Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

6FM100X 12V 100Ah(10hr)

The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid
electrolyte is absorbed by separators and plates and thus immobilized. Should the
battery be accidentally overcharged producing hydrogen and oxygen, special one-
way valves allow the gases to escape thus avoiding excessive pressure build-up.
Otherwise, the battery is completely sealed and is, therefore, maintenance-free,
leak proof and usable in any position.

Battery Construction
Component Positive plate Negative plate Container Cover Safety valve Terminal Separator Electrolyte
Raw material Lead dioxide Lead ABS ABS Rubber Copper Fiberglass Sulfuric acid

General Features Performance Characteristics


● Absorbent Glass Mat (AGM) technology Nominal Voltage 12V
for efficient gas recombination of up to Number of cell 6
99% and freedom from electrolyte
Design Life 10 years
maintenance or water adding.
o
Nominal Capacity 77 F(25 C)o
● Not restricted for air transport-complies
with IATA/ICAO Special Provision A67. 10 hour rate (10.0A, 10.8V) 100Ah
● UL-recognized component. 5 hour rate (16.6A, 10.5V) 83Ah
● Can be mounted in any orientation. 1 hour rate (61A, 9.6V) 61Ah
● Computer designed lead, calcium tin alloy Internal Resistance
grid for high power density. Fully Charged battery 77oF(25oC) 5.2mOhms
● Long service life, float or cyclic Self-Discharge
applications.
3% of capacity declined per month at 20oC(average)
● Maintenance-free operation.
Operating Temperature Range
● Low self discharge.
Discharge -20~60oC
Charge -10~60oC
Dimensions and Weight Storage -20~60oC
o o
Max. Discharge Current 77 F(25 C) 900A(5s)
Length(mm / inch) 330 / 12.99
Width(mm / inch) 171 / 6.73 Short Circuit Current 2100A
Height(mm / inch) 215 / 8.46 Charge Methods: Constant Voltage Charge 77oF(25oC)
Total Height(mm / inch) 222 / 8.74 Cycle use 2.30-2.35VPC
Approx. Weight(Kg / lbs) 29 / 63.9 Maximum charging current 30A
Temperature compensation -30mV/oC
Standby use 2.23-2.27VPC
Temperature compensation -20mV/oC

Discharge Constant Current (Amperes at 77oF25oC)


End Point
10min 15min 30min 1h 3h 5h 10h 20h
Volts/Cell
1.60V 229 185 108 16.2 27.9 19.0 10.8 5.50
1.65V 221 178 104 62.50 27.7 18.3 10.60 5.45
1.70V 200 164 96 61.50 27.2 18.0 10.5 5.40
1.75V 187 153 93 60.50 26.9 17.5 10.3 5.35
1.80V 175 143 91 57.4 25.3 17.2 10.0 5.30

Discharge Constant Power (Watts at 77oF25oC)


End Point
10min 15min 30min 45min 1h 2h 3h 5h
Volts/Cell
1.60V 392 321 199 150 124 70.6 52.80 35.80
1.65V 379 315 188 146 118 67.8 51.20 35.40
1.70V 360 299 183 137 114 66.8 50.90 35.00
1.75V 353 294 177 134 111 64.5 49.10 34.40
1.80V 329 279 171 131 109 62.5 48.50 34.0

(Note)The above characteristics data are average values obtained within


three charge/discharge cycles not the mimimum values.

page1 of 2 www.vision-batt.com
6FM100X 12V 100Ah

Charged
O
Discharge characteristic (25 C)

Current

Voltage
Volume
Constant voltage charging
o
characteristic (0.25CA,25 C)
(%) (XCA) (V)
12.0
140

120
Battery voltage(V)

0.25
15.0 CHARGED VOLUME
100 0.20
10.0A 14.0 CHARGE VOLTAGE
24.1A 16.6A 80
9.6 0.15
13.0
95A 61.0A 60
200A
0.10
40 12.0

20 0.05
0 11.0 CHARGING CURRENT
1 2 3 5 10 20 30 60 2 3 5 10 20
0 0
min h 0 2 4 6 8 10 12 14 16 18 20
Discharge time Charging time (hours)

Relationship between Self-discharge characteristic


charging voltage and temperature
110
(V/12V)

(V/CELL)
(V/6V)
(V/8V)

(V/4V)

100

90

Capacity(%)
15.6 10.4 7.8 5.2 2.6
80
15.0 10.0 7.5 5.0 2.5

70
14.4 9.6 7.2 4.8 2.4

13.8 9.2 6.9 4.6 2.3 60

13.2 8.8 6.6 4.4 2.2 50

-10 0 10 20 30 40 50 60
40
0 2 4 6 8 10 12 14 16 18 20
Ambient temperature( oC) Storage time: months

Cycle service life in relation to


Life characteristics of Standby use
120 depth of discharge
120

100
100
Capacity(%)

80
Capacity(%)

80

60 60
Testing conditions: floating voltage: 2.27 to 2.30V/Cell 30% Depth of discharge
ambient temperature: 25 oC(77 oF)
40 40

20 20

0 200 400 600 800 1000 1200 1400


0 4 6 8
Life(year) Number of cycles(cycles)

Temperature effects on float life Temperature effects on capacity


15
120

100
Life(years)

10
Capacity (%)

80

60
5

40

20

0 0
10 20 30 40 50
-20 -10 0 10 20 30 40 50( o C)
Temperature( oC)

THE INTERNATIONAL CERTIFICATION NETWORK

MH25860 G4M19906-9202-E-16
ISO9001:2000

Shenzhen Center Power Tech. Co., Ltd. www.vision-batt.com


Center Power Industrial Park, Tongfu Industrial District Dapeng Town, 518120 Shenzhen, China
Tel: (+86-755) 8431 8088 Fax: (+86-755) 8431 8038 E-mail: sales@vision-batt.com

Copy Right Shenzhen Center Power Technology Co., Ltd (Edition 2011-8)

Page 2 of 2