The operational parameters can be viewed or set by UPPM command. The following
formats of the command are possible:

Command UPS response Description

UPPM(cr) ACPM(cr)(lf) PARAMETER LIST A listing of the adjustable parameters is


0(cr) P01(cr)(lf) requested.
P02(cr)(lf)
P03(cr)(lf)
P04(cr)(lf)
P05(cr)(lf)
P06(cr)(lf)
P07(cr)(lf)
P08(cr)(lf)
P09(cr)(lf)
P13(cr)(lf)
P16(cr)(lf)
P18(cr)(lf)
P19(cr)(lf)
P20(cr)(lf)
P23(cr)(lf)
P24(cr)(lf)
P25(cr)(lf)
P26(cr)(lf)
P27(cr)(lf)
P28(cr)(lf)
P29(cr)(lf)
P30(cr)(lf)
P31(cr)(lf)
P32(cr)(lf)
UPPM(cr) ACPM(cr)(lf) PARAMETER VALUE The present value nn of the parameter mm
Pmm(cr) PmmVnn(cr)(lf) Parameter is requested.
UPPM(cr) ACPM(cr)(lf) SET UPS PARAMETER The parameter mm value is changed to nn.
PmmVnn(cr) PmmVnn(cr)(lf) Parameter and operation

The second part (second row) of the command defines the command function:
• List of all adjustable parameters: second part is 0(cr). No change to any parameters is
done. UPS lists all existing parameters in 9305.
• A parameter value: second part is Pmm(cr), where the first character is always P
(Parameter) followed by the number of the parameter mm which value is requested. No
change is done, but the value presently in the memory of the UPS is transmitted in
acknowledgement: PmmVnn(cr), where mm is the number of the parameter and nn is the
number of the operation.
• Set a parameter value: second part is Pmm, followed by V (Value), the number of the
operation nn, and by Line Terminator. If the parameter number and operation value are
correct, the new value for the parameter is stored in the non-volatile memory of the
unit. The value of the parameter is transmitted in acknewledgement.

The operational parameters that can be viewed and set with UPPM command are:

1011496I NEW UPS code II Powerware 9305 7.5 - 60 kVA 16(47)


Powerware UPScode II Serial Interface Protocol
mm Parameter nn Operation

01 Battery size 7.5-15kVA 00 Unknown batteries, BTIME always ‘9999.00’


1)
01 7.0 Ah
02-21 N x 7.0 Ah, N = {2, 3, ..., 21}
2)
20-60kVA 00 Unknown batteries, BTIME always ‘9999.00’
01 2.0 Ah
02 3.0 Ah
03 4.0 Ah
04 5.0 Ah
05 6.0 Ah
06 7.0 Ah
07 8.0 Ah
08 9.0 Ah
09 10 Ah
10 11 Ah
11 12 Ah
12 14 Ah
13 15 Ah
14 17 Ah
15 19 Ah
16 21 Ah
17 24 Ah
18 27 Ah
19 30 Ah
20 34 Ah
21 38 Ah
22 42 Ah
23 48 Ah
24 53 Ah
25 60 Ah
26 65 Ah
27 76 Ah
28 80 Ah
29 96 Ah
30 100 Ah
31 114 Ah
32 130 Ah
33 152 Ah
34 168 Ah
35 180 Ah
36 195 Ah
37 225 Ah
38 260 Ah
39 285 Ah
40 325 Ah
41 360 Ah
42 390 Ah
43 450 Ah
44 520 Ah
45 560 Ah
46 620 Ah
47 700 Ah
48 780 Ah
49 870 Ah
50 980 Ah
51 1090 Ah
52 1220 Ah
53 1370 Ah
54 1530 Ah
55 1700 Ah
56 1900 Ah
57 2150 Ah
58 2400 Ah
59 2700 Ah
60 3000 Ah
61 3350 Ah
62 3750 Ah
63 4200 Ah

1011496I NEW UPS code II Powerware 9305 7.5 - 60 kVA 17(47)


Powerware UPScode II Serial Interface Protocol
1)
02 Modem communication test 00 The UPS calls to a service centre only when alarm condition occurs
mode 01 The UPS calls also if utility failure is detected
1)
03 Output voltage 00 230 V
01 220 V
02 240 V
3)
04 Output frequency 00 50 Hz
01 60 Hz
1)
05 Battery low alarm level 00 Nominal voltage level
01 Higher level
02 Lower level
4)
06 Synchronization window 00 Narrow ± 0.5 Hz
1)
01 Wide ± 2.0 Hz
02 ± 1.0 Hz
1)
07 Operation mode of RS232 00 The interface operates locally
interface X101 01 The interface operates remotely via modem
1)
08 Audible alarm 7.5-15kVA 00 Sound ON
01 Suppress line failure
02 Suppress all alarms
20-60kVA 00 Sound ON
01 Suppress line failure
5)
02 Suppress all alarms
1)
09 Line failure alarm delay 05 Relay, buzzer & UPScode status activated 5 seconds after failure
00-99 Relay, buzzer & UPScode status activated after 0-99 seconds
1)
13 ABM functions 00 All ABM functions enabled
01 ABM battery charging cycles disabled
02 Battery failure alarms disabled
03 Battery failure alarms and ABM battery charging cycles disabled
1)
16 Bypass limits 00 -15%...+10% of nominal voltage
0h h = {1, 2, ..., 9}: low limit -2%, high limit defined by h, see below
l0 l = {1, 2, ..., 9}: high limit +2%, low limit defined by l, see below
lh l, h = {1, 2, ..., 9}: l defines the low limit, h defines the high limit:
l = 1 ⇒ -4% h = 1 ⇒ +4% of nominal voltage (UPPM P03)
l = 2 ⇒ -6% h = 2 ⇒ +6%
l = 3 ⇒ -8% h = 3 ⇒ +8%
l = 4 ⇒ -10% h = 4 ⇒ +10%
l = 5 ⇒ -12% h = 5 ⇒ +12%
l = 6 ⇒ -14% h = 6 ⇒ +14%
l = 7 ⇒ -16% h = 7 ⇒ +16%
l = 8 ⇒ -18% h = 8 ⇒ +18%
l = 9 ⇒ -20% h = 9 ⇒ +20%
6) 1)
18 Frequency slew rate 00 Low, <0.5 Hz/s
01 Normal, 2.5 Hz/s
02 High
1)
19 Service modes 00 Normal operation
01 Battery operation (backfeed relay open)
02 Bypass operation, inverter on
03 Bypass operation, inverter off
04 Bypass operation, inverter on, backfeed relay open
05 Bypass operation, inverter off, backfeed relay open
7)
06 Output breaker trip command
1)
20 UPS type string 00 Takes the response to UPTP command from non-volatile memory
01 Sends “UPS” and firmware revision as response to UPTP command
6) 1)
23 Efficiency optimizer mode 00 No efficiency optimizer mode
01-99 Bypass must be synchronized and voltage level ok 1 - 99 min before transfer from
inverter to bypass
6) 1)
24 Transfer acceptance 00 Requires synchronization
01 Transfers also while unsynchronized
1)
25 Operational priority during 00 On battery
rectifier input break 01 On bypass

1011496I NEW UPS code II Powerware 9305 7.5 - 60 kVA 18(47)


Powerware UPScode II Serial Interface Protocol