
acceleration acceleration Perceptio
(m/s2) (m/s2) n range
G+50 0.000005 0.0016 < 0.005 Humans cannot 8) In G+20 peak acceleration is obtained at framed tube with
Perceive Motion. Waffle Slab are maximum in all terrain categories and
G+40 0.000006 0.0022 < 0.005 Humans cannot minimum acceleration is obtained at framed tube with Normal
Perceive Motion.
G+30 0.000016 0.0037 < 0.005 Humans cannot
Slab. So normal slab structure is safer in G+20 Story.
Perceive Motion.
G+20 0.000005 0.0077 0.005-0.0 Sensitive people can 9) In G+50, G+40, G+30 and G+20 Terrain Category 1 (TC1)
10 perceive motion.
Hanging objects may obtained the minimum Acceleration and Terrain Category 4
move slightly (TC4) obtained the maximum acceleration.
Published By:
Retrieval Number: B6688129219/2019©BEIESP Blue Eyes Intelligence Engineering
DOI: 10.35940/ijitee.B6688.129219 2272 & Sciences Publication
International Journal of Innovative Technology and Exploring Engineering (IJITEE)
ISSN: 2278-3075, Volume-9, Issue-2, December 2019
AUTHORS PROFILE
Arvind Vishwakarma, PG Scholar, Doing his
Master of Engineering(ME) in Computer Aided
Structural Design & Drafting (CASDD) at
Ujjain Engineering College,Ujjain.Teaching
Experience 2 years.
Email id: visharvind28@gmail.com
Published By:
Retrieval Number: B6688129219/2019©BEIESP
2273 Blue Eyes Intelligence Engineering
DOI: 10.35940/ijitee.B6688.129219
View publication stats
& Sciences Publication