Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Calculation by GMLS

Registration status - Legal copy.


This program run 0/1
This calculation 2
Calculation - Comprimo case
Report number T1-026

Revision Table
___________________________________________________________________________
Issue Date Initial Description
___________________________________________________________________________
PA 03 Feb 2023 BPVM Preliminary, for information only
___________________________________________________________________________

ッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッ
METAL TEMPERATURE REPORT

ッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッ
Boiler data - CB-81001
______________________________________________________________________

Boiler configuration = No flue


Boiler type = Saturated steam
Boiler model = CB-81001
Elevated drum = True
Actual evaporation = 63000 [kg/hour]
Turn down ratio = 4 []
Feed water temperature = 110 [ー C]
Blow down, percent of feed = 5 [%]
Input Flue Gas Temperature = 710 [ー C]
Input Flue Gas Pressure = 2.5 [ー C]
Use the standard model size to calculate flow = False
Use the standard model dimensions = False
Which standard dimensions to use = Unknown

ッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッッ
METAL TEMPERATURE RESULTS
______________________________________________________________________

Mean metal operating temperatures for stress analysis purposes...


Saturated steam temperatures
Design steam temperature 265.3 ーC 509.4 ーF
Max operating steam temperature 261.3 ーC 502.4 ーF
Max' safety valve relief 268.8 ーC 515.9 ーF

Boiler shell temperature 261.3 ーC 502.4 ーF


First pass tubes inlet
-inside surface temperature 397.9 ーC 748.2 ーF
-mean tube temperature 332.9 ーC 631.2 ーF
-outside surface temperature 267.9 ーC 514.2 ーF
Boiler shell - front tube plate [1] 531.0 ーC 987.8 ーF
Boiler shell - rear tube plate [2] 305.9 ーC 582.6 ーF
Front tube plate [3] 348.0 ーC 658.3 ーF

Temperature notes
[1] Tube plate bare
[2] Conservative estimate
[3] Tube plate protected with ceramic ferrule