WIRING SCHEDULE

FEEDER CABLE GROUND WIRE CONDUIT SIZE


SYMBOL SIZE TYPE NO. OF AMPACITY SIZE TYPE RSC, IMC PVC
mm² CABLE OR EMT
Y400 400 THHN 3 515 60 TW or THHN 100 110
Y325 325 THHN 3 470 60 TW or THHN 90 110
Y250 250 THHN 3 400 30 TW or THHN 80 90
Y200 200 THHN 3 355 30 TW or THHN 80 90
Y150 150 THHN 3 295 30 TW or THHN 65 75
Y125 125 THHN 3 265 22 TW or THHN 65 75
Y100 100 THHN 3 225 22 TW or THHN 50 63
Y80 80 THHN 3 205 22 TW or THHN 50 63
Y60 60 THHN 3 170 14 TW or THHN 50 63
Y50 50 THHN 3 150 14 TW or THHN 40 50
Y38 38 THHN 3 130 14 TW or THHN 40 50
Y30 30 THHN 3 115 8 TW or THHN 32 40
Y22 22 THHN 3 90 8 TW or THHN 25 32
Y14 14 THHN 3 70 8 TW or THHN 20 25
Y8.0 8 THHN 3 50 5.5 TW or THHN 20 25
Y5.5 5.5 THHN 3 40 5.5 TW or THHN 15 20
Y3.5 3.5 THHN 3 30 3.5 TW or THHN 15 20
X100 100 THHN 2 225 22 TW or THHN 50 63
X80 80 THHN 2 205 22 TW or THHN 50 63
X60 60 THHN 2 170 14 TW or THHN 40 50
X50 50 THHN 2 150 14 TW or THHN 32 40
X38 38 THHN 2 130 14 TW or THHN 32 40
X30 30 THHN 2 115 8 TW or THHN 25 32
X22 22 THHN 2 90 8 TW or THHN 25 32
X14 14 THHN 2 70 8 TW or THHN 20 25
X8.0 8 THHN 2 50 5.5 TW or THHN 15 20
X5.5 5.5 THHN 2 40 5.5 TW or THHN 15 20
X3.5 3.5 THHN 2 30 3.5 TW or THHN 15 20