The operational parameters can be viewed or set by UPPM command. The following
formats of the command are possible:
The second part (second row) of the command defines the command function:
• List of all adjustable parameters: second part is 0(cr). No change to any parameters is
done. UPS lists all existing parameters in 9305.
• A parameter value: second part is Pmm(cr), where the first character is always P
(Parameter) followed by the number of the parameter mm which value is requested. No
change is done, but the value presently in the memory of the UPS is transmitted in
acknowledgement: PmmVnn(cr), where mm is the number of the parameter and nn is the
number of the operation.
• Set a parameter value: second part is Pmm, followed by V (Value), the number of the
operation nn, and by Line Terminator. If the parameter number and operation value are
correct, the new value for the parameter is stored in the non-volatile memory of the
unit. The value of the parameter is transmitted in acknewledgement.
The operational parameters that can be viewed and set with UPPM command are: