How To Test The Ups
How To Test The Ups
1. You disconnect contactor (OFF) F1 (rectifier input) bypass switch remains in OFF position
3. Check that battery led is lit (orange) second icon. Now batteries supply power to the consumers.
4. From display measurements check all data navigate in the menu with the up and down bottons.
For Battery Voltage (in the photo 292 284) the difference has to be less than 4 V in order the
batteries to be in a good condition.
If the Battery Voltage difference between the two values is greater than 4 V, then one or more
batteries might be faulty and need to be checked.
5. Connect (ON) F1, battery LED is off, only the first one LED (mains) is on and the UPS is again
supplied by the vessel’s network.