MAS For 'SKM' Products

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 202

S.K.

M Air Conditioning LLC


Pre Qualification Brochure

facebook.com/skmaircon www.skmaircon.com @skmaircon

Sharjah Economic Excellence


Award winner

AIR CONDITIONING EQUIPMENT


SKM offers premium international quality air conditioning equipment
and it is committed to total customer satisfaction. SKM is proud of its
equipment that work efficiently in various geographic locations like:

Lebanon Afghanistan
Iraq
Morocco Jordan
Algeria
Kuwait Pakistan
Libya
Egypt Saudi Bahrian
Arabia Qatar Bangladesh
UAE India
Oman

Eritrea Yemen Thailand


Gambia Philippines

Kenya

Tanzania

UAE | Saudi Arabia | Kuwait | Bahrain | Qatar | Oman | Iraq | Egypt


Lebanon | Jordan | Libya | Yemen | Bangladesh | India | Pakistan |
Thailand | Philippines | Eritrea | Tanzania | Gambia
Algeria | Kenya | Morocco | Afghanistan | South Korea

For more details on SKM projects please visit


www.skmaircon.com/skm_projects
Index
Company Introduction 04
History 06
SKM Manufacturing Standards 07
SKM Major Vendors 08
SKM Product Line 11
Certifications 15
SKM Laboratory 16
Spare Parts Division 17
Service Center 19
Regional Offices 22

3
AIR CONDITIONING EQUIPMENT
AIR CONDITIONING EQUIPMENT

VISION
To grow internationally with competent products and employees to provide consistent
quality and customer satisfaction.

MISSION
Total Customer Satisfaction.

INTRODUCTION

S.K.M Air Conditioning LLC is one of the leading manufacturers of HVAC (Heating,
Ventilation and Air Conditioning) equipment in the Gulf. It was founded with a single-
minded objective; to meet the growing needs of indoor environment quality in some of
the world’s harshest climates. Driven by its mission “Total Customer Satisfaction”, SKM
offers a broad portfolio of premium international quality products that have worked
efficiently in various geographic locations. SKM has provided solutions for many blue
chip projects for the companies, organizations and government agencies across the
region, to view its major projects portfolio please follow the link:
www.skmaircon.com/skm_projects

SKM is the proud winner of Sharjah Economic Excellence Award in the Gold category; it
is also recipient of ISO 9001:2008, ISO 14001:2004 and OHSAS 18001:2007 certifications.
Additionally SKM products are certified by internationally recognized testing and
certification bodies such as Eurovent certified Air Handling Units, AHRI Certified Air
Cooled Chilling package, AHRI Certified - Chilled Water / Hot Water Coils, TÜV certified
Hygienic Air Handling Units and unitary Packaged Air Conditioners. To know more about
the certifications it received please follow the link:
www.skmaircon.com/certificates

4
HEAD OFFICE
Sharjah, UAE

SKM units provide continuous excellent


performance in the extreme Gulf Environments
and in other specific applications such as
Onshore and Offshore Oil and Gas Installations,
Sewage Treatment Plants and Ammunition
Depots where explosion proof equipment are
required.
SKM is committed to offer products of superior
quality at competitive prices. Whether it is
Custom Built Units or any of the standard units,
which are manufactured and sold widely by
SKM each year, SKM philosophy remains one:
attention to detail and commitment to Total
Customer Satisfaction.

5
AIR CONDITIONING EQUIPMENT
History
1974 Four decades ago, SKM commenced production of air conditioning equipment
at industrial area 1 Sharjah. At the outset, SKM sourced collaboration and technical
agreements with manufacturers around the world.
1984 Continuing to comply with international product design standards, in 1984 SKM
completed an ambitious production facility expansion program and entered into a
licensing and technical agreement to manufacture standard packaged and ducted split
air conditioning units.
1994 In SKM’s endeavor to provide its customers with the latest and updated technology,
in 1994, SKM entered a Technology Transfer Agreement to produce swimpool products
with unique applications for the Gulf area.
1995 In 1995, SKM received ISO 9001 certification certifying that quality management
systems are being implemented in the company.
2002 Continuing with expansion plans, SKM shifted its production facility from
Industrial Area 1 to Industrial Area 13 Sharjah; it is modern state of the art 43,000 m2
factory, making it one of the largest air conditioned facilities of its kind in the entire
Gulf region. It is equipped with the latest technology and most advanced machinery to
produce air conditioning equipment that best serves the market needs.
In the same year, SKM also established another HVAC factory in the 2nd industrial City in
Dammam, Saudi Arabia. It is dedicated to the production of ducted splits units, fan coil
units and other air conditioning equipment.
2005 To enter more markets, SKM received Eurovent Certification for its Modular Air
Handling Units.
2010 Complying with international quality standards, SKM received ISO 14001
Certification certifying that it’s complying with environmental management standards
set by ISO.
In the same year SKM also received TÜV certification for its unitary Packaged Air
Conditioners series.
2011 In May 2011, SKM received Sharjah Economic Excellence Award Gold Category,
being recognized for its quality products and higher standards.
During the same year SKM also became recipient of OHSAS 18001 Certification certifying
that it is conforming to occupational health and safety.
2014 In the year of 2014, SKM received TÜV certification for its Hygienic Air Handling
Units which has special application in hospitals, laboratories and where absolute clean
air is required.
SKM also received AHRI Certification for its Air Cooled Screw Chillers.

6
SKM SALES HEAD OFFICE
Sharjah, UAE

SKM SHARJAH MANUFACTURING


FACILITY
Located at Industrial Area 13, SKM
operates out of a modern state of the art
43,000 squere meters factory, making it
one of the largest air conditioned facilities
of its kind in the entire Gulf region. It is
equipped with the latest technology and
most advanced machinery to produce air
conditioning equipment that best serves
the market needs.

SKM SAUDI MANUFACTURING FACILITY


Continuing with its expansion program
to cater every corner of the region, SKM
established another HVAC factory as a
scaled down version of Sharjah facility in
the 2nd industrial City in Dammam, Saudi
Arabia in the year of 2002.

7
AIR CONDITIONING EQUIPMENT
SKM Major Vendors

8
9
AIR CONDITIONING EQUIPMENT
International standards followed for SKM products:
All SKM units are designed, manufactured,  rated and tested in the Gulf to comply/
certified with  the  following  codes  and  standards.

UNITS / PRODUCTS CODE / STANDARD


Air Handling Units ARI 430, Eurovent OM-5, AMCA 210/ASHRAE 51

Chillers ASHRAE 30 and ANSI/ARI 550-590

Coils ARI 410 and ASHRAE 33

Compressors DIN Standard, ARI Standard 540, ARI 500

Condensing Units ARI 365

Expansion Valves ASHRAE 17 and ANSI/ARI Standard 750

Fan Coil Units ARI 440 & ASHRAE 79

Fans ANSI/ASHRAE 51 & ANSI/AMCA 210

Air Filters ARI 850, ASHRAE 52.1 & ASHRAE 52.2

Motors IEC Standard

Tubes & FiƩings ANSI B 16.22, ANSI B 31.5, ASHRAE 15, ASTM B88 & B280

Liquid Receivers ANSI/ARI 495


Split & Packaged Units ANSI/ARI 210/240 and 340/360

Safety Codes ANSI/ASHRAE 15


Solenoid Valves ARI 760

Valves ARI 720


InsulaƟon NFPA-90 A & B

Controllers & Wirings NEC 430 & 440


Liquid Line Driers ARI 710

Refrigerant Pressure RegulaƟng Valves ARI 770


Heat Wheel

Heat Pipe
ASHRAE 84 & ARI 1061
Fixed Plate

Run-Around-Coil

10
SKM Product Line

11
AIR CONDITIONING EQUIPMENT
12
13
AIR CONDITIONING EQUIPMENT
AIR CONDITIONING EQUIPMENT
14
Certifications

Some of the Certifications SKM


received

For more information about SKM certifications please visit:


www.skmaircon.com/certificates

15
15
AIR CONDITIONING EQUIPMENT
SKM Laboratory
AHRI Certified
SKM Laboratory is primarily dedicated to Research and Development of SKM product line to further
strengthen its quality and to contribute in solving Heating, Ventilating, and Air-conditioning
industry issues. It also offers a comprehensive range of performance tests for SKM customers, other
air-conditioning equipment manufacturers and any other interested parties.

SKM Laboratory testing procedures are based on AMCA, ASHRAE and AHRI standards which cover
operating performance, cooling and heating capacity, energy consumption, air flow rate, and the
likes whichever is applicable. Furthermore, we at SKM lab follow TUV Certified testing methods.

SKM testing laboratory is run by qualified engineers and technicians to ensure quality test output.

SKM laboratory set-up has been designed and built in accordance with:
• ASHRAE 30 - “Methods of Testing Liquid Chilling packages”
• ASHRAE 37 -”Method of Testing for Rating Electrically Driven Unitary Air-conditioning and Heat
Pump Equipment”
• ASHRAE 41.1 –“Standard Method for Temperature Measurement”
• ASHRAE 41.2 –“Standard Method for Laboratory Airflow Measurement”
• ASHRAE 41.3 –“Standard Method for Pressure Measurement”
• ASHRAE 41.6 – “Standard Method of Measurement of Moist Air Properties”
• ASHRAE 51 – “Laboratory Methods of Testing Fans for Aerodynamic Performance Rating”
• ASHRAE 79 – “Method of Testing for Rating Fan-Coil Conditioners”

The facility is made up of an indoor, outdoor and computers aided control room. Computers aided
control room allows simulation and flexibility to control different variables for a certain test procedure
for specific unit. Indoor side contains psychrometric loop wherein reconditioning equipment and
airflow measuring apparatus are integrated. The outdoor side temperature is being controlled
based on the required ambient temperature for the test unit.

16
Spare Parts Division
Get Genuine
SKM MISSION STATEMENT

PROMISE OF QUALITY SERVICE

SKM has always believed in assured quality services in all our projects and / or services we
undertake, be it a supply of equipment, spare parts, a project, installation or maintenance.

SKM services not only end with fulfilling the customer’s requirement or request but we believe
in taking our services a step forward with continuous follow-up. This is the key to why our
clients opt to deal with SKM from time to time with new projects / requirements which helps
SKM acquire new clients from competitors.

The business of the Air conditioning industry has grown at a tremendous speed in the past few
years and we believe this growth will continue with time.

SKM Air conditioning Equipment is fully equipped and prepared for market growth as it is in
the forefront of the industry as market leaders. Our vision is therefore to sustain our position
as market leaders and achieve our goals of setting standards and to satisfy our clients in every
aspect of their requirement.

SKM sincerely hopes to be at service to clients today and in future in the supply of Air conditioning
equipment & Spare parts.

SKM Air conditioning Equipment has been an HVAC manufacturer, spare parts and equipments
supply company representing international brand components.

SKM takes great pride in introducing itself as a leading manufacturer & supplier of HVAC
equipment and spare parts.

SKM Air conditioning Equipment LLC holds inventory of major Air conditioning equipment
spare parts.

17
15
AIR CONDITIONING EQUIPMENT
Spare Parts

18
Service Centre
Continuous Proactive Product Support

SKM Service Center provides continuous proactive product support to its clients
throughout the whole life cycle of their equipment, saving them time and money by
avoiding their equipment downtime.

SKM parts are periodically quality checked. SKM research and development group is
not only improving the spare parts product quality but also developing products for
lower maintenance needs and better customer satisfaction. SKM combines integrated
servicing solutions with highly dependable maintenance and parts support.

SKM Service Centre provides:

- High quality Original Equipment Manufacturer parts

- Professional advice from selecting the right parts to choosing the best maintenance and
servicing package

- A wide range of maintenance and servicing contracts to match the mix of the nature of your
business and your budget

- Technical and Engineering advice

- Troubleshooting

- Start-up of equipment

- Periodic maintenance on contractual basis

- Supply of spare parts

- Factory and site training as and when required

19
15
AIR CONDITIONING EQUIPMENT
20
NOTES

21
15
AIR CONDITIONING EQUIPMENT
HEAD OFFICE
P.O Box: 6004
Sharjah, United Arab Emirates
Tel: +971 6 514 3333
Fax: +971 6 514 3300
Email: sales@skmaircon.com
Email: info@skmaircon.com

Spare Parts Division


Email: spareparts.skm@skmaircon.com

Service Centre
Email: aftersales.skm@skmaircon.com

REGIONAL OFFICES
United Arab Emirates Saudi Arabia (Production Facility)
Abu Dhabi SKM Air Conditioning Factory
P.O Box: 27788 Eastern province
Tel: +971 2 6445223 AD Dammam
Fax: +971 2 6445145 2nd industrial city
Email: abudhabisales.skm@skmaircon.com Abqiq main road Hail Street
Tel: +966 3 8123332 / 4 / 5
Al Ain
Fax: +966 3 8123337 / +966 3 8123092
Tel: +971 3 7619921
Email: saudifactory.skm@skmaircon.com
Fax: +971 3 7619941
Email: alainsales.skm@skmaircon.com Egypt
Dubai 9 Mosadak Street,
P.O Box: 98822 3rd floor, Dokki, Giza
Tel: +971 4 2940900 Tel: +20 2 37619617 / +20 2 37621974
Fax: +971 4 2940029 Fax: +20 2 37621973
Email: dubaisales.skm@skmaircon.com Email: egyptsales.skm@skmaircon.com

Kuwait Algeria
Dasman Aissat Idir ( EX-ENMA) City
P.O Box: 1215-PC 15463 Bldg1, Flat 2, Dar El Beida Algiers
Tel: +965 2 2492200 Tel: +213 21 508197
Fax: +965 2 2494400 Fax: +213 21 508197
Email: kuwaitsales.skm@skmaircon.com Email: algeriasales.skm@skmaircon.com

For SKM Distributors visit:


www.skmaircon.com
ACD/TGS/016-B/2023 Date: 26th Feb 2023

M/s. AL HASHAR ENGINEERING LLC


SULTANATE OF OMAN

Kind attn.: Mr. Rahul Jangir - Asst. Project Manager

Subject: Supply Only of ‘SKM’ ACs - Split type Units & ‘SKM’ Package ACs for your Proposed Nesto Project
in Al Amerat.

Dear Sir,

Further to the meeting had with you and your MEP Engineer, Mr. Ravi B Pandya, dated on 23rd Feb 2023,
regarding the above subject and our earlier offer Ref. ACD/TGS/016-A/2023 Dated on 01st Feb 2023 and have
pleasure in giving our offer for the same as per the following annexure.

ANNEXURE 1 - Equipment Schedule

ANNEXURE 2 - Commercial Offer

ANNEXURE 3 - List of Makes / Scope of Works

ANNEXURE 4 - Term & Conditions / Excluded Work and Services

ANNEXURE 5 - Quality Test Certificate

ANNEXURE 6 - Operating Temperature (Ambient) certificate

ANNEXURE 7 - Reference of the Package unit Landmark projects

We hope that the above is in line with your requirement and look forward to the pleasure of receiving your
valued order.
Thanking you and assuring you our best attention at all times.

Yours faithfully,

For, KHIMJI RAMDAS L.L.C


Air Conditioning & Appliances Division

Thirugnanam Sivanandam
Senior Sales Engineer
GSM: +968 91106461
ACD/TGS/016-B/2023 Date: 26th Feb 2023

ANNEXURE 1

Equipment Schedule:

 As per your BOQ

ITEM Qty
ITEM DESCRIPTION UNIT
NO. (Nos)
Split Type Air conditioner
18,000 BTU/HR capacity high-level wall mounted split type air conditioner
A including connection to electrical outlet, condensing drainage and concrete No. 1
base foundation.
23,200 BTU/HR capacity high-level wall mounted split type air conditioner
B including connection to electrical outlet, condensing drainage and concrete No. 4
base foundation.
ceiling suspended ducted split AC with DX unit - capacity 1.5 Tr as per
C No.
equipment schedule in the IFC drawings.
9
ceiling suspended ducted split AC with DX unit - capacity 2.0 Tr as per
D No.
equipment schedule in the IFC drawings.
ceiling suspended ducted split AC with DX unit - capacity 2.5 Tr as per
E No. 3
equipment schedule in the IFC drawings.
ceiling suspended ducted split AC with DX unit - capacity 3.0 Tr as per
F No. 2
equipment schedule in the IFC drawings.
ceiling suspended ducted split AC with DX unit - capacity 3.5 Tr as per
G No.
equipment schedule in the IFC drawings.
20
ceiling suspended ducted split AC with DX unit - capacity 4.0 Tr as per
H No.
equipment schedule in the IFC drawings.
ceiling suspended ducted split AC with DX unit - capacity 4.5 Tr as per
J No.
equipment schedule in the IFC drawings.
6
ceiling suspended ducted split AC with DX unit - capacity 5.0 Tr as per
K No.
equipment schedule in the IFC drawings.
Roof Top Package Unit
Roof top package unit, Total cooling capacity 30 TR with Aeris Coating for
A No. 8
Condenser
Roof top package unit, Total cooling capacity 20 TR with Aeris Coating for
B No. 1
Condenser

Page 2 of 18
ACD/TGS/016-B/2023 Date: 26th Feb 2023

Unit Summary

Brand: ‘SKM’, Country of origin: KSA, Refrigerant: R410A for Split type Units

Brand: ‘SKM’, Country of origin: Sharjah - UAE, Refrigerant: R410A for Package AC Units

Nominal
Sl. Capacity Qty Selection
Model Ref. Type of Unit Cooling
No. Class (Nos) Condition
Capacity
1 APMR52420G1 'SKM' Package AC Unit 30 TR 8 The Package AC
Units selection
2 APMR52300 'SKM' Package AC Unit 20 TR 1 @ Actual as per
your instruction
'SKM' Ducted ACs - Split type
3 DDP60+RX60 52,000 Btu/hr 4.5 TR 6
Units
'SKM' Ducted ACs - Split type
4 DDP48+RX48 48,000 Btu/hr 4.0 TR 20
Units
'SKM' Ducted ACs - Split type
5 DDP36+RX36 34,500 Btu/hr 3.0 TR 2 The Split type
Units
'SKM' Ducted ACs - Split type AC Units
6 DDP30+RX30 28,000 Btu/hr 2.5 TR 3 selection @
Units
'SKM' Ducted ACs - Split type Nominal as per
7 DDP24+RX24 23,500 Btu/hr 2.0 TR 9 your instruction
Units
'SKM' Wall Mounted ACs -
8 MSKMP-24C 23,200 Btu/hr 2.0 TR 4
Split type Units
'SKM' Wall Mounted ACs -
9 MSKMP-18C 18,000 Btu/hr 1.5 TR 1
Split type Units
Total No. of Units 54 Nos
Total Capacity of the Project (TR) 408 TR

Page 3 of 18
ACD/TGS/016-B/2023 Date: 26th Feb 2023

ANNEXURE 2

Commercial offer: -

Price: ‘SKM’ ACs Refrigerant R410A (Made in KSA/Sharjah - UAE)

Sl. Nominal Cooling Capacity


Model Ref. Type of Unit Qty (Nos)
No. Capacity Class
1 APMR52420G1 'SKM' Package AC Unit - 30 TR 8
2 APMR52300 'SKM' Package AC Unit - 20 TR 1

3 DDP60+RX60 'SKM' Ducted ACs - Split type Units 52,000 Btu/hr 4.5 TR 6

4 DDP48+RX48 'SKM' Ducted ACs - Split type Units 48,000 Btu/hr 4.0 TR 20

5 DDP36+RX36 'SKM' Ducted ACs - Split type Units 34,500 Btu/hr 3.0 TR 2

6 DDP30+RX30 'SKM' Ducted ACs - Split type Units 28,000 Btu/hr 2.5 TR 3

7 DDP24+RX24 'SKM' Ducted ACs - Split type Units 23,500 Btu/hr 2.0 TR 9

'SKM' Wall Mounted ACs - Split type


8 MSKMP-24C 23,200 Btu/hr 2.0 TR 4
Units
'SKM' Wall Mounted ACs - Split type
9 MSKMP-18C 18,000 Btu/hr 1.5 TR 1
Units

 Our Very special price for the above mentioned scope of works (Supply Only) shall be
R.O. 85,995/- (Including of VAT = 5%)

Kind Note:
 Further to meeting had with you & Mr. Ravi B Pandya, dated on 23rd Feb 2023, since the above
capacities & Quantities are instructed by you.
 As per your instruction dated on 23rd Feb 2023, all the Package AC Units selection is actual Cooling
Capacity (30 TR @ 46 Deg C & 20 TR @ 46 Deg C ).
 As per your instruction dated on 23rd Feb 2023, all the Ducted ACs & Wall mounted ACs - Split type
Units the capacity mentioned above are nominal Cooling Capacity only.
 The above equipment schedule areas are considered in the offer and other than areas are not
considered in the offer.
 2.0 TR has been proposed in the place of 1.5 TR as Ducted ACs - Split type Units are unavailable in that
capacity in our product range
 4.0 TR has been proposed in the place of 3.5 TR as Ducted ACs - Split type Units are unavailable in that
capacity in our product range

Page 4 of 18
ACD/TGS/016-B/2023 Date: 26th Feb 2023

 4.5 TR has been proposed in the place of 5.0 TR as Ducted ACs - Split type Units are unavailable in that
capacity in our product range
 In case of any model change / up-gradation of the above quoted models, the necessary charges
applicable will be extra.
 Installation of the AC units, Ducting works, Sound attenuators, VAV device, crane charges, Air curtain,
Ventilation systems, Control Panel & Maintenance/Service for New ACs & Maintenance/Service for
Existing ACs are not considered in the offer.
 Crane Service required for lifting & offloading of the material at the site to be provided by main
contractor or MEP contractor.
 Unless otherwise mentioned, all units confirm to original manufacturers standard and any special
treatments such anti corrosive coating (Thermo Guard Coating for ODU & IDU) have been excluded.
 Khimji Ramdas nominated sub-contractor contractors shall be executing the works for installation,
testing & commissioning works under the supervision of KR project team in order to maintain standard
and quality by KR.
 Anything that has not been specifically stated also stands excluded from our scope, which kindly note.
 Please read the Terms & Conditions and Exclusions.

Delivery Period:
 For Split type AC units = Ex stock, subject to prior sale.
 For package AC units = 12 to 16 weeks from the date of drawing and MAS approval, Please note that
against approval of MAS and Shop drawing, we will be able to start Ducting works immediately after the
AC drawing approval & MAS Approval.

Validity: This quotation is valid for 15 days from the date of this offer & subject to extension through mutual
consent only.

Payment terms: 100% as irrevocable LC, to be opened along with the confirmation of the order.

Cancellation charges: In the event of cancellation of an order before starting of works, you undertake to
reimburse us a fee equivalent to 15% of order value. Cancellation after the start of work will carry a fee
equivalent to 15% of order value plus value of the works carried out. Any Goods that have to be returned have
to be in Factory packed condition. Else KR shall not be obliged to accept such returns.

FORCE MAJEURE
No failure or omission by either party to carry out or observe any of the stipulations, conditions or obligations to
be performed hereunder shall give rise to any claims against such party or be deemed to be a breach of contract
if such failure or omission arises from a cause or event reasonably beyond the control of such party. An event
constituting such force majored would include inter-alia war-whether declared or not, or any hostile act or by
against a belligerent power, terrorism, explosion caused by either weapons or bombs stored in the vessel or
COVID Pandemic condition or Government action in other premises.

Page 5 of 18
ACD/TGS/016-B/2023 Date: 26th Feb 2023

Warranty: Applicable for a period of 12 months warranty for units shall be applicable from the date of supply
(Delivery. If operation of any unit is started for any reason whatsoever, the warranty period will commence from
the date of such use. Applicable for a period of 60 months warranty for compressors shall be applicable from the
date of supply (Delivery). If operation of any unit is started for any reason whatsoever, the warranty period will
commence from the date of such use. It will at KR’s sole discretion to repair or replace faulty components as KR
finds defective during the warranty period. Warranty does not include labour or any consumables like
refrigerant, oil, etc. Our offer does not include warranty against corrosion and electrical voltage fluctuation. The
warranty must be considered invalid in cases like expiration of the term, first start-up carried out by
unauthorized personnel, failure to comply with payment schedule, faulty installation, maintenance / repairs
/modifications made by unauthorized personnel, incorrect use of the unit. Wear & tear, lifting / crane / handling
shall not be covered under warranty.

ANNEXURE 3

List of makes and other considerations:


 Brand: ‘SKM’
 Country of origin: Sharjah - UAE for Package AC Units
 Brand: ‘SKM’
 Country of origin: KSA for Split type Units
 Refrigerant: R410A
 Necessary sleeves to be provided by others for running of AC refrigerant pipes and the refrigerant
pipes will go through the nearest Shaft/Sleeve up to Roof.
 All the AC Outdoor units to be kept on the roof level of the Penthouse Floor.
 Drain pipes for all the units to be provided by others located close to the AC provision.
 1PH & 3PH Power point/DP switches to be provided by others (Main contractor / MEP contractor), up
to the ODU/with the weather-proof isolator.

Scope of works:
 Supply Only of ‘SKM’ ACs - Split type Units & Package AC Units
 Installation & Ducting Works are not considered in the offer.
 Internal refrigerant piping and ducting will be hanged with threaded rods at regular intervals as per
standards.
 ODU location considered very nearest to sleeve/Shaft location
 Any variation in quantity due to change in location/design reworks shall be charged extra as per actual
at site.
 Noise level shall be as per manufacturer standard and we have worked on drawing shared to us &
subsequent discussion had with your good selves.
 Please read the Terms & Conditions and Exclusions.

Page 6 of 18
ACD/TGS/016-B/2023 Date: 26th Feb 2023

ANNEXURE 4

TERMS & CONDITIONS:


1. The prices quoted are for Supply only for the given location only. VAT INCLUDED.
2. In case PVC trunking is required, a 2” x 4” size will be used & charged at R.O. 6/- per meter.
3. Delivery charges will be charged appropriately, unless otherwise specified.
4. All deliveries to the Site /place of delivery will be signed by you. In case the person receiving the Goods is
different from the personnel signing the contract, an Authorization letter has to be given by you using the
enclosed letter. Kindly note that in case your authorized Representative is unavailable at the time of delivery,
please note that additional delivery charges at actual will be levied.
5. Your Order has to be confirmed either through a commercially valid Purchase Order (LPO applicable for
Companies only), or by an Agreement which will be signed both by us (KR) & your good selves.
6. Once such Orders are placed, you must arrange to receive /take delivery at the assigned time. In case you are
unable to do so, for whatever reasons, kindly note that the goods will be made available for sale to the next
customer. The delivery period, as stated in our quotation, will then be reapplied. However we shall do our best to
shortening this delivery period.
7. In case of such delays on your part as in para (6) above, please note that Models may change without prior
notice, as specified in the Manufacturer’s catalogue. If this should occur, any modifications to the site, piping etc
will have to be borne by you. This may also include, and not limited to, change in price of the AC Units itself.
8. Warranty conditions entail replacement of Compressors (where applicable), within the Warranty period as
applicable. Any consumables used like Oil, Gas etc will be charged extra as applicable. However if such repetitive
failures occur due to manufacturing defects, we will replace the Compressor with consumables free of cost.
9. Within the warrantee period of the Air conditioner or the Compressor, if the AC should be repaired by an Agency
external to Khimji Ramdas, such warranty will be ‘null & void’. This applies to any part of the Air conditioner. Any
further repairs shall only be on chargeable basis.
10. Some jobs in air conditioning have to be approved by you / your Consultant, through the Drawings presented to
you. Kindly note that any changes to this after work has started, can be accommodated only at extra cost.
11. For Ducted types of ACs, where changes in Ducting are required after the Duct has been manufactured, and extra
cost will have to be borne from your end, as the older version cannot be reused.
12. In case of any changes in statutory levies from the Quotation Date, it is agreed that the same shall be paid by you
at actuals.
13. KR has indicated sizes of ACCESS PANELS which are required for the routine maintenance /repairs in the drawings
provided. KR shall not be held responsible for providing this access at a later stage as and when the need may
arise.
14. Khimji Ramdas nominated sub-contractor contractors shall be executing the works for installation, testing &
commissioning works under the supervision of KR project team in order to maintain standard and quality by KR.
15. Crane Service required for lifting & offloading of the material at the site. All transportation shall be by KR or KR
nominated contractors
16. Unless otherwise mentioned, all units confirm to original manufacturers standard and any special treatments
such anti corrosive coating (Thermo Guard Coating for ODU & IDU) have been excluded.

Page 7 of 18
ACD/TGS/016-B/2023 Date: 26th Feb 2023

Exclusions:

Your special attention is invited to the following exclusions from our scope of work. This has to be undertaken
by you at your cost:
1. All Masonry & Civil work including breaking & making good of walls, pedestals for outdoor units,
MS Wall brackets, painting etc.
2. Installation & Ducting Works are not considered in the offer.
3. All Carpentry work required like cutting & making good of False Ceiling, provision of Access Doors for
Ducted Split ACs, either after Installation of ACs or for subsequent Maintenance Service.
4. Provision of adequately sized Condensate (Drain) water pipes near the Indoor Unit as may be
required.
5. All Electrical work like provision of DP switches, Isolators at roof top or any levels, cabling etc up to
the required location to enable Installation of the AC, Isolator to be fixed nearest to ODU ( Maximum
distance between ODU and Isolator shall be 1.5 meter)
6. Conduit for running thermostat cable for ducted, Cassette, floor standing AC units (from thermostat
location to IDU) & Package units (from thermostat location to Package units - Roof)
7. Separate lockable storage facility for keeping ACs & associated material or such Units ordered by you
before Installation.
8. Costs of Cranes required for lifting ACs to the roof top, or such locations.
9. Scaffolding for accessing the Installation locations.
10. Supply of temporary electrical & water supply that may be required for Installation.
11. Sleeves for carrying Refrigerant piping.
12. Cables Trays for carrying Refrigerant piping, Corra Cloth insulation, G.I trucking and electrical wires.
13. Wooden frame work for fixing AC Grilles.
14. BMS/Automation.
15. Any associated Insurance required for covering the work & work site.
16. Anything that has not been specifically stated also stands excluded from our scope, which kindly note.

We hope that you will find our offer in line with your requirement and we look forward to receive your valued
order at your earliest

Thanking you,

For, KHIMJI RAMDAS L.L.C


Air Conditioning & Appliances Division

Thirugnanam Sivanandam
Senior Sales Engineer
GSM: +968 91106461

Page 8 of 18
ACD/TGS/016-B/2023 Date: 26th Feb 2023

ANNEXURE 5

Quality Test Certificate:

Page 9 of 18
ACD/TGS/016-B/2023 Date: 26th Feb 2023

ANNEXURE 6
Operating Temperature(Ambient) certificate

Page 10 of 18
ACD/TGS/016-B/2023 Date: 26th Feb 2023

ANNEXURE 7
Reference of the Package unit Landmark projects

KR – ‘SKM’ Package unit Landmark projects -Partial list


Sl. Project
Project Name Customer / Contractor Location Status
No. Capacity (TR)
1 NESTO Hypermarket @ Saham Assarain Cont. 382 TR Saham completed
Sohar
M/s. Oman Fasteners
2 Fasteners Factory 63.4 TR Industrial completed
Company LLC
Area
3 Ware house M/s. OSWS 63.4 TR Sohar Port completed
4 Jindal Dawood Contracting PAC Sohar Port completed
Al Jufra -
5 Al Jufra Mosque Direct Customer 133.2 TR completed
Sohar
6 Al Huwail Mosque Direct Customer 108.2 TR Saham Completed
7 MOH Renal Dialysis Hospital MOH 75.1 TR Saham On going
8 Mr Husam Al Harthy customer Villa Direct Customer 10.4 TR Qurm On going
9 Mcdonalds Direct Customer 46.7 TR Qurm Completed
10 Rameez hypermarket Direct Customer PAC Rustaq Completed
11 RCA , Royal Yatch K&D Dawood Contracting PAC Muscat Completed
12 Al Mamura Majlis Direct Customer PAC Nizwa Completed
13 HE Mohammad Nasser Al Rasby - Villa Direct Customer PAC Muscat Completed
14 School - Duqum Al Tamam PAC Duqum Completed
15 RCA Mosque Vission Tech PAC Salalah Completed
16 REACO substation ONEIC PAC Duqum Completed
17 New International school Direct Customer PAC Muscat Completed
18 ROP Academy - Nizwa, PH 1 Saif Al Harasi PAC Nizwa Completed
19 ROP VIF - Sohar Al Nabeel PAC Sohar Completed
20 ROP VIF - Ibra Al Nabeel PAC Sohar Completed
21 PDO - Marmaul Al Rafaa PAC Marmul Completed
22 ROP -Armory Magazine store Modern Gulf Cont. PAC Nizwa Completed
23 Mosque GIC Gulf international PAC Muscat Completed
24 Villa - Mehta Direct Customer PAC Muscat Completed
25 Dr. Saif Villa Direct Customer PAC Muscat Completed
26 School - Salalah Al Tamam PAC Salalah Completed
27 VIP Villa Direct Customer PAC Sohar Completed
28 Al Bijar Trading Direct Customer PAC Muscat Completed
29 ROP STF - Shinas Saif Al Harasi PAC Shinas Completed
30 ROP STF- Saham Saif Al Harasi PAC Shinas Completed
31 Nizwa Foods NABC PAC Nizwa On going
* PAC – Package AC Units

Page 11 of 18
ACD/TGS/016-B/2023 Date: 26th Feb 2023

Page 12 of 18
ACD/TGS/016-B/2023 Date: 26th Feb 2023

LIST OF SOME PRESTIGIOUS PROJECTS SUPPLIED WITH SKM EQUIPMENTS


Sr.
Name of Project Name of Client Name of Contractor
No.
1 ROP Yanqul Royal Oman Police Al Amjad National projects
2 STF Complex at Nizwa Royal Oman Police Shamel International
3 ROP Nakhal Royal Oman Police Service & Trade Co. LLC.
4 ROP Rustaq Royal Oman Police Service & Trade Co. LLC.
5 STF Complex at Sohar Royal Oman Police Service & Trade Co. LLC.
ROP- Salalah
6 Royal Oman Police Al Mukhaini International Trdg. & Cont. L.L.C.
Recreation Centre
7 ROP-Yanqool Royal Oman Police Al Amjad National Projects
ROP- Khatmath
8 Royal Oman Police Al Mukhaini International Trdg. & Cont. L.L.C.
malaha
9 ROP- Mudaibi Royal Oman Police Al Mukhaini International Trdg. & Cont. L.L.C.
Rub Al Khalli Border
10 Royal Oman Police Galfar Engg. & Cont. SAOG.
post
11 ROP- Qurum Royal Oman Police Al Mukhaini International Trdg. & Cont. L.L.C.
Sultan Qaboos International Refrigeration & Air conditioning Co.
12 Royal Court Affairs
Mosque at Bidbid L.L.C.
Mcdonald outlet at Al Daud Restaurants
13 Al Daud Restaurants LLC.
Buraimi LLC.
Oman International
14 container Terminal at Sohar port Al Raffa Trdg. & Contg. L.L.C.
Sohar port
Shopping complex at
15 Private client National Construction & Electrical L.L.C.
Bani Bu Ali.
International Refrigeration & Air conditioning Co.
16 Hisn Sumookh Ph 14 A Royal Court Affairs
L.L.C.
Petroleum
17 Sai Rawl camp Cemec Engg. & Trading L.L.C.
Development Oman
Sultan Qaboos
18 Royal Court Affairs Modern Centre Electrical & Sanitary L.L.C.
Mosque at Sumail
RGO Surgent Mess at
19 Royal Court Affairs Al Ansari Trading Enterprises LLC.
BAB
Missile store in RAFO-
20 Ministry of Defense Al Bunyaan Trading LLC.
Salalah

Page 13 of 18
ACD/TGS/016-B/2023 Date: 26th Feb 2023

Sr.
Name of Project Name of Client Name of Contractor
No.
21 RAFO -Thumrait Ministry of Defense Sharikat Fanniya Omaniya (Salalah) LLC.
Petroleum Shamel International Industries Trdg. & contracting
22 Amal HRSG
Development Oman L.L.C.
Renal Dialysis Unit at
23 Ministry of Health Dolphin Radiators & Cooling Systems L.L.C.
Bausher
24 Hisn Sumookh Royal Court Affairs International Refrigeration & Airconditioning Co. L.L.C.
ABG Resort at Millenium Hotel,
25 Convrgnt Engg. & Const. Co.
Millennium Hotel Musannah
Renal Dialysis Unit at Mustafa Sultan Refrigeration & Airconditioning Co.
26 Ministry of Health
Shinas Services L.L.C.
Petroleum
27 PDO PACs at Lekhwair Al Raffa Trdg. & Contg. L.L.C.
Development Oman
Haya water at Al
28 Haya Water Development Services L.L.C.
Ansab
Other Rank
Shamel International Industries Trdg. & contracting
29 Accommodation at Ministry of Defense
L.L.C.
Bidbid
Sultan Qaboos
30 Royal Court Affairs Al Ansari Trading Enterprises L.L.C.
Mosque at Mahdha
PDO - Marmul & Petroleum
31 Al Raffa Trdg. & Contg. L.L.C.
Harwell Development Oman
32 ROP - Al Ajais Royal Oman Police Al Mukhaini International Trdg. & Cont. L.L.C.
33 ROP -Nizwa Royal Oman Police Al Mukhaini International Trdg. & Cont. L.L.C.
Office Building at Shamel International Industries Trdg. & contracting
34 Salim Shanfari
Greater Matrah L.L.C.
Containerized Building Petroleum
35 Arabian Industrial Engg. Co. L.L.C.
at Al Noor Development Oman
Sharikat Fanniya
36 HE Mosque at Salalah Sharikat Fanniya Omaniya (Salalah) LLC.
Omaniya (Salalah) LLC.
Renovation of Ruwi
37 Ruwi City Centre MEP Land & Marine L.L.C.
City Centre
38 MOD ASD Ministry of Defense TMTEC Trading & Technical Services L.L.C.
39 ROP - Bani Bu Ali Royal Oman Police Al Mukhaini International Trdg. & Cont. L.L.C.
Refurbishment of TV
40 TV Studio at Salalah Naif Home Appliance & Electronics LLC.
Studio at Salalah

Page 14 of 18
ACD/TGS/016-B/2023 Date: 26th Feb 2023

Sr.
Name of Project Name of Client Name of Contractor
No.
Life Line Hospital - Life Line Hospital -
41 Lotus Technical Services
Salalah Salalah
Minis of Higher
42 Minis of HE Sharikat Fanniya Omaniya (Salalah) LLC.
Education at Salalah
Car park - RGO
43 Royal Guard Oman Al Ansari Trading Enterprises LLC.
campus at Seeb
44 MOD -SAFTR GALAH Ministry of Defense Technique L.L.C.
Allied Business
45 Nizwa Resturant Al Noor Projects
Corporation
PDO- Amin & Al
46 PDO Technique L.L.C.
Khatala
47 MOD-WUDAM Ministry of Defense Mohamed & Ahmed Al Khonji L.L.C.
Sultan Qaboos
48 Royal Court Affairs Al Ansari Trading Enterprises LLC.
Mosque at Mabella
National Mineral National Mineral
49 Al Bunyaan Trading L. L. C.
water Co. at Salalah water Co.
Lectur hall- Ministry of
50 Ministry of Manpower Larsen & Toubro (Oman) LLC.
Manpower
51 British Council British Council Cemec Engg. & Trading L.L.C.
Sultan Qaboos
52 Royal Court Affairs Modern centre Electrical & Sanitary L.L.C.
Mosque at Madha
53 ROP - Bidiya & Yanqul Royal Oman Police Al Adrak Trading & Contracting Co. LLC.
Awaqd Villa No. 20 at
54 Royal Court Affairs Sharikat Fanniya Omaniya(Salalah) LLC.
Salalah
Permanent
55 accommodation at PDO Al Raffa Trdg. & Contg. L.L.C.
Marmul & Bhaja
Barr Al Jissah Coffe
56 Barr Al Jissah Al Bunya'an Trading L.L.C.
House
Robert Girl's School
57 Shamel International Industries Trdg. & contracting
and Sultan
58 Qaboos Boy's School Royal Court Affairs L.L.C.
59 Nizwa University Nizwa University Al Bunya'an Trading
ROP Nizwa
60 Royal Oman Police Al Bunya'an Trading
Headquarter

Page 15 of 18
ACD/TGS/016-B/2023 Date: 26th Feb 2023

Sr.
Name of Project Name of Client Name of Contractor
No.
61 12 & 14 Horse Box RCA Genetco
62 Airport Substation M.E.W Technique L.L.C.
63 Azaiba Substation M.E.W Technique L.L.C.
64 Saham Grid Station M.E.W Technique L.L.C.
65 Liwa Grid Substation M.E.W Technique L.L.C.
66 Muladha Substation M.E.W Technique L.L.C.
11 KVA Switchgear
67 PDO Al Bunya'an Trading
Building
68 Interlink Reversal PDO Al Bunya'an Trading
69 MOD -Wudam Ministry of Defense Technique L.L.C.
70 ROP ROP Diba Station Mohamed & Ahmed Al Khonji L.L.C.
71 Royal garrage at Seeb Royal Guard Oman Larsen & Toubro(Oman) LLC.
72 Al Barwani Villa Private client Khimji Ramdas L.L.C.
73 Muladah Substation M.E.W Technique L.L.C.
74 Arzat Development Ministry of Defence Modern Centre L.L.C.
75 Oasis Water Zubair Enterprises Technique L.L.C.
76 Baldiyah Hospital Ministry of Health Ahmed al Kharushi L.L.C.
77 Office Building ROP Al Ansari Trading Enterprises LLC.
78 Green house SQU Al Ansari Trading Enterprises LLC.
79 Famco SQU Technique L.L.C.
Ceremony Building @
80 Ministry of Defense SSB
Al Khoudh
Computer Building @
81 Ministry of Health Al Ansari Trading Enterprises LLC.
MOH Head Office
Various Facilities @
82 Ministry of Defense Modern Centre L.L.C.
Khasab
Ghubra Central
83 DGPM Al Ansari Trading Enterprises LLC.
Kitchen
Muscat Governorate
84 DGPM Modern Centre L.L.C.
Office
85 Bait Al Mamurah DGPM Al Bunya'an Trading
Tower Extension @
86 Ministry of Defense Technique L.L.C.
BAF
87 SBSNB Ministry of Defense Al Ansari Trading Enterprises LLC.
Bait Al Barakah Villa
88 DGPM Al Bunya'an Trading L.L.C.
no 8
89 Qasr Al - Alam DGPM Galfar Engg. & Cont. SAOG.
90 Hospital @ DUGM Ministry of Health Al Ansari Trading Enterprises LLC.

Page 16 of 18
ACD/TGS/016-B/2023 Date: 26th Feb 2023

Sr.
Name of Project Name of Client Name of Contractor
No.
91 Royal Flight DGPM Al Ansari Trading Enterprises LLC.
Salalah Hotels
92 Salalah Holiday Inn Salalah Hotels Company
Company
Pharmacy @ Khoula
93 Ministry of Health Al Ansari Trading Enterprises LLC.
Hospital
94 AL Nahda Hospital Ministry of Health Ahmed al Kharushi L.L.C.
95 Al-Quriat Hospital Ministry of Health Ahmed al Kharushi L.L.C.
96 Store at Nizwa Ministry of Health Al Ansari Trading Enterprises LLC.
97 Store at Busher Ministry of Health Al Ansari Trading Enterprises LLC.
98 RAFO - Salalah Ministry of Defense SARCO
99 Khasab Hospital Ministry of Health Al Ansari Trading Enterprises LLC.
100 Private Restaurant Towel Group Genetco
101 Lulu Ware House Lulu Group SARCO
102 HESG Villa DGPM Al Ansari Trading Enterprises LLC.
103 Helicopter Hanger Ministry of Defense SARCO
104 Khoula Hospital Ministry of Health Al Ansari Trading Enterprises LLC.
105 Taimur Villa DGPM IRACO
106 Khasab Air Port Ministry of Defense Al Ansari Trading Enterprises LLC.
Governers Office
107 Ministry Al Moram
complex
108 Royal Horse Stable DGPM Ahmed al Kharushi
Al Kuwair
109 Refurbishment of DGPM DGPM
Office for HM's
110 Barrake Ministry of Defense Ibn Saud
111 MOH(DGPRA) Ministry of Defense Al Ansari Trading Enterprises LLC.
Red Wing @ Khoula
112 Ministry of Health Al Ansari Trading Enterprises LLC.
Hospital
VIP Lounge @ RAFO
113 Ministry of Defense Mohamed & Ahmed Al Khonji L.L.C.
Seeb
114 Hospital @ Sinaw Minsitry of Health Al Ansari Trading Enterprises LLC.

Page 17 of 18
ACD/TGS/016-B/2023 Date: 26th Feb 2023

Sr.
Name of Project Name of Client Name of Contractor
No.
Salalah Waste Water
115 Ministry Mohamed & Ahmed Al Khonji L.L.C.
Collection System
116 Ware House Ministry of Defense Ibn Saud L.L.C.
Various facilities @
117 Ministry of Defense Al Ansari Trading Enterprises LLC.
Buraimi
Parade Ground @
118 Ministry of Defense Al Ansari Trading Enterprises LLC.
MAM
Accomodation Sohar Hospitality for
119 Al Jizzi
Facilities @ Qarnalam PDO
120 RNOTC Ministry of Health Al Ansari Trading Enterprises LLC.
Wool Worth city
121 Sharaf Group Sharaf Group
centre
122 Bait Al Mamurah DGPM Al Bunya'an Trading L.L.C.
123 Al Bustan hotel DGPM IRACO
124 DG Stores Ministry of Health Al Ansari Trading Enterprises LLC.
125 Defence Study Centre Ministry of Defense SARCO
126 Bahla Hospital Ministry of Health Al Ansari Trading Enterprises LLC.
Accomodation Sohar Hospitality for
127 Mohd Riyami Trading
facilities @ Fahud PDO
Accommodation Sohar Hospitality for
128 Mohd Riyami Trading
facilities @ Nimir PDO
129 Spray Paint Workshop Ministry of Defense Al Ansari Trading Enterprises LLC.
Jalan Bin Bu ali
130 Ministry of Health Galfar Engg. & Cont. SAOG.
hospital
131 Office at Seeb Ministry of Defense Moshin Haider Darwish
RAFO officers Mess
132 Ministry of Defense Galfar Engg. & Cont. SAOG.
Kitchen
Guest complex at Bait
133 DGPM Galfar Engg. & Cont. SAOG.
Al Barkha
Work shop at RAFO
134 Ministry of Defense Mideast Construction
thumrait
135 AOC building at RAFO Ministry of Defense Mideast Construction
136 Catering Building Oman Aviation Galfar Engg. & Cont. SAOG.
137 School of Control Ministry of Defense Middle East Construction

Page 18 of 18
High Efficient Wall Mounted
Decorative Unit

Since

50Hz
1974

Nominal Range: (1 TR to
3 TR (3.5 kW to 10.6 kW)

Made in UAE ‫صنع في اﻻمارات‬

‫شهادة ا�طابقة الخليجية‬


Made in KSA ‫ﺻﻨﻊ ﰲ اﳌﻤﻠﻜﺔ اﻟﻌﺮﺑﯿﺔ اﻟﺴﻌﻮدﯾﺔ‬

‫شهادة ا�طابقة الخليجية‬


High Efficient Wall Mounted

Contents
Introduction.................................................................. 2 Specifications.................................................. 5
Standard Features ������������������������������������������������������ 3 Dimensional Data.........................................6-8
Performance Table ����������������������������������������������������� 4 Typical Wiring Diagram..............................9-13

Introduction

SKM decorative split system are available in different models covering one TR to three TR (1 – 3 TR / 3.5 kW to 10.6
kW) at nominal condition, which make them ideally suited for many Application areas. The Outdoor unit a small foot print
for space saving and a pleasant exterior appearance for the Indoor units.

SKM decorative split system designed accordance with G.C.C regulations and to conform specifically ESMA, MEW and
G-Mark standards.

SKM decorative split units are suitable to operate in a wide range of ambient temperature. (Minimum outdoor operating
ambient in cooling mode is 63°F (17°C), maximum is 125.6°F (52°C).

SKM decorative split units are internally wired and all that required to be done on site is refrigerant piping, power supply,
suitable Indoor unit installation and field wiring, which reduces the installation work and consequently keeps to a minimum
cost. SKM decorative split units are made in KSA and SKM provides qualified service and stock of replacement parts in
all major cities of the G.C.C. countries.

You name it.....We cool it

SKM reserves the right to change, in part or in whole the specifications of its Air Conditioning
Equipment at any time in order to add the latest technology. Therefore, the enclosed information
may change without any prior notice.

2
R410-A
REFRIGERANT

Hi Wall Mounted Features

SKM

Note: all fins are golden except


for 36K-C condenser
‫مينع بشكل فعال تكاثر البكترييا ويعمل‬
‫ هذا الطالء الذهبي‬.‫عىل تحسني الكفاءة‬ Note:
Note:allallfins
finsare
aregolden
goldenexcept
except
‫الفريد عىل سطح املكثف يضمن لك‬ for
for36K-C
36K-Ccondenser
condenser
‫سطح اكرث مقاومة للعنارص املسببة للتآكل‬

SKM

SKM

‫الكهربايئ‬

SKM

‫يحافظ‬

SKM

‫خرطوم‬

SKM

Standard Features

Optional Features.

SKM S.K.M Air Conditioning LLC


3
High Efficient Wall Mounted

Performance Table
ESMA
Model MSKMP 12CVMS21 18CVMS31 24CVMS21 30CVMS21 36CVMS21
Power supply V,Hz,Ph 220-240V, 50Hz, 1Ph
Btu/h 12000 18000 23200 28000 31400
Capacity
kW 3.52 5.28 6.80 8.21 9.20
Cooling(T1) Input W 980 1530 1885 2330 2615
Rated current A 4.35 6.79 8.31 10.48 12.60
EER Btu/h/W 12.24 11.76 12.31 12.02 12.01
Btu/h 10400 16000 20000 25000 27200
Capacity
kW 3.05 4.69 5.86 7.33 7.97
Cooling(T3) Input W 1125 1776 2215 2900 3080
Rated current A 4.98 7.8 9.78 13 14.3
EER Btu/h/W 9.24 9.01 9.03 8.62 8.83
Table 1
OMAN/EWA
Model MSKMP 12CVMS21 18CVMS31 24CVMS21 30CVMS21 36CVMS21
Power supply V,Hz,Ph 220-240V, 50Hz, 1Ph
Btu/h 12000 18000 23200 28000 31400
Capacity
kW 3.52 5.28 6.80 8.21 9.20
Cooling(T1) Input W 980 1530 1885 2330 2615
Rated current A 4.35 6.79 8.31 10.48 12.60
EER Btu/h/W 12.244 11.764 12.307 12.017 12.007
Btu/h 10400 16000 20000 25000 27200
Capacity
kW 3.05 4.69 5.86 7.33 7.97
Cooling(T3) Input W 1125 1776 2215 2900 3080
Rated current A 4.98 7.8 9.78 13.00 14.3
EER Btu/h/W 9.24 9.009 9.029 8.620 8.831
Table 2
KUWAIT
Model MSKMP 12CVMS21 18CVMS41 24CVMS21 30CVMS21 36CVMS21
Power supply V,Hz,Ph 220-240V, 50Hz, 1Ph
Btu/h 12000 18000 23200 28000 31400
Capacity
kW 3.52 5.28 6.80 8.21 9.20
Cooling(T1) Input W 980 1440 1885 2330 2730
Rated current A 4.35 6.34 8.31 10.48 13.60
EER Btu/h/W 11.974 12.500 12.308 12.017 11.502
Btu/h 9800 15200 19400 24000 27000
Capacity
kW 2.87 4.45 5.69 7.03 7.91
Input W 1175 1770 2325 2890 3270
Cooling(T4)
Rated current A 5.02 7.46 9.86 12.54 15.10
EER Btu/h/W 8.340 8.588 8.344 8.300 8.257
EER kW/TR 1.44 1.40 1.44 1.45 1.45
Table 3

Note:

1. The design conditions are based as per ISO 5151:


a. The evaporator air entering of 80.6°F/66.2°F (27.0°C/19.0°C) DB/WB temperature and at 95°F (35°C) outside air dry bulb for T1 conditions.
b. The evaporator air entering of 84.2°F/66.2°F(29.0°C/19.0°C) DB/WB temperature and at 114.8°F(46°C) outside air dry bulb for T3 conditions.
c. The evaporator air entering of 80°F/67°F(26.6°C / 19.4°C) DB/WB temperature and at 118.4°F (48°C) outside air dry bulb for T4 conditions.
2. The values given in the table for the noise level reflect the levels in anechoic chamber.

4
R410-A
REFRIGERANT

Unit Specification
Model MSKMP 12CVMS21 18CVMS31 18CVMS41 24CVMS21 30CVMS21 36CVMS21
Power supply V,Hz,Ph 220-240V, 50Hz, 1Ph
Max. input consumption W 1800 2250 2050 2900 4000 4000
Max. current A 9.5 13.5 11 19 25 20
Starting current A 25 42 42 48 58 71
Compressor Type ROTARY Twin-ROTARY
Output W 20 45 58
Indoor Fan Motor Capacitor uF / 3 /
Speed(Turbo/Hi/Mi/Lo) r/min 1400/1120/1000/850 1230/1120/1020/950 1230/1120/1020/950 1450/1200/1080/980 1400/1230/1080/980 1400/1230/1080/980
Fin spacing mm 1.3
Fin type (code) Golden Hydrophilic Aluminium
Indoor Coil
Tube outside dia.and type mm Φ7,innergroove tube
Coil length x height x width mm 605x294x26.74 820x336x26.74 965x378x40.11
Indoor air flow (Turbo/Hi/Mi/Lo) m3/h 735/580/500/410 1160/1040/955/880 1400/1150/1000/900 1500/1320/1130/1010
Indoor noise level (Turbo/Hi/Mi/Lo) dB(A) 44/38/35/30 48/46/43/40 47.5/45/42/40 52/48/44/41 52/50/46/43 52/51/47/44
Dimension(W*D*H) mm 802x189x297 1080x226x335 1259x282x362
Indoor unit Packing (W*D*H) mm 875x285x375 1155x315x415 1340x380x450
Net/Gross weight Kg 8.9/11.3 14.9/18.4 14.9/18.5 13.8/17.4 19.8/25.3 19.8/25.6
Output W 48 65 60 120
Outdoor Fan Motor Capacitor uF 2.5 3 5 /
Speed r/min 830 890 825 870 850
Fin spacing mm 1.2 1.3 1.4
Fin type (code) Golden Hydrophilic Aluminium
Outdoor Coil Tube outside dia.and type mm Ф5,Inner groove tube Φ7, innergroove tube
900x609x13.37 910x609x26.74
Coil length x height x width mm 875x507x23.2 1005x756x26.74 1000x756x40.11
+550x609x13.37 +540x609x13.37
Outdoor noise level dB(A) 54 56 57 60 59 62
Dimension(W*D*H) mm 805x330x554 890x342x673 946x410x810
Outdoor unit Packing (W*D*H) mm 915x370x615 995x398x740 1090x500x875
Net/Gross weight Kg 32.3/35 39.5/42.1 46.2/49.5 50.4/53.6 66/69.9 68.5/73.2
Type R410A
Refrigerant
Charge g 800 1040 1320 1750 2100 2600
Design pressure MPa 4.8/1.5 4.8/1.5 4.8/1.5 4.8/1.5 4.8/1.5 4.8/1.5
Liquid side/ Gas side mm(inch) Φ6.35/Φ12.7(1/4"/1/2") Φ9.52/Φ15.9(3/8"/5/8") Φ9.52/Φ19(3/8"/3/4")
Refrigerant piping Max. refrigerant pipe length m 20 25
Max. difference in level m 8 10
Connection wiring 1.5x3 3x2.5 2.5x3 2.5x4 1.0x4
Plug type 1.5x3/BS Plug 2.5x3/no-plug 4.0x3/no-plug
Thermostat type Remote Control
Operation temperature °C 17~30
Indoor(cooling) °C 17~32
Room temperature
Outdoor(cooling) °C 18~52 18~54
Power Supply Connection IDU ODU

Table 4

Note:
1. Thermostat Operation temperature range for Oman: 17~30°C, other regions: 20~28°C
2. Remote Controller for Oman: RG57A2, other regions: RG57A16

S.K.M Air Conditioning LLC


5
High Efficient Wall Mounted

Dimensional Data

INDOOR UNITS

Dimension W D H
CA MSKMP mm
CA 12 802 189 297
CA 18/24 1080 226 335
CA & 36CA 30/36 1259 282 362
Table 5

6
R410-A
REFRIGERANT

Dimensional Data
OUTDOOR UNIT- MSKMP-12CVMS21, 18CVMS31

OUTDOOR UNIT - MSKMP- 18CVMS41, 24CVMS21

S.K.M Air Conditioning LLC


7
High Efficient Wall Mounted

Dimensional Data
OUTDOOR UNIT - MSKMP- 30CVMS21, 36CVMS21

8
R410-A
REFRIGERANT

Typical Wiring Diagram


INDOOR UNIT: MSKMP-12CVMS21

/UVC

MAIN BOARD

1 2(N)

INDOOR UNIT: MSKMP-18CVMS31, 18CVMS41

WIRING DIAGRAM Notes:


VERTICAL This symbol indicates the element
SWING MOTOR is optional,the actual shape shall
SWING MOTOR
be prevail.
RELAY ASSISTANT BOARD
OPTIONAL M M M
N.O. COM. C_1 C_2 CN1_COMP CN2_COMP ION 5 5 PLASMA/UVC

5
BLACK

RED

12345 12345
WHITE 12345 12345 1 2
CN_COMP2
CN11
CN_N2

WHITE CN9
CN_ION CN10
CN4

RED RED 2
M CN6 (OR CN12) ELECTRONIC HEATER

~ 3
CN4 (CN7) CN32
INDOOR MOTOR
MAIN BOARD MULTI-FUNCTION
CONTROL BOARD

CNL
CURRENT DETECT
CNN
①B R O W N ( o r ② R E D ) ( o r ③ B L A C K )
①BLUE(or②BLACK)( or③WHITE)

CN_TO CN_TIN CN3 CN2 CN5


CN_T3 1 2 1 2 1 2 1 2
BROWN(or RED)
BLUE(OR BLACK)

1 2 1 2 1 2 1 2 8(4)
Y/G or Green

8(4/7)
TRANSFORMER OR OPTIONAL
Y/G POWER BOARD 2
Wire Contoller
OPTIONAL
T2_PIPE
T1_room DISPLAY WiFi
TO T3 BOARD
Contoller

L N 1 2(N) 2
CN602

POWER INDOOR UNIT NOTES:


1.The Color Of Power Supply Cord(L,N,E) Measures Up To
SUPPLY ①The IEC Standards(BROWN,BLUE,Y/G) or
② The India Standards(RED,BLACK,Y/G) or
③ The UL Standards(BLACK,WHITE,GREEN)
TO OUTDOOR UNIT 2.The Functions In The Rectangle Are Available For Particular Air-condition;

S.K.M Air Conditioning LLC


9
High Efficient Wall Mounted

Typical Wiring Diagram


INDOOR UNIT: MSKMP-24CVMS21

WIRING DIAGRAM
SWING MOTOR
OPTIONAL

FAN CAPACITOR BOARD


TO M M M OPTIONAL

PC1_1 PC2_1 OXYGEN ENRICHMENT VERTICAL


OR ANION GENERATOR
5 5 5 SWING
WHITE WHITE MOTOR
OPTIONAL

BLACK RED 12345 12345


INDOOR MOTOR
M CN6 CN_ION 12345 12345
~ CN4 CN12(OR CN10) CN11
OPTIONAL
OPTIONAL

CN_N1(or CNN) OPTIONAL


①B L U E ( o r ② B L A C K ) ( o r ③ W H I T E )

1 2
①B R O W N ( o r ② R E D ) ( o r ③ B L A C K )

CN9 PLASMA/UVC
CN_L1(or CNL)
MAIN BOARD CN32
CURRENT MULTI-FUNCTION
DETECT CONTROL BOARD

CN_COMP1 OPTIONAL
CN_TO CN_TIN CN3 CN2
BROWN(or RED)

CN5 Notes:
BLUE(OR BLACK)

(or CN_COMP) CN_T3 1(2)3(4) 1 2 1 2 1 2


This symbol indicates the element
BROWN

1(2)3(4) 1 2 1 2 1 2 8(4)
2(4) is optional,the actual shape shall
be prevail.
OPTIONAL

TRANSFORMER OR
Y/G POWER BOARD Wire Contoller
Y/G(or GREEN)

T2 T1 2

OPTIONAL DISPLAY
TO T3
BOARD WiFi

1 2(N) 3 4 2
Contoller

CN602
OPTIONAL

POWER INDOOR UNIT NOTES:


OPTIONAL

SUPPLY 1.The Color Of Power Supply Cord(L,N,E) Measures Up To


①The IEC Standards(BROWN,BLUE,Y/G) or
TO OUTDOOR UNIT ② The India Standards(RED,BLACK,Y/G) or
③ The UL Standards(BLACK,WHITE,GREEN)
2.The Functions In The Rectangle are Available For Particular Air-condition;

INDOOR UNIT: MSKMP-30CVMS21

10
R410-A
REFRIGERANT

Typical Wiring Diagram

INDOOR UNIT: MSKMP-36CVMS21

INDOOR WIRING DIAGRAM


OPTIONAL
OPTIONAL INDOOR
Y/G Applicable to FAN
ION AC motor only M M
M
3 5(3) 5

OPTIONAL CN12_1CN12_2 CN6 CN4 P_1


HEATER CN5 CN14 MICRO SWITCH
CN6_1
2
CN6_2 2 2 PLASMA
L-OUT CN43 CN44
RED
ROOM TEMPERATURE SENSOR
BLUE(BLACK) L-IN RY1 CN8
YELLOW
Y/G CN10A
N (CN10) CN9
PIPE TEMPERATURE SENSOR
CN16 S
INDOOR UNIT
1(L) 2(N) S OPTIONAL 8(7) OPTIONAL
DISPLAY BOARD
JX1 WiFi Controller
MULTI-FUCTION CONTROL BOX 8 8 CN1(OR CN201)
CN602
OPTIONAL WiFi Controller 4 4 4 CN3(OR CN301)
Magnet ring

OUTDOOR UNIT
OPTIONAL Wire Controller 5 5 5 CN2(OR CN101) Wire Controller
OPTIONAL

OUTDOOR UNIT: MSKMP-12CVMS21

S.K.M Air Conditioning LLC


11
High Efficient Wall Mounted

Typical Wiring Diagram

OUTDOOR UNIT: MSKMP-18CVMS31, 18CVMS41


MSKM410A-18CEP5

OUTDOOR UNIT: MSKMP-24CVMS21

BLACK
BROWN
FAN RED BLACK
YELLOW
BLUE CAP1
MOTOR

BLUE RED BLACK


RED
CAP2 BLUE BLACK(or WHITE)
R CS
RED(BROWN) 1(3) 2(4) RED

RED A1 A2 COMP
RED
BROWN(RED)
BLACK FAN MOTOR
Reactance
Y/G
XT
FOR OUTDOOR POWER SUPPLY Y/G
XT Y/G
L N 1
FOR INDOOR POWER SUPPLY
Y/G
XT OUTDOOR
OUTDOOR UNIT 1 2(N) 3 UNIT
POWER
TO INDOOR
TO INDOOR UNIT 29 UNIT

INDOOR UNIT
L N 1
INDOOR
1 2(N) 3 UNIT

12
R410-A
REFRIGERANT

Typical Wiring Diagram

OUTDOOR UNIT: MSKMP-30CVMS21

FAN2 BLACK
KM1 2
M RED 5 6 RED O.L.P
1 2 RED WHITE(or BLACK)
1
C S
BLUE
BROWN A1 A2

CAP2 1 2 RED BLACK


COMP
TRANS1 CODE PART NAME
RED R UNIT1 OUTDOOR CONTROL PCB
COMP COMPRESSOR
BLUE
RT3 XP1 XS1 1 CAP1 COMPRESSOR RUN CAPACITOR
CAP2 OUTDOOR FAN CAPACITOR
XT2 FAN2 OUTDOOR FAN
1 2 CAP1 XT1 TERMINAL
Xt2 MIDDLE TERMINAL
CN1 CN2 BLACK
1 XP1,XS1 CONNECTORS
CN8 OPTION RT3 PIPE TEMPERATURE SENSOR
BLACK BLACK BLACK
BLACK PTCR
KM1 AC CONTACTOR
CT/T320
UNIT1
CT CURRENT INDUCTOR
Reactance
RED RED( or BROWN) VALVE REVERSING VALVE
TRANSFORMER
CN3 TRANS1
CN6 WHITE 1 PTCR PTCR STARER
CN4
RED CN1-CN11 PCB SOCKETS
CN15 CN16 RED
CN5 OR N
BLACK XT1
1 2(N) S L N
H-PRO H-PRO Notes:
symbol 1 indicates the element is optional,the actual shape shall be prevail.
L-PRO L-PRO Symbol 2 indicates compressor internal or external components.
TO INDOOR UNIT POWER SUPPLY
1

OUTDOOR UNIT: MSKMP-36CVMS21

OPTION KM1
3 WHITE
M 1(3) 2(4)
(OR BLACK)
RED RED
1 VALVE C
Y/G
RED A1 A2
S
BLUE BLUE
3 OPTION
COMP Y/G CODE PART NAME
UNIT1 OUTDOOR CONTROL PCB
RT3
COMP COMPRESSOR
CN3 R 1
Y/G 5 BLACK
H-PRO
CAP1 COMPRESSOR RUN CAPACITOR
Cn1 BLUE CAP2 OUTDOOR FAN CAPACITOR
CN13 XP1
OPTION RED
XT2 FAN2 OUTDOOR FAN
XS1 RED 1 2 CAP1 XT1 TERMINAL
5 1 2
BLACK XT2、XT3 MIDDLE TERMINAL
CN_FAN CN_T3 RED
BLACK 1 XP1,XS1 CONNECTORS
CN_4V BLACK OPTION
RT3 PIPE TEMPERATURE SENSOR
CT1 BLACK
CN_COMP PTCR KM1 AC CONTACTOR
CT CURRENT INDUCTOR
CN _EA RTH1 UNIT1 BLUE (OR BLACK)
RED TRANS1 TRANSFORMER
CN_S WHITE
CN_EA RTH2 CN1-CN11 PCB SOCKETS
VALVE REVERSING VALVE
CN_N BLACK XT1
CN_HLP1
1 2(N) S L N
RED
CN_HLP2 CN_L
H-PRO
REACTOR
TO INDOOR UNIT POWER SUPPLY Notes:
L-PRO
symbol 1 , 3 and 4 indicates the element is optional,the actual shape shall be prevail.
Symbol 2 indicates compressor internal or external components.

S.K.M Air Conditioning LLC


13
High Efficient Wall Mounted

NOTES

14
R410-A
REFRIGERANT

NOTES

S.K.M Air Conditioning LLC


15
High Efficient Wall Mounted
CONTACT US
HEAD OFFICE

P.O Box: 6004, Sharjah,


United Arab Emirates

Tel: +971 6 514 3333


Fax: +971 6 514 3300

Email: sales@skmaircon.com
Email: info@skmaircon.com

Spare Parts Division


spareparts.skm@skmaircon.com

Service Center
aftersales.skm@skmaircon.com

For SKM Regional Offices & Distributors


visit: www.skmaircon.com

243/2022
16
APMRG1 Series R 22
REFRIGERANT

Packaged Air Conditioners

50Hz

Range 4.6 TR to 45.8 TR


R 22
(16.1 kW to REFRIGERANT
161.2 kW)

S.K.M Air Conditioning LLC


1
Contents Introduction
Legend ................................................. 2 Electrical Data ...................................... 14
Nomenclature ....................................... 2 Field Connection................................. 15
SKM APMRG1 New PackagedAir Conditioners
Introduction ......................................... 2 Typical Wiring Diagram ...................... 16 Series are designed and manufactured to meet
General Features ............................... 3 Dimensional Data .................................. 17 the requirements of Gulf’s severe climatic
Main Component Features .................. 3 Loading Points ....................................... 22 conditions and are built specifically for ducted
Optional Features ................................ 4 Recommended Clearances ................. 23 systems which will enable them to be installed
Engineering Specifications ...................7 Installation & Commissioning ............... 26 easily on roof tops or on the ground.
Capacity Ratings ................................ 10 Guide Specifications ............................. 27
Fan Performance ............................... 13 The APMRG1 series PackagedAir Conditioners
are compact, quiet, most efficient and self
contained units are ideal for commercial and
Legend top end residential applications.

The following legends are used throughout this manual: APMRG1 Series is also designed to perform as
per ESMA regulation to achieve high efficiency
AFR ................................... Air Flow Rate lbs......................................Pounds weight level in gulf conditions
BPF..................................By Pass Factor L/s.................................Liters per second
CFM.....................Cubic feet per minute MBh.....................................BTUHx1000
Available in 19 different sizes from 4.6 to 45.8
Pa..................................................Pascal
EER..................Energy Efficiency Ratio TR (16.1kW to 161.2kW) in 50 Hz at nominal
Ph....................................................Phase
ESP.................External Static Pressure AHRI conditions. APMRG1 series packaged
PI ......Power Input of Compressor in kW
Hz ....................................................Hertz RPM ...................Revolutions Per Minute air conditioners are designed to operate in a
in. wg...............................Inch water gauge RPS...........................Rated Power Supply wide ambient temperature range between 50°F
kW.............................................Kilowatts TR.............................Tons of Refrigeration (10°C) to 125°F (51.7°C), based on specific
V..........................................................Volts conditions & model applies. Two independent
kg........................................Kilogram
refrigeration circuits are provided where two
compressors are used.

APMRG1 series units from SKM are completely


Nomenclature assembled, leak tested, vacuumed, internally
wired and fully charged with R-410A refrigerant
A P M R - 5 1 050 G1 Y at factory. Each unit is fully factory tested
before dispatch and is ready for installation.
Air Cooled Power Supply Code All that is required on the site is to connect
Y : 380V-415/3Ph/50Hz ducts, drain lines, main power supply and field
Package
wiring to the thermostat. This greatly reduces
Scroll
Compressor G1 : High Efficiency the installation work and cost.

R-410A
SKM provides qualified service and stock
Nominal Capacity in MBh
5 = 50 Hz of replacement parts in all major cities of the
1 : Single Circuit G.C.C. countries, Egypt, Jordan, and Pakistan.
2 : Double Circuit See back cover for details or call SKM.

SKM Air Conditioning LLC

SKM reserves the right to change, in part


or in whole the specifications of its Air
Conditioning Equipment at any time in order
to add the latest technology. Therefore, the
enclosed information may change without any
prior notice.
You name it.....We cool it
General Features Condenser Coils R 22
REFRIGERANT
The APMRG1 Series is a modern, diversified and environment Condenser coils are manufactured from Corrugated fin and Hi-X
friendly series of packaged air conditioners which use R-410A seamless copper tubes mechanically bonded to aluminium fins
refrigerant. to ensure optimum heat transfer. All coils are tested against
leakage by high air pressure 715psig (4930kPa) under water.
The APMRG1 Series Packaged Air Conditioners are yet another An integral subcooling circuit is incorporated in the lower section
new unique series from SKM incorporates many salient features of the condenser to increase system capacity. The additional
which, together, provides a heavy duty, robust, long lasting condenser surface provides more cooling using less energy at
commercial unit meant for high end residential and commercial no additional cost.
applications. The APMRG1 series models combine high efficiency
condenser and cooling coils, evaporator blower and heavy duty
Condenser Fans
motor in addition to premium safety and operational controls.
Condenser fans are propeller type with aluminum alloy blades
The complete APMRG1 packaged unit provides an extremely and are directly driven by electric motors. Motors are Totally
rugged, long life, energy efficient, self contained packaged air Enclosed Air Over (TEAO), six pole with Class F insulation and
conditioner that will provide cooling with higher efficiency over IP54/55 protection depending on models. Complete fan assembly
a long and extended life. is provided with fan guard.

What makes APMRG1 series yet another model in the top class
range of SKM products is the use of:
Evaporator
• High efficiency totally sealed scroll hermetic compressors. Evaporator coils are manufactured from Hi-X seamless copper
• Totally enclosed, Class F insulated,condenser and evaporator tubes mechanically bonded to aluminium Corrugated fins to
fan motors. ensure optimum heat transfer. All evaporator coils are tested
• Heavy duty condenser and evaporator coils optimised in against leakage by high air pressure of 450 psig (3100kPa) under
water. Coils conform to AHRI-410.
design for long-life maintenance free operation.
• Cabinet construction specifically designed for Gulf climates.
• Electronic control board for the unit operation.
• Typically, much heavier gauge tubing and thicker fins for Evaporator Fan & Drive
ruggedness and long life. Evaporator fans are forward curved centrifugal double inlet, double
width, statically and dynamically balanced. Bearings used in the
fans are self aligning and lubricated for life. Evaporator fans are
belt driven and use “V” belts with an adjustable variable pitch
motor pulley resulting in an accurate fan air flow adjustment.
Main Component Features
Fans are driven by Totally Enclosed, IP-55 Protected, 4 pole
The common standard features of all APMRG1 series packaged
Class F insulated electric motors. The motors are factory wired to
units include the following
the control panel where the motor starters are located to control
the operation of the motors. The motors conform to relevant IEC
Compressors standards.

Compressors used in APMRG1 packaged unit series are


hermetically sealed, compact scroll with the following features: Casing and Structure
• High Efficiency. The unit casing used in APMRG1 series is made of hot dip
galvanized (zinc coated) steel sheets, conforming to JIS-G
• Quiet operation, Low Sound levels.
3302 and ASTMA653, which is phosphatized and baked after an
• Compact and light.
electrostatic powder coat of approx. 60 microns. This finish and
• Limited wear. coating can pass a 1000 hour in 5% salt spray testing at 95°F
• 70% fewer moving parts than comparably sized reciprocating (35°C) and 95% relative humidity as per ASTM B117.
compressors.
• Unique ability to hadle liquid refrigerant. The evaporator section is insulated from all the sides with 1/2”
• Suction gas motor cooling. for model 51055G1 to 51120G1 & 1” for model 52130G1 to
• Suction screen. 52550G1 thick fiber glass insulation with extremely tough and
• Centrifugal oil pumps with filter and magnet. durable black composite surface. The insulation cum sound liner
• Brazed fittings or Rotalock options. meets the fire requirements of NFPA90A & 90B and is secured
• Two refrigerant circuits on larger units provides efficient part with mechanical fasteners in addition to water resistant adhesive.
load.
• No internal valves.

S.K.M Air Conditioning LLC


3
SKM Packaged Air Conditioners APMRG1 Series

Refrigerant R- 410A
Why 410A? Optional Features
R-410A has a higher volumetric cooling capacity compared to As with all SKM air conditioning units, the APMRG1 Series
R-22 and has better thermal exchange properties. This results Packaged Units are available with multitude of optional features
in overall performance gains in terms of system efficiency. The available on request:
greater density of the vapour in R-410A permits higher system
velocities, reduces pressure drop losses and allows smaller Double Skin Evaporator (DSE)
diameter tubing to be used. In other words a smaller unit can Double skin evaporator section with galvanized inner skin.
be developed using a smaller displacement compressor, less (Applicable only for models 52130G1 to 52550G1)
coil and less refrigerant while maintaining system efficiencies
comparable to current day R-22 equipment.
Double Skin Insulation (DSI)
Inner skin in the evaporator section is provided with foam board
Benefits
insulation. (Applicable only for models 52130G1 to 52550G1)
• No ozone depletion potential or phase-out date
Using chlorine-free R-410A with zero Ozone Depletion
Potential (ODP) helps protect both the environment and your 1” (25mm) Thick Fiber Glass Insulation (1SG)
investment. That’s because new equipment using R-410A Evaporator section with 1” thick fiber glass insulation.
faces no mandated phase-out date over a 20 to 30 year (This option applicable for models 51055G1 up to 51120G1)
equipment life expectancy.

• Reduced service costs Temperature Based Economizer (ECRU)


R-410A refrigerant has no significant “glide.” If a leak occurs, Simple temperature based economizer.
only the lost refrigerant must be replaced.
2” (50mm) Flat Filter Section (FSIP2)
Attention points For heavy filtration need a section can be provided without or
• Pressure level: 1.6 times of R-22. with aluminium cleanable filter.
• Lubricating oil: Ester Oil absorb moisture easily
(Never mix with mineral oil).
Alternative Condenser Material
• Tools exclusive for R-410A.
• Never mix R-410A with other refrigerant. Made of copper tubes and alternative fin material and/or
• Driers, valves and even copper tube must be approved for protective coating.
use with R-410A. • Pre Coated aluminum fins (FAP).
• Never allow refrigerant cylinders to exceed 60°C. • Aluminum Fins with Aeris post Coat Protection (FAA).
• Copper Fins (FC).
• Copper Fins with Aeris post Coat Protection (FCA).
Control Panel
Alternative Evaporator Material
The APMRG1 packaged Air Conditioners are provided with IP-
Made of copper tubes and alternative fin material and/or
54 control panel enclosure comprising all starting, operating &
protective coating.
safety controls. The panel is factory wired in accordance with NEC
430 & 440, labelled, tagged and features 220V / 240V controls. • Pre Coated aluminum fins (EFAP).
• Aluminum Fins with Aeris post Coat Protection (EFAA).
• Starting contactors for compressors and motors. • Copper Fins (EFC).
• Copper Fins with Aeris post Coat Protectionn (EFCA).
• Internal overload protection for compressors.
• Internal or External overload protection for the motors Anti-Freeze Thermostat (AFT)
(depending on the model). For evaporator coil freeze -up protection.
• Electronic control board for unit operation.
• Diagnostic LEDs on the control board for easy Western Make Scroll Compressor (WMSC)
troubleshooting . Western make scroll compressor.
• Compressor short cycling protection.
Compressor Run Hour Meter (RHM)
• Control switch for unit on/off.
To monitor operating hours of each compressor.
• Control circuit breaker.
• Power and control circuit terminal blocks. Circuit Breaker for compressor (CBC)
• High pressure protection. For those electrical specification which requires additional short
• Low pressure protection. circuit and overload protection for the compressors.

4
External Overload Protection (EOP)
● BMSP – BMS Protocol * R 22
For those electrical specification requires additional overload REFRIGERANT
protection for the compressors.(Not required with CBC option) (For interfacing the units with major BMS protocols such as
BACnet, Modbus or LON. An extra hardware may be required
Manual Reset Type High Pressure Switch (MHP) depending on the protocol)
To replace standard auto reset, capsule type pressure switch.
Extra Ball Valve (XFV)
Electric Heating (HTR1) Extra ball valve can be incorporated in the liquid line.
Electric heating batteries are made up of finned heating elements,
constructed from high quality 80/20 nickel chrome resistance wire Pressure relief valve (PRV)
centred in metal tube by compressed magnesium oxide. To protect the unit from being over - pressurized.
Helical fins are tightly wound around the tubular heating element.
Heater batteries when ordered comes with stage contactors,
primary auto reset thermal safety cut-out, secondary manual Pressure Gauges (SDG1)
reset thermal safety cut-out and air flow switch. Suction and discharge indication of each refrigerant circuit.
Gauges mounted outside the Control Panel.
Control of the heaters will be from the unit controller.
Following are the optional kW ratings for electric heater. Ratings
other than those specified here can be supplied on request. Liquid Line Sight Glass (RSG)
Consult SKM for details (Applicable only for models 52130G1 For monitoring refrigerant charge and to provide visual indication
of moisture presence in the system.
to 52550G1)

Model Condenser Coil Guard (CGP)


Heater Kw No. of Stages
APMR Wire mesh guard, in painted finish for condensers coils.
Recommended on ground level installation where coil needs to
52130G1 be protected against vandalism.
52150G1
Stainless Steel Drain Pan (Grade 304) (SDP-304)
52170G1 18
Stainless steel drain pan(Grade 304). Insulation under drain pan
52180G1 as per SKM standard.
52210G1
52240G1 Stainless Steel Drain Pan (SDP-316)
Heavy gauge 316 stainless steel drain pan under the entire cooling
52270G1 2 coil.
52300G1 24 Insulation under drain pan as per SKM standard.

52340G1 Circuit breaker for Motors** (CBM)


52380G1 For those electrical specification which requires additional short
circuit and overload protection for the fan motors.
52420G1
48
52500G1 IP 55 Control Panel (ICP)
Table 1

Control Panel for special applications to meet IP55 requirements.


52550G1
Main Isolator (without door interlock) (ISO)
Rotalock Valves on compressors (RVC) For main power isolation. (Consult SKM)
For additional facilitation of maintenance of unit.

Advanced Micro Processor Control System (AMCS) BMS Interface Volt Free Contacts (BMVF)
An advanced microprocessor based controller can be provided Volt free contacts for run status, common fault status, auto
for the units as option, in case required. This controller mode status and provision for remote on/off shall be provided
will be with built-in display keypad and has many features. as option if required.
For this feature, additional options can be provided and to be For additional requirements, please contact SKM.
specified during time of order:
● DTS – Duct Temperature Sensor *
(In order to control the unit based on return/supply air duct
temperature.) (This is not required with CHTS options)

S.K.M Air Conditioning LLC


5
SKM Packaged Air Conditioners APMRG1 Series

Voltage Monitor Module (VMM) Options for Field Installation


Provides protection in the event of:
• Phase burn-out. Anti-vibration mounts (CAVM)
• Phase reversal. Recomended for roof mounted units or other location in the
• Under / over voltage on the incoming line voltage. vicinity of occupied spaces. where noise may be objectionable.
Up Size Evaporator Motor** (USM)
Low Voltage Thermostat (CHTS)
Unit with one up size evaporator motor. For wall mounting and for cooling /heating operation with 1 or 2
Voltage Monitoring Module as per DEWA (DVM) stages as per model. (Not required with AMCS option).
Under voltage relay as per DEWA regulations. This option is
● DTS-TH – Duct Temperature Sensor for 24V Thermostat *
available for Dubai, UAE only.(VMM option is not required if
(In order to control the unit based on return/supply air duct
this option is opted.)
temperature.) (This is not required with AMCS options)
Ball Valve (BLV)
Ball valve can be incorporated in the liquid line. Note:

- *DTS & BMSP options are only available along with AMCS option.
Pump Down Facility with solenoid Valve (PDS)
The compressors will switch off each time with a Pumpdown - *DTS-TH option is only available along with CHTS option.
Cycle in order to prevent Liquid refrigerant migration to the
compressor during Off Cycle periods. - **If CBM combined with USM option please consult SKM as
component might changed.
Fire Alarm Interlock (VFC-F)
To provide provision for fire alarm interlock. - Whenever multiple options related to unit control, please consult
SKM for the drawings, as the size of the control panel might change.
Marine Paint (MP)
To provide increased corrosion resistance for coastal environments
and offshore location.

6
ENGINEERING SPECIFICATIONS R 22
REFRIGERANT
Model APMR 51055G1 51070G1 51080G1 51090G1 51100G1 51120G1 52130G1
MBh 46.60 59.20 66.40 72.50 82.80 95.70 108.10
Cooling Capacity (1) kW 13.66 17.35 19.46 21.2 24.27 28.05 31.68
EER 8.45 8.33 8.38 8.45 8.39 8.41 8.40
Refrigerant Type - R410A
Type - Hermetic Scroll
Quantity - 1 1 1 1 1 1 2
Compressor
US Gal 0.52 0.47 0.47 0.66 0.86 0.86 1.19
Oil Charge Ckt (A / B)
Liter 1.95 1.77 1.77 2.51 3.25 3.25 4.50
Type - Hi-X tubes
Condenser Coil ft2 18.7 21.3 24 24 24 25.4 37.3
Face Area 2
m 1.7 2.0 2.2 2.2 2.2 2.4 3.5
Type - Propeller Direct Drive
Condenser Fan
Code / Quantity - 630 / 1 630 / 1 710 / 1 710 / 1 710 / 1 710 / 1 710 / 2
Condenser Motor Type - Totally Enclosed Air Over, Class F insulation, 6-pole, IP-54/55 Protected
Type - Hi-X tubes
Evaporator Coil ft2 5.8 5.8 8.9 8.9 8.9 10.7 13.3
Face Area 2
m 0.54 0.54 0.83 0.83 0.83 0.99 1.24
Type - Centrifugal double inlet double width belt drive
Code / Quantity 10/10 12/12 12/12 15/15 15/15 15/15 12/12 R2
Evaporator Fan
cfm 1700 2100 2800 3200 3500 4100 4500
Air Flow Rate
l/s 802 991 1321 1510 1651 1934 2123
Type - Totally Enclosed Fan Cooled, Class F insulation, 4-pole IP55 Protected
Evaporator Motor
Size kW 0.55 0.55 0.75 1.1 1.1 1.5 1.5
lbs 14.99 16.38 19.80 20.22 20.33 29.63 15.78 / 15.78
Approximate Operating Gas Charge Ckt (A / B)
kg 6.80 7.43 8.98 9.17 9.22 13.44 7.16 / 7.16
Number of Refrigerant Circuits - 1 1 1 1 1 1 2
lbs 645 669 814 894 914 1040 1622
Unit Operating Weight
kg 293 304 369 405 414 471 736
Table 2

Notes:
(1) Evaporator entering air conditions of 84.2°/66.2°F (29.0°C/19.0°C) dry bulb/wet bulb and condenser entering air temperature
of 114.8°F (46°C ) dry bulb, (Net Capacity).

S.K.M Air Conditioning LLC


7
SKM Packaged Air Conditioners APMRG1 Series

ENGINEERING SPECIFICATIONS

Model APMR 52150G1 52170G1 52180G1 52210G1 52240G1 52270G1 52300G1


MBh 123.30 135.90 145.80 162.70 188.90 212.90 240.60
Cooling Capacity (1) kW 36.14 39.83 42.73 47.7 55.36 62.39 70.51
EER 8.40 8.33 8.20 8.21 8.18 8.26 8.32
Refrigerant Type - R410A
Type - Hermetic Scroll
Quantity - 2 2 2 2 2 2 2
Compressor
US Gal 0.47 0.47 0.66 0.86 0.86 1.90 0.86
Oil Charge Ckt (A / B)
Liter 1.77 1.77 2.51 3.25 3.25 7.20 3.25
Type - Hi-X tubes
Condenser Coil ft2 37.3 52 52 52 52 53.3 53.3
Face Area
2
m 3.5 4.8 4.8 4.8 4.8 5.0 5.0
Type - Propeller Direct Drive
Condenser Fan
Code / Quantity - 710 / 2 710 / 2 710 / 2 710 / 2 710 / 2 710 / 3 710 / 3
Condenser Motor Type - Totally Enclosed Air Over, Class F insulation, 6-pole, IP-54/55 Protected
Type - Hi-X tubes
Evaporator Coil ft2 13.3 15.6 15.6 15.6 21.7 21.7 21.7
Face Area
m2 1.24 1.45 1.45 1.45 2.02 2.02 2.02
Type - Centrifugal double inlet double width belt drive
Code / Quantity - 12/12 R2 12/12 R2 12/12 R2 12/12 R2 12/12 R2 15/15 R2 15/15 R2
Evaporator Fan
cfm 5000 5800 6200 6500 7000 8000 9000
Air Flow Rate
l/s 2359 2737 2926 3067 3303 3775 4247
Type - Totally Enclosed Fan Cooled, Class F insulation, 4-pole IP55 Protected
Evaporator Motor
Size kW 1.5 2.2 2.2 3 3 3 3
lbs 15.78 / 15.78 20.26 / 20.26 20.26 / 20.26 28.79 / 28.79 30.03 / 30.03 31.24 / 31.24 31.24 / 31.24
Approximate Operating Gas Charge Ckt (A / B)
kg 7.16 / 7.16 9.19 / 9.19 9.19 / 9.19 13.06 / 13.06 13.62 / 13.62 14.17 / 14.17 14.17 / 14.17
Number of Refrigerant Circuits - 2 2 2 2 2 2 2
lbs 1622 1956 2032 2090 2288 2724 2739
Unit Operating Weight
kg 736 887 922 948 1038 1235 1242
Table 3

Notes:
(1) Evaporator entering air conditions of 84.2°/66.2°F (29.0°C/19.0°C) dry bulb/wet bulb and condenser entering air temperature
of 114.8°F (46°C ) dry bulb, (Net Capacity).

8
ENGINEERING SPECIFICATIONS R 22
REFRIGERANT
Model APMR 52340G1 52380G1 52420G1 52500G1 52550G1
MBh 274.60 319.30 357.80 404.80 449.00
Cooling Capacity (1) kW 80.48 93.58 104.86 118.6 131.59
EER 8.10 8.15 7.99 8.01 7.90
Refrigerant Type - R410A
Type - Hermetic Scroll
Quantity - 2 2 2 2 2
Compressor
US Gal 0.86 1.19 / 0.86 1.19 1.19 / 1.19 1.19
Oil Charge Ckt (A / B)
Liter 3.25 4.5 / 3.25 4.50 4.5 / 4.5 4.50
Type - Hi-X tubes
Condenser Coil ft2 60 65 69.3 78 130
Face Area 2
m 5.6 6.0 6.4 7.2 12.1
Type - Propeller Direct Drive
Condenser Fan
Code / Quantity - 710 / 3 710 / 4 800 / 3 800 / 3 800 / 4
Condenser Motor Type - Totally Enclosed Air Over, Class F insulation, 6-pole, IP-54/55 Protected
Type - Hi-X tubes
Evaporator Coil 2
ft 26 30.3 30.3 37.5 37.5
Face Area 2
m 2.42 2.81 2.81 3.48 3.48
Type - Centrifugal double inlet double width belt drive
Code / Quantity - 15/15 R2 18/18 R2 18/18 R2 18/18 R2 18/18 R2
Evaporator Fan
cfm 10000 10800 11800 13500 15800
Air Flow Rate
l/s 4719 5097 5568 6371 7456
Type - Totally Enclosed Fan Cooled, Class F insulation, 4-pole IP55 Protected
Evaporator Motor
Size kW 4 4 5.5 5.5 7.5
lbs 34.88 / 34.88 42.11 / 42.11 52.91 / 52.91 60.43 / 60.43 66.14 / 66.14
Refrigerant Operating Charge Ckt (A / B)
kg 15.82 / 15.82 19.1 / 19.1 24 / 24 27.41 / 27.41 30 / 30
Number of Refrigerant Circuits - 2 2 2 2 2
lbs 2776 3391 3603 3835 4857
Unit Operating Weight
kg 1259 1538 1634 1739 2203

Table 4

Notes:
(1) Evaporator entering air conditions of 84.2°/66.2°F (29.0°C/19.0°C) dry bulb/wet bulb and condenser entering air temperature
of 114.8°F (46°C ) dry bulb, (Net Capacity).

S.K.M Air Conditioning LLC


9
SKM Packaged Air Conditioners APMRG1 Series

GROSS CAPACITY RATINGS


AFR Condenser Entering Air Temperature
cfm 95°F (35°C) 105°F (40.6°C) 114.8°F (46°C) 118.4°F (48°C) 125.6°F (52°C)
Model EWB
APMR l/s Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI

(BPF) °F MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW
1600 62 49.4 14.5 49.4 14.5 3.4 46.7 13.7 46.7 13.7 3.9 43.8 12.8 43.8 12.8 4.5 44.6 13.1 44.6 13.1 4.7 42.3 12.4 42.3 12.4 5.1
755 66.2 53.5 15.7 47.4 13.9 3.4 50.5 14.8 46.3 13.6 3.9 47.2 13.8 45.1 13.2 4.5 46.0 13.5 44.6 13.1 4.7 43.6 12.8 43.6 12.8 5.1
0.09 72 59.9 17.6 37.8 11.1 3.5 56.5 16.5 36.6 10.7 4.0 52.2 15.3 35.2 10.3 4.6 50.6 14.8 34.7 10.2 4.9 47.6 13.9 33.7 9.9 5.3
1700 62 50.0 14.7 50.0 14.7 3.4 47.2 13.8 47.2 13.8 3.9 46.2 13.5 46.2 13.5 4.5 45.0 13.2 45.0 13.2 4.7 42.6 12.5 42.6 12.5 5.1
51055G1 802 66.2 54.0 15.8 49.1 14.4 3.4 50.9 14.9 48.0 14.1 3.9 47.6 14.0 46.7 13.7 4.5 46.4 13.6 46.3 13.6 4.7 44.0 12.9 44.0 12.9 5.1
0.09 72 60.5 17.7 39.0 11.4 3.5 56.8 16.6 37.7 11.1 4.0 52.4 15.4 36.3 10.6 4.6 50.9 14.9 35.8 10.5 4.9 47.8 14.0 34.8 10.2 5.3
2600 62 55.4 16.2 55.4 16.2 3.4 52.1 15.3 52.1 15.3 4.0 48.6 14.2 48.6 14.2 4.5 47.3 13.9 47.3 13.9 4.8 44.6 13.1 44.6 13.1 5.2
1227 66.2 57.1 16.7 57.1 16.7 3.4 53.8 15.8 53.8 15.8 4.0 50.3 14.7 50.3 14.7 4.6 48.9 14.3 48.9 14.3 4.8 46.2 13.5 46.2 13.5 5.2
0.13 72 62.8 18.4 48.5 14.2 3.5 58.6 17.2 47.2 13.8 4.1 - - - - - - - - - - - - - - -
1600 62 61.1 17.9 59.5 17.4 4.8 57.6 16.9 57.6 16.9 5.5 54.1 15.8 54.1 15.8 6.2 52.8 15.5 52.8 15.5 6.4 50.2 14.7 50.2 14.7 6.9
755 66.2 67.6 19.8 53.1 15.6 4.9 63.4 18.6 51.4 15.1 5.6 59.0 17.3 49.6 14.5 6.3 57.4 16.8 49.0 14.4 6.5 54.4 15.9 47.8 14.0 7.0
0.09 72 73.7 21.6 42.7 12.5 5.0 69.7 20.4 41.2 12.1 5.7 65.6 19.2 39.8 11.7 6.4 64.0 18.8 39.2 11.5 6.6 61.0 17.9 38.2 11.2 7.1
2100 62 64.0 18.8 64.0 18.8 4.8 60.4 17.7 60.4 17.7 5.5 56.7 16.6 56.7 16.6 6.2 55.3 16.2 55.3 16.2 6.5 52.5 15.4 52.5 15.4 7.0
51070G1 991 66.2 69.7 20.4 61.0 17.9 4.9 65.4 19.2 59.4 17.4 5.6 61.2 17.9 57.8 16.9 6.3 59.6 17.5 57.2 16.8 6.6 56.6 16.6 56.0 16.4 7.0
0.11 72 77.4 22.7 48.5 14.2 5.1 73.0 21.4 47.0 13.8 5.8 68.5 20.1 45.5 13.3 6.4 66.8 19.6 44.9 13.2 6.7 63.0 18.5 43.7 12.8 7.1
2600 62 66.2 19.4 66.2 19.4 4.9 62.5 18.3 62.5 18.3 5.6 61.0 17.9 61.0 17.9 6.3 59.4 17.4 59.4 17.4 6.6 56.4 16.5 56.4 16.5 7.0
1227 66.2 71.5 20.9 68.7 20.1 5.0 67.2 19.7 67.1 19.7 5.6 62.8 18.4 62.8 18.4 6.3 61.3 18.0 61.3 18.0 6.6 58.1 17.0 58.1 17.0 7.0
0.13 72 79.9 23.4 53.9 15.8 5.1 75.1 22.0 52.4 15.3 5.8 69.7 20.4 50.6 14.8 6.5 67.8 19.9 50.0 14.7 6.7 64.0 18.8 48.8 14.3 7.1
2500 62 74.8 21.9 74.8 21.9 5.1 70.8 20.8 70.8 20.8 5.8 69.6 20.4 69.6 20.4 6.7 68.0 19.9 68.0 19.9 7.0 64.7 19.0 64.7 19.0 7.5
1180 66.2 80.7 23.7 72.9 21.4 5.2 76.4 22.4 71.3 20.9 5.9 71.8 21.1 69.6 20.4 6.7 70.2 20.6 68.9 20.2 7.0 66.9 19.6 66.9 19.6 7.6
0.09 72 90.3 26.5 57.9 17.0 5.4 85.4 25.0 56.3 16.5 6.1 80.0 23.5 54.5 16.0 6.9 78.1 22.9 53.8 15.8 7.2 74.4 21.8 52.6 15.4 7.7
2800 62 76.2 22.3 76.2 22.3 5.1 75.3 22.1 75.3 22.1 5.9 70.8 20.7 70.8 20.7 6.7 69.1 20.3 69.1 20.3 7.0 65.7 19.3 65.7 19.3 7.5
51080G1 1321 66.2 82.1 24.1 78.0 22.8 5.2 77.6 22.7 76.3 22.4 5.9 73.0 21.4 73.0 21.4 6.7 71.3 20.9 71.3 20.9 7.0 68.0 19.9 68.0 19.9 7.6
0.1 72 91.5 26.8 61.2 17.9 5.4 86.2 25.3 59.5 17.4 6.1 80.9 23.7 57.8 16.9 6.9 79.0 23.2 57.2 16.8 7.2 75.3 22.1 56.0 16.4 7.7
4000 62 83.3 24.4 83.3 24.4 5.2 78.6 23.0 78.6 23.0 6.0 73.7 21.6 73.7 21.6 6.8 71.9 21.1 71.9 21.1 7.0 68.4 20.0 68.4 20.0 7.6
1888 66.2 85.9 25.2 85.9 25.2 5.3 81.2 23.8 81.2 23.8 6.0 76.5 22.4 76.5 22.4 6.8 74.7 21.9 74.7 21.9 7.1 71.2 20.9 71.2 20.9 7.6
0.13 72 94.1 27.6 73.7 21.6 5.5 88.9 26.1 72.1 21.1 6.2 83.8 24.6 70.5 20.7 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2500 62 79.5 23.3 79.5 23.3 5.5 75.2 22.0 75.2 22.0 6.3 70.5 20.7 70.5 20.7 7.3 68.7 20.1 68.7 20.1 7.6 68.1 20.0 68.1 20.0 8.2
1180 66.2 85.9 25.2 74.9 22.0 5.7 81.0 23.7 73.0 21.4 6.5 75.8 22.2 71.1 20.8 7.4 74.0 21.7 70.4 20.6 7.7 70.3 20.6 69.0 20.2 8.2
0.09 72 95.7 28.1 59.8 17.5 6.0 90.4 26.5 57.9 17.0 6.7 84.9 24.9 56.1 16.4 7.4 82.6 24.2 55.3 16.2 7.7 78.3 22.9 53.9 15.8 8.2
3200 62 82.8 24.3 82.8 24.3 5.6 81.3 23.8 81.3 23.8 6.5 76.1 22.3 76.1 22.3 7.4 74.2 21.7 74.2 21.7 7.7 70.3 20.6 70.3 20.6 8.2
51090G1 1510 66.2 88.9 26.1 86.4 25.3 5.8 83.7 24.5 83.7 24.5 6.6 78.5 23.0 78.5 23.0 7.4 76.5 22.4 76.5 22.4 7.7 72.8 21.3 72.8 21.3 8.2
0.11 72 98.8 28.9 67.5 19.8 6.1 92.6 27.1 65.5 19.2 6.8 86.6 25.4 63.6 18.6 7.4 84.5 24.8 62.9 18.4 7.6 80.2 23.5 61.6 18.0 8.1
4000 62 88.7 26.0 88.7 26.0 5.8 83.4 24.5 83.4 24.5 6.6 78.0 22.9 78.0 22.9 7.4 76.0 22.3 76.0 22.3 7.7 72.0 21.1 72.0 21.1 8.2
1888 66.2 91.3 26.8 91.3 26.8 5.8 86.0 25.2 86.0 25.2 6.6 80.7 23.6 80.7 23.6 7.4 78.7 23.1 78.7 23.1 7.7 74.8 21.9 74.8 21.9 8.2
0.13 72 100.3 29.4 75.7 22.2 6.1 94.3 27.6 73.8 21.6 6.8 88.4 25.9 72.0 21.1 7.4 86.3 25.3 71.3 20.9 7.6 0.0 0.0 0.0 0.0 0.0
2500 62 87.7 25.7 87.7 25.7 6.5 82.8 24.3 82.8 24.3 7.4 77.7 22.8 77.7 22.8 8.3 75.9 22.2 75.9 22.2 8.7 72.3 21.2 72.3 21.2 9.3
1180 66.2 95.9 28.1 78.9 23.1 6.6 89.9 26.4 76.5 22.4 7.5 84.1 24.7 74.2 21.8 8.5 82.1 24.1 73.4 21.5 8.8 78.1 22.9 71.9 21.1 9.4
0.09 72 105.5 30.9 63.2 18.5 6.8 99.9 29.3 61.2 17.9 7.8 94.3 27.6 59.3 17.4 8.8 92.2 27.0 58.6 17.2 9.1 88.1 25.8 57.2 16.8 9.7
3500 62 92.7 27.2 92.7 27.2 6.6 87.5 25.6 87.5 25.6 7.5 85.5 25.1 85.5 25.1 8.5 83.5 24.5 83.5 24.5 8.8 79.4 23.3 79.4 23.3 9.5
51100G1 1652 66.2 99.8 29.2 94.8 27.8 6.7 94.0 27.6 92.7 27.2 7.6 88.2 25.8 88.2 25.8 8.6 86.0 25.2 86.0 25.2 8.9 82.0 24.0 82.0 24.0 9.5
0.11 72 111.0 32.5 74.4 21.8 6.9 104.6 30.7 72.3 21.2 7.9 98.0 28.7 70.2 20.6 8.9 95.6 28.0 69.4 20.3 9.2 90.9 26.6 67.9 19.9 9.8
4000 62 94.5 27.7 94.5 27.7 6.6 92.8 27.2 92.8 27.2 7.6 86.9 25.5 86.9 25.5 8.5 84.8 24.8 84.8 24.8 8.9 80.6 23.6 80.6 23.6 9.5
1888 66.2 101.4 29.7 101.4 29.7 6.7 95.5 28.0 95.5 28.0 7.7 89.6 26.3 89.6 26.3 8.6 87.5 25.6 87.5 25.6 9.0 83.4 24.4 83.4 24.4 9.6
0.13 72 112.4 32.9 79.5 23.3 6.9 105.6 30.9 77.3 22.7 7.9 99.1 29.0 75.3 22.1 8.9 96.7 28.3 74.5 21.8 9.3 0.0 0.0 0.0 0.0 0.0
3000 62 104.3 30.6 104.3 30.6 7.4 98.3 28.8 98.3 28.8 8.5 92.1 27.0 92.1 27.0 9.7 89.8 26.3 89.8 26.3 10.1 85.2 25.0 85.2 25.0 10.9
1416 66.2 114.1 33.5 94.3 27.6 7.5 106.8 31.3 91.4 26.8 8.6 99.6 29.2 88.6 26.0 9.8 97.1 28.5 87.6 25.7 10.2 92.2 27.0 85.7 25.1 11.0
0.09 72 125.9 36.9 75.6 22.1 7.8 119.0 34.9 73.1 21.4 8.9 111.8 32.8 70.7 20.7 10.0 109.3 32.0 69.8 20.5 10.4 104.4 30.6 68.1 20.0 11.1
4100 62 110.0 32.2 110.0 32.2 7.4 103.6 30.4 103.6 30.4 8.6 101.0 29.6 101.0 29.6 9.8 98.4 28.9 98.4 28.9 10.3 93.4 27.4 93.4 27.4 11.0
51120G1 1935 66.2 118.6 34.7 111.9 32.8 7.6 111.5 32.7 109.3 32.0 8.7 104.1 30.5 104.1 30.5 9.9 101.5 29.8 101.5 29.8 10.3 96.5 28.3 96.5 28.3 11.1
0.11 72 132.2 38.7 88.0 25.8 8.0 124.3 36.4 85.4 25.0 9.1 115.9 34.0 82.7 24.2 10.1 112.9 33.1 81.7 24.0 10.4 107.5 31.5 80.0 23.4 11.2
4800 62 112.5 33.0 112.5 33.0 7.5 110.3 32.3 110.3 32.3 8.7 103.0 30.2 103.0 30.2 9.9 100.3 29.4 100.3 29.4 10.3 95.1 27.9 95.1 27.9 11.0
2265 66.2 120.9 35.4 120.9 35.4 7.7 113.6 33.3 113.6 33.3 8.8 106.2 31.1 106.2 31.1 9.9 103.6 30.4 103.6 30.4 10.3 98.6 28.9 98.6 28.9 11.1
0.13 72 134.2 39.3 95.2 27.9 8.1 125.7 36.8 92.5 27.1 9.1 117.4 34.4 89.9 26.3 10.1 114.5 33.6 89.0 26.1 10.5 109.2 32.0 87.3 25.6 11.2
3700 62 116.0 34.0 116.0 34.0 8.1 109.7 32.1 109.7 32.1 9.3 102.7 30.1 102.7 30.1 10.5 104.5 30.6 104.5 30.6 11.0 99.0 29.0 99.0 29.0 11.9
1746 66.2 125.4 36.8 110.3 32.3 8.2 118.2 34.6 107.5 31.5 9.4 110.6 32.4 104.6 30.7 10.6 107.7 31.6 103.6 30.4 11.1 102.2 29.9 101.5 29.7 12.1
0.09 72 139.5 40.9 87.8 25.7 8.3 131.6 38.6 85.0 24.9 9.6 122.6 35.9 82.0 24.0 11.1 119.2 34.9 80.9 23.7 11.7 112.6 33.0 78.8 23.1 12.8
4500 62 119.9 35.1 119.9 35.1 8.2 117.8 34.5 117.8 34.5 9.4 110.2 32.3 110.2 32.3 10.6 107.3 31.5 107.3 31.5 11.1 101.6 29.8 101.6 29.8 12.0
52130G1 2124 66.2 128.8 37.8 123.5 36.2 8.3 121.3 35.6 120.7 35.4 9.4 113.6 33.3 113.6 33.3 10.7 110.7 32.4 110.7 32.4 11.2 105.0 30.8 105.0 30.8 12.2
0.1 72 142.8 41.8 96.6 28.3 8.3 133.6 39.2 93.6 27.4 9.6 124.5 36.5 90.7 26.6 11.2 121.1 35.5 89.6 26.3 11.8 114.6 33.6 87.5 25.7 13.0
5900 62 129.4 37.9 129.4 37.9 8.3 121.6 35.6 121.6 35.6 9.4 113.5 33.3 113.5 33.3 10.7 110.5 32.4 110.5 32.4 11.2 104.5 30.6 104.5 30.6 12.2
2784 66.2 133.1 39.0 133.1 39.0 8.3 125.4 36.8 125.4 36.8 9.5 117.3 34.4 117.3 34.4 10.8 114.4 33.5 114.4 33.5 11.4 108.4 31.8 108.4 31.8 12.4
0.12 72 145.5 42.6 111.0 32.5 8.3 136.4 40.0 108.2 31.7 9.7 127.3 37.3 105.4 30.9 11.4 124.0 36.3 104.3 30.6 12.1 0.0 0.0 0.0 0.0 0.0

Table 5

See Notes on page 12

10
GROSS CAPACITY RATINGS R 22
REFRIGERANT
AFR Condenser Entering Air Temperature
cfm 95°F (35°C) 105°F (40.6°C) 114.8°F (46°C) 118.4°F (48°C) 125.6°F (52°C)
Model EWB
APMR l/s Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI

(BPF) °F MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW
3700 62 128.7 37.7 128.7 37.7 9.4 121.7 35.7 121.7 35.7 10.6 114.4 33.5 114.4 33.5 12.0 111.6 32.7 111.6 32.7 12.6 106.2 31.1 106.2 31.1 13.6
1746 66.2 141.0 41.3 116.5 34.1 9.5 132.4 38.8 113.1 33.1 10.8 123.8 36.3 109.7 32.2 12.2 120.7 35.4 108.5 31.8 12.7 114.6 33.6 106.2 31.1 13.7
0.09 72 156.1 45.7 93.5 27.4 9.8 147.6 43.3 90.6 26.5 11.1 138.7 40.7 87.5 25.6 12.5 135.4 39.7 86.3 25.3 13.0 128.6 37.7 84.0 24.6 13.9
5000 62 135.6 39.7 135.6 39.7 9.5 128.3 37.6 128.3 37.6 10.7 125.3 36.7 125.3 36.7 12.2 122.2 35.8 122.2 35.8 12.7 115.8 33.9 115.8 33.9 13.7
52150G1 2360 66.2 146.4 42.9 137.5 40.3 9.6 138.1 40.5 134.3 39.4 10.9 129.2 37.9 129.2 37.9 12.3 125.9 36.9 125.9 36.9 12.8 119.5 35.0 119.5 35.0 13.8
0.11 72 164.0 48.1 108.4 31.8 9.9 154.3 45.2 105.2 30.8 11.2 143.4 42.0 101.7 29.8 12.5 139.4 40.9 100.4 29.4 13.0 131.7 38.6 97.9 28.7 13.9
5900 62 139.0 40.7 139.0 40.7 9.5 136.8 40.1 136.8 40.1 10.9 127.9 37.5 127.9 37.5 12.3 124.6 36.5 124.6 36.5 12.8 118.0 34.6 118.0 34.6 13.7
2784 66.2 149.6 43.9 149.6 43.9 9.7 140.9 41.3 140.9 41.3 11.0 131.9 38.7 131.9 38.7 12.4 128.6 37.7 128.6 37.7 12.9 122.0 35.8 122.0 35.8 13.8
0.12 72 166.9 48.9 117.8 34.5 10.0 156.0 45.7 114.3 33.5 11.2 145.2 42.6 110.9 32.5 12.6 141.3 41.4 109.7 32.2 13.1 133.7 39.2 107.3 31.5 13.9
4300 62 144.2 42.3 144.2 42.3 10.0 136.7 40.1 136.7 40.1 11.5 129.0 37.8 129.0 37.8 13.1 126.2 37.0 126.2 37.0 13.7 120.2 35.2 120.2 35.2 14.8
2029 66.2 157.1 46.1 132.7 38.9 10.2 148.3 43.5 129.2 37.9 11.7 139.5 40.9 125.8 36.9 13.3 136.3 40.0 124.6 36.5 13.9 129.9 38.1 122.2 35.8 15.0
0.09 72 174.8 51.2 106.4 31.2 10.5 166.1 48.7 103.4 30.3 12.0 156.9 46.0 100.2 29.4 13.6 153.5 45.0 99.1 29.0 14.2 146.4 42.9 96.7 28.3 15.2
5800 62 151.9 44.5 151.9 44.5 10.2 143.8 42.2 143.8 42.2 11.6 141.2 41.4 141.2 41.4 13.3 137.9 40.4 137.9 40.4 13.9 131.2 38.4 131.2 38.4 15.0
52170G1 2737 66.2 163.7 48.0 157.2 46.1 10.3 154.8 45.4 153.8 45.1 11.8 145.6 42.7 145.6 42.7 13.4 142.3 41.7 142.3 41.7 14.0 135.7 39.8 135.7 39.8 15.1
0.11 72 183.0 53.7 123.4 36.2 10.7 172.4 50.5 120.0 35.2 12.1 161.7 47.4 116.5 34.1 13.7 157.9 46.3 115.3 33.8 14.2 150.5 44.1 112.9 33.1 15.3
7000 62 162.6 47.7 162.6 47.7 10.3 153.7 45.1 153.7 45.1 11.7 144.4 42.3 144.4 42.3 13.4 140.9 41.3 140.9 41.3 13.9 134.0 39.3 134.0 39.3 15.0
3304 66.2 167.5 49.1 167.5 49.1 10.4 158.5 46.4 158.5 46.4 11.8 149.2 43.7 149.2 43.7 13.4 145.8 42.7 145.8 42.7 14.0 139.0 40.7 139.0 40.7 15.1
0.13 72 185.5 54.4 135.6 39.7 10.8 174.9 51.3 132.2 38.8 12.2 164.5 48.2 129.0 37.8 13.7 160.7 47.1 127.8 37.5 14.3 153.4 45.0 125.5 36.8 15.3
4300 62 153.5 45.0 153.5 45.0 10.8 145.1 42.5 145.1 42.5 12.4 136.2 39.9 136.2 39.9 14.4 132.9 39.0 132.9 39.0 15.1 126.4 37.1 126.4 37.1 16.4
2029 66.2 168.3 49.3 137.2 40.2 11.2 157.9 46.3 133.0 39.0 12.8 147.5 43.2 128.9 37.8 14.6 143.7 42.1 127.4 37.4 15.2 136.6 40.0 124.7 36.5 16.4
0.09 72 185.0 54.2 110.0 32.2 11.6 175.2 51.3 106.5 31.2 13.2 165.1 48.4 103.0 30.2 14.7 161.3 47.3 101.7 29.8 15.3 153.9 45.1 99.2 29.1 16.3
6200 62 163.1 47.8 163.1 47.8 11.0 154.1 45.2 154.1 45.2 12.7 150.6 44.1 150.6 44.1 14.6 146.8 43.0 146.8 43.0 15.2 139.3 40.8 139.3 40.8 16.4
52180G1 2926 66.2 175.7 51.5 167.4 49.1 11.4 165.6 48.5 163.6 48.0 13.0 155.2 45.5 155.2 45.5 14.7 151.3 44.4 151.3 44.4 15.3 143.9 42.2 143.9 42.2 16.4
0.12 72 195.9 57.4 131.4 38.5 12.0 184.5 54.1 127.7 37.4 13.4 172.3 50.5 123.8 36.3 14.7 167.9 49.2 122.4 35.9 15.2 159.3 46.7 119.6 35.1 16.2
7000 62 165.9 48.6 165.9 48.6 11.1 163.1 47.8 163.1 47.8 12.9 152.8 44.8 152.8 44.8 14.6 148.9 43.6 148.9 43.6 15.3 141.2 41.4 141.2 41.4 16.4
3304 66.2 178.3 52.3 178.3 52.3 11.4 168.0 49.2 168.0 49.2 13.0 157.5 46.2 157.5 46.2 14.7 153.6 45.0 153.6 45.0 15.3 146.1 42.8 146.1 42.8 16.3
0.13 72 198.4 58.1 139.7 40.9 12.1 185.9 54.5 135.7 39.8 13.5 173.9 51.0 131.9 38.7 14.7 169.6 49.7 130.6 38.3 15.2 161.2 47.2 127.9 37.5 16.1
4300 62 172.1 50.4 163.5 47.9 12.3 162.6 47.7 159.2 46.7 14.0 152.6 44.7 152.6 44.7 16.0 149.0 43.7 149.0 43.7 16.7 141.8 41.5 141.8 41.5 18.0
2029 66.2 189.1 55.4 145.8 42.7 12.6 179.9 52.7 142.0 41.6 14.3 167.9 49.2 137.1 40.2 16.2 163.3 47.9 135.2 39.6 16.9 154.8 45.4 131.8 38.6 18.2
0.09 72 206.5 60.5 117.7 34.5 12.8 196.2 57.5 114.0 33.4 14.6 185.3 54.3 110.1 32.3 16.5 181.4 53.2 108.7 31.9 17.3 173.6 50.9 106.0 31.1 18.6
6500 62 183.8 53.9 183.8 53.9 12.5 174.2 51.1 174.2 51.1 14.2 163.8 48.0 163.8 48.0 16.1 160.0 46.9 160.0 46.9 16.8 152.1 44.6 152.1 44.6 18.2
52210G1 3068 66.2 199.6 58.5 180.7 53.0 12.7 188.3 55.2 176.4 51.7 14.4 176.7 51.8 172.1 50.4 16.4 172.5 50.6 170.5 50.0 17.1 164.2 48.1 164.2 48.1 18.4
0.12 72 221.7 65.0 142.7 41.8 13.0 210.2 61.6 138.9 40.7 14.8 198.4 58.1 135.0 39.6 16.9 194.1 56.9 133.6 39.2 17.6 184.3 54.0 130.5 38.2 19.0
7000 62 185.9 54.5 185.9 54.5 12.5 176.1 51.6 176.1 51.6 14.3 165.5 48.5 165.5 48.5 16.2 161.5 47.3 161.5 47.3 16.9 160.5 47.1 160.5 47.1 18.3
3304 66.2 201.3 59.0 188.3 55.2 12.7 190.0 55.7 184.0 53.9 14.5 178.4 52.3 178.4 52.3 16.4 174.1 51.0 174.1 51.0 17.1 165.7 48.6 165.7 48.6 18.4
0.13 72 224.1 65.7 148.1 43.4 13.0 212.2 62.2 144.2 42.3 14.9 200.0 58.6 140.2 41.1 16.9 195.1 57.2 138.6 40.6 17.6 185.3 54.3 135.5 39.7 19.0
6000 62 209.1 61.3 209.1 61.3 14.7 197.1 57.8 197.1 57.8 16.9 184.6 54.1 184.6 54.1 19.4 180.0 52.8 180.0 52.8 20.2 170.8 50.1 170.8 50.1 21.9
2832 66.2 228.7 67.0 189.0 55.4 15.0 214.2 62.8 183.1 53.7 17.2 199.7 58.5 177.5 52.0 19.6 194.6 57.1 175.5 51.4 20.4 184.9 54.2 171.8 50.4 22.0
0.09 72 252.5 74.0 151.5 44.4 15.6 238.5 69.9 146.6 43.0 17.8 224.3 65.7 141.6 41.5 20.0 219.1 64.2 139.9 41.0 20.8 209.3 61.3 136.6 40.0 22.2
7000 62 214.8 63.0 214.8 63.0 14.8 202.5 59.4 202.5 59.4 17.0 189.5 55.5 189.5 55.5 19.4 184.8 54.2 184.8 54.2 20.3 183.2 53.7 183.2 53.7 22.0
52240G1 3304 66.2 232.8 68.2 205.1 60.1 15.1 218.7 64.1 199.6 58.5 17.3 204.4 59.9 194.3 56.9 19.7 199.2 58.4 192.3 56.4 20.5 189.2 55.5 188.5 55.3 22.0
0.1 72 259.1 75.9 163.1 47.8 15.8 244.5 71.7 158.1 46.3 18.0 229.5 67.3 153.1 44.9 20.1 223.4 65.5 151.1 44.3 20.8 212.2 62.2 147.4 43.2 22.2
9700 62 226.0 66.2 226.0 66.2 14.9 221.6 64.9 221.6 64.9 17.4 206.7 60.6 206.7 60.6 19.7 201.3 59.0 201.3 59.0 20.5 190.9 56.0 190.9 56.0 22.1
4578 66.2 242.7 71.1 242.7 71.1 15.3 228.2 66.9 228.2 66.9 17.5 213.3 62.5 213.3 62.5 19.8 208.0 61.0 208.0 61.0 20.6 197.9 58.0 197.9 58.0 22.1
0.13 72 269.0 78.9 191.8 56.2 16.1 252.0 73.9 186.3 54.6 18.2 235.6 69.0 181.2 53.1 20.2 229.8 67.4 179.4 52.6 20.9 219.2 64.2 176.0 51.6 22.3
6000 62 230.7 67.6 223.8 65.6 16.2 217.0 63.6 217.0 63.6 18.6 202.8 59.4 202.8 59.4 21.4 197.5 57.9 197.5 57.9 22.4 187.1 54.8 187.1 54.8 24.4
2832 66.2 254.6 74.6 199.6 58.5 16.6 238.9 70.0 193.1 56.6 19.1 221.3 64.9 186.0 54.5 21.8 215.0 63.0 183.5 53.8 22.8 203.0 59.5 178.8 52.4 24.6
0.09 72 277.5 81.3 160.4 47.0 16.9 262.0 76.8 154.8 45.4 19.5 245.9 72.1 149.2 43.7 22.3 240.1 70.4 147.1 43.1 23.4 228.4 67.0 143.1 41.9 25.3
8000 62 242.0 70.9 242.0 70.9 16.4 228.0 66.8 228.0 66.8 18.9 213.2 62.5 213.2 62.5 21.6 207.7 60.9 207.7 60.9 22.6 196.5 57.6 196.5 57.6 24.5
52270G1 3776 66.2 263.2 77.1 231.1 67.7 16.7 246.6 72.3 224.8 65.9 19.2 229.9 67.4 218.5 64.1 21.9 223.8 65.6 216.2 63.4 23.0 211.8 62.1 211.7 62.0 24.8
0.11 72 291.6 85.5 183.4 53.8 17.1 274.9 80.6 177.8 52.1 19.7 257.6 75.5 172.0 50.4 22.6 251.2 73.6 169.9 49.8 23.7 237.0 69.5 165.3 48.5 25.5
9700 62 249.4 73.1 249.4 73.1 16.5 234.9 68.9 234.9 68.9 19.0 219.3 64.3 219.3 64.3 21.7 222.5 65.2 222.5 65.2 22.9 210.3 61.7 210.3 61.7 24.8
4578 66.2 269.1 78.9 257.3 75.4 16.8 252.7 74.1 251.2 73.6 19.3 235.6 69.1 235.6 69.1 22.1 229.3 67.2 229.3 67.2 23.1 217.2 63.7 217.2 63.7 25.0
0.13 72 299.5 87.8 201.6 59.1 17.2 281.9 82.6 195.9 57.4 19.8 261.9 76.7 189.5 55.5 22.7 254.6 74.6 187.2 54.9 23.8 240.8 70.6 182.8 53.6 25.7
6000 62 249.4 73.1 232.3 68.1 18.5 233.7 68.5 225.1 66.0 21.2 217.7 63.8 217.7 63.8 24.0 211.9 62.1 211.9 62.1 25.0 200.6 58.8 200.6 58.8 26.9
2832 66.2 272.3 79.8 206.9 60.7 19.0 257.4 75.5 200.7 58.8 21.7 239.9 70.3 193.5 56.7 24.4 232.7 68.2 190.6 55.9 25.4 219.0 64.2 185.1 54.2 27.2
0.09 72 297.3 87.1 167.7 49.2 19.5 280.8 82.3 161.6 47.4 22.1 263.2 77.2 155.3 45.5 24.8 256.8 75.3 153.0 44.8 25.8 244.2 71.6 148.6 43.5 27.6
9000 62 265.2 77.7 265.2 77.7 18.9 249.5 73.1 249.5 73.1 21.5 233.1 68.3 233.1 68.3 24.3 227.0 66.5 227.0 66.5 25.3 214.8 63.0 214.8 63.0 27.1
52300G1 4248 66.2 289.1 84.7 255.1 74.8 19.4 270.2 79.2 248.0 72.7 21.9 251.4 73.7 240.9 70.6 24.6 244.7 71.7 238.4 69.9 25.6 231.4 67.8 231.4 67.8 27.4
0.12 72 319.7 93.7 202.0 59.2 19.7 300.8 88.2 195.7 57.3 22.4 280.9 82.3 189.1 55.4 25.2 273.5 80.2 186.7 54.7 26.1 258.2 75.7 181.7 53.3 27.8
9700 62 268.2 78.6 268.2 78.6 19.0 252.3 74.0 252.3 74.0 21.6 235.7 69.1 235.7 69.1 24.3 229.3 67.2 229.3 67.2 25.3 226.5 66.4 226.5 66.4 27.3
4578 66.2 291.2 85.4 265.7 77.9 19.4 272.6 79.9 258.6 75.8 22.0 253.9 74.4 251.6 73.7 24.7 246.9 72.4 246.9 72.4 25.6 233.6 68.5 233.6 68.5 27.4
0.13 72 323.3 94.8 209.5 61.4 19.7 303.9 89.1 203.1 59.5 22.4 283.5 83.1 196.4 57.6 25.2 275.4 80.7 193.8 56.8 26.2 259.5 76.1 188.7 55.3 27.8

Table 6

See Notes on page 12

S.K.M Air Conditioning LLC


11
SKM Packaged Air Conditioners APMRG1 Series

GROSS CAPACITY RATINGS


AFR Condenser Entering Air Temperature
Model cfm 95°F (35°C) 105°F (40.6°C) 114.8°F (46°C) 118.4°F (48°C) 125.6°F (52°C)
EWB

APMR l/s Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI

(BPF) °F MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW
7200 62 292.0 85.6 275.4 80.7 22.8 274.8 80.5 267.6 78.4 25.7 257.7 75.5 257.7 75.5 28.8 251.5 73.7 251.5 73.7 29.8 239.5 70.2 239.5 70.2 31.9
3398 66.2 319.4 93.6 245.3 71.9 23.5 302.9 88.8 238.4 69.9 26.5 282.8 82.9 230.2 67.5 29.4 275.2 80.7 227.1 66.6 30.4 260.8 76.4 221.3 64.9 32.4
0.09 72 348.0 102.0 198.0 58.0 24.1 329.5 96.6 191.2 56.0 27.0 310.5 91.0 184.4 54.1 30.0 303.6 89.0 182.0 53.3 31.0 0.0 0.0 0.0 0.0 0.0
10000 62 307.1 90.0 307.1 90.0 23.2 289.9 85.0 289.9 85.0 26.1 272.4 79.8 272.4 79.8 29.1 266.0 78.0 266.0 78.0 30.2 253.2 74.2 253.2 74.2 32.2
52340G1 4719 66.2 334.4 98.0 290.2 85.1 23.8 313.8 92.0 282.3 82.7 26.7 293.7 86.1 274.7 80.5 29.6 286.5 84.0 272.0 79.7 30.7 272.6 79.9 266.8 78.2 32.7
0.11 72 368.4 108.0 230.0 67.4 24.4 348.0 102.0 223.1 65.4 27.4 327.0 95.8 216.1 63.3 30.3 319.2 93.6 213.5 62.6 31.4 0.0 0.0 0.0 0.0 0.0
11600 62 314.0 92.0 314.0 92.0 23.4 296.5 86.9 296.5 86.9 26.3 278.6 81.6 278.6 81.6 29.3 271.7 79.6 271.7 79.6 30.3 269.5 79.0 269.5 79.0 32.6
5475 66.2 339.4 99.5 314.4 92.2 23.9 319.2 93.6 306.8 89.9 26.8 299.2 87.7 299.2 87.7 29.8 291.9 85.5 291.9 85.5 30.8 277.5 81.3 277.5 81.3 32.8
0.12 72 376.3 110.3 247.1 72.4 24.5 354.8 104.0 240.1 70.4 27.5 332.3 97.4 232.8 68.2 30.4 323.4 94.8 230.0 67.4 31.4 0.0 0.0 0.0 0.0 0.0
8400 62 334.2 98.0 318.4 93.3 26.0 315.3 92.4 309.9 90.8 29.4 296.5 86.9 296.5 86.9 33.0 289.6 84.9 289.6 84.9 34.4 276.1 80.9 276.1 80.9 36.8
3964 66.2 366.6 107.4 283.6 83.1 26.7 348.3 102.1 276.0 80.9 30.2 324.7 95.2 266.4 78.1 33.7 316.3 92.7 263.0 77.1 34.9 300.3 88.0 256.6 75.2 37.3
0.09 72 399.3 117.0 228.5 67.0 27.4 378.7 111.0 221.0 64.8 30.8 357.7 104.9 213.6 62.6 34.4 349.9 102.6 210.8 61.8 35.6 334.5 98.0 205.4 60.2 37.9
10800 62 347.6 101.9 347.6 101.9 26.3 328.7 96.4 328.7 96.4 29.7 309.5 90.7 309.5 90.7 33.3 302.4 88.6 302.4 88.6 34.6 288.5 84.6 288.5 84.6 37.0
52380G1
5097 66.2 379.6 111.3 322.3 94.5 27.0 356.7 104.5 313.4 91.8 30.4 334.4 98.0 304.8 89.3 33.9 326.4 95.7 301.8 88.5 35.1 311.0 91.2 296.0 86.8 37.5
0.11 72 417.4 122.3 256.3 75.1 27.7 395.3 115.9 248.7 72.9 31.2 372.6 109.2 241.0 70.6 34.7 364.1 106.7 238.2 69.8 35.9 347.2 101.8 232.6 68.2 38.1
13600 62 360.1 105.5 360.1 105.5 26.6 340.6 99.8 340.6 99.8 30.0 320.3 93.9 320.3 93.9 33.6 313.0 91.7 313.0 91.7 34.8 310.8 91.1 310.8 91.1 37.5
6418 66.2 388.6 113.9 365.0 107.0 27.2 366.5 107.4 356.7 104.5 30.6 344.3 100.9 344.3 100.9 34.1 336.1 98.5 336.1 98.5 35.3 320.1 93.8 320.1 93.8 37.6
0.13 72 431.8 126.6 286.6 84.0 28.0 407.9 119.5 278.8 81.7 31.4 382.1 112.0 270.4 79.3 34.9 372.0 109.0 267.2 78.3 36.1 352.7 103.4 261.0 76.5 38.3
3964 66.2 397.6 116.5 296.9 87.0 29.2 379.0 111.1 288.8 84.7 33.1 359.3 105.3 280.6 82.2 37.3 352.0 103.2 277.5 81.3 38.8 334.6 98.1 270.4 79.2 41.6
0.09 72 434.2 127.3 241.6 70.8 29.9 413.7 121.2 233.9 68.5 33.8 392.2 115.0 225.9 66.2 38.0 384.1 112.6 223.0 65.3 39.4 368.0 107.9 217.2 63.7 42.2
11800 62 385.8 113.1 385.8 113.1 29.0 365.4 107.1 365.4 107.1 32.8 344.5 101.0 344.5 101.0 37.0 336.8 98.7 336.8 98.7 38.6 321.6 94.3 321.6 94.3 41.4
52420G1 5569 66.2 425.1 124.6 354.1 103.8 29.7 399.4 117.0 344.0 100.8 33.5 374.3 109.7 334.3 98.0 37.6 365.3 107.1 330.9 97.0 39.1 348.1 102.0 324.4 95.1 41.8
0.11 72 463.4 135.8 281.1 82.4 30.5 440.1 129.0 273.1 80.0 34.4 416.2 122.0 264.9 77.6 38.5 407.3 119.4 262.0 76.8 39.9 389.4 114.1 255.9 75.0 42.6
13600 62 394.0 115.5 394.0 115.5 29.1 373.3 109.4 373.3 109.4 33.0 352.1 103.2 352.1 103.2 37.2 344.3 100.9 344.3 100.9 38.7 328.9 96.4 328.9 96.4 41.6
6418 66.2 429.8 126.0 380.5 111.5 29.8 404.9 118.7 371.1 108.8 33.6 380.5 111.5 362.0 106.1 37.7 371.8 109.0 358.7 105.1 39.2 354.6 103.9 352.3 103.2 41.9
0.13 72 473.7 138.8 300.5 88.1 30.7 449.5 131.7 292.4 85.7 34.6 424.6 124.5 284.2 83.3 38.7 415.2 121.7 281.2 82.4 40.1 396.4 116.2 275.1 80.6 42.7
10400 62 418.2 122.6 396.1 116.1 32.4 395.0 115.8 385.7 113.0 36.8 371.9 109.0 371.9 109.0 41.8 363.4 106.5 363.4 106.5 43.5 346.8 101.6 346.8 101.6 46.8
4908 66.2 458.8 134.5 353.2 103.5 33.3 436.5 127.9 343.9 100.8 37.8 408.5 119.7 332.4 97.4 42.5 397.9 116.6 328.1 96.2 44.2 377.7 110.7 320.0 93.8 47.3
0.09 72 500.9 146.8 285.3 83.6 34.3 475.6 139.4 276.0 80.9 38.8 449.1 131.6 266.6 78.1 43.4 439.4 128.8 263.1 77.1 45.0 420.4 123.2 256.5 75.2 48.0
13500 62 435.6 127.7 435.6 127.7 32.8 412.6 120.9 412.6 120.9 37.3 388.9 114.0 388.9 114.0 42.1 380.2 111.4 380.2 111.4 43.8 363.0 106.4 363.0 106.4 47.0
52500G1 6371 66.2 477.4 139.9 403.7 118.3 33.7 448.9 131.6 392.6 115.1 38.1 420.7 123.3 381.8 111.9 42.8 410.6 120.3 378.0 110.8 44.4 391.3 114.7 370.7 108.7 47.5
0.11 72 525.2 153.9 321.4 94.2 34.9 497.5 145.8 311.8 91.4 39.3 469.0 137.5 302.2 88.6 43.9 458.5 134.4 298.6 87.5 45.5 437.9 128.3 291.8 85.5 48.3
16800 62 450.7 132.1 450.7 132.1 33.1 427.0 125.1 427.0 125.1 37.6 402.4 117.9 402.4 117.9 42.4 392.9 115.1 392.9 115.1 44.1 390.5 114.4 390.5 114.4 47.4
7929 66.2 488.1 143.0 453.9 133.0 34.0 460.4 134.9 443.5 130.0 38.4 432.6 126.8 432.6 126.8 43.1 422.3 123.8 422.3 123.8 44.7 402.3 117.9 402.3 117.9 47.6
0.13 72 542.7 159.1 357.1 104.6 35.3 512.9 150.3 347.4 101.8 39.7 481.9 141.2 337.3 98.9 44.3 469.4 137.6 333.3 97.7 45.8 445.6 130.6 325.6 95.4 48.5
10400 62 461.8 135.3 416.3 122.0 34.2 435.6 127.7 404.1 118.4 38.7 409.3 119.9 392.1 114.9 44.3 399.7 117.1 387.8 113.6 46.4 381.0 111.7 379.4 111.2 50.3
4908 66.2 498.3 146.0 370.0 108.4 34.8 475.9 139.5 360.4 105.6 39.6 451.5 132.3 350.1 102.6 45.1 442.1 129.6 346.2 101.5 47.1 421.4 123.5 337.7 99.0 50.8
0.09 72 546.2 160.1 302.3 88.6 35.8 521.3 152.8 293.0 85.9 40.6 493.7 144.7 282.6 82.8 45.9 482.9 141.5 278.7 81.7 47.9 461.7 135.3 271.1 79.4 51.5
15800 62 489.2 143.4 489.2 143.4 34.7 464.5 136.1 464.5 136.1 39.3 438.5 128.5 438.5 128.5 44.8 428.7 125.6 428.7 125.6 46.8 409.2 119.9 409.2 119.9 50.7
52550G1 7452 66.2 540.3 158.3 460.1 134.8 35.7 508.8 149.1 447.8 131.2 40.3 476.3 139.6 435.4 127.6 45.6 464.5 136.1 431.1 126.4 47.5 441.9 129.5 422.6 123.9 51.1
0.12 72 593.1 173.8 365.2 107.0 36.9 563.2 165.1 354.9 104.0 41.6 531.0 155.6 344.1 100.8 46.8 519.0 152.1 340.1 99.7 48.6 495.1 145.1 332.3 97.4 52.1
16800 62 493.8 144.7 493.8 144.7 34.8 469.0 137.4 469.0 137.4 39.4 442.7 129.7 442.7 129.7 44.9 432.8 126.8 432.8 126.8 46.9 413.0 121.0 413.0 121.0 50.7
7929 66.2 543.0 159.1 474.7 139.1 35.8 511.8 150.0 462.9 135.7 40.4 479.7 140.6 450.8 132.1 45.6 468.0 137.1 446.4 130.8 47.6 445.4 130.5 437.9 128.3 51.2
0.13 72 598.8 175.5 375.8 110.1 37.0 568.4 166.6 365.6 107.2 41.7 535.6 157.0 354.7 104.0 46.9 523.1 153.3 350.7 102.8 48.7 499.2 146.3 342.9 100.5 52.2

Table 7

Notes:
1. See Page 2 for legend.
2. Ratings are based on 84.2°F (29°C) DB evaporator air entering temperature.
3. Direct interpolation is permissible. Do not extrapolate.
4. SKM Computer Selection Software are available for quick and accurate selections.
5. Capacity is gross capacity which does not include the effect of evaporator fan motor heat.
* Power input (PI) mentioned in this page is for compressor only and should not be used for cable or fuse selection.
MCA and MFA values given in the electrical data (page 14) should be referred for the same.

12
FAN PERFORMANCE R 22
REFRIGERANT
External Static Pressure - in.wg (Pa)
Internal Static
Model AirFlowRate
Pressure 0.2(50) 0.4(100) 0.5(125) 0.6(150) 0.8(200) 1(250) 1.2(300)
APMR
cfm l/s in.wg Pa RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1600 755 0.28 70 653 0.19 756 0.24 805 0.26 852 0.29 945 0.34 1035 0.4 1125 0.47
51055G1 1700 802 0.31 78 678 0.22 777 0.27 823 0.3 868 0.32 957 0.38 1043 0.44 1128 0.51
2600 1227 0.73 183 944 0.68 1015 0.76 1049 0.8 1083 0.84 1147 0.92 1209 1 1270 1.08
1600 755 0.28 70 - - 662 0.21 711 0.25 759 0.28 - - - - - -
51070G1 2100 991 0.47 117 665 0.31 749 0.37 790 0.41 829 0.45 905 0.52 978 0.61 1050 0.7
2600 1227 0.73 183 791 0.55 862 0.63 896 0.67 929 0.71 994 0.8 1056 0.89 1117 0.99
2500 1180 0.29 72 607 0.34 692 0.42 732 0.46 770 0.5 843 0.57 912 0.66 979 0.74
51080G1 2800 1321 0.36 89 655 0.45 734 0.54 771 0.58 807 0.63 876 0.71 941 0.8 1003 0.89
4000 1888 0.74 185 881 1.2 938 1.32 967 1.38 995 1.45 1049 1.57 1101 1.7 1151 1.82
2500 1180 0.29 72 474 0.25 556 0.33 594 0.38 632 0.43 704 0.53 - - - -
51090G1 3200 1510 0.46 115 558 0.46 627 0.56 659 0.61 691 0.66 751 0.78 810 0.9 867 1.03
4000 1888 0.74 185 670 0.83 727 0.95 755 1.02 781 1.08 833 1.21 883 1.35 931 1.49
2500 1180 0.29 72 474 0.25 556 0.33 594 0.38 632 0.43 704 0.53 - - - -
51100G1 3500 1652 0.56 139 599 0.58 663 0.69 693 0.74 723 0.8 780 0.92 834 1.05 888 1.18
4000 1888 0.74 185 670 0.83 727 0.95 755 1.02 781 1.08 833 1.21 883 1.35 931 1.49
3000 1416 0.29 72 486 0.33 563 0.43 598 0.47 633 0.52 698 0.63 760 0.74 821 0.87
51120G1 4100 1935 0.53 132 608 0.74 669 0.86 698 0.92 726 0.98 780 1.11 832 1.25 881 1.38
4800 2265 0.74 185 695 1.15 749 1.29 775 1.36 800 1.43 848 1.57 895 1.72 940 1.88
3700 1746 0.28 71 - - 698 0.56 746 0.62 792 0.69 881 0.85 967 1.02 1052 1.22
52130G1 4500 2124 0.41 101 676 0.69 765 0.84 807 0.92 847 1 925 1.16 1000 1.34 1072 1.53
5900 2784 0.72 178 841 1.43 912 1.63 946 1.73 980 1.83 1044 2.03 1106 2.23 1166 2.45
3700 1746 0.28 71 - - 698 0.56 746 0.62 792 0.69 881 0.85 967 1.02 1052 1.22
52150G1 5000 2360 0.5 126 733 0.91 814 1.08 853 1.16 891 1.25 963 1.42 1033 1.61 1100 1.8
5900 2784 0.72 178 841 1.43 912 1.63 946 1.73 980 1.83 1044 2.03 1106 2.23 1166 2.45
4300 2029 0.28 70 611 0.55 706 0.7 751 0.77 794 0.84 876 1 954 1.17 1030 1.35
52170G1 5800 2737 0.5 124 754 1.18 832 1.37 868 1.47 904 1.57 972 1.76 1037 1.96 1100 2.16
7000 3303 0.74 185 885 1.98 951 2.22 983 2.33 1014 2.45 1074 2.69 1131 2.92 1187 3.16
4300 2029 0.28 70 611 0.55 706 0.7 751 0.77 794 0.84 876 1 954 1.17 1030 1.35
52180G1 6200 2926 0.57 143 797 1.41 870 1.62 905 1.72 939 1.83 1004 2.04 1067 2.25 1127 2.46
7000 3303 0.74 185 885 1.98 951 2.22 983 2.33 1014 2.45 1074 2.69 1131 2.92 1187 3.16
4300 2029 0.28 70 611 0.55 706 0.7 751 0.77 794 0.84 876 1 954 1.17 1030 1.35
52210G1 6500 3067 0.63 158 830 1.61 900 1.83 934 1.94 966 2.05 1030 2.26 1090 2.48 1148 2.71
7000 3303 0.74 185 885 1.98 951 2.22 983 2.33 1014 2.45 1074 2.69 1131 2.92 1187 3.16
6000 2831 0.28 70 674 1.04 755 1.24 794 1.34 832 1.44 903 1.64 971 1.84 1035 2.05
52240G1 7000 3303 0.37 93 757 1.56 827 1.78 862 1.9 896 2.02 961 2.25 1023 2.49 1083 2.72
9700 4577 0.73 183 1006 3.9 1057 4.2 1083 4.35 1108 4.51 1159 4.83 1208 5.15 1257 5.48
6000 2831 0.28 70 508 0.71 588 0.91 626 1.01 662 1.12 730 1.34 796 1.59 860 1.85
52270G1 8000 3775 0.49 122 620 1.47 686 1.72 717 1.85 748 1.98 805 2.25 860 2.53 913 2.82
9700 4577 0.73 183 730 2.51 786 2.81 813 2.96 839 3.11 890 3.43 939 3.75 986 4.08
6000 2831 0.28 70 508 0.71 588 0.91 626 1.01 662 1.12 730 1.34 796 1.59 860 1.85
52300G1 9000 4247 0.63 156 684 2.04 744 2.31 772 2.46 800 2.6 854 2.89 905 3.2 954 3.51
9700 4577 0.73 183 730 2.51 786 2.81 813 2.96 839 3.11 890 3.43 939 3.75 986 4.08
7200 3398 0.28 70 529 0.99 605 1.21 640 1.33 673 1.45 737 1.69 797 1.94 855 2.21
52340G1 10000 4719 0.53 132 676 2.37 735 2.66 763 2.81 791 2.96 843 3.28 894 3.6 942 3.92
11600 5474 0.73 181 770 3.6 821 3.94 846 4.11 871 4.28 918 4.64 964 5 1008 5.36
8400 3964 0.28 70 436 1.05 500 1.33 530 1.48 560 1.64 617 1.98 672 2.35 727 2.77
52380G1 10800 5097 0.45 113 521 1.99 574 2.34 600 2.51 624 2.69 672 3.07 718 3.47 763 3.89
13600 6418 0.74 183 634 3.77 678 4.19 699 4.41 720 4.63 760 5.07 799 5.53 837 6
8400 3964 0.28 70 436 1.05 500 1.33 530 1.48 560 1.64 617 1.98 672 2.35 727 2.77
52420G1 11800 5568 0.54 136 560 2.53 610 2.91 634 3.1 657 3.29 701 3.69 745 4.11 786 4.55
13600 6418 0.74 183 634 3.77 678 4.19 699 4.41 720 4.63 760 5.07 799 5.53 837 6
10400 4908 0.28 71 465 1.58 524 1.91 551 2.07 577 2.24 628 2.6 676 2.97 723 3.37
52500G1 13500 6371 0.46 115 567 3.13 615 3.56 638 3.77 661 3.98 704 4.41 745 4.85 784 5.3
16800 7928 0.73 183 687 5.79 727 6.32 746 6.59 765 6.85 802 7.38 838 7.91 872 8.44
10400 4908 0.28 71 465 1.58 524 1.91 551 2.07 577 2.24 628 2.6 676 2.97 723 3.37
52550G1 15800 7456 0.64 161 650 4.86 692 5.36 713 5.61 733 5.86 771 6.36 808 6.86 844 7.36
16800 7928 0.73 183 687 5.79 727 6.32 746 6.59 765 6.85 802 7.38 838 7.91 872 8.44

Table 8
Notes:
1. Areas shaded in blue indicate factory setting of RPM.
2. Areas shaded in grey indicate operating range outside the standard motor. Shift to larger motor size in this area.
3. Internal static pressure is based on pressure drops through evaporator coil, fan casing and 1” flat filter.
4. The shown RPM range is with standard pulleys combination.

S.K.M Air Conditioning LLC


13
SKM Packaged Air Conditioners APMRG1 Series

ELECTRICAL DATA
Power Supply: 380~415V/3PH/50Hz

Model Unit Characteristic Compressor Condenser Fan Motor Evaporator Fan Motor
APMR
MFA MCA ICF QTY RLA LRA QTY FLA LRA FLA LRA

51055G1 32 17 79 1 11 74 1 1.2 3.6 1.2 7.4

51070G1 40 20 105 1 14 100 1 1.2 3.6 1.2 7.4

51080G1 40 21 106 1 14 101 1 1.2 3.6 1.7 10.2

51090G1 40 24 101 1 16 95 1 1.2 3.6 2.4 16.2

51100G1 50 28 117 1 19 111 1 1.2 3.6 2.4 16.2

51120G1 50 30 125 1 20 118 1 1.2 3.6 3.3 25.0

52130G1 50 33 94 2 12 74 2 1.2 3.6 3.3 25.0

52150G1 63 38 122 2 14 100 2 1.2 3.6 3.3 25.0

52170G1 63 39 124 2 14 101 2 1.2 3.6 4.5 32.4

52180G1 63 43 120 2 16 95 2 1.2 3.6 4.5 32.4

52210G1 80 50 139 2 19 111 2 1.2 3.6 4.5 32.4

52240G1 80 52 147 2 20 118 2 1.2 3.6 4.5 32.4

52270G1 80 58 151 2 21 118 3 1.2 3.6 6.2 44.6

52300G1 100 67 177 2 25 140 3 1.2 3.6 6.2 44.6

52340G1 125 77 217 2 29 174 3 1.2 3.6 8.2 57.9

52380G1 125 84 273 1+1 34 + 29 229 + 174 4 1.2 3.6 8.2 57.9

52420G1 160 98 291 2 34 229 3 3.3 11.0 10.8 92.9

52500G1 160 107 382 1+1 42 + 34 320 + 229 3 3.3 11.0 10.8 92.9

52550G1 200 122 397 2 42 320 4 3.3 11.0 14.3 114.4

Table 9

Legend
MFA Maximum Fuse Amps (for fuse/circuit breaker sizing), RLA Rated Load Amps. (at worst operating condition)
complies with NEC Article 440-22 & 430-52. LRA Locked Rotor Amps
FLA Full Load Amps
MCA Minimum Circuit Amps.(for wire sizing), complies with NEC
article 440-33.
ICF Maximum Instantaneous Current Flow

Note : Voltage imbalance not to exceed ± 2 % of the rated voltage.

14
Field Connections
R 22
REFRIGERANT
APMRG1 series self-contained heavy duty air cooled packaged units are designed for minimum field interaction. Power hook ups and
control wiring of room thermostat as per field wiring diagrm is all that is required to electrically connect any model of APMRG1 series.
Every APMRG1 series packaged air conditioning unit requires, at most,field installed fused disconnect switches or circuit breakers
and room thermostat.

Refer below for schematic representation of required field electrical hook-ups for a standard APMRG1 series packaged air conditioning
unit. All field wiring must be done in accordance with applicable local & national codes.

For the maximum fuse ampere for fuse sizing & minimum circuit amps for cable sizing, see page 14.

The APMRG1 series is then ready to provide cooling, on demand.

Field
Field Wiring Wiring Requirement
Requirement Schematic Schematic

L1 L2 L3 N

CIRCUIT BREAKER
OR FUSED
DISCONNECT SWITCH
(NOT BY SKM)

3 PHASE,
4WIRE SYSTEM
380-415V/3PH/50HZ

L1
L2
L3
N

GROUND

E
CONTROL TERMINAL
BLOCK

LINE VOLTAGE
FIELDWIRING (BY OTHERS)
APMR-G1 SERIES
COOLING STAGE-1 ON / OFF
COOLING STAGE-2 ON / OFF
EVAPORATOR FAN ON / OFF

CONTROL PANEL LOW VOLTAGE


FIELDWIRING (BY OTHERS)
24V AC

REFER ACTUAL WIRING DIAGRAM


FURNISHED WITH THE UNIT FOR
EXACT IDENTIFICATION OF WIRE NUMBERS.

TYPICAL ROOM THERMOSTAT ( BY OTHERS )


( 1 STAGE OR 2 STAGE - COOLING OR COOLING & HEATING )

S.K.M Air Conditioning LLC


15
16
LEGEND
_____ FIELD CONNECTIONS & FIELD
SUPPLIED DEVICES
FDS FUSED DISCONNECT SWITCH
LPS LOW PRESSURE SWITCH
HPS HIGH PRESSURE SWITCH
FDS ( BY OTHERS )
-XM POWER SUPPLY (V/Ph/hZ) CS CONTROL SWITCH
1 2 R
L1 CCH CRANK CASE HEATER
3 4 S
L2 F MINIATURE CIRCUIT BREAKER
5 6 T
L3
SS
N
EFM EVAPORATOR FAN MOTOR
N
OLR OVER LOAD PROTECTOR
E
L2 L3
PE 1 3 5 CFM CONDENSER FAN MOTOR
L1
L1 L2 L3 L1 L2 L3 -K5 T1

-K1 -K2 /1.7 2 4 6


T2 T3 CM COMPRESSOR MOTOR
/1.6 T1 T2 T3 /1.6 T1 T2 T3 1 3 5 1 3 5
L1 L2 L3
Typical Wiring Diagram

-K3 -K4 1 3 5
/1.8 2 4 6 /1.8 2 4 6 -OLR1
K CONTACTOR
/1.6 2 4 6
T1 T2 T3
XM POWER TERMINAL BLOCK
X2 CONTROL TERMINALS BLOCK
SV SOLENOID VALVE
TRF TRANSFORMER
2 TK THERMAL OVERLOAD PROTECTION
-F1

L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
1

M M M M M
3~ 3~ 3~ 3~ 3~
NO NC NO NC
NO NC NO NC NO NC
/1.3 /1.4
/1.1 /1.2 /1.2 /1.2 /1.5 /1.3 /1.4
/1.2 /1.2 /1.5 /1.3 /1.4
/1.2 /1.3 /1.5
/1.2 /1.3
-CM1 -CM2 -CFM1 -CFM2 -EFM

A2 A2
A2 A2 A2
SKM Packaged Air Conditioners

A1 A1
A1 A1 A1 -K3 -K4
-K1 -K2 -K5 CFM1 CFM2
CM1 CM2 EFM

A2 A2
P P
A1 A1
-FCS1 -FCS2
NO NO
SEC1

CM1
CM2
P1
P2
IN-FAN
HTR1
HTR2
X1
X2
O-FAN1
O-FAN2

-SATURN1
-DOs
ID

P-COM1
OD

-X2 -TFR
TB
1N
BLK
BLK
WHITE
WHITE

RLY1
RLY2
RLY3
RLY4
RLY5
RLY6
RLY7
RLY8
RLY9
RLY10
RLY11

ECB
SEC1

10V 24V

S1 DIP SWITCH
TFR

x1 x1 SEQ. CONTROL
4
3
2
1

220~
PRI1

ON OFF 240VAC
RED
RED

1 TEST MODE NORMAL MODE


ON

CCH1
x2 x2 T5A L250V

-CCH2
2 COMP.1 LEAD BALANCE MODE
OFF 1 2 3 4 3 PDS ENBL PDS DISBL

S1 4 SINGLE STAGE DUAL STAGE


3 3
F1

-K1 -K2
/1.6 4 /1.6 4
APMRG1 Series

POWER DIs THERMOS


N1
ON/OFF ON/OFF HP1 HP1 HP2 HP2 LP1 LP1 LP2 LP2
R C G Y1 Y2 W1 W2
L1

4 11 A 11 A NO NO
P P P P
3 -S1 12 12
NO -HPS1 -HPS2 -LPS1 -LPS2
ON/OFF
95
X2
-OLR1
96
/1.5
Dimensional Data R 22
REFRIGERANT
APMR Model - 51055G1 APMR 51055G1

03 LEGEND

01 CONTROL PANEL
APMR 51055G1 02 COMPRESSOR
03 CONDENSER FAN
04 04 CONDENSER COIL
03 05 EVAPORATOR
LEGEND COIL
06 EVAPORATOR FAN
01 CONTROL PANEL
07 EVAPORATOR FAN MOTOR
02 COMPRESSOR
08 1" THICK FLAT FILTER
03 CONDENSER FAN
04 04 CONDENSER
ALL DIMENSIONS ARE INCOIL
INCHES[mm]
F A1-A4 05
AREEVAPORATOR
LOADING POINTSCOIL
DRAIN 06 EVAPORATOR
F=4.7 [120] FOR 1" FLAT FAN
FILTER(STANDARD)
2 x FPT 3/4 [19] F=5.7 [145]
07 EVAPORATOR FAN MOTOR
FOR 2"FLAT FILTER(OPTIONAL)
08 1" THICK45 FLAT FILTER
[1143]
50.8 ALL DIMENSIONS ARE IN INCHES[mm]
[1291] 38
F A1-A4 ARE LOADING POINTS
19.7 1 [965]
DRAIN F=4.7 [120] FOR 1" FLAT FILTER(STANDARD)
[500] [25] 13.03
2 x FPT 3/4 [19] F=5.7 [145] FOR 2"FLAT FILTER(OPTIONAL)

[20]
AIR OUT

1
07 06 [331]
45
[1143]
50.8

7.5 11.38
[190] [289]
01 [1291] 38
19.7 S/A 1 [965]
[500] [25] 13.03

[20]
AIR IN AIR OUT

1
[1069]

[331]
[1186]

07
[1131]
06
42.1
46.7

44.5

R/A
[559]
7.5 11.38
[190] [289]
02 01
22

S/A

AIR IN
[1069]
2.4 [1186]

2.9[1131]
42.1
46.7

44.5

05 08
[62]

[73]

R/A
[559]

02
22

POWER SOURCE ACCESS PANEL


HOLES Ø 1 [25] FOR COMPRESSOR
ACCESS PANEL
CONTROL CIRCUIT ON BOTH SIDES
HOLES Ø 0.75 [19]

05 08
[62]

[73]
2.9
2.4

APMR 51070G1
POWER SOURCE ACCESS PANEL
HOLES Ø 1 [25] FORAPMR
COMPRESSOR
03 51055G1 ACCESS PANEL
CONTROL CIRCUIT
APMR Model - 51070G1
HOLES Ø 0.75 [19]
ON BOTH SIDES

03 LEGEND
APMR 51070G1 01 CONTROL PANEL
04
03 02 COMPRESSOR
03 CONDENSER FAN
04 04 CONDENSER COIL
05 EVAPORATOR COIL
06 EVAPORATOR FAN
04 07 EVAPORATOR FAN MOTOR
08 1" THICK FLAT FILTER
F 45
DRAIN ALL DIMENSIONS ARE IN INCHES[mm]
2 x FPT 3/4 [19] [1143]
F A1-A4 ARE LOADING 38 POINTS
54.8 F=4.7 [120] FOR [965]
1" FLAT FILTER(STANDARD)
DRAIN
[1391]
2 x FPT 3/4 [19]1
23.6 F=5.7 [145] FOR 2"FLAT FILTER(OPTIONAL)
15.55
[600] [25] 45
[20]

AIR OUT F [395]


1

07 06 [1143] 45
50.8 DRAIN
2 x FPT 3/4 [19] [1143]
38
[1291]
01 54.8 19.7 1 [965]38
13.43
[341]

[1391] [500] [25] 13.03[965]


S/A
1 [20]

AIR OUT 23.6 1


7.5 11.38[291] 1

07 06 15.55
[331]
[600] [25]
[20]

AIR OUT [395]


11.4

07 06
[1222]
[1339]

[1284]
48.1
52.7

AIR IN
13.43[289]
50.5

01
S/A
01
[341]

R/A
[559]11.4 [190]

S/A
[559]

02 AIR IN
22
[1069]
48.1 [1186]

50.5 [1131]
42.1
46.7

44.5

[291]
[1222]
[1339]

R/A
2.9 [1284]
52.7

AIR IN 02
22

05 08 R/A
[62]

[73]
2.4

[559]

02 ACCESS PANEL
22

POWER SOURCE ACCESS PANEL ON BOTH SIDES


HOLES Ø 1 [25] FOR COMPRESSOR
CONTROL CIRCUIT 05 08
[62]

[73]
2.9
2.4

HOLES Ø 0.75 [19]


POWER SOURCE ACCESS PANEL
HOLES Ø 1 [25] FOR COMPRESSOR 05 08
[62]

[73]

ACCESS PANEL
2.9
2.4

CONTROL CIRCUIT ON PANEL


ACCESS BOTH SIDES
HOLES
POWER Ø 0.75 [19]ACCESS PANEL
SOURCE ON BOTH SIDES
HOLES Ø 1 [25] FOR COMPRESSOR
CONTROL CIRCUIT
HOLES Ø 0.75
APMR [19]
51070G1

03

04
S.K.M Air Conditioning LLC
17
SKM Packaged Air Conditioners APMRG1 Series

Dimensional Data
APMR Models - 51080G1 to 51120G1 APMR 51080G1 - 51120G1

03
APMR 51080G1 - 51120G1
DIMENSIONS
Model
03 APMR
L W A B C D J G H

60.2 47 40 32 11.3 23.6 13.43 15.55 60.4


04 51080G1
[1530] [1194] [1016] [813] [288] [600] [341] [395] [1535]

51090G1
63 47 40 32 8.9 26.4 15.91 18.54 60.5

Table 10
04 [1600] [1194] [1016] [813] [225] [670] [404] [471] [1536]
51100G1

63 55 48 32 8.9 26.4 15.91 18.54 60.5


51120G1
[1600] [1397] [1219] [813] [225] [670] [404] [471] [1536]
F
DRAIN
ALL DIMENSIONS ARE IN INCHES[MM]
2 x FPT 3/4 [19]
W
L 1
[25] F A
DRAIN
36.6 D 3/4 [19]
2 x FPT
[930] G
W

[20]
L 1

1
06
AIR OUT [25] A
36.6 D
[930] G

[20]
1J
06 S/A
01 AIR OUT

C
J
S/A
[1525]
60

H
[1222]
48.1

AIR 01
IN
B C

R/A
[1525]

02
60

H
[1222]
48.1

AIR IN

R/A
B

02
07 05 08
[62]

[73]
2.4

2.9

POWER SOURCE ACCESS PANEL


HOLES Ø 1 [25] FOR COMPRESSOR ACCESS PANEL
CONTROL CIRCUIT ON BOTH SIDES
HOLES Ø 0.75 [19] 07 05 08
[62]

[73]
2.4

2.9

POWER SOURCE ACCESS PANEL


HOLES Ø 1 [25] FOR COMPRESSOR ACCESS PANEL
CONTROL CIRCUIT ON BOTH SIDES
HOLES Ø 0.75 [19]
APMR 52130G1 & 52150G1

APMR Models - 52130G1 &4-Ø0.79


52150G1
10 10

[20] HOLES [254] [254] LEGEND


FOR ANCHOR BOLTS
APMR 52130G1 & 52150G1
A1 A3 01 CONTROL PANEL
04
10 10 02 COMPRESSOR
[254] [254] LEGEND
4-Ø0.79 [20] HOLES 03 CONDENSER FAN
FOR ANCHOR BOLTS
A1 A3 04 CONTROL PANEL
01 CONDENSER COIL
04 05 COMPRESSORCOIL
02 EVAPORATOR
03 EVAPORATOR
06 CONDENSER FAN FAN
01
POWER
SOURCE
CONTROL
CIRCUIT 04 EVAPORATOR
07 CONDENSER COILFAN MOTOR
DETAIL AT `A' 08 EVAPORATOR
05 1" COIL
THICK FLAT FILTER
01 09 EVAPORATORPOCKET
06 FORKLIFTING FAN
POWER CONTROL
SOURCE CIRCUIT 07 EVAPORATOR FAN MOTOR
03 ALL DIMENSIONS ARE IN INCHES
DETAIL AT `A' 08 1" THICK FLAT FILTER
A1-A4 ARE LOADING
09 FORKLIFTING POINTS [mm]
POCKET
F=4.7 [120] FOR 1" FLAT FILTER(STANDARD)
03 ALL DIMENSIONS ARE IN FILTER(OPTIONAL)
[145] FOR 2"FLAT INCHES
F=5.7
A2 A4 F
A1-A4 ARE LOADING
75
POINTS [mm]
DRAIN F=4.7 [120] FOR 1" FLAT FILTER(STANDARD)
[1905]
2 x FPT 1 [25]
F=5.7 [145]60FOR 2"FLAT FILTER(OPTIONAL)
A2 A4 F
75 1 [1524]
75
[1905] DRAIN [25]
28 2 x FPT 1 [25] [1905]
43.7
[711] [1109]
[38]
1.5

60
07 06
75 1 [1524]
[1905] [25]
28 43.7
13.43
[341]
[183]

[711] [1109]
7.2

[38]

S/A
1.5

07 06

08
13.43
[341]
[183]
7.2
[1567]

S/A
61.71

[1515]
59.6
[1227]

AIR IN
48.3

R/A
[813]

08
32
[1567]
61.71

[126]

[1515]
59.6
[1227]

AAIR IN
5
48.3

R/A
[813]
32
[126]

A
5

02 09 05
[140]

[100]
3.94
5.5

RIGGING HOLES
Ø0.79 [20] x 4Nos. ACCESS PANEL
ON BOTH SIDES
02 09 05
[140]

[100]
3.94
5.5

RIGGING HOLES
Ø0.79 [20] x 4Nos. ACCESS PANEL
ON BOTH SIDES

18
Dimensional Data R 22
REFRIGERANT
APMR Models - 52170G1 to 52240G1
APMR 52170G1, 52180G1, 52210G1 & 52240G1

LEGEND
10 ALL DIMENSIONS ARE IN INCHES[mm]
10 4-Ø0.79 [20] HOLES 01 CONTROL PANEL
[254] A1 FOR ANCHOR BOLTS [254] A1-A4 ARE LOADING POINTS
A3 02 COMPRESSOR
F=4.7 [120] FOR 1" FLAT FILTER(STANDARD)
03 CONDENSER FAN
04
APMR 52170G1, 52180G1, 52210G1 & 52240G1 F=5.7 [145] FOR 2"FLAT FILTER(OPTIONAL)
04 CONDENSER COIL
MODEL 52240G1 EVAPORATOR COIL INCLINED TYPE ARRANGEMENTS
LEGEND COIL
05 EVAPORATOR
ALL DIMENSIONS ARE IN INCHES[mm]
10 4-Ø0.79 [20] HOLES 0610EVAPORATOR
01 CONTROL
FAN PANEL
[254] A1 FOR ANCHOR BOLTS A3 [254] A1-A4 ARE LOADING POINTS
07 02 COMPRESSOR
EVAPORATOR FAN MOTOR
F=4.7 [120] FOR 1" FLAT FILTER(STANDARD)
08 1" THICK CONDENSER
03 FLAT FILTER FAN
01 04 F=5.7 [145] FOR 2"FLAT
POWER
SOURCE CIRCUIT FILTER(OPTIONAL)
CONTROL

04 CONDENSER
09 FORKLIFTING POCKETSCOIL DETAIL AT `A'
MODEL 52240G1 EVAPORATOR COIL INCLINED TYPE ARRANGEMENTS
05 EVAPORATOR COIL
06 EVAPORATOR FAN DIMENSIONS
Model
07 EVAPORATOR FAN MOTOR
03
APMR
08 1" THICK FLAT FILTER L
01
A B
POWER
SOURCE
C
CONTROL
CIRCUIT
D H
09 FORKLIFTING POCKETS DETAIL AT `A'
91 70 32 7.2 28 59.6

Table 11
52170G1 / 52180G1 /
52210G1 [2311] [1778] [813] [182] [711] [1515]
A2 A4 F 95 78 35.6 9.3 32 65.47
DRAIN 52240G1
03 2 x FPT 1 [25] [2413] [1981] [904] [236] [813] [1663]
ALL DIMENSIONS ARE IN INCHES[MM]
88
L [2235]
A263 A4 F A
D 1
DRAIN
[1600] [25]
2 x FPT 1 [25] = 43.7 =

[38]
AIR OUT 1.5 [1109]
06
07 88
L [2235]
C

[344]
13.5

S/A
63 D 1 A
[1600] [25] [38]
= 43.7 =
1.5

AIR OUT 08 [1109]


[1567]
61.71

06
[1227]

AIR IN
48.3

H
07
R/A
C

[344]
13.5
B

S/A
[126]
5

08
[1567]
[100] 61.71

[1227]

AIR IN
48.3

H
02 09 05 R/A
[140]
5.5

ACCESS PANEL
3.94

RIGGING HOLES
ON BOTH SIDES
[126]

Ø0.79 [20] x 4Nos.


5

02 09 05
[140]
[100]

5.5

ACCESS PANEL
3.94

RIGGING HOLES
Ø0.79 [20] x 4Nos. ON BOTH SIDES
APMR 52270G1, 52300G1 & 52340G1

APMR Models - 52270G1 to 52340G1


10
4-Ø0.79 [20] HOLES
10
[254] FOR ANCHOR
APMR BOLTS & 52340G1
52270G1, 52300G1
[254]
A1 A3

01 10 10
[254]
4-Ø0.79 [20] HOLES [254]
FOR ANCHOR BOLTS
A1 A3
DIMENSIONS
Model APMR
01
L M D B C H

CABLE ENTRY 105.6 73 32.6 40 9.7 72.65


52270G1 / 52300G1
Table 12
[2682] [1854] [828] [1016] [247] [1845]
116 81 35 42.5 10.66 76.1
52340G1
MODEL 52340G1 EVAPORATOR COIL INCLINED TYPE ARRANGEMENTS
[2946] [2057] [889] [1080] [271] [1933]

CABLE ENTRY 88 ALL DIMENSIONS ARE IN INCHES[MM]


A2 A4 F [2235]

DRAIN 78
2 x FPT 1 [25] MODEL 52340G1 EVAPORATOR COIL INCLINED TYPE ARRANGEMENTS
[1981]
L

M D 1 = 52.3 88 =
A2 A4
[25] F [1328] [2235]
03 07 06
[38]
1.5

DRAIN 78
2 x FPT 1 [25] [1981]
L
15.91
[404]

M DS/A 1 = 52.3 =
[25] [1328]
03 07 06
[38]
1.5
C

08
[1940]
76.4

[1600]

H
63

15.91
[404]

S/A
R/A
B

C
[126]
5

A 08
[1940]

05
76.4

[1600]

H
63

02 09 04 R/A
B
[100]

[140]
3.94

5.5

RIGGING HOLES ACCESS PANEL


Ø0.79 [20] x 4Nos.
[126]

ON BOTH SIDES
5

A
05

02 09 04
[100]

[140]
3.94

5.5

RIGGING HOLES ACCESS PANEL


Ø0.79 [20] x 4Nos. ON BOTH SIDES

S.K.M Air Conditioning LLC


19
SKM Packaged Air Conditioners
MODEL :- APMR-52380G1 APMRG1 Series
10 10
4-Ø0.79 [20] HOLES
[254] FOR ANCHOR BOLTS [254]
A1 A3 LEGEND
01 CONTROL PANEL

Dimensional
01 Data 02 COMPRESSOR
03 CONDENSER FAN

APMR Model - 52380G1


MODEL :- APMR-52380G1
04 CONDENSER COIL
05 EVAPORATOR COIL
06 EVAPORATOR FAN
10
4-Ø0.79 [20] HOLES
10
POWER CONTROL 07 EVAPORATOR FAN MOTOR
CIRCUIT
[254] [254]
SOURCE
A1
FOR ANCHOR BOLTS
A3 DETAIL AT `A' 08 1" THICK FLAT FILTER
LEGEND
CABLE ENTRY
0109 FORKLIFTING
CONTROL PANEL POCKETS
02 COMPRESSOR
01 ALL03DIMENSIONS
CONDENSER FAN ARE IN INCHES[mm]
04 CONDENSER
F=4.72 [120] FORCOIL
1" FLAT FILTER(STANDARD)
05 EVAPORATOR COIL
F=5.7 [145] FOR 2"FLAT FILTER(OPTIONAL)
06 EVAPORATOR FAN
POWER CONTROL 07 EVAPORATOR FAN MOTOR 88
CIRCUIT
08 1" THICK FLAT FILTER[2235]
SOURCE

A2
CABLE ENTRY A4 DETAIL AT `A'
F 09 FORKLIFTING POCKETS
DRAIN 78
2 x FPT 1 [25] [1981]
ALL DIMENSIONS ARE IN INCHES[mm]
130 F=4.72 [120] FOR 1" FLAT FILTER(STANDARD)
[3302] = 61.89 =
87 43 1 F=5.7 [145] FOR 2"FLAT FILTER(OPTIONAL)

[38]
1.5
[2210] [1092] [25] 88 [1572]
06 [2235]
A2 A4
03 07 F
DRAIN 78
2 x FPT 1 [25]

18.82 10.63 1.518.82


[1981]

[478] [270][38][478]
130
[3302]
S/A = 61.89 =
87 43 1
[1572]
[2210] 06 [1092] [25]
03 07

S/A
08

[2208]
86.9
[1965]

[1257][270]
49.5 10.63
77.4

[1600]
63

08
R/A

[2208]
86.9
[1965]
77.4

[1600]
63

[1257]
49.5

A R/A

RIGGING HOLES 02 09
05
[125]

[165]
4.9

6.5 6.5

Ø0.79 [20] x 4Nos. RIGGING HOLES


04 ACCESS
02 09 PANEL
05
Ø0.79 [20] x 4Nos. ON BOTH SIDES
[125]

[165]
4.9

04 ACCESS PANEL
ON BOTH SIDES

MODEL :- APMR-52420G1
MODEL :- APMR-52420G1 & 52500G1
APMR Models - 52420G1
10 10
10 [254] A3 [254] 10
A1
LEGEND [254] [254]
A1 A3
01 CONTROL PANEL
02 COMPRESSOR ACCESS
03 CONDENSER FAN
04 CONDENSER COIL
05 EVAPORATOR COIL CONTROL
POWER
06 EVAPORATOR FAN SOURCE CIRCUIT
DETAIL AT `A'
POWER
SOURCE
CONTROL
CIRCUIT
DETAIL AT `A'
07 EVAPORATOR FAN MOTOR
08 1" THICK FLAT FILTER
09 FORKLIFTING POCKETS

ALL DIMENSIONS ARE IN INCHES[mm]


88 A2 A4
F=4.72 [120] FOR 1" FLAT FILTER(STANDARD)
[2235] DRAIN Ø1 1/4 [32] x2Nos.
F 130
F=5.7 [145] FOR 2"FLAT FILTER(OPTIONAL)
A [3302]

61.89 1 43 87
88
[38]
1.5

[1572] [25]A2 [1092] [2210]


[2235] A4
DRAIN Ø1 1/4 [32] x2Nos. 03
F 130
78
18.82
[478]

[3302]
[1981]
01
61.89 1 43 87
[38]

[25] [1092] [2210]


1.5

[1572]
06 07
03
C
18.82
[478]
H

H1

S/A 01
B
10.63
[270]

08
[2208]

[2110]
86.9

83.1

08
05 06 07 04 02
[1257]

9 RIGGING HOLES
[125]
49.5
4.92

ACCESS PANEL Ø.79 [20] 4 Nos.


R/A BOTH SIDES

08 05 RIGGING HOLES
09 04 02 Ø.79[20] 4 Nos.
[125]

[165]
4.9

6.5

ACCESS PANEL
BOTH SIDES

20
Dimensional Data R 22
MODEL:- APMR-52500G1 REFRIGERANT
APMR Model - 52500G1
10 10
LEGEND [254] A3 [254]
A1
01 CONTROL PANEL
02 COMPRESSOR ACCESS
03 CONDENSER FAN
04 CONDENSER COIL
05 EVAPORATOR COIL
POWER CONTROL
CIRCUIT
06 EVAPORATOR FAN SOURCE
DETAIL AT `A'
07 EVAPORATOR FAN MOTOR
08 1" THICK FLAT FILTER
09 FORKLIFTING POCKETS

ALL DIMENSIONS ARE IN INCHES [mm]


F=4.72[120] FOR 1" FLAT FILTER(STANDARD)
F=5.7[145] FOR 2"FLAT FILTER(OPTIONAL)

A2 A4
88 F DRAIN Ø1 1/4 [32] x2Nos. 130
[2235] [3302]

75
[1905]
61.9 1 43 87
[38]
1.5
[1572] [25] [1092] [2210]

03
[478]
18.8

01
[102]
4
103.24
[2622]

[2313]
91.1
[1839]
72
[125]
4.92

08
05 04
[50]

06 07 09 02 RIGGING HOLES
2

ACCESS PANEL Ø.79 [20] 4 Nos.


BOTH SIDES
MODEL:- APMR-52550G1

APMR Model - 52550G1 10


[254]
10
[254]

A1 A3 A5

LEGEND
1 CONTROL PANEL
2 COMPRESSOR
3 CONDENSER FAN
4 CONDENSER COIL
5 EVAPORATOR COIL
6 EVAPORATOR FAN
7 EVAPORATOR FAN MOTOR
8 1" THICK FLAT FILTER

ALL DIMENSIONS ARE IN INCHES [MM]


F=4.72 [120] FOR 1" FLAT FILTER(STANDARD)
A2 A4 A6
F=5.7 [145] FOR 2"FLAT FILTER(OPTIONAL)
F DRAIN Ø1 1/4 [32] x2Nos.
88
[2235]
137.5
75
[3493]
[1905]
1 43 94.5
61.9
[25] [1092] [2401]
[1572] 3
[38]
1.5

4
[478]
18.8

1
[144]
5.7

[2923]
115.1
[2540]
[2640]

100
104

[1829]
72

DETACHABLE
PLATE FOR
CABLE ENTRY

8
5
[50]

6 7 2 RIGGING HOLES
[100]

2
3.94

Ø 7/8 [22] 4 Nos. STEEL WIRE


ACCESS PANEL
BOTH SIDES

S.K.M Air Conditioning LLC


21
SKM Packaged Air Conditioners APMRG1 Series

Loading Points
MODEL LOAD AT EACH POINT Lbs (Kgs) TOTAL
APMR A1 A2 A3 A4 A5 A6 WEIGHT
174 200 129 142 645
51055G1 - -
[79] [91] [59] [64] [293]
181 207 134 147 669
51070G1 - -
[82] [94] [61] [67] [304]
220 252 163 179 814
51080G1 - -
[100] [114] [74] [81] [369]
241 277 179 197 894
51090G1 - -
[109] [126] [81] [89] [405]
247 283 183 201 914
51100G1 - -
[112] [128] [83] [91] [414]
281 322 208 229 1040
51120G1 - -
[127] [146] [94] [104] [471]
363 363 448 448 1622
52130G1 - -
[165] [165] [203] [203] [736]
363 363 448 448 1622
52150G1 - -
[165] [165] [203] [203] [736]
421 421 557 557 1956
52170G1 - -
[191] [191] [253] [253] [887]
451 451 565 565 2032
52180G1 - -
[205] [205] [256] [256] [922]
484 484 561 561 2090
52210G1 - -
[220] [220] [254] [254] [948]
537 537 615 599 2288
52240G1 - -
[244] [244] [279] [272] [1038]
484 473 913 854 2724
52270G1 - -
[220] [215] [414] [387] [1235]
490 478 915 856 2739
52300G1 - -
[222] [217] [415] [388] [1242]
598 580 824 774 2776
52340G1 - -
[271] [263] [374] [351] [1259]
814 723 967 887 3391
52380G1 - -
[369] [328] [439] [402] [1538]
940 977 822 864 3603
52420G1 - -
[426] [443] [373] [392] [1634]
1018 1073 840 904 3835
52500G1 - -
[462] [487] [381] [410] [1739]
550 580 1261 1171 594 701 4857
52550G1
[249] [263] [572] [531] [269] [318] [2203]
Table 13

22
Recommended Clearances R 22
MODEL REFRIGERANT
A B C
APMR-
46 76
51055G1
[1168] 42 [1930]
SPACING FOR AIR FLOW
[1067]
51070G1
SPACING FOR AIR FLOW
51080G1 / 51090G1 / 44
51100G1 [1118]
SPACING FOR AIR FLOW
52 SPACING FOR SERVICE
51120G1
52 [1321] 88
[1321] 64 [2235]
52130G1 / 52150G1 SPACING FOR SERVICE
[1626]
52170G1 / 52180G1 / 74 SPACING FOR SERVICE

Table 14
52210G1 [1880]
82
52240G1
[2083] C
ALL DIMENSIONS ARE IN INCHES [MM]
B
A C 30
[762] DUCT
A C B
A 30
A B
A [762] DUCT
30
A
A [762] DUCT
A
A
A
DUCT 30
DUCT B A
B 30 [762]
[762] DUCT 30 A
DUCT B
B
APMR- 51055G130 DUCT APMR-
[762]
30 C
51055G1
DUCT [762]
30
B
[762]
B
[762] B
A C 30
[762] DUCT
A C B
A 30
A B
A [762] DUCT
30
A
A [762] DUCT
A
A
A
DUCT 30
DUCT B A
B 30 [762]
[762] DUCT 30 A
DUCT B
B 30 DUCT [762]
30
DUCT [762]
30
B
[762]
A B A C
APMR- 51070G1 - 51120G1
[762] APMR- 51070G1 - 51120G1
A A C

A A C
A A
[762]

[762]
30

30

A A
[762]

[762]
30

30

A A
[762]

[762]
30

30

DUCT 30
B
DUCT DUCT
B [762] 30
DUCT 30 DUCT DUCT [762]
B
B [762] 30
DUCT 30
B
DUCT DUCT
B [762]
[762] 30
[762]
APMR- 52130G1 - 52240G1 APMR- 52130G1 - 52240G1

SINGLE UNIT MULTIPLE UNIT

S.K.M Air Conditioning LLC


23
SKM Packaged Air Conditioners APMRG1 Series

Recommended Clearances

A B C
MODEL APMR-
68 120
52270G1 / 52300G1
[1727] [3048]
76 82 136
52340G1
[1930] [2083] [3454]
SPACING FOR SERVICE SPACING FOR AIR FLOW
52380G1 / 52420G1

Table 15
82 148
[2083] 79 [3759]
52500G1
[2007]

ALL DIMENSIONS ARE IN INCHES [MM]

A A A C A
[762]

[762]
30

30

DUCT 30 DUCT DUCT


B
B [762] 30
APMR- 52270G1 - 52340G1 [762]
APMR- 52270G1 - 52340G1

A A A C A
[762]

[762]
30

30

DUCT 30 DUCT DUCT


B
B [762] 30
APMR- 52380G1 APMR- 52380G1 [762]

A A A C A
[762]

[762]
30

30

DUCT 30 DUCT DUCT


B
B [762] 30
[762]
APMR- 52420G1 & 52500G1 APMR- 52420G1 & 52500G1

SINGLE UNIT MULTIPLE UNIT

24
Recommended Clearances R 22
REFRIGERANT

[1168]
46

SPACING FOR SERVICE

SPACING FOR AIR FLOW

84*
DUCT 84*
[2134] [2134]

SINGLE UNIT
[1168]
46

84*
DUCT DUCT
90 84*
[2134] [2286] [2134]

* SPACING FOR BOTH AIR FLOW & SERVICE


MULTIPLE UNIT

APMR- 52550G1

S.K.M Air Conditioning LLC


25
SKM Packaged Air Conditioners APMRG1 Series

Installation and Commissioning


• Install the unit in such a location which is flat and strong enough to support its weight.
• Provide a trap of over 2" (50mm) in the drain piping for water seal.
• All field wiring must comply with applicable local and national codes.

INSTALLATION & COMMISSIONING
Service spacing should be provided as shown in the figure. If any obstacles are around the unit, distributed air is short-circuited
so that the unit stops frequently and access to the unit is difficult for inspection and aftersales services.

No obstacle

CONTROL
SPACING FOR AIRFLOW
PANEL BOX

3000
POWER AIR OUT
SOURCE SPACING FOR SERVICE
CONTROL
CIRCUIT AIR IN

S.AIR
AIR IN
No obstacle

R.AIR

3000
AIR OUT
CONTROL CONTROL
AIR IN
AIR IN PANEL BOX CIRCUIT
AIR OUT

POWER
SOURCE
APMR- 51055G1 - 51120G1
APMR-51055G1 - 51120G1
AIR IN

S.AIR

S.AIR

R.AIR

No obstacle CONTROL CONTROL


AIR IN
PANEL BOX CIRCUIT
AIR OUT
3000

AIR OUT
AIR OUT
POWER
SOURCE
AIR IN

APMR- 52130G1 - 52240G1


AIR IN

APMR-52130G1 - 52240G1

S.AIR

S.AIR

R.AIR

AIR OUT

AIR IN
CONTROL
No obstacle PANEL BOX
3000

AIR OUT
AIR IN

APMR-APMR-52270G1
52270G1 - 52500G1
- 52500G1
AIR OUT

AIR OUT

S.AIR

S.AIR

R.AIR

APMR- 52550G1
APMR-52550G1

26
GUIDE SPECIFICATIONS R 22
REFRIGERANT

GENERAL
Packaged Air Conditioners shall be composed of REFRIGERANT PIPING
compressor(s), condenser & evaporator coils with fans, refrigerant The refrigerant circuit piping shall be fabricated from ACR grade
piping, electrical components & enclosing cabinet in one piece. copper piping, with 1 & 2 refrigeration circuits, each liquid line
These units shall be factory assembled, internally wired, fully shall include filter drier and thermostatic expansion valve.
refrigerant charged with R410A, tested under strict quality
standards & are suitable for outdoor installation on rooftop or Suction line shall be insulated with ½” (12mm) wall thickness
ground level with ducted system. enclosed cell pipe insulation with maximum K factor
0.28 Btu.in /ft2 .h.°F. (0.040 W/mK).
COMPRESSOR(S)
Compressor shall be hermetic scroll, refrigerant gas cooled
furnished with internal overload protection device, crankcase
heater, and shall be mounted on rubber isolators.
CASING
Casing shall be made of hot dip galvanized (zinc coated),
phosphatized steel sheets which are then electrostatically
polyester powder coated to provide an extremely tough, scratch
resistance & excellent anti-corrosive protection. Casing shall
CONDENSER COIL(S)
pass1000 hours in 5% salt spray testing at 95°F (35°C) & 95%
Condenser coils shall be air cooled with integral sub cooler,
relative humidity as per ASTM B117. Evaporator section shall
constructed of special inner grooved seamless copper tubes
be sealed with vinyl gaskets & completely insulated faced with
3/8” OD mechanically expanded into corrugated aluminum cross
black glass tissue (BGT) heavy density, fire retardant, permanent
fins with maximum 16 fpi (1.6mm) spacing. These coils shall be
odorless fiberglass insulation of minimum 1” (25 mm) thickness
tested against leakage by high air pressure air 715psig (4930kPa)
and 32 kg/m3 density having maximum k factor 0.23 Btu.in/ft2
under water, cleaned & dehydrated at the factory.
h°f. (0.033 W / m °k). Unit casing shall be provided with access
panels for easy service and maintenance of all unit parts.

CONDENSER FAN(S) & MOTOR(S)


Condenser Fans shall be direct driven propeller type discharging
air vertically upward, equipped with statically & dynamically
FILTER SECTION
Flat Filter Section incorporating 1” (25mm) thick is provided as
balanced aluminum alloy blades, inherent corrosion resistant
standard and 2” (50mm) thick filter having an average arrestance
shaft & PVC coated steel wire fan guard. Condenser fan
efficiency of 54% as per ASHRAE Standard 52.1 or equivalent
motor(s) shall be Totally Enclosed Air Over (TEAO), 6 pole with
can be provided as an option.
class-F insulation, minimum IP-54 protection & wired to unit
control panel.

CONTROL PANEL
The panel shall be factory wired and confirm to IP-54 requirements.
EVAPORATOR COIL
Control panel shall contain compressor and motor starting
Evaporator coil shall be constructed of Hi-X copper tubes 3/8”
contactors, electronic control board for unit operation, compressor
OD mechanically bonded to aluminum (copper) corrugated fins
anti-recycle time delay, control on/off switch, control circuit breaker
with maximum 14 fpi (1.8mm) spacing. Coil consists of headers of
and power & control terminal blocks. High and Low pressure
seamless copper tubing, thermostatic expansion valve(s) & multi-
switches should be provided for protection.
circuited distributor(s). These coils shall be tested against leakage
by high air pressure 450psig(3100kPa) under water, cleaned &
dehydrated at the factory. Coil shall conform to AHRI-410.

EVAPORATOR FAN & MOTOR


Fans of evaporator shall be forward curved, double inlet double
width (DIDW), centrifugal type, statically & dynamically balanced,
mounted on a single heavy duty shaft with permanently lubricated
bearings and belt driven by V belts with an adjustable variable
pitch motor pulley. Motor shall be Totally Enclosed Fan Cooled
(TEFC), 4 poles, class-F insulated, minimum IP55 protection &
wired to unit control panel.

S.K.M Air Conditioning LLC


27
SKM Packaged Air Conditioners
CONTACT
APMRG1 Series
US
HEAD OFFICE

P.O Box: 6004, Sharjah,


United Arab Emirates

Tel: +971 6 514 3333


Fax: +971 6 514 3300

Email: sales@skmaircon.com
Email: info@skmaircon.com

Spare Parts Division


spareparts.skm@skmaircon.com

Service Center
aftersales.skm@skmaircon.com

For SKM Regional Offices & Distributors


visit: www.skmaircon.com

28 224/2021
46
2
7

You might also like