Design of Automatic Fire Sprinkler System
An Automatic Fire Sprinkler System is designed to contain and control an unfriendly fire
allowing your family the precious time needed to escape from danger and decrease the
amount of damage to your valuables from heat and smoke. An Automatic Fire Sprinkler
System is a network of water-filled pipes which starts at your domestic water service line and
ends with strategically spaced fire sprinkler heads located throughout your home. The
sprinkler heads are frangible bulbs filled with a liquid that, when heated, expand causing the
bulb(s) to break and the system to release water. The water from the sprinkler head will cover
the area where the fire is located and will continue to operate until the fire department can
fully extinguish the fire.
Almost all newly built commercial or industrial buildings require automatic fire sprinkler
systems for life safety, the protection of the property, the safety of the firefighters, and to
minimize business interruption. These systems are designed and installed as prescribed in the
National Fire Protection Association (NFPA) Standard for the Installation of Sprinkler
Systems or NFPA 13. In the simplest form, these systems include a series of connected pipes
and fittings, with valves, alarm initiating devices, and automatic sprinklers that are supplied
by a reliable water supply.
The four primary systems are the wet pipe system, the dry pipe system, the preaction system
and the deluge system.
Wet Pipe System
The wet pipe sprinkler system is, in general, the most cost-effective, the most
versatile as far as protection strategies and pipe installation are concerned, and the
easiest to maintain. Its cost effectiveness is based on its having fewer components,
requiring less maintenance and testing and having fewer design restrictions than any
of the other three types of systems. Wet pipe systems are installed where
temperatures will not fall below 40°F (4°C) and where one of the design objectives is
to put water on a relatively small fire as quickly as possible.
In a wet pipe system, components are arranged in such a manner that, as soon as
the heat from a fire operates the heat responsive element of an automatic sprinkler,
the water is discharged through the sprinkler to the fire. It is possible to design these
systems for fire control – controlling a fire to the room or area of origin until the fire
department arrives and extinguishes the fire; fire suppression – actually suppressing
the fire; or life safety protection – as in residential occupancies. The wet pipe system
can also include additives such as antifreeze or foam concentrate.
Design issues relative to the wet pipe sprinkler systems would include the following:
Is there a possibility or potential for freezing anywhere the water-filled
components are installed?
Is interior or exterior corrosion a factor to be concerned about?
What are the appropriate materials for a wet pipe system?
Dry Pipe System
When sprinkler systems are required in buildings, or areas of buildings, where the
ambient temperature will not be maintained above 40°F (4°C) dry pipe systems are
an option. The dry pipe system is more expensive than the wet pipe system;
requires more maintenance and testing (weekly, monthly, annually, and over its
lifetime); and has additional design requirements beyond those of the basic wet pipe
system.
Preaction System
The preaction system is similar to a dry pipe system. It has a similar valve, and in
general the same pipe, fittings, alarm initiating devices, and automatic sprinklers. In
addition to the sprinkler system, however, the preaction system incorporates a
detection system. Preaction systems areusually less cost-effective than the dry pipe
systems and require additional maintenance and testing as well as maintenance and
testing of the detection system.
There are many types of detectors and detection systems that can be used with the
preaction systems. It is in the system designer’s best interest to work closely with
the owner and the architect to utilize the type of detection system that is appropriate
for each specific area or system. An example of such an area is the data or
computer room, where the products of combustion can do as much damage to
sensitive equipment as the thermal damage from a fire or the resultant application of
water. In these rooms, an air sampling detection system may be more appropriate
than smoke detectors. The air sampling system may detect particles of combustion
before the human eye or nose does and can send signals or warnings before there is
actual smoke damage or a fire or before water is necessary.
Deluge System
Deluge systems are similar to preaction systems, in most cases utilizing the same
valves, pipe, fittings, alarm initiating devices, automatic sprinklers, and detectors,
although all of the sprinklers are open and do not include the heat responsive
element. Spray nozzles can be used in deluge systems instead of the open
automatic sprinklers. The difference between preaction and deluge systems is that
with the sprinklers open at all times, neither air nor water can be maintained in the
piping. The deluge system requires a detection system to operate and signal the
deluge valve, opening the valve and allowing water to flow through the piping and
discharge through all of the sprinklers or nozzles simultaneously.
Deluge systems can be installed in warm or cold very high hazard areas and the
primary objective is to put as much water on a fire as is required to contain or control
a severe fire hazard as quickly as possible. These systems are utilized where a
large amount of water is necessary quickly such as in flammable and combustible
dispensing operations, aircraft hangars, and transformers. The deluge systems
frequently include foam concentrates.
The type of sprinkler system must be determined early in the design process. That decision in
turn has implications on the remainder of the system design, from hydraulic criteria to water
supply and system components. The owner’s or client’s operations, processes, and overall
needs must be included in determining the type of system for a specific project.
Finally, long-term effects such as the cost of inspection, testing, and maintenance of the
sprinkler and detection systems, as well as life expectancy of the pipe, fittings, and other
components must be included in the overall evaluation.
Looped Sprinkler System
A sprinkler system in which multiple cross mains are tied together so as to provide
more than one path for water to flow to an operating sprinkler and branch lines are
not tied together.
Classification of Occupancies
Extra Hazard (Group 1) : where the quantity and combustibility of contents are every high
and dust, lint or other materials are present. Examples: Aircraft hangers, combustible
hydraulic fluid, printing, rubber reclaiming etc
Extra Hazard (Group 2): where moderate to substantial amounts of flammable or
combustible liquids are present. Examples: Flammable liquids spraying, open oil quenching,
plastic manufacturing, varnish and paint dipping etc.
System Component Definitions
Branch Lines: The pipes supplying sprinkler, either directly or through or through springs,
drops, return bends, or arm-overs.
Arm - Over: A horizontal pipe that extends from the branch line to a single sprinkler or a
sprinkler above and below a ceiling.
Cross Mains: The pipes supplying the branch lines, either directly or through risers.
Feed Mains: The pipes supplying cross mains, either directly or through risers.
Riser Nipple : Vertical piece of pipe between the main and branch line.
Refer to Table 6.2.5.1 for Sprinkler Temperature Ratings, Classifications and Color Coding's
of Sprinklers
Pipe Material Specifications
Piping above ground for size upto 4 inches (100 mm) shall be Galvanized Iron, Seamless,
Class’s’, Heavy duty - BS 1387 or according to Table 6.3.1.1. Pipe above 4” (100 mm) shall
be Black Steel, Wrought Steel, Sch 40, Seamless or according to table 6.3.1.1.
The maximum floor area on any floor to be protected by sprinklers supplied by any one
sprinkler system riser or combined system riser shall be as follows:
Extended Coverage Upright and Pendent Spray Sprinklers - Protection Areas and
Maximum Spacing. Table 8.8.2.1.2.
Protection Areas and Maximum Spacing for CMSA (Control Mode Specific
Application) Sprinklers. Table 8.11.2.2.1
Protection Areas and Maximum Spacing for ESFR (Early Suppression Fast-Response)
Sprinklers. Table 8.12.2.2.1
Sprinklers in Electrical Room
Rated Pressure
System components shall be rated for the maximum system working pressure to which they
are exposed but shall not be rated at less than 175 psi (12.1 bar) for components installed
above ground and 150 psi (10.4 bar) for components installed underground.
Pressure Reducing Valves
If water pressure in excess of 175 psi (12.1 bar), a listed pressure reducing valve shall be
installed and set for an outlet pressure not exceeding 165 psi (11.2 bar) at the maximum inlet
pressure.
Pressure gauges shall be led on the inlet and outlet sides of each pressure reducing valves.
A relief valve of not less than 13 mm in size shall be provided on the discharge side of the
PRV to set to operate at a pressure not exceeding 175 psi (12.1 bar).
Calculating Pipe Sizes
Pipe sizes shall be in accordance with Table 22.5.2.2.1 for Light Hazard Pipe
Schedules, Table 22,5,3,4 for Ordinary Hazard Pipe Schedule, Table 22.5.3.7 for Upright
Sprinklers Above and Pendent Sprinklers below a Ceiling and pipe sizes for extra hazard
shall be hydraulically calculated (Table A.22.5.4 for reference purpose only).
Sprinkler Discharge Patter (Figure A.8.5.5.1)
The discharge pattern for most sprinklers is fully developed at about a four foot distance
below the sprinkler. ... A small portion of the discharge wets the wall behind the sprinkler.
The discharge from sidewall sprinklers is less effective compared to upright and
pendent sprinklers.
Floor Control Valve Stations (also called Zone Control Valve Assembly)
Zone Control Valve is a system designed to separate the area in case of maintenance and to
get the indication of fire zone on a combination of Butterfly valve, Flow Switch, Pressure
Gauge and Test & Drain Valves.
Its main purpose it to regulate water flow in the designated “zones” or areas and in some
buildings, by floors / levels, thus named zone control valve.
Pipe Supports and Hangers
Figure A.9.1.1 Common Types of Acceptable Hangers
Figure A.9.2.3.4.4(b) Examples of Acceptable Hangers
Branch Pipe shall not exceed 8 Sprinklers.
On a branch pipe we can only install maximum up to 08 Nos. of sprinklers according to KFD
regulations
Sprinkler Head installation without false ceiling:
Distance between slab and sprinkler shall be minimum 1" (25 mm) and maximum 12" (300
mm)
Pendent sprinkler heads installation when false ceiling height is less than 80 cm.
Two layer sprinkler heads when false ceiling height is more than 80 cm.
Install one sprinkler below any duct or cable tray when width is more than 80 cm
below.
Local alarms shall be provided on all sprinklers system having more than 20 sprinklers.
The FDC shall be on the street side of the building. A listed check valve shall be installed in
each fire department connection.
Sidewall sprinklers shall be installed at the bottom of each elevator hoisting not more than 2
ft (0.61 m) above the floor of the pit.
Upright and pendent sprinklers shall be installed at the top of the elevator hoist ways.
B) Multilevel basements.
D) Departmental stores or shops, if the aggregate covered area exceed 500 m2.
E) All non-domestic floors of mixed occupancy which constitute a hazard and are not
provided with staircase independent of the remainder of the buildings.
A) 55% of fires were extinguished by the operation of two or less sprinkler heads.