Instructions for EATON UPS 9305

How to set the parameter: actual autonomy time of the batteries.

The autonomy time of the UPS depends in the capacity of the batteries of UPS.

In LYD the capacity of the batteries in IAS UPS is 38 Ah as shown in Fig.1.

Fig.1: Batteries EATON 9305 IAS UPS

The parameter that needs to be set is the P01V00 .

In LYD the P01V00 was set to P01V21 (*).

(*) See attached table which connects the capacity of the batteries in LYD 38 Ah with the parameter
number: 21.

How to set the parameter P01V…. using the up and down buttons in the interface window of the
UPS, as shown in Fig.2.

Fig.2: UPS EATON 9305 interface window

1. Scroll up and down with the ↑ and ↓ buttons

2. Go to UPS PARAMETERS and select it by pressing Enter.

3. If Password is required with the ↑ and ↓ buttons write the word : USER. With the buttons you
can scroll up and down to all letters and with the Enter you select each letter.

4. Then you enter to the parameters and you select Parameter P01V00 and with the use of up and
down buttons and enter you adjust the parameter to the correct value according to the capacity of
the batteries.
5. Finally to exit to the firs screen you have to press the MENU button.